Manual Agz 125
Manual Agz 125
Hazard Identification
DANGER
Dangers indicate a hazardous situation which will result in death or serious injury if not avoided.
WARNING
Warnings indicate potentially hazardous situations, which can result in property damage, severe personal injury, or death if not avoided.
CAUTION
Cautions indicate potentially hazardous situations, which can result in personal injury or equipment damage if not avoided.
This manual contains information on the optional factory-installed pump packages for
AGZ-D (REV 0A) vintage air-cooled scroll chillers. For other product information, go to
www.DaikinApplied.com.
Cover Picture: Pump package shown during manufacture without evaporator insulation installed and without the
shipped loose pump inlet “Y” strainer and outlet triple-duty valve.
©2016 Daikin Applied. Illustrations and data cover the Daikin Applied product at the time of publication and we reserve the right to make
changes in design and construction at anytime without notice.
2 IM 1110-2
FOR PUMP PACKAGE UNITS ONLY
FILE NO.: TBA
DATE: Apr 25, 2013
SUPERSEDES: Sep 28, 2012
DATE: N/A
Page 1 of 2
NOTE:
For independent sensorless operation, go to Section 1.
For independent external sensor operation, go to Section 2.
For external controller, go to Section 3.
11. Put the VFD into AUTO mode. The pump will ramp up to get to the setpoint pressure and as the
demand in the system decreases, the setpoint will also decrease to ride the control curve down to the
minimum pressure set in parameter 22-87. As demand increases, it will ride back up the control curve to
full design setpoint.
A G Z XXX D H
Air-Cooled Application
Global Design H = Standard Packaged
Scroll Compressor
Nominal Tons
Design Vintage
WARNING
Installation is to be performed by qualified personnel who are familiar with local codes and regulations.
CAUTION
Sharp edges on unit and coil surfaces are a potential hazard to personal safety. Avoid contact with them.
Note: Use this manual in conjunction with the current Installation and Maintenance Manual and Operation Manual,
for AGZ-D packaged chillers. Both manuals are available on www.DaikinApplied.com.
General Description
This manual covers optional on-board, integrated, chilled PLUS
water pump package available on all Daikin Model AGZ-D
• “Y" type inlet strainer
(REV 0A) chillers. Factory-installed pump packages provide
important benefits: • Combination triple-duty outlet valve having a drip-tight
discharge shutoff valve, non-slam check valve, and flow
• Greatly simplify the chilled water system design and
throttling valve
installation
• Combination suction guide with flow stabilizing outlet
• Provide installation savings by reducing field piping,
vanes and stainless steel strainer with a disposable fine-
wiring and control costs
mesh strainer for start-up
• Save valuable floor space inside the building
• Factory power and control wiring from the AGZ-D
• Reduce project engineering content chiller to the pump package control panel
• Greatly reduce pump operating cost with the optional • Flow switch mounted and wired
variable flow pump Variable Frequency Drive (VFD)
• Interconnecting schedule 40 piping with Victaulic® cou-
Standard Components plings
Single Pump (Model 4380) is a single spring inside seal, • Insulation of all cold surfaces
vertical, in-line, radially split-case pump, serviceable without
Options
breaking pipe connections. The motor and pump rotating
• Water pressure gauges on the pump suction and dis-
assembly can be serviced without removing the pump casing
from the line. charge
• Expansion tank with size increments from 4.4 to 90 gal-
Dual Pumps in a Single Casting (Model 4392) single-spring lons, field installed (small sizes can be factory mounted
inside-seal vertical, in-line, radially split-case pumps, mounted
• Air separator with air vent, field installed
in a common casing with a common inlet connection and
outlet connection and including a flapper valve to prevent • Flex piping connections, field installed
recirculation when only one pump is operating. For 4392 • Storage tanks, vertical, insulated. (150, 300, 600, 1000
series twin pumps: In the event that one pump needs to be gallon sizes) with optional immersion heater, field
removed while the other pump is operational, the operating installed.
pump will have to be temporarily turned off while the second Optional Variable Flow VFD
pump is removed. After installation of a gasket and blanking
plate in place of the removed pump, the operating pump may The operating cost savings resulting from using variable
then be restarted and operated. The pumps are designed for chilled water flow via a pump VFD has been well known for
duty/standby, not parallel operation. All information and many years. In the past, however, its usage has been somewhat
performance curves for the single pump arrangement (Model limited by the cost and uncertainty of field installing the
4380) can be used for the dual pump arrangement (Model required system pressure differential sensors.
4392.)
IM 1110-2 3
Introduction
Daikin Applied can now offer a variable chilled water flow 4 Remote Sensor Control: The VFD is wired to pressure
system, completely self-contained within the pump package, sensors mounted in the chilled water piping system. This
by simply ordering the optional pump VFD-no external is the standard VFD control when a sensorless VFD is
sensors required. not used.
Including sensorless operation, there are four operating modes Pump Description
available with the optional factory-installed variable flow • Pump casing is cast iron.
VFD:
• The casing suction and discharge connections are the
1 Sensorless Pressure Control: Onboard measurements same size and have tapped seal vent and pressure gauge
allow control of the pump speed to optimize chilled connections.
water flow with respect to water system pressure.
• The mechanical seal is single-spring inside type with
External pressure sensors are not required, eliminating
carbon against silicon carbide faces. EPDM elastomer
design and installation effort. The unit is factory-
with stainless steel and hardware are provided.
configured for this mode.
• Impellers are bronze, trimmed to design conditions and
2 BAS Input: The pump speed will be controlled then balanced.
according to the voltage level from a BAS input signal.
• The shaft sleeve is bronze extending the full length of
3 Locally Selected Constant Speed Control: Operation the seal area.
of the pump at a constant speed selected on the VFD
control panel. Among other things, this mode allows
selecting a pump speed to match the actual system curve.
Figure 1: Model 4380 Design Features 1.Industry standard face mounted motor.
2.Flush and vent connection removes entrained air and ensures liquid at seal
face at all times.
3.Inside type mechanical seal with Silicon Carbide seat, serviceable without
breaking pipe connections.
4.Heavy cylindrical bracket with 360° register on both flanges provides a
rigid union of pump and motor.
5.Dynamically balanced impeller assures smooth vibration-free operation.
6.Radially split casing with equal suction and discharge flange sizes. Separate
tapped openings for gauge, flush and drain connections.
7. Liberal inlet passageways and straightening vanes provide optimum suction
performance and quiet operation.
8.Ribs cast integral with casing. Machined surface to accept floor support
when specified.
9. Confined casing gasket to meet stringent industrial temperature and
pressure applications.
4 IM 1110-2
Introduction
Component Location
Figure 2: Component location for models AGZ025D - AGZ070D
Dual
Vertical
Pumps
“Y”Type
Inlet
Strainer
Brazed-Plate
Inlet Evaporator
Guide
Optional
VFD
Controllers Pump
Chilled Package
Water Control
Outlet Panel
Triple-Duty
Outlet Valve Flow Drain Evap Out Press.
Swt. Guage Port
Notes:
1 Dual pumps having a common housing and inlet and outlet connections as shown. An available single pump arrangement can
replace the dual pump and will have a similar piping layout.
2 The inlet strainer and triple-duty valve are shipped separate for field installation.
3 The pump package control panel is located under the main unit control panel. The piping connections are on the left side of
the chiller unit when looking at the control panel.
4 Pump drains are located under the pump casing, ¼ in. NPT.
5 Pipe drains are 1 in. NPT.
IM 1110-2 5
Introduction
Figure 3: Component location for models AGZ075D - AGZ130D
Pump Package
Control Panel
Evap In
Press. Ga. Port
Dual
Vertical
Pumps
Optional
VFD
Controllers
Brazed-Plate
Evaporator
Drain Port
Chilled
Water
Inlet Flow Switch
Chilled
Water
Triple-Duty
Outlet
Outlet Valve
Evap Out
Press. Ga. Port
Notes:
1 Dual pump having a common inlet and outlet shown. An available single pump arrangement can replace the dual pump and
will have a similar piping layout.
2 The inlet strainer and triple-duty valve are shipped separate for field installation.
3 The pump package control panel is located under the main unit control panel. The piping connections are at the rear of the
unit, opposite the control panel.
4 Pump drains are located under the pump casing, ¼ in. NPT.
5 Pipe drains are 1 in. NPT.
6 IM 1110-2
Introduction
Figure 4: Component location for models AGZ140D - AGZ190D
Evap In
Press Ga. Port
Pump
Package
Dual Control
Vertical Panel
Pumps
Shell-and-Tube
“Y” Type Evaporator
Inlet
Strainer
Drain Port
Optional
VFD
Controllers
Flow Switch
Chilled
Water Evap Out Press. Ga. port
Inlet
Triple-Duty
Chilled Outlet valve
Inlet Water
Guide Outlet
Notes:
1 Dual pump having a common inlet and outlet shown. An available single pump arrangement can replace the dual pump and
will have a similar piping layout.
2 The inlet strainer and triple-duty valve are shipped separate for field installation.
3 The pump package control panel is located under the main unit control panel. The piping connections are at the rear of the
unit, opposite the control panel.
4 Pump drains are located under the pump casing, ¼ in. NPT.
5 Pipe drains are 1 in. NPT.
IM 1110-2 7
Selection Procedures
Selection Procedure Total Dynamic System Head
Selection Procedures
8 IM 1110-2
Selection Procedures
Pump Selection Procedure Using the required flow and total system head, select the best
pump from the table. Flow values are shown for minimum,
A family of pump sizes has been pre-selected for groups of nominal, and near-maximum flow rates for each AGZ size. For
AGZ units and shown in Table 3. flow rates falling between these values, check the pump
selection for the higher and lower flow. The impeller will be
trimmed for specific job conditions after order placement.
Pump Nomenclature
2 x 1.5 x 5.5
Suction Size (in.)
Impeller Size (in.)
Discharge Size (in.)
Selection Examples From Table 3., select a dual 2 x 2 x 6 pump, 3600 rpm, 7.5 hp.
Select: a pump for an AGZ 025-D with 65 gpm of water flow Although a 5 hp pump is adequate at design conditions, a 7.5
at a 90 ft external head, dual pumps. From Table 1., the hp pump will provide non-overloading characteristics.
internal pump package pressure drop is 3.7 ft.
From the pressure drop curves on page 15, the evaporator
pressure drop is 9.4 ft.
Internal Pump Package 3.7
Evaporator 9.4
External 90.0
Total Head 103.1
IM 1110-2 9
Selection Procedures
Table 3: AGZ-D Unit/Pump Combinations Continued
Unit Nom. Nom. Min. Max. Unit Total
Single Dual
Model Tons gpm gpm gpm gpm Head
ft. Size rpm HP Size rpm HP
52 50 2x2x8 1800 3 2x2x8 1800 3
52 75 1.5x1.5x6 3600 3 2x2x6 3600 5
52 100 1.5x1.5x6 3600 5 2x2x6 3600 5
52 125 1.5x1.5x6 3600 5 2x2x6 3600 7.5
84 25 2x2x6 1800 2 2x2x6 1800 2
84 50 2x2x8 1800 3 2x2x8 1800 3
AGZ 035D 34.9 84 52 140 84 75 2x2x6 3600 5 2x2x6 3600 5
84 100 1.5x1.5x6 3600 5 2x2x6 3600 7.5
84 125 2x2x6 3600 7.5 2x2x6 3600 7.5
112 25 2x2x8 1800 2 2x2x8 1800 2
112 50 2x2x8 1800 3 2x2x8 1800 3
112 75 2x2x6 3600 5 2x2x6 3600 5
112 100 2x2x6 3600 7.5 2x2x6 3600 7.5
57 50 2x2x8 1800 3 2x2x8 1800 3
57 75 1.5x1.5x6 3600 3 3x3x6 3600 5
57 100 1.5x1.5x6 3600 5 2x2x6 3600 5
57 125 1.5x1.5x6 3600 5 2x2x6 3600 7.5
91 25 2x2x6 1800 2 2x2x6 1800 2
91 50 2x2x8 1800 3 2x2x8 1800 3
AGZ 040D 37.9 91 57 152 91 75 2x2x6 3600 5 2x2x6 3600 5
91 100 2x2x6 3600 7.5 2x2x6 3600 7.5
91 125 2x2x6 3600 7.5 2x2x6 3600 7.5
121 25 3x3x6 1800 2 3x3x6 1800 2
121 50 2x2x8 1800 3 2x2x8 1800 3
121 75 2x2x6 3600 5 2x2x6 3600 5
121 100 2x2x6 3600 7.5 2x2x6 3600 7.5
64 50 2x2x8 1800 3 2x2x8 1800 3
64 75 1.5x1.5x6 1800 5 3x3x6 1800 5
64 100 1.5x1.5x6 3600 5 2x2x6 3600 5
64 125 1.5x1.5x6 3600 5 2x2x6 3600 7.5
102 25 3x3x6 1800 2 3x3x6 1800 2
102 50 2x2x8 1800 3 2x2x8 1800 3
AGZ 045D 42.6 102 64 170
102 75 2x2x6 3600 5 2x2x6 3600 5
102 100 2x2x6 3600 7.5 2x2x6 3600 7.5
136 25 3x3x6 1800 2 3x3x6 1800 2
136 50 2x2x8 1800 5 2x2x8 1800 5
136 75 2x2x6 3600 5 2x2x6 3600 5
136 100 2x2x6 3600 7.5 2x2x6 3600 7.5
72 50 2x2x8 1800 3 2x2x8 1800 3
72 75 1.5x1.5x6 3600 3 2x2x6 3600 5
72 100 1.5x1.5x6 3600 5 2x2x6 3600 7.5
72 125 2x2x6 3600 7.5 2x2x6 3600 7.5
115 25 2x2x8 1800 2 2x2x8 1800 2
115 50 2x2x8 1800 3 2x2x8 1800 3
AGZ 050D 48.1 115 72 192
115 75 2x2x6 3600 5 2x2x6 3600 5
115 100 2x2x6 3600 7.5 2x2x6 3600 7.5
154 25 3x3x6 1800 2 3x3x6 1800 2
154 50 2x2x8 1800 5 2x2x8 1800 5
154 75 2x2x6 3600 7.5 2x2x6 3600 7.5
154 100 2x2x6 3600 7.5 2x2x6 3600 7.5
Note: Some unit gpm and head combination do not have a valid selection and are absent from the table.
10 IM 1110-2
Selection Procedures
Table 3: AGZ-D Unit/Pump Combinations Continued
Unit Nom. Nom. Min. Max. Unit Total Head Single Pump Dual Pumps
Model Tons gpm gpm gpm gpm ft. Size RPM HP Size RPM HP
77 50 2x2x8 1800 3 2x2x8 1800 3
77 75 1.5x1.5x6 3600 3 2x2x6 3600 5
77 100 1.5x1.5x6 3600 5 2x2x6 3600 7.5
77 125 2x2x6 3600 7.5 2x2x6 3600 7.5
124 25 3x3x6 1800 2 3x3x6 1800 2
AGZ 055D 51.6 124 77 206 124 50 2x2x8 1800 3 2x2x8 1800 3
124 75 2x2x6 3600 5 2x2x6 3600 5
124 100 2x2x6 3600 7.5 2x2x6 3600 7.5
165 25 3x3x6 1800 2 3x3x6 1800 2
165 50 3x3x8 1800 5 3x3x8 1800 5
165 75 2x2x6 3600 7.5 2x2x6 3600 7.5
84 50 2x2x8 1800 3 2x2x8 1800 3
84 75 2x2x6 3600 5 2x2x6 3600 5
84 100 1.5x1.5x6 3600 5 2x2x6 3600 7.5
84 125 2x2x6 3600 7.5 2x2x6 3600 7.5
135 25 3x3x6 1800 2 3x3x6 1800 2
135 50 2x2x8 1800 5 2x2x8 1800 5
135 75 2x2x6 3600 5 2x2x6 3600 5
AGZ 060D 56.1 135 84 224
135 100 2x2x6 3600 7.5 2x2x6 3600 7.5
135 125 2x2x6 3600 10 2x2x6 3600 10
180 25 3x3x6 1800 2 3x3x6 1800 2
180 50 3x3x8 1800 5 3x3x8 1800 5
180 75 3x3x6 3600 7.5 3x3x6 3600 7.5
180 100 2x2x6 3600 10 2x2x6 3600 10
180 125 2x2x8 3600 10 2x2x8 3600 10
87 50 2x2x8 1800 3 2x2x8 1800 3
87 75 2x2x6 3600 5 2x2x6 3600 5
87 100 2x2x6 3600 7.5 2x2x6 3600 7.5
87 125 2x2x6 3600 7.5 2x2x6 3600 7.5
139 25 3x3x6 1800 2 3x3x6 1800 2
139 50 2x2x8 1800 5 2x2x8 1800 5
AGZ 065D 58.1 139 87 232 139 75 2x2x6 3600 5 2x2x6 3600 5
139 100 2x2x6 3600 7.5 2x2x6 3600 7.5
139 125 2x2x6 3600 10 2x2x6 3600 10
186 25 3x3x6 1800 2 3x3x6 1800 2
186 50 3x3x8 1800 5 3x3x8 1800 5
186 75 3x3x6 3600 7.5 3x3x6 3600 7.5
186 100 2x2x6 3600 10 2x2x6 3600 10
96 50 2x2x8 1800 3 2x2x8 1800 3
96 75 2x2x6 3600 5 2x2x6 3600 5
96 100 2x2x6 3600 7.5 2x2x6 3600 7.5
96 125 2x2x6 3600 10 2x2x6 3600 10
154 25 3x3x6 1800 2 3x3x6 1800 2
154 50 2x2x8 1800 5 2x2x8 1800 5
AGZ 070D 64.1 154 96 256 154 75 2x2x6 3600 7.5 2x2x6 3600 7.5
154 100 2x2x6 3600 7.5 2x2x6 3600 7.5
154 125 1.5x1.5x8 3600 10 2x2x6 3600 10
205 25 3x3x8 1800 3 3x3x8 1800 3
205 50 3x3x8 1800 5 3x3x8 1800 5
205 75 3x3x6 3600 7.5 3x3x6 3600 7.5
205 100 3x3x6 3600 10 3x3x6 3600 10
Note: Some unit gpm and head combination do not have a valid selection and are absent from the table.
IM 1110-2 11
Selection Procedures
Table 3: AGZ-D Unit/Pump Combinations Continued
Unit Nom. Nom. Min. Max. Unit Total Head Single Pump Dual Pumps
Model Tons gpm gpm gpm gpm ft. Size rpm HP Size rpm HP
110 50 2x2x8 1800 3 2x2x8 1800 3
110 75 2x2x6 3600 5 2x2x6 3600 5
110 100 2x2x6 3600 7.5 2x2x6 3600 7.5
110 125 2x2x6 3600 10 2x2x6 3600 10
175 50 3x3x8 1800 5 3x3x8 1800 5
175 75 3x3x6 3600 7.5 3x3x6 3600 7.5
AGZ 075D
73.1 175 110 292 175 100 2x2x6 3600 10 2x2x6 3600 10
175 125 2x2x8 3600 15 2x2x8 3600 15
234 25 3x3x8 1800 3 3x3x8 1800 3
234 50 3x3x8 1800 5 3x3x8 1800 5
234 75 3x3x6 3600 7.5 3x3x6 3600 7.5
234 100 2x2x8 3600 15 2x2x8 3600 15
234 125 2x2x8 3600 15 2x2x8 3600 15
122 50 2x2x8 1800 3 2x2x8 1800 3
122 75 2x2x6 3600 5 2x2x6 3600 5
122 100 2x2x6 3600 7.5 2x2x6 3600 7.5
122 125 2x2x6 3600 10 2x2x6 3600 10
195 25 3x3x6 1800 3 3x3x6 1800 3
195 50 3x3x8 1800 5 3x3x8 1800 5
195 75 3x3x6 3600 7.5 3x3x6 3600 7.5
AGZ 080D 81.1 195 122 324
195 100 2x2x6 3600 10 2x2x6 3600 10
195 125 2x2x8 3600 15 2x2x8 3600 15
260 25 3x3x6 1800 3 3x3x6 1800 3
260 50 3x3x8 1800 5 3x3x8 1800 5
260 75 3x3x6 3600 7.5 3x3x6 3600 7.5
260 100 2x2x6 3600 10 2x2x6 3600 10
260 120 2x2x8 3600 15 2x2x8 3600 15
134 50 2x2x8 1800 5 2x2x8 1800 5
134 75 2x2x6 3600 5 2x2x6 3600 5
134 100 2x2x6 3600 7.5 2x2x6 3600 7.5
134 125 2x2x6 3600 10 2x2x6 3600 10
214 50 3x3x8 1800 5 3x3x8 1800 5
214 75 3x3x6 3600 7.5 3x3x6 3600 7.5
AGZ 090D 89.2 214 134 357
214 100 4x4x6 3600 15 4x4x6 3600 15
214 125 2x2x8 3600 15 2x2x8 3600 15
285 25 4x4x6 1800 3 4x4x6 1800 3
285 50 3x3x8 1800 7.5 3x3x8 1800 7.5
285 75 3x3x6 3600 10 3x3x6 3600 10
285 100 4x4x6 3600 15 4x4x6 3600 15
150 50 2x2x8 1800 5 2x2x8 1800 5
150 75 2x2x6 3600 7.5 2x2x6 3600 7.5
150 100 2x2x6 3600 7.5 2x2x6 3600 7.5
150 125 2x2x6 3600 15 2x2x6 3600 15
240 25 3x3x8 1800 3 3x3x8 1800 3
240 50 3x3x8 1800 5 3x3x8 1800 5
AGZ 100D 99.8 240 150 399 240 75 3x3x6 3600 7.5 3x3x6 3600 7.5
240 100 2x2x8 3600 15 2x2x8 3600 15
240 125 2x2x8 3600 15 2x2x8 3600 15
319 25 4x4x6 1800 3 4x4x6 1800 3
319 50 3x3x8 1800 7.5 3x3x8 1800 7.5
319 75 3x3x8 3600 10 3x3x8 3600 10
319 100 4x4x6 3600 15 4x4x6 3600 15
Note: Some unit gpm and head combination do not have a valid selection and are absent from the table.
12 IM 1110-2
Selection Procedures
Table 3: AGZ-D Unit/Pump Combinations Continued
Unit Nom. Nom. Min. Max. Unit Total Head Single Pump Dual Pumps
Model Tons gpm gpm gpm gpm ft. Size rpm HP Size rpm HP
159 50 2x2x8 1800 5 2x2x8 1800 5
159 75 2x2x6 3600 7.5 2x2x6 3600 7.5
159 100 2x2x6 3600 7.5 2x2x6 3600 7.5
159 125 2x2x6 3600 15 2x2x6 3600 15
255 25 3x3x6 1800 3 3x3x6 1800 3
255 50 3x3x8 1800 5 3x3x8 1800 5
AGZ 110D 106.1 255 159 424 255 75 3x3x6 3600 7.5 3x3x6 3600 7.5
255 100 2x2x6 3600 10 2x2x6 3600 10
255 125 2x2x8 3600 15 2x2x8 3600 15
340 25 4x4x6 1800 3 4x4x6 1800 3
340 50 3x3x8 1800 7.5 3x3x8 1800 7.5
340 75 4x4x6 3600 10 4x4x6 3600 10
340 100 4x4x6 3600 15 4x4x6 3600 15
176 50 3x3x8 1800 5 3x3x8 1800 5
176 75 3x3x6 3600 7.5 3x3x6 3600 7.5
176 100 2x2x6 3600 10 2x2x6 3600 10
176 125 2x2x8 3600 15 2x2x8 3600 15
281 25 4x4x6 1800 3 4x4x6 1800 3
281 50 3x3x8 1800 7.5 3x3x8 1800 7.5
AGZ 125D 117.1 281 176 468
281 75 3x3x6 3600 10 3x3x6 3600 10
281 100 4x4x6 3600 15 4x4x6 3600 15
375 25 4x4x6 1800 5 4x4x6 1800 5
375 50 3x3x6 3600 10 4x4x8 3600 10
375 75 4x4x6 3600 15 4x4x6 3600 15
375 100 4x4x6 3600 15 4x4x6 3600 15
194 25 3x3x6 1800 3 3x3x6 1800 3
194 50 3x3x8 1800 5 3x3x8 1800 5
194 75 3x3x6 3600 7.5 3x3x6 3600 7.5
194 100 2x2x6 3600 10 2x2x6 3600 10
194 125 2x2x8 3600 15 2x2x8 3600 15
311 25 4x4x6 1800 3 4x4x6 1800 3
AGZ 130D 129.6 311 194 518 311 50 3x3x8 1800 7.5 3x3x8 1800 7.5
311 75 3x3x8 3600 10 3x3x8 3600 10
311 100 4x4x6 3600 15 4x4x6 3600 15
415 25 3x3x6 3600 7.5 4x4x8 3600 10
415 50 4x4x6 3600 10 4x4x8 3600 10
415 75 4x4x6 3600 15 4x4x6 3600 15
415 100 4x4x6 3600 15 4x4x6 3600 15
204 50 3x3x8 1800 5 3x3x8 1800 5
204 75 3x3x6 3600 7.5 3x3x6 3600 7.5
204 100 3x3x6 3600 10 4x4x6 3600 15
204 125 3x3x6 3600 15 3x3x6 3600 15
327 50 3x3x8 1800 7.5 3x3x8 1800 7.5
327 75 3x3x8 3600 10 3x3x8 3600 10
AGZ 140D 136.2 327 204 545
327 100 4x4x6 3600 15 4x4x6 3600 15
327 125 3x3x8 3600 20 3x3x8 3600 20
436 25 4x4x8 1800 5 4x4x8 1800 5
436 50 4x4x8 1800 10 4x4x8 1800 10
436 75 4x4x6 3600 15 4x4x6 3600 15
436 100 3x3x8 3600 20 3x3x8 3600 20
Note: Some unit gpm and head combination do not have a valid selection and are absent from the table.
IM 1110-2 13
Selection Procedures
Table 3: AGZ-D Unit/Pump Combinations Continued
Unit Nom. Nom. Min. Max. Unit Total Head Single Pump Dual Pumps
Model Tons gpm gpm gpm gpm ft. Size rpm HP Size rpm HP
230 50 3x3x8 1800 5 3x3x8 1800 5
230 75 3x3x6 3600 7.5 3x3x6 3600 7.5
230 100 3x3x6 3600 15 3x3x6 3600 15
230 125 3x3x8 3600 15 3x3x8 3600 15
368 25 4x4x6 1800 5 4x4x6 1800 5
368 50 4x4x8 1800 10 4x4x8 1800 10
AGZ 160D 153.3 368 230 613 368 75 4x4x6 3600 15 4x4x6 3600 15
368 100 4x4x6 3600 15 4x4x6 3600 15
368 125 3x3x8 3600 20 3x3x8 3600 20
491 25 4x4x8 1800 7.5 4x4x8 1800 7.5
491 50 4x4x8 1800 10 4x4x8 1800 10
491 75 4x4x6 3600 15 4x4x6 3600 15
491 100 3x3x8 3600 20 3x3x8 3600 20
258 50 3x3x8 1800 5 3x3x8 1800 5
258 75 3x3x6 3600 7.5 3x3x6 3600 7.5
258 100 4x4x6 3600 15 4x4x6 3600 15
258 125 3x3x8 3600 20 3x3x8 3600 20
413 25 4x4x8 1800 5 4x4x8 1800 5
413 50 4x4x8 1800 10 4x4x8 1800 10
AGZ 180D 172.2 413 258 689 413 75 4x4x6 3600 15 4x4x6 3600 15
413 100 4x4x6 3600 15 4x4x6 3600 15
413 125 3x3x8 3600 20 3x3x8 3600 20
551 25 4x4x8 1800 7.5 4x4x8 1800 7.5
551 50 4x4x8 1800 10 4x4x8 1800 10
551 75 4x4x6 3600 15 4x4x6 3600 15
551 100 4x4x6 3600 20 4x4x6 3600 20
270 50 3x3x8 1800 7.5 3x3x8 1800 7.5
270 75 3x3x6 3600 10 3x3x6 3600 10
270 100 4x4x6 3600 15 4x4x6 3600 15
270 125 3x3x8 3600 20 3x3x8 3600 20
432 25 4x4x8 1800 5 4x4x8 1800 5
432 50 4x4x8 1800 10 4x4x8 1800 10
AGZ 190D 180.1 432 270 720
432 75 4x4x6 3600 15 4x4x6 3600 15
432 100 3x3x8 3600 20 3x3x8 3600 20
576 25 4x4x8 1800 7.5 4x4x8 1800 7.5
576 50 4x4x8 1800 15 4x4x8 1800 15
576 75 4x4x6 3600 15 4x4x6 3600 15
576 100 4x4x6 3600 20 4x4x6 3600 20
Note: Some unit gpm and head combination do not have a valid selection and are absent from the table.
14 IM 1110-2
Pressure Drop Data
Figure 5: Pressure Drop Curves
Pressure Drop Data
100 A
B
C
D
U
E
F T
G F S
CD E G J K L M NO P Q
H B H R
I
I
A
J
K
L
M
)t
(f 1 0 N
p
D O U
P T
Q F S
R CD E G H J K L M NO P Q
B R
S I
T A
U
1
10 100 1000
F lo w R a te (g p m )
IM 1110-2 15
Installation Information
This section provides additional information on optional pump Flush the system water piping thoroughly before making
Installation Information
packages factory-mounted on Daikin Model AGZ-D (REV connections to the unit evaporator.
0A) scroll compressor chillers. The current chiller installation,
System Water Volume
operating, and maintenance manuals are available at
www.DaikinApplied.com. It is important to have adequate water volume in the system to
provide an opportunity for the chiller to sense a load change,
Inspection adjust to the change and stabilize. As the expected load change
When the equipment is received, carefully check all items becomes more rapid, a greater water volume is needed. The
against the bill of lading to check for a complete shipment. system water volume is the total amount of water in the
Check all units for damage upon arrival. All shipping damage evaporator, air handling products and associated piping. If the
must be reported to the carrier and a claim must be filed with water volume is too low, operational problems can occur
the carrier. Check the unit's serial plate before unloading the including rapid compressor cycling, rapid loading and
unit to be sure that it agrees with the power supply available. unloading of compressors, erratic refrigerant flow in the
Physical damage to unit after acceptance is not the chiller, improper motor cooling, shortened equipment life and
responsibility of Daikin Applied. other undesirable occurrences.
Note: Installation and maintenance are to be performed only For normal comfort cooling where the cooling load changes
by qualified personnel who are familiar with local codes and relatively slowly, we recommend a minimum system volume
regulations, and experienced with this type of equipment. in gallons of 2 to 3 times the flow rate (gpm). For example, if
the design chiller flow rate is 350 gpm, we recommend a
Handling and Rigging
minimum system volume of 700 to 1050 gallons.
Follow the directions in IM 1100 for locating, handling and Since there are many other factors that can influence
rigging the unit. The addition of the optional pump package performance, systems can successfully operate below these
does not change installation procedure. However, vibration suggestions. However, as the water volume decreases below
isolator selection and location, lifting and operating weights, these suggestions, the possibility of problems increases.
dimensions, and electrical data will differ from units without a
pump package. Refer to dimension drawings for center-of- Freeze Protection
gravity locations. In installations where the unit is subject to sub-freezing
temperatures, some method of preventing pipe and component
Field Water Piping
freezing and subsequent damage is required. The pump will
Piping design must be provided by a qualified Architect or start on a signal from the chiller controller when either the
Systems HVAC Design Engineer familiar with piping design, chilled water leaving or entering temperature reaches the
as well as local codes and regulations. The manufacturer chiller freeze point setting to help prevent freeze up. If
recommendations are to be used as a general guide, but do not constant chilled water circulation is not possible or desired,
replace system design by a qualified professional. All field one or more of the following procedures must be used:
piping, wiring, and procedures must be performed in
• Drain the outdoor portion of the system and cap with a
accordance with ASHRAE, EPA, and industry standards.
nitrogen charge.
Use best practice for piping design with a minimum number of
• Heat trace all outdoor components.
bends and changes in elevation to keep system cost down and
performance up. See AGZ-D installation manual, IM 1100, for • Add sufficient anti-freeze to prevent freezing.
general unit piping information. Note: the evaporator is equipped with a water heater to help
The chilled water piping contains vent and drain connections protect from freezing. This heater does not protect the pump
as well as taps for inlet and outlet pressure gauges. Install a package piping or components.
manual or automatic vent and a drain valve. Install a single, Adding of a concentration of a glycol anti-freeze with a freeze
valved pressure gauge as shown in the chiller unit installation point 10°F below the lowest expected outdoor temperature will
manual. The unit inlet and outlet connections are marked. It is result in decreased capacity and increased pressure drop in the
prudent to double check the unit dimension drawing to confirm chiller. AGZ units are selected to provide the required
the connections. capacity with the fluid specified when selected.
The inlet guide and the outlet triple duty valve are shipped Temporary Strainer
separately to protect them from shipping damage. Install on The suction guide strainer contains a tempory strainer that
the unit and support as necessary. Support the chilled water must be removed after startup. See page 81 in the Startup and
piping independently from the unit. Shutdown section. for complete instructions.
CAUTION
Improper rigging, lifting, or moving of a unit can result in property damage, severe personal injury or death. Follow rigging
and moving instructions carefully. Do not use automotive grade antifreezes as it contains inhibitors harmful to chilled water
systems. Use only glycols designated for use in building cooling systems.
16 IM 1110-2
Unit Weights
Lifting Locations
AGZ025D-180D - Approximate Lifting Locations AGZ190D - Approximate Lifting Locations
See Dimension Drawing for location See Dimension Drawing for location
L3 L1 L5 L3 L1
CONTROL PANEL
CONTROL PANEL
L4 L2 L6 L4 L2
Unit Weights
IM 1110-2 17
Unit Weights
Operating Weights & Vibration Isolators Installation of spring isolators requires flexible pipe
connections and at least three feet of conduit flex tie-ins.
Vibration isolators are recommended for all roof-mounted Support piping and conduit independently from the unit to not
installations or wherever vibration transmission is a stress connections. Mounting locations are on the unit
consideration. Initially install the unit on shims or blocks at the dimension drawings beginning on page 23. Isolator selections
"free height" of the isolator. When all piping, wiring, flushing, are different for AGZ-D units with a pump package than those
charging, etc. is complete, adjust the springs upward to load without one.
them and to provide clearance to free the blocks, which are
then removed.
Table 6: Operating and Mounting Weights
MOUNTING WEIGHT BY LOCATION (AL FIN COILS)
OPERATING WEIGHT
(SEE NOTE FOR COPPER FIN COILS)
UNIT MODEL ALUMINUM COPPER FIN
M1 M2 M3 M4 M5 M6 M7 M8
FIN COILS COILS
LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG
AGZ025D 4404 1998 4722 2142 1040 472 1127 511 1074 487 1164 528 - - - - - - - -
AGZ030D 4436 2012 4754 2156 1058 480 1120 508 1097 498 1161 527 - - - - - - - -
AGZ035D 4446 2017 4764 2161 1067 484 1116 506 1106 502 1157 525 - - - - - - - -
AGZ040D 4526 2053 5060 2295 1075 488 1138 516 1123 509 1189 539 - - - - - - - -
AGZ045D 4686 2126 5220 2368 1113 505 1180 535 1162 527 1231 558 - - - - - - - -
AGZ050D 4766 2162 5300 2404 1137 516 1203 546 1178 534 1247 566 - - - - - - - -
AGZ055D 4796 2175 5330 2418 1144 519 1212 550 1184 537 1255 569 - - - - - - - -
AGZ060D 4921 2232 5455 2474 1172 532 1254 569 1206 547 1290 585 - - - - - - - -
AGZ065D 4956 2248 5592 2536 1179 535 1268 575 1209 548 1300 590 - - - - - - - -
AGZ070D 5366 2434 6002 2722 1323 600 1285 583 1400 635 1359 616 - - - - - - - -
AGZ080D 6850 3107 7650 3470 1854 841 1748 793 1672 758 1576 715 - - - - - - - -
AGZ090D 6945 3150 7899 3583 1850 839 1738 788 1731 785 1626 738 - - - - - - - -
AGZ100D 7080 3211 8034 3644 1900 862 1808 820 1728 784 1644 746 - - - - - - - -
AGZ110D (208/230) 8694 3944 9766 4430 1412 640 1416 642 1447 656 1451 658 1482 672 1486 674 - - - -
AGZ125D (208/230) 8929 4050 10205 4629 1470 667 1453 659 1497 679 1479 671 1524 691 1506 683 - - - -
AGZ130D (208/230) 9074 4116 10350 4695 1510 685 1531 694 1502 681 1523 691 1494 678 1514 687 - - - -
AGZ110D (460/575) 8634 3916 9706 4403 1379 626 1378 625 1439 653 1439 653 1500 680 1499 680 - - - -
AGZ125D (460/575) 8869 4023 10145 4602 1435 651 1413 641 1490 676 1467 665 1545 701 1521 690 - - - -
AGZ130D (460/575) 9014 4089 10290 4667 1476 670 1491 676 1495 678 1510 685 1513 686 1528 693 - - - -
AGZ140D 11929 5411 13525 6135 1636 742 1717 779 1524 691 1600 726 1390 630 1459 662 1270 576 1333 605
AGZ160D 12079 5479 13675 6203 1690 767 1744 791 1564 709 1614 732 1413 641 1458 661 1278 580 1319 598
AGZ180D 12244 5554 13840 6278 1731 785 1815 823 1585 719 1661 753 1409 639 1478 670 1252 568 1313 596
AGZ190D 13093 5939 15008 6808 1719 780 1780 807 1650 748 1709 775 1577 715 1633 741 1486 674 1539 698
NOTE: For AGZ025-100D (4 mounting points): to calculate corner mounting w eights for units w ith copper fin coils add 1/4 of the copper vs. aluminum operating
w eight to each aluminum mounting w eight. For AGZ110-130D (6 mounting points):: to calculate corner mounting w eights for units w ith copper fin coils add 1/6 of
the copper vs. aluminum operating w eight to each aluminum mounting w eight. For AGZ140-190D (8 Mounting Points): to calculate corner mounting w eights for
units w ith copper fin coils add 1/8 of the copper vs. aluminum operating w eight to each aluminum mounting w eight.
18 IM 1110-2
Vibration Isolators
Figure 6: RP-4 Rubber-in-Shear Isolator Dimensions
Vibration Isolators
6.25
5.00
3.75
3.00 ø .500-13NC-2B
R4
4.63
3.87 VM&C
VM&C
.56 TYP. R.28
TYP.
R4
R.250 TYP.
RECESSED
GRIP RIBS R.750 TYP.
DURULENE
MATERIAL
1.13 ± .25
APPROX.
1.63
.38
IM 1110-2 19
Vibration Isolators
Figure 7: C2P
20 IM 1110-2
Triple Duty Valve
Figure 8: Triple Duty Discharge Valve Diagram
Triple Duty Valve
Flow Indicator
Bonnet “O” Ring
Flow /Temperate
Measurement orts
Drain Connections High Strength Resin
(on opposite side) Seat EPDM for 8”
and larger
Bronze Disc
Determining Flow Rate - Valve In Full Open Position To calculate flow rate of valve in the throttled position,
Measure and record the differential pressure across the valve multiply the flow rate by the percentage flow rate divided by
using a CBDM- 135/60 meter, or pressure gauges with PMP 100.
adapters. Example:
CAUTION • Valve size 4 inch.
• Differential Pressure is 5.4 ft. (1.65 m).
Safety glasses should be used and the probe should not be left
inserted into fittings for prolonged periods of time as leakage • Number of rings open = 3. Therefore: 3 rings ÷ 6 rings x
from the PMP may occur when probe is removed. 100 = 50% throttled.
From the Performance Curve (Figure 9), a 4 inch, valve
Locate Pressure Differential on left hand side of Performance with 5.4 ft. pressure drop (1.65 m) represents a flow of 400
Curve (Figure 9) and extend line horizontally across to valve USgpm (25.2 l/s).
size being used. Drop line vertically down and read flow rate From Flow Characteristic Curve (Figure 10)., a 4 inch
from bottom of chart. valve 50% open, represents 34% of maximum flow.
Approximate flow of a 4 inch valve, with a 5.4 ft. (1.65 m)
Determining Flow Rate - Valve In Throttled Position pressure drop when 50% throttled is:
Record the size of the valve and stem position using the Flow 400 x 34/100 = 136USgpm
Indicator Scale. Calculate percentage of valve opening or in metric, 25.2 x 34100 = 8.57l/s
referring to table below: Note: To prevent premature valve failure it is not
Table 11: Valve Size and Number of Rings
recommended that the valve operate in the throttled position
Valve Size 2 1/2 3 4 5 6 8 10 12
with more than 25 ft. pressure differential. Instead the pump
Number of Rings impeller should be trimmed or valves located elsewhere in the
5 5 6 9 10 12 18 28
(valve full open)
system be used to partially throttle the flow.
Measure and record the differential pressure across the valve
in the throttled position. Project a line vertically up to intersect Flow Indicator Scale
with the Valve Curve and from this point project line The valve stem with its grooved
horizontally across to the left of the chart and record the rings and positioning sleeve
percentage of maximum flow rate. indicates the throttled position of
the valve. The quarter turn
On the Performance Curve (Figure 9) locate the differential
graduations on the sleeve, with the
pressure obtained above and project a line horizontally across
scribed line on the stem provides
to intercept with Valve Performance Curve. Drop a line
for approximate flow measurement.
vertically down to read the flow rate at the bottom of the chart.
Note: The valve is shipped in the closed position. The
indicator on the plastic sleeve is aligned with the vertical
scribed line on the stem.
IM 1110-2 21
Triple Duty Valve
Figure 9: Performance Curve - Valve in Full Open Position
Performance Curve
with Valve in Full Open Position
3 10 10
5.0 5.0
2.0 2.0
.5 50 100 500 1000 2000 4000 6000
FLOWRATE (USGPM)
80
PERCENT OF MAX FLOW
60
40
20
0
0 20 40 60 80 100
PERCENT OF FULL OPEN
22 IM 1110-2
Dimensions
Figure 11: AGZ025D - AGZ070D with Pump Package (COG dimensions on page 29 )
Dimensions
M3 M1
COMPRESSORS
CIRCUIT #2
COMPRESSORS
CIRCUIT #1
PUMPS
EVAP
19
.75
QTY. 4
NOTES:
290 L4 L2
11.4 M4 M2 52 1. SUCTION STRAINER, SHUT OFF VALVE AND TRIPLE DUTY VALVE WILL BE SHIPPED LOOSE
2.0 FOR FIELD INSTALLATION.
2. DUE TO VARIATIONS IN PUMP SIZE, OPERATING WEIGHT WITH WATER MAY VARY UP TO 5%.
SEE NOTE 1. 3. TO CALCULATE CORNER LIFTING WEIGHTS FOR UNITS WITH COPPER FIN COILS: ADD
1/4 OF THE COPPER VS. ALUMINUM SHIPPING WEIGHT TO EACH ALUMINUM LIFTING
CORNER WEIGHTS.
506 L3 L1 506
19.9 L4 L2 19.9 CONTROL
BOX
693 823
27.3 32.4
Z
2396
94.3
498 64
19.6 2.5
FIELD CONTROL 64 POWER ENTRY POINTS
CONNECTIONS 2.5 .875" KNOCKOUTS 2538
.875" KNOCKOUTS FRONT OR RIGHT SIDE 99.9
CG 2408
94.8
1094 1094
43.1 43.1
165 366
6.5 14.4
PUMP
CONTROL X
PANEL
2235 CERT. DWG, AGZ-D 4 FANS R410A, w/PUMPS
88.0 *331749211001*
DIMENSION DOES NOT INCLUDE
LIFTING BRACKETS
IM 1110-2 23
Dimensions
Figure 12: AGZ075D - AGZ080D with Pump Package (COG dimensions on page 29 )
52
2.0
SEE NOTE 1.
COMPRESSORS
CIRCUIT #2
EVAP
19 COMPRESSORS
.75 CIRCUIT #1
PUMPS
QTY. 4
L4 L2 52
M4 M2 2.0
51 NOTES:
2.0
127 1. SUCTION STRAINER, SHUT OFF VALVE AND TRIPLE DUTY VALVE
5.0 WILL BE SHIPPED LOOSE FOR FIELD INSTALLATION.
492 2. DUE TO VARIATIONS IN PUMP SIZE, OPERATING WEIGHT
19.4 WITH WATER MAY VARY UP TO 5%.
CG
3. TO CALCULATE CORNER LIFTING WEIGHTS FOR UNITS
WITH COPPER FIN COILS: ADD 1/4 OF THE COPPER VS.
ALUMINUM SHIPPING WEIGHT TO EACH ALUMINUM
LIFTING WEIGHT.
SEE 1186
NOTE 1. Y 46.7
206
CONTROL BOX WIDTH
8.1 REF.
L3 L1
L4 L2 POWER ENTRY POINTS
442 610 .875 KNOCKOUTS
17.4 24.0 610 CONTROL FRONT AND RIGHT SIDE
24.0 BOX
Z
3426
134.9
497
19.6 64
2.5
FIELD CONTROL
CONNECTIONS 64
.875 KNOCKOUTS 2.5 2537
76 99.9
CG
3.0
EVAP WATER 2413
INLET 95.0
VICTAULIC 1094 1094
CONNECTION 43.1 43.1
24 IM 1110-2
Dimensions
Figure 13: AGZ090D - AGZ100D with Pump Package (COG dimensions on page 29 )
52
2.0
EVAP
19 COMPRESSORS
.75 CIRCUIT #1
PUMPS
QTY. 4
L4 L2 52
2.0
M4 M2
80
3.1 POWER ENTRY POINTS
OPPOSITE SIDE OF
CONTROL BOX.
.875 KNOCKOUTS
51
2.0
127 NOTES:
5.0
493
1. SUCTION STRAINER, SHUT OFF VALVE AND TRIPLE DUTY VALVE
19.4
CG WILL BE SHIPPED LOOSE FOR FIELD INSTALLATION.
2. DUE TO VARIATIONS IN PUMP SIZE, OPERATING WEIGHT
WITH WATER MAY VARY UP TO 5%.
3. TO CALCULATE CORNER LIFTING WEIGHTS FOR UNITS
SEE 1186 WITH COPPER FIN COILS: ADD 1/4 OF THE COPPER VS.
NOTE 1. Y 46.7 ALUMINUM SHIPPING WEIGHT TO EACH ALUMINUM
LIFTING WEIGHT.
L3 L1
442 610 L4 L2
17.4 24.0 610
24.0 206
CONTROL BOX WIDTH
8.1 REF.
Z
POWER ENTRY POINTS
3426 .875 KNOCKOUTS
134.9 CONTROL
FRONT AND RIGHT SIDE
BOX
497
102 19.6 64
4.0 2.5
EVAP WATER FIELD CONTROL
INLET CONNECTIONS 64
.875 KNOCKOUTS 2.5 2537
VICTAULIC
CONNECTION 99.9
CG
2413
95.0
1094 1094
816 43.1 43.1
32.1
290
11.4
165 366
102 PUMP 6.5 14.4
1258 331749212
4.0 CONTROL X
49.5
EVAP WATER PANEL CERT. DWG. AGZ-D 6 FANS, R410A w/PUMPS
OUTLET 2235
VICTAULIC 88.0
CONNECTION DIMENSION DOES NOT INCLUDE
LIFTING BRACKETS
IM 1110-2 25
Dimensions
Figure 14: AGZ110D - AGZ130D with Pump Package (COG dimensions on page 29 )
52
2.0
EVAP
COMPRESSORS
CIRCUIT #2
SEE NOTE 1.
COMPRESSORS
CIRCUIT #1
PUMPS
19
.75 52
QTY. 6 2.0
L4 L2
M6 M4 M2
POWER ENTRY POINTS
ARE ON THE OPPOSITE
SIDE OF CONTROL BOX.
.875" KNOCKOUTS
51
127
2.0
5.0
NOTES:
CG
1. SUCTION STRAINER, SHUT OFF VALVE AND TRIPLE DUTY VALVE
WILL BE SHIPPED LOOSE FOR FIELD INSTALLATION.
1209 2. DUE TO VARIATIONS IN PUMP SIZE, OPERATING WEIGHT
Y 47.6 WITH WATER MAY VARY UP TO 5%.
3. TO CALCULATE CORNER LIFTING WEIGHTS FOR UNITS
WITH COPPER FIN COILS: ADD 1/4 OF THE COPPER VS.
ALUMINUM SHIPPING WEIGHT TO EACH ALUMINUM
LIFTING WEIGHT.
L3 L1
L4 L2 610
610 24.0
24.0
Z
POWER ENTRY POINTS
CONTROL .875" KNOCKOUTS
4396 BOX FRONT AND RIGHT SIDE
173.1
299 64
102 11.8 2.5
4.0 FIELD CONTROL 64
EVAP WATER CONNECTIONS 2.5
INLET .875" KNOCKOUTS
VICTAULIC 2538
CONNECTION 99.9
2413
CG 95.0
165
102 6.5 167
PUMP
4.0 1118 CONTROL 6.6
44.0 X
EVAP WATER PANEL
OUTLET 2235
VICTAULIC 331749213 88.0
CONNECTION CERT. DWG, AGZ-D 8 FANS, R410A, w/PUMPS DIMENSION DOES NOT
INCLUDE LIFTING BRACKETS
26 IM 1110-2
Dimensions
Figure 15: AGZ140D - AGZ180D with Pump Package (COG dimensions on page 29 )
NOTES:
1. SUCTION STRAINER, SHUT OFF VALVE AND TRIPLE DUTY VALVE
WILL BE SHIPPED LOOSE FOR FIELD INSTALLATION.
2. DUE TO VARIATIONS IN PUMP SIZES, OPERATING WEIGHT
WITH WATER IS APPROXIMATE AND MAY VARY UP TO 5%.
3. TO CALCULATE L1 THRU L6 LIFTING WEIGHTS FOR UNITS
WITH COPPER FIN COILS: ADD 1/6 OF THE COPPER VS.
ALUMINUM SHIPPING WEIGHT TO EACH L1 THRU L6
ALUMINUM LIFTING WEIGHT.
COMPRESSORS
CIRCUIT #2
COMPRESSORS
CIRCUIT #1
52
2.0
L6 L4 L2
M8 M6 M4 M2
PUMPS POWER ENTRY POINTS
ARE ON THE OPPOSITE
SIDE OF CONTROL BOX.
.875" KNOCKOUTS
50" COILS
51
2.0
86 127
3.4 5.0
SEE NOTE 1.
CG
1209
47.6
EVAP Y
L5 L3 L1
L6 L4 L2
394 2252 3552 610
15.5 88.7 139.8 24.0
Z
POWER ENTRY POINTS
6808 .875" KNOCKOUTS
FRONT AND RIGHT SIDE
268.0
CONTROL
BOX
1116 1116
43.9 43.9
432
17.0
822 508
165
32.4 20.0 167
PUMP 6.5
6.6
CONTROL
102 PANEL X
4.0
EVAP WATER 2235
INLET 88.0
VICTAULIC CONNECTION DIMENSION DOES NOT
INCLUDE LIFTING BRACKETS
IM 1110-2 27
Dimensions
Figure 16: AGZ190D with Pump Package (COG dimensions on page 29 )
NOTES:
M7 M5 M3 M1
378 2286 1826 1719 315
14.9 90.0 71.9 67.7 12.4
L5 L3 L1
19 52
.75 2.0
QTY. 8
COMPRESSORS
CIRCUIT #2
SEE NOTE 1.
COMPRESSORS
CIRCUIT #1
52
2.0
L6 L4 L2
PUMPS
M8 M6 M4 M2
POWER ENTRY POINTS
ARE ON THE OPPOSITE
SIDE OF CONTROL BOX.
86 .875" KNOCKOUTS
50" 3.4
COILS
51
2.0 127
5.0
CG
Y 1209
EVAP 47.6
L5 L3 L1
L6 L4 L2
299 64
11.8 2.5
FIELD CONTROL 64
CONNECTIONS
.875" KNOCKOUTS 2.5
102 2538
4.0 CG 2413 99.9
EVAP WATER 95.0
INLET
VICTAULIC 1116 1116
CONNECTION 43.9 43.9
432
17.0
28 IM 1110-2
Dimensions
Table 12: Center of Gravity Dimensions
IM 1110-2 29
Electrical Information
Figure 17: Pump Panel Wiring Diagram with Dual Pumps/Dual Control
Electrical Information
Power Wiring Control wiring to start and stop the pump(s) is always factory
wired from the chiller electric panel to the pump package.
As standard, power to the pump package control panel is Dual pumps have two output signals and single pumps have
factory wired from the chiller electrical panel. When the one.
optional chiller multi-point power wiring is specified, the
pump power originates from power circuit #1. The pump panel schematic, Figure 28, shows the standard dual
pump arrangement. Optionally a VFD can be substituted for
There is an option for field power wiring the pumps in lieu of the contacts shown. A VFD line reactor can also be added.
factory wiring. In this case the necessary electrical data begins
in Table 11 on page 40. In all cases, field power wiring A single pump can be ordered, in which case only one run
connections are made to L1, L2, L3 and GND on the pump signal is factory wired in.
panel circuit breaker. VFD Option, the VFD will require field wiring if the optional
Power wiring to the chiller unit will be as shown in the chiller BAS control is used or if the VFD is wired to field-mounted
catalog and installation manual. differential switches. The pump BAS protocol will be the same
as specified for the chiller unit. The standard sensorless
Control Wiring arrangement does not require field wiring.
Control wiring to the chiller unit will be as shown in the chiller For BAS connection, use RS485 and wire to terminals 68 (+)
catalog and installation manual except that the flow switch and and 69 (-) for Modbus, FLN or Metasys protocols. The
pump output signals shown as field wiring will be factory terminals are located in the lower-right corner of the pump-
wired. mounted VFD enclosure under the keypad.
30 IM 1110-2
Electrical Information
Table 13: Electrical Data - Single Point
Pum p R a t in g s L u g Ran g e
M odel V o lt a g e
HP FL A M CA RFS M FS P o w e r B lo c k ( 1 ) D is c o n n e c t S w it c h ( 1 )
208V 4 .6 154 175 175 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
230V 4 .2 153 175 175 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
1 .0
460V 2 .1 76 90 90 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
575V 1 .7 66 70 70 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
208V 6 .6 156 175 175 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
230V 6 .0 155 175 175 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
1 .5
460V 3 .0 77 90 90 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
575V 2 .4 67 70 70 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
208V 7 .5 157 175 175 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
A GZ 025D 230V 6 .8 156 175 175 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
2 .0
P UM P 460V 3 .4 78 90 90 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
575V 2 .7 67 70 70 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
208V 1 0 .6 160 175 175 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
230V 9 .6 159 175 175 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
3 .0
460V 4 .8 79 90 90 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
575V 3 .9 68 80 80 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
208V 1 6 .7 166 175 175 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
230V 1 5 .2 164 175 175 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
5 .0
460V 7 .6 82 90 90 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
575V 6 .1 70 80 80 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
208V 4 .6 163 175 175 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
230V 4 .2 156 175 175 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
1 .0
460V 2 .1 85 100 100 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
575V 1 .7 69 80 80 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
208V 6 .6 165 175 175 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
230V 6 .0 158 175 175 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
1 .5
460V 3 .0 86 100 100 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
575V 2 .4 70 80 80 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
208V 7 .5 165 175 175 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
A GZ 030D 230V 6 .8 158 175 175 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
2 .0
P UM P 460V 3 .4 86 100 100 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
575V 2 .7 70 80 80 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
208V 1 0 .6 169 175 175 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
230V 9 .6 161 175 175 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
3 .0
460V 4 .8 87 100 100 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
575V 3 .9 72 80 80 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
208V 1 6 .7 175 200 200 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
230V 1 5 .2 167 175 175 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
5 .0
460V 7 .6 90 100 100 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
575V 6 .1 74 80 80 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
208V 6 .6 175 200 200 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
230V 6 .0 171 200 200 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
1 .5
460V 3 .0 88 100 100 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
575V 2 .4 70 80 80 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
208V 7 .5 176 200 200 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
230V 6 .8 172 200 200 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
2 .0
460V 3 .4 89 100 100 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
575V 2 .7 70 80 80 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
208V 1 0 .6 179 200 200 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
A GZ 035D 230V 9 .6 174 200 200 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
3 .0
P UM P 460V 4 .8 90 100 100 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
575V 3 .9 72 80 80 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
208V 1 6 .7 185 200 200 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
230V 1 5 .2 180 200 200 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
5 .0
460V 7 .6 93 110 110 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
575V 6 .1 74 80 80 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
208V 2 4 .2 193 225 225 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
230V 2 2 .0 187 200 200 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
7 .5
460V 1 1 .0 96 110 110 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
575V 9 .0 77 80 80 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
Note: Power block and disconnect switch sizes are minimums. Larger sizes may be used, however the lug range must be the same.
IM 1110-2 31
Electrical Information
Table 14: Electrical Data - Single Point (Continued)
Pum p R a t in g s L u g Ran g e
M odel V o lt a g e
HP FL A M CA RFS M FS P o w e r B lo c k ( 1 ) D is c o n n e c t S w it c h ( 1 )
208V 6 .6 185 200 200 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
230V 6 .0 183 200 200 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
1 .5
460V 3 .0 91 100 100 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
575V 2 .4 70 80 80 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
208V 7 .5 185 200 200 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
230V 6 .8 183 200 200 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
2 .0
460V 3 .4 91 100 100 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
575V 2 .7 70 80 80 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
208V 1 0 .6 189 200 200 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
A GZ 040D 230V 9 .6 186 200 200 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
3 .0
P UM P 460V 4 .8 93 110 110 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
575V 3 .9 72 80 80 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
208V 1 6 .7 195 225 225 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
230V 1 5 .2 192 225 225 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
5 .0
460V 7 .6 95 110 110 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
575V 6 .1 74 80 80 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
208V 2 4 .2 202 225 225 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
230V 2 2 .0 199 225 225 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
7 .5
460V 1 1 .0 99 110 110 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
575V 9 .0 77 80 80 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
208V 6 .6 235 250 250 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 6 .0 234 250 250 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
1 .5
460V 3 .0 95 110 110 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
575V 2 .4 79 90 90 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
208V 7 .5 236 250 250 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 6 .8 235 250 250 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
2 .0
460V 3 .4 95 110 110 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
575V 2 .7 79 90 90 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
208V 1 0 .6 239 250 250 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
A GZ 045D 230V 9 .6 238 250 250 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
3 .0
P UM P 460V 4 .8 97 110 110 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
575V 3 .9 81 90 90 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
208V 1 6 .7 245 250 250 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 1 5 .2 243 250 250 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
5 .0
460V 7 .6 100 110 110 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
575V 6 .1 83 90 90 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
208V 2 4 .2 252 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 2 2 .0 250 250 250 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
7 .5
460V 1 1 .0 103 110 110 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
575V 9 .0 86 100 100 ( 1 ) 2 /0 - # 1 4 ( 1 ) 1 /0 - # 1 4
208V 6 .6 255 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 6 .0 254 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
1 .5
460V 3 .0 113 125 125 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
575V 2 .4 99 110 110 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
208V 7 .5 256 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 6 .8 255 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
2 .0
460V 3 .4 113 125 125 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
575V 2 .7 100 110 110 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
208V 1 0 .6 259 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
A GZ 050D 230V 9 .6 258 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
3 .0
P UM P 460V 4 .8 115 125 125 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
575V 3 .9 101 110 110 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
208V 1 6 .7 265 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 1 5 .2 263 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
5 .0
460V 7 .6 117 125 125 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
575V 6 .1 103 110 110 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
208V 2 4 .2 272 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 2 2 .0 270 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
7 .5
460V 1 1 .0 121 125 125 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
575V 9 .0 106 125 125 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
Note: Power block and disconnect switch sizes are minimums. Larger sizes may be used, however the lug range must be the same.
32 IM 1110-2
Electrical Information
Table 15: Electrical Data - Single Point (Continued)
Pum p R a t in g s L u g Ran g e
M odel V o lt a g e
HP FL A M CA RFS M FS P o w e r B lo c k ( 1 ) D is c o n n e c t S w it c h ( 1 )
208V 6 .6 263 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 6 .0 261 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
1 .5
460V 3 .0 121 125 125 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
575V 2 .4 108 125 125 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
208V 7 .5 264 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 6 .8 262 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
2 .0
460V 3 .4 122 125 125 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
575V 2 .7 108 125 125 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
208V 1 0 .6 267 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
A GZ 055D 230V 9 .6 264 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
3 .0
P UM P 460V 4 .8 123 125 125 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
575V 3 .9 109 125 125 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
208V 1 6 .7 273 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 1 5 .2 270 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
5 .0
460V 7 .6 126 150 150 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
575V 6 .1 112 125 125 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
208V 2 4 .2 281 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 2 2 .0 277 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
7 .5
460V 1 1 .0 129 150 150 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
575V 9 .0 115 125 125 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
208V 7 .5 272 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 6 .8 268 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
2 .0
460V 3 .4 129 150 150 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
575V 2 .7 116 125 125 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
208V 1 0 .6 275 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 9 .6 270 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
3 .0
460V 4 .8 131 150 150 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
575V 3 .9 117 125 125 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
208V 1 6 .7 281 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
A GZ 060D 230V 1 5 .2 276 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
5 .0
P UM P 460V 7 .6 134 150 150 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
575V 6 .1 119 125 125 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
208V 2 4 .2 288 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 2 2 .0 283 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
7 .5
460V 1 1 .0 137 150 150 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
575V 9 .0 122 125 125 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
208V 3 0 .8 295 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 2 8 .0 289 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
1 0 .0
460V 1 4 .0 140 150 150 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
575V 1 1 .0 124 125 125 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
208V 7 .5 280 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 6 .8 276 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
2 .0
460V 3 .4 133 150 150 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
575V 2 .7 116 125 125 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
208V 1 0 .6 283 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 9 .6 278 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
3 .0
460V 4 .8 134 150 150 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
575V 3 .9 117 125 125 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
208V 1 6 .7 289 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
A GZ 065D 230V 1 5 .2 284 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
5 .0
P UM P 460V 7 .6 137 150 150 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
575V 6 .1 119 125 125 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
208V 2 4 .2 296 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 2 2 .0 291 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
7 .5
460V 1 1 .0 140 150 150 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
575V 9 .0 122 125 125 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
208V 3 0 .8 303 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 2 8 .0 297 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
1 0 .0
460V 1 4 .0 143 150 150 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
575V 1 1 .0 124 125 125 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
Note: Power block and disconnect switch sizes are minimums. Larger sizes may be used, however the lug range must be the same.
IM 1110-2 33
Electrical Information
Table 16: Electrical Data - Single Point (Continued)
Pum p R a t in g s L u g Ran g e
M odel V o lt a g e
HP FL A M CA RFS M FS P o w e r B lo c k ( 1 ) D is c o n n e c t S w it c h ( 1 )
208V 7 .5 315 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 6 .8 313 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
2 .0
460V 3 .4 141 150 150 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
575V 2 .7 119 125 125 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
208V 1 0 .6 318 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 9 .6 316 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
3 .0
460V 4 .8 143 150 150 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
575V 3 .9 120 125 125 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
208V 1 6 .7 324 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
A GZ 070D 230V 1 5 .2 324 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
5 .0
P UM P 460V 7 .6 146 175 175 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
575V 6 .1 123 125 125 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
208V 2 4 .2 332 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 2 2 .0 328 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
7 .5
460V 1 1 .0 149 175 175 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
575V 9 .0 126 150 150 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
208V 3 0 .8 339 400 400 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1
230V 2 8 .0 334 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
1 0 .0
460V 1 4 .0 152 175 175 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
575V 1 1 .0 128 150 150 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
208V 1 0 .6 366 400 400 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1
230V 9 .6 365 400 400 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1
3 .0
460V 4 .8 158 175 175 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
575V 3 .9 129 150 150 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
208V 1 6 .7 372 400 400 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
230V 1 5 .2 370 400 400 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
5 .0
460V 7 .6 161 175 175 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
575V 6 .1 132 150 150 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
208V 2 4 .2 379 450 450 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
A GZ 075D 230V 2 2 .0 377 400 400 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
7 .5
P UM P 460V 1 1 .0 164 175 175 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
575V 9 .0 135 150 150 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
208V 3 0 .8 386 450 450 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
230V 2 8 .0 383 450 450 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
1 0 .0
460V 1 4 .0 167 175 175 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
575V 1 1 .0 137 150 150 ( 1 ) 2 /0 - # 1 4 ( 1 ) 3 /0 - # 1 4
208V 4 6 .2 401 450 450 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
230V 4 2 .0 397 450 450 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
1 5 .0
460V 2 1 .0 174 200 200 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
575V 1 7 .0 143 150 150 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
208V 1 0 .6 403 450 450 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
230V 9 .6 402 450 450 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
3 .0
460V 4 .8 176 200 200 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
575V 3 .9 151 175 175 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
208V 1 6 .7 409 450 450 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
230V 1 5 .2 408 450 450 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
5 .0
460V 7 .6 179 200 200 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
575V 6 .1 153 175 175 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
208V 2 4 .2 417 500 500 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
A GZ 080D 230V 2 2 .0 415 500 500 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
7 .5
P UM P 460V 1 1 .0 182 200 200 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
575V 9 .0 156 175 175 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
208V 3 0 .8 423 500 500 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
230V 2 8 .0 421 500 500 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
1 0 .0
460V 1 4 .0 185 200 200 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
575V 1 1 .0 158 175 175 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
208V 4 6 .2 439 500 500 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
230V 4 2 .0 435 500 500 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
1 5 .0
460V 2 1 .0 192 225 225 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
575V 1 7 .0 164 175 175 ( 1 ) 2 /0 - # 1 4 ( 2 ) 3 0 0 - 1 /0
Note: Power block and disconnect switch sizes are minimums. Larger sizes may be used, however the lug range must be the same.
34 IM 1110-2
Electrical Information
Table 17: Electrical Data - Single Point (Continued)
Pum p R a t in g s L u g Ran g e
M odel V o lt a g e
HP FL A M CA RFS M FS P o w e r B lo c k ( 1 ) D is c o n n e c t S w it c h ( 1 )
208V 1 0 .6 437 500 500 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
230V 9 .6 436 500 500 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
3 .0
460V 4 .8 193 225 225 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
575V 3 .9 170 200 200 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
208V 1 6 .7 443 500 500 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
230V 1 5 .2 441 500 500 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
5 .0
460V 7 .6 195 225 225 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
575V 6 .1 172 200 200 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
208V 2 4 .2 450 500 500 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
A GZ 090D 230V 2 2 .0 448 500 500 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
7 .5
P UM P 460V 1 1 .0 199 225 225 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
575V 9 .0 175 200 200 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
208V 3 0 .8 457 500 500 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
230V 2 8 .0 454 500 500 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
1 0 .0
460V 1 4 .0 202 225 225 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
575V 1 1 .0 177 200 200 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
208V 4 6 .2 472 500 500 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
230V 4 2 .0 468 500 500 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
1 5 .0
460V 2 1 .0 209 250 250 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
575V 1 7 .0 183 200 200 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
208V 1 0 .6 496 600 600 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
230V 9 .6 495 600 600 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
3 .0
460V 4 .8 227 250 250 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
575V 3 .9 203 250 250 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
208V 1 6 .7 502 600 600 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
230V 1 5 .2 501 600 600 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
5 .0
460V 7 .6 230 250 250 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
575V 6 .1 205 250 250 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
208V 2 4 .2 510 600 600 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
A GZ 100D 230V 2 2 .0 507 600 600 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
7 .5
P UM P 460V 1 1 .0 234 250 250 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
575V 9 .0 208 250 250 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
208V 3 0 .8 516 600 600 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
230V 2 8 .0 513 600 600 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
1 0 .0
460V 1 4 .0 237 250 250 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
575V 1 1 .0 210 250 250 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
208V 4 6 .2 532 600 600 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
230V 4 2 .0 527 600 600 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
1 5 .0
460V 2 1 .0 244 250 250 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
575V 1 7 .0 216 250 250 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
208V 1 0 .6 539 600 600 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
230V 9 .6 538 600 600 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
3 .0
460V 4 .8 227 250 250 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
575V 3 .9 186 200 200 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
208V 1 6 .7 545 600 600 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
230V 1 5 .2 544 600 600 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
5 .0
460V 7 .6 229 250 250 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
575V 6 .1 188 200 200 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
208V 2 4 .2 553 600 600 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
A GZ 110D 230V 2 2 .0 550 600 600 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
7 .5
P UM P 460V 1 1 .0 233 250 250 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
575V 9 .0 191 200 200 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
208V 3 0 .8 559 600 600 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
230V 2 8 .0 556 600 600 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
1 0 .0
460V 1 4 .0 236 250 250 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
575V 1 1 .0 193 200 200 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
208V 4 6 .2 575 600 600 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
230V 4 2 .0 570 600 600 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
1 5 .0
460V 2 1 .0 243 250 250 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
575V 1 7 .0 199 200 200 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
Note: Power block and disconnect switch sizes are minimums. Larger sizes may be used, however the lug range must be the same.
IM 1110-2 35
Electrical Information
Table 18: Electrical Data - Single Point (Continued)
Pum p R a t in g s L u g Ran g e
M odel V o lt a g e
HP FL A M CA RFS M FS P o w e r B lo c k ( 1 ) D is c o n n e c t S w it c h ( 1 )
208V 1 0 .6 587 600 600 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
230V 9 .6 586 600 600 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
3 .0
460V 4 .8 271 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
575V 3 .9 217 250 250 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
208V 1 6 .7 593 600 600 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
230V 1 5 .2 591 600 600 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
5 .0
460V 7 .6 274 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
575V 6 .1 219 250 250 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
208V 2 4 .2 600 600 600 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
A GZ 125D 230V 2 2 .0 598 600 600 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
7 .5
P UM P 460V 1 1 .0 277 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
575V 9 .0 222 250 250 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
208V 3 0 .8 607 600 600 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
230V 2 8 .0 604 600 600 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
1 0 .0
460V 1 4 .0 280 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
575V 1 1 .0 224 250 250 (1) 600 - #2 ( 2 ) 3 0 0 - 1 /0
208V 4 6 .2 622 700 700 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
230V 4 2 .0 618 700 700 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
1 5 .0
460V 2 1 .0 287 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
575V 1 7 .0 230 250 250 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
208V 1 0 .6 630 700 700 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
230V 9 .6 629 700 700 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
3 .0
460V 4 .8 312 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
575V 3 .9 245 250 250 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
208V 1 6 .7 636 700 700 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
230V 1 5 .2 635 700 700 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
5 .0
460V 7 .6 315 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
575V 6 .1 247 250 250 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
208V 2 4 .2 644 700 700 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
A GZ 130D 230V 2 2 .0 642 700 700 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
7 .5
P UM P 460V 1 1 .0 318 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
575V 9 .0 250 250 250 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
208V 3 0 .8 651 700 700 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
230V 2 8 .0 648 700 700 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
1 0 .0
460V 1 4 .0 321 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
575V 1 1 .0 252 250 250 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
208V 4 6 .2 666 700 700 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
230V 4 2 .0 662 700 700 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
1 5 .0
460V 2 1 .0 328 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
575V 1 7 .0 258 250 250 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
208V 1 6 .7 652 700 700 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
230V 1 5 .2 651 700 700 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
5 .0
460V 7 .6 322 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
575V 6 .1 253 250 250 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
208V 2 4 .2 660 700 700 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
230V 2 2 .0 657 700 700 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
7 .5
460V 1 1 .0 326 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
575V 9 .0 256 250 250 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
208V 3 0 .8 666 700 700 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
A GZ 140D 230V 2 8 .0 663 700 700 (2) 500 - #6 ( 3 ) 5 0 0 - 3 /0
1 0 .0
P UM P 460V 1 4 .0 329 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
575V 1 1 .0 258 250 250 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
208V 4 6 .2 682 700 700 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
230V 4 2 .0 677 700 700 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
1 5 .0
460V 2 1 .0 336 350 350 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1
575V 1 7 .0 264 250 250 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
208V 5 9 .4 695 700 700 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
230V 5 4 .0 689 700 700 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
2 0 .0
460V 2 7 .0 342 350 350 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1
575V 2 2 .0 269 250 250 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
Note: Power block and disconnect switch sizes are minimums. Larger sizes may be used, however the lug range must be the same.
36 IM 1110-2
Electrical Information
Table 19: Electrical Data - Single Point (Continued)
Pum p R a t in g s L u g Ran g e
M odel V o lt a g e
HP FL A M CA RFS M FS P o w e r B lo c k ( 1 ) D is c o n n e c t S w it c h ( 1 )
208V 1 6 .7 738 800 800 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
230V 1 5 .2 736 800 800 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
5 .0
460V 7 .6 355 400 400 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1
575V 6 .1 301 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
208V 2 4 .2 745 800 800 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
230V 2 2 .0 743 800 800 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
7 .5
460V 1 1 .0 358 400 400 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1
575V 9 .0 304 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
208V 3 0 .8 752 800 800 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
A GZ 160D 230V 2 8 .0 749 800 800 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
1 0 .0
P UM P 460V 1 4 .0 361 400 400 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1
575V 1 1 .0 306 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
208V 4 6 .2 767 800 800 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
230V 4 2 .0 763 800 800 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
1 5 .0
460V 2 1 .0 368 400 400 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
575V 1 7 .0 312 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
208V 5 9 .4 781 800 800 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
230V 5 4 .0 775 800 800 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
2 0 .0
460V 2 7 .0 374 400 400 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
575V 2 2 .0 317 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
208V 1 6 .7 892 1000 1000 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
230V 1 5 .2 816 800 800 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
5 .0
460V 7 .6 402 450 450 (2) 500 - #4 ( 2 ) 5 0 0 - 3 /0
575V 6 .1 345 350 350 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1
208V 2 4 .2 900 1000 1000 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
230V 2 2 .0 822 800 800 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
7 .5
460V 1 1 .0 405 450 450 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
575V 9 .0 348 350 350 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1
208V 3 0 .8 906 1000 1000 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
A GZ 180D 230V 2 8 .0 828 800 800 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
1 0 .0
P UM P 460V 1 4 .0 408 450 450 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
575V 1 1 .0 350 350 350 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1
208V 4 6 .2 922 1000 1000 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
230V 4 2 .0 842 800 800 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
1 5 .0
460V 2 1 .0 415 450 450 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
575V 1 7 .0 356 400 400 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1
208V 5 9 .4 935 1000 1000 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
230V 5 4 .0 854 800 800 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
2 0 .0
460V 2 7 .0 421 450 450 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
575V 2 2 .0 361 400 400 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
208V 1 6 .7 908 1000 1000 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
230V 1 5 .2 831 800 800 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
5 .0
460V 7 .6 409 450 450 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
575V 6 .1 351 350 350 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1
208V 2 4 .2 915 1000 1000 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
230V 2 2 .0 838 800 800 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
7 .5
460V 1 1 .0 412 450 450 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
575V 9 .0 354 350 350 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1
208V 3 0 .8 922 1000 1000 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
A GZ 190D 230V 2 8 .0 844 800 800 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
1 0 .0
P UM P 460V 1 4 .0 415 450 450 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
575V 1 1 .0 356 350 350 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1
208V 4 6 .2 937 1000 1000 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
230V 4 2 .0 858 800 800 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
1 5 .0
460V 2 1 .0 422 450 450 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
575V 1 7 .0 362 350 350 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
208V 5 9 .4 950 1000 1000 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
230V 5 4 .0 870 800 800 (4) 500 - #6 ( 4 ) 5 0 0 - 3 /0
2 0 .0
460V 2 7 .0 428 450 450 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
575V 2 2 .0 367 350 350 (2) 500 - #6 ( 2 ) 5 0 0 - 3 /0
Note: Power block and disconnect switch sizes are minimums. Larger sizes may be used, however the lug range must be the same.
IM 1110-2 37
Electrical Information
Table 20: Electrical Data - Multi-Point
Multiple Point Field Data - Circuit #1 Multiple Point Field Data - Circuit #2
Pump
Model Voltage Ratings Lug Range Ratings Lug Range
HP FLA MCA RFS MFS Power Block (1) Disconnect Switch [1] MCA RFS MFS Power Block (1) Disconnect Switch [1]
208V 4.6 83 110 110 (1) 2/0 - #14 (1) 1/0 - #14 78 100 100 (1) 2/0 - #14 (1) 1/0 - #14
230V 4.2 83 110 110 (1) 2/0 - #14 (1) 1/0 - #14 78 100 100 (1) 2/0 - #14 (1) 1/0 - #14
1.0
460V 2.1 41 50 50 (1) 2/0 - #14 (1) 1/0 - #14 39 50 50 (1) 2/0 - #14 (1) 1/0 - #14
575V 1.7 36 45 45 (1) 2/0 - #14 (1) 1/0 - #14 34 45 45 (1) 2/0 - #14 (1) 1/0 - #14
208V 6.6 85 110 110 (1) 2/0 - #14 (1) 1/0 - #14 78 100 100 (1) 2/0 - #14 (1) 1/0 - #14
230V 6.0 84 110 110 (1) 2/0 - #14 (1) 1/0 - #14 78 100 100 (1) 2/0 - #14 (1) 1/0 - #14
1.5
460V 3.0 42 50 50 (1) 2/0 - #14 (1) 1/0 - #14 39 50 50 (1) 2/0 - #14 (1) 1/0 - #14
575V 2.4 36 45 45 (1) 2/0 - #14 (1) 1/0 - #14 34 45 45 (1) 2/0 - #14 (1) 1/0 - #14
208V 7.5 86 110 110 (1) 2/0 - #14 (1) 1/0 - #14 78 100 100 (1) 2/0 - #14 (1) 1/0 - #14
AGZ025D 230V 6.8 85 110 110 (1) 2/0 - #14 (1) 1/0 - #14 78 100 100 (1) 2/0 - #14 (1) 1/0 - #14
2.0
PUMP 460V 3.4 43 50 50 (1) 2/0 - #14 (1) 1/0 - #14 39 50 50 (1) 2/0 - #14 (1) 1/0 - #14
575V 2.7 37 45 45 (1) 2/0 - #14 (1) 1/0 - #14 34 45 45 (1) 2/0 - #14 (1) 1/0 - #14
208V 10.6 89 110 110 (1) 2/0 - #14 (1) 1/0 - #14 78 100 100 (1) 2/0 - #14 (1) 1/0 - #14
230V 9.6 88 110 110 (1) 2/0 - #14 (1) 1/0 - #14 78 100 100 (1) 2/0 - #14 (1) 1/0 - #14
3.0
460V 4.8 44 50 50 (1) 2/0 - #14 (1) 1/0 - #14 39 50 50 (1) 2/0 - #14 (1) 1/0 - #14
575V 3.9 38 45 45 (1) 2/0 - #14 (1) 1/0 - #14 34 45 45 (1) 2/0 - #14 (1) 1/0 - #14
208V 16.7 95 110 110 (1) 2/0 - #14 (1) 3/0 - #14 78 100 100 (1) 2/0 - #14 (1) 1/0 - #14
230V 15.2 94 110 110 (1) 2/0 - #14 (1) 1/0 - #14 78 100 100 (1) 2/0 - #14 (1) 1/0 - #14
5.0
460V 7.6 47 60 60 (1) 2/0 - #14 (1) 1/0 - #14 39 50 50 (1) 2/0 - #14 (1) 1/0 - #14
575V 6.1 40 50 50 (1) 2/0 - #14 (1) 1/0 - #14 34 45 45 (1) 2/0 - #14 (1) 1/0 - #14
208V 4.6 88 110 110 (1) 2/0 - #14 (1) 1/0 - #14 83 110 110.3 (1) 2/0 - #14 (1) 1/0 - #14
230V 4.2 84 110 110 (1) 2/0 - #14 (1) 1/0 - #14 80 100 100.3 (1) 2/0 - #14 (1) 1/0 - #14
1.0
460V 2.1 46 60 60 (1) 2/0 - #14 (1) 1/0 - #14 44 60 60.3 (1) 2/0 - #14 (1) 1/0 - #14
575V 1.7 37 50 50 (1) 2/0 - #14 (1) 1/0 - #14 36 45 45.3 (1) 2/0 - #14 (1) 1/0 - #14
208V 6.6 90 110 110 (1) 2/0 - #14 (1) 1/0 - #14 83 110 110.3 (1) 2/0 - #14 (1) 1/0 - #14
230V 6.0 86 110 110 (1) 2/0 - #14 (1) 1/0 - #14 80 100 100.3 (1) 2/0 - #14 (1) 1/0 - #14
1.5
460V 3.0 47 60 60 (1) 2/0 - #14 (1) 1/0 - #14 44 60 60.3 (1) 2/0 - #14 (1) 1/0 - #14
575V 2.4 38 50 50 (1) 2/0 - #14 (1) 1/0 - #14 36 45 45.3 (1) 2/0 - #14 (1) 1/0 - #14
208V 7.5 91 110 110 (1) 2/0 - #14 (1) 1/0 - #14 83 110 110.3 (1) 2/0 - #14 (1) 1/0 - #14
AGZ030D 230V 6.8 87 110 110 (1) 2/0 - #14 (1) 1/0 - #14 80 100 100.3 (1) 2/0 - #14 (1) 1/0 - #14
2.0
PUMP 460V 3.4 47 60 60 (1) 2/0 - #14 (1) 1/0 - #14 44 60 60.3 (1) 2/0 - #14 (1) 1/0 - #14
575V 2.7 38 50 50 (1) 2/0 - #14 (1) 1/0 - #14 36 45 45.3 (1) 2/0 - #14 (1) 1/0 - #14
208V 10.6 94 125 125 (1) 2/0 - #14 (1) 1/0 - #14 83 110 110.3 (1) 2/0 - #14 (1) 1/0 - #14
230V 9.6 89 110 110 (1) 2/0 - #14 (1) 1/0 - #14 80 100 100.3 (1) 2/0 - #14 (1) 1/0 - #14
3.0
460V 4.8 48 60 60 (1) 2/0 - #14 (1) 1/0 - #14 44 60 60.3 (1) 2/0 - #14 (1) 1/0 - #14
575V 3.9 40 50 50 (1) 2/0 - #14 (1) 1/0 - #14 36 45 45.3 (1) 2/0 - #14 (1) 1/0 - #14
208V 16.7 100 125 125 (1) 2/0 - #14 (1) 3/0 - #14 83 110 110.3 (1) 2/0 - #14 (1) 1/0 - #14
230V 15.2 95 110 110 (1) 2/0 - #14 (1) 3/0 - #14 80 100 100.3 (1) 2/0 - #14 (1) 1/0 - #14
5.0
460V 7.6 51 60 60 (1) 2/0 - #14 (1) 1/0 - #14 44 60 60.3 (1) 2/0 - #14 (1) 1/0 - #14
575V 6.1 42 50 50 (1) 2/0 - #14 (1) 1/0 - #14 36 45 45.3 (1) 2/0 - #14 (1) 1/0 - #14
208V 6.6 90 110 110 (1) 2/0 - #14 (1) 1/0 - #14 94 125 125 (1) 2/0 - #14 (1) 1/0 - #14
230V 6.0 86 110 110 (1) 2/0 - #14 (1) 1/0 - #14 93 125 125 (1) 2/0 - #14 (1) 1/0 - #14
1.5
460V 3.0 47 60 60 (1) 2/0 - #14 (1) 1/0 - #14 46 60 60 (1) 2/0 - #14 (1) 1/0 - #14
575V 2.4 38 50 50 (1) 2/0 - #14 (1) 1/0 - #14 36 45 45 (1) 2/0 - #14 (1) 1/0 - #14
208V 7.5 91 110 110 (1) 2/0 - #14 (1) 1/0 - #14 94 125 125 (1) 2/0 - #14 (1) 1/0 - #14
230V 6.8 87 110 110 (1) 2/0 - #14 (1) 1/0 - #14 93 125 125 (1) 2/0 - #14 (1) 1/0 - #14
2.0
460V 3.4 47 60 60 (1) 2/0 - #14 (1) 1/0 - #14 46 60 60 (1) 2/0 - #14 (1) 1/0 - #14
575V 2.7 38 50 50 (1) 2/0 - #14 (1) 1/0 - #14 36 45 45 (1) 2/0 - #14 (1) 1/0 - #14
208V 10.6 94 125 125 (1) 2/0 - #14 (1) 1/0 - #14 94 125 125 (1) 2/0 - #14 (1) 1/0 - #14
AGZ035D 230V 9.6 89 110 110 (1) 2/0 - #14 (1) 1/0 - #14 93 125 125 (1) 2/0 - #14 (1) 1/0 - #14
3.0
PUMP 460V 4.8 48 60 60 (1) 2/0 - #14 (1) 1/0 - #14 46 60 60 (1) 2/0 - #14 (1) 1/0 - #14
575V 3.9 40 50 50 (1) 2/0 - #14 (1) 1/0 - #14 36 45 45 (1) 2/0 - #14 (1) 1/0 - #14
208V 16.7 100 125 125 (1) 2/0 - #14 (1) 3/0 - #14 94 125 125 (1) 2/0 - #14 (1) 1/0 - #14
230V 15.2 95 110 110 (1) 2/0 - #14 (1) 3/0 - #14 93 125 125 (1) 2/0 - #14 (1) 1/0 - #14
5.0
460V 7.6 51 60 60 (1) 2/0 - #14 (1) 1/0 - #14 46 60 60 (1) 2/0 - #14 (1) 1/0 - #14
575V 6.1 42 50 50 (1) 2/0 - #14 (1) 1/0 - #14 36 45 45 (1) 2/0 - #14 (1) 1/0 - #14
208V 24.2 107 125 125 (1) 2/0 - #14 (1) 3/0 - #14 94 125 125 (1) 2/0 - #14 (1) 1/0 - #14
230V 22.0 102 125 125 (1) 2/0 - #14 (1) 3/0 - #14 93 125 125 (1) 2/0 - #14 (1) 1/0 - #14
7.5
460V 11.0 55 70 70 (1) 2/0 - #14 (1) 1/0 - #14 46 60 60 (1) 2/0 - #14 (1) 1/0 - #14
575V 9.0 45 50 50 (1) 2/0 - #14 (1) 1/0 - #14 36 45 45 (1) 2/0 - #14 (1) 1/0 - #14
Note: Power block and disconnect switch sizes are minimums. Larger sizes may be used, however the lug range must be the same.
38 IM 1110-2
Electrical Information
Table 21: Electrical Data - Multi-Point (Continued)
Multiple Point Field Data - Circuit #1 Multiple Point Field Data - Circuit #2
Pump
Model Voltage Ratings Lug Range Ratings Lug Range
HP FLA MCA RFS MFS Power Block (1) Disconnect Switch [1] MCA RFS MFS Power Block (1) Disconnect Switch [1]
208V 6.6 100 125 125 (1) 2/0 - #14 (1) 3/0 - #14 94 125 125 (1) 2/0 - #14 (1) 1/0 - #14
230V 6.0 99 125 125 (1) 2/0 - #14 (1) 3/0 - #14 93 125 125 (1) 2/0 - #14 (1) 1/0 - #14
1.5
460V 3.0 49 60 60 (1) 2/0 - #14 (1) 1/0 - #14 46 60 60 (1) 2/0 - #14 (1) 1/0 - #14
575V 2.4 38 50 50 (1) 2/0 - #14 (1) 1/0 - #14 36 45 45 (1) 2/0 - #14 (1) 1/0 - #14
208V 7.5 101 125 125 (1) 2/0 - #14 (1) 3/0 - #14 94 125 125 (1) 2/0 - #14 (1) 1/0 - #14
230V 6.8 100 125 125 (1) 2/0 - #14 (1) 3/0 - #14 93 125 125 (1) 2/0 - #14 (1) 1/0 - #14
2.0
460V 3.4 50 60 60 (1) 2/0 - #14 (1) 1/0 - #14 46 60 60 (1) 2/0 - #14 (1) 1/0 - #14
575V 2.7 38 50 50 (1) 2/0 - #14 (1) 1/0 - #14 36 45 45 (1) 2/0 - #14 (1) 1/0 - #14
208V 10.6 104 125 125 (1) 2/0 - #14 (1) 3/0 - #14 94 125 125 (1) 2/0 - #14 (1) 1/0 - #14
AGZ040D 230V 9.6 103 125 125 (1) 2/0 - #14 (1) 3/0 - #14 93 125 125 (1) 2/0 - #14 (1) 1/0 - #14
3.0
PUMP 460V 4.8 51 60 60 (1) 2/0 - #14 (1) 1/0 - #14 46 60 60 (1) 2/0 - #14 (1) 1/0 - #14
575V 3.9 40 50 50 (1) 2/0 - #14 (1) 1/0 - #14 36 45 45 (1) 2/0 - #14 (1) 1/0 - #14
208V 16.7 110 125 125 (1) 2/0 - #14 (1) 3/0 - #14 94 125 125 (1) 2/0 - #14 (1) 1/0 - #14
230V 15.2 108 125 125 (1) 2/0 - #14 (1) 3/0 - #14 93 125 125 (1) 2/0 - #14 (1) 1/0 - #14
5.0
460V 7.6 54 70 70 (1) 2/0 - #14 (1) 1/0 - #14 46 60 60 (1) 2/0 - #14 (1) 1/0 - #14
575V 6.1 42 50 50 (1) 2/0 - #14 (1) 1/0 - #14 36 45 45 (1) 2/0 - #14 (1) 1/0 - #14
208V 24.2 118 150 150 (1) 2/0 - #14 (1) 3/0 - #14 94 125 125 (1) 2/0 - #14 (1) 1/0 - #14
230V 22.0 115 150 150 (1) 2/0 - #14 (1) 3/0 - #14 93 125 125 (1) 2/0 - #14 (1) 1/0 - #14
7.5
460V 11.0 57 70 70 (1) 2/0 - #14 (1) 1/0 - #14 46 60 60 (1) 2/0 - #14 (1) 1/0 - #14
575V 9.0 45 50 50 (1) 2/0 - #14 (1) 1/0 - #14 36 45 45 (1) 2/0 - #14 (1) 1/0 - #14
208V 6.6 127 150 150 (1) 2/0 - #14 (1) 3/0 - #14 120 150 150 (1) 2/0 - #14 (1) 3/0 - #14
230V 6.0 126 150 150 (1) 2/0 - #14 (1) 3/0 - #14 120 150 150 (1) 2/0 - #14 (1) 3/0 - #14
1.5
460V 3.0 52 70 70 (1) 2/0 - #14 (1) 1/0 - #14 49 60 60 (1) 2/0 - #14 (1) 1/0 - #14
575V 2.4 43 50 50 (1) 2/0 - #14 (1) 1/0 - #14 40 50 50 (1) 2/0 - #14 (1) 1/0 - #14
208V 7.5 128 175 175 (1) 2/0 - #14 (1) 3/0 - #14 120 150 150 (1) 2/0 - #14 (1) 3/0 - #14
230V 6.8 127 150 150 (1) 2/0 - #14 (1) 3/0 - #14 120 150 150 (1) 2/0 - #14 (1) 3/0 - #14
2.0
460V 3.4 52 70 70 (1) 2/0 - #14 (1) 1/0 - #14 49 60 60 (1) 2/0 - #14 (1) 1/0 - #14
575V 2.7 43 50 50 (1) 2/0 - #14 (1) 1/0 - #14 40 50 50 (1) 2/0 - #14 (1) 1/0 - #14
208V 10.6 131 175 175 (1) 2/0 - #14 (1) 3/0 - #14 120 150 150 (1) 2/0 - #14 (1) 3/0 - #14
AGZ045D 230V 9.6 130 175 175 (1) 2/0 - #14 (1) 3/0 - #14 120 150 150 (1) 2/0 - #14 (1) 3/0 - #14
3.0
PUMP 460V 4.8 53 70 70 (1) 2/0 - #14 (1) 1/0 - #14 49 60 60 (1) 2/0 - #14 (1) 1/0 - #14
575V 3.9 44 50 50 (1) 2/0 - #14 (1) 1/0 - #14 40 50 50 (1) 2/0 - #14 (1) 1/0 - #14
208V 16.7 137 175 175 (1) 2/0 - #14 (1) 3/0 - #14 120 150 150 (1) 2/0 - #14 (1) 3/0 - #14
230V 15.2 135 175 175 (1) 2/0 - #14 (1) 3/0 - #14 120 150 150 (1) 2/0 - #14 (1) 3/0 - #14
5.0
460V 7.6 56 70 70 (1) 2/0 - #14 (1) 1/0 - #14 49 60 60 (1) 2/0 - #14 (1) 1/0 - #14
575V 6.1 47 60 60 (1) 2/0 - #14 (1) 1/0 - #14 40 50 50 (1) 2/0 - #14 (1) 1/0 - #14
208V 24.2 144 175 175 (1) 2/0 - #14 (2) 300 - 1/0 120 150 150 (1) 2/0 - #14 (1) 3/0 - #14
230V 22.0 142 175 175 (1) 2/0 - #14 (1) 3/0 - #14 120 150 150 (1) 2/0 - #14 (1) 3/0 - #14
7.5
460V 11.0 60 70 70 (1) 2/0 - #14 (1) 1/0 - #14 49 60 60 (1) 2/0 - #14 (1) 1/0 - #14
575V 9.0 49 60 60 (1) 2/0 - #14 (1) 1/0 - #14 40 50 50 (1) 2/0 - #14 (1) 1/0 - #14
208V 6.6 137 175 175 (1) 2/0 - #14 (1) 3/0 - #14 131 175 175 (1) 2/0 - #14 (1) 3/0 - #14
230V 6.0 137 175 175 (1) 2/0 - #14 (1) 3/0 - #14 131 175 175 (1) 2/0 - #14 (1) 3/0 - #14
1.5
460V 3.0 61 80 80 (1) 2/0 - #14 (1) 1/0 - #14 58 80 80 (1) 2/0 - #14 (1) 1/0 - #14
575V 2.4 54 70 70 (1) 2/0 - #14 (1) 1/0 - #14 51 70 70 (1) 2/0 - #14 (1) 1/0 - #14
208V 7.5 138 175 175 (1) 2/0 - #14 (1) 3/0 - #14 131 175 175 (1) 2/0 - #14 (1) 3/0 - #14
230V 6.8 138 175 175 (1) 2/0 - #14 (1) 3/0 - #14 131 175 175 (1) 2/0 - #14 (1) 3/0 - #14
2.0
460V 3.4 61 80 80 (1) 2/0 - #14 (1) 1/0 - #14 58 80 80 (1) 2/0 - #14 (1) 1/0 - #14
575V 2.7 54 70 70 (1) 2/0 - #14 (1) 1/0 - #14 51 70 70 (1) 2/0 - #14 (1) 1/0 - #14
208V 10.6 141 175 175 (1) 2/0 - #14 (1) 3/0 - #14 131 175 175 (1) 2/0 - #14 (1) 3/0 - #14
AGZ050D 230V 9.6 140 175 175 (1) 2/0 - #14 (1) 3/0 - #14 131 175 175 (1) 2/0 - #14 (1) 3/0 - #14
3.0
PUMP 460V 4.8 63 80 80 (1) 2/0 - #14 (1) 1/0 - #14 58 80 80 (1) 2/0 - #14 (1) 1/0 - #14
575V 3.9 55 70 70 (1) 2/0 - #14 (1) 1/0 - #14 51 70 70 (1) 2/0 - #14 (1) 1/0 - #14
208V 16.7 148 200 200 (1) 2/0 - #14 (2) 300 - 1/0 131 175 175 (1) 2/0 - #14 (1) 3/0 - #14
230V 15.2 146 175 175 (1) 2/0 - #14 (2) 300 - 1/0 131 175 175 (1) 2/0 - #14 (1) 3/0 - #14
5.0
460V 7.6 66 80 80 (1) 2/0 - #14 (1) 1/0 - #14 58 80 80 (1) 2/0 - #14 (1) 1/0 - #14
575V 6.1 57 70 70 (1) 2/0 - #14 (1) 1/0 - #14 51 70 70 (1) 2/0 - #14 (1) 1/0 - #14
208V 24.2 155 200 200 (1) 2/0 - #14 (2) 300 - 1/0 131 175 175 (1) 2/0 - #14 (1) 3/0 - #14
230V 22.0 153 200 200 (1) 2/0 - #14 (2) 300 - 1/0 131 175 175 (1) 2/0 - #14 (1) 3/0 - #14
7.5
460V 11.0 69 90 90 (1) 2/0 - #14 (1) 1/0 - #14 58 80 80 (1) 2/0 - #14 (1) 1/0 - #14
575V 9.0 60 70 70 (1) 2/0 - #14 (1) 1/0 - #14 51 70 70 (1) 2/0 - #14 (1) 1/0 - #14
Note: Power block and disconnect switch sizes are minimums. Larger sizes may be used, however the lug range must be the same.
IM 1110-2 39
Electrical Information
Table 22: Electrical Data - Multi-Point (Continued)
Multiple Point Field Data - Circuit #1 Multiple Point Field Data - Circuit #2
Pump
Model Voltage Ratings Lug Range Ratings Lug Range
HP FLA MCA RFS MFS Power Block (1) Disconnect Switch [1] MCA RFS MFS Power Block (1) Disconnect Switch [1]
208V 6.6 137 175 175 (1) 2/0 - #14 (1) 3/0 - #14 139 175 175 (1) 2/0 - #14 (1) 3/0 - #14
230V 6.0 137 175 175 (1) 2/0 - #14 (1) 3/0 - #14 138 175 175 (1) 2/0 - #14 (1) 3/0 - #14
1.5
460V 3.0 61 80 80 (1) 2/0 - #14 (1) 1/0 - #14 67 90 90 (1) 2/0 - #14 (1) 1/0 - #14
575V 2.4 54 70 70 (1) 2/0 - #14 (1) 1/0 - #14 60 80 80 (1) 2/0 - #14 (1) 1/0 - #14
208V 7.5 138 175 175 (1) 2/0 - #14 (1) 3/0 - #14 139 175 175 (1) 2/0 - #14 (1) 3/0 - #14
230V 6.8 138 175 175 (1) 2/0 - #14 (1) 3/0 - #14 138 175 175 (1) 2/0 - #14 (1) 3/0 - #14
2.0
460V 3.4 61 80 80 (1) 2/0 - #14 (1) 1/0 - #14 67 90 90 (1) 2/0 - #14 (1) 1/0 - #14
575V 2.7 54 70 70 (1) 2/0 - #14 (1) 1/0 - #14 60 80 80 (1) 2/0 - #14 (1) 1/0 - #14
208V 10.6 141 175 175 (1) 2/0 - #14 (1) 3/0 - #14 139 175 175 (1) 2/0 - #14 (1) 3/0 - #14
AGZ055D 230V 9.6 140 175 175 (1) 2/0 - #14 (1) 3/0 - #14 138 175 175 (1) 2/0 - #14 (1) 3/0 - #14
3.0
PUMP 460V 4.8 63 80 80 (1) 2/0 - #14 (1) 1/0 - #14 67 90 90 (1) 2/0 - #14 (1) 1/0 - #14
575V 3.9 55 70 70 (1) 2/0 - #14 (1) 1/0 - #14 60 80 80 (1) 2/0 - #14 (1) 1/0 - #14
208V 16.7 148 200 200 (1) 2/0 - #14 (2) 300 - 1/0 139 175 175 (1) 2/0 - #14 (1) 3/0 - #14
230V 15.2 146 175 175 (1) 2/0 - #14 (2) 300 - 1/0 138 175 175 (1) 2/0 - #14 (1) 3/0 - #14
5.0
460V 7.6 66 80 80 (1) 2/0 - #14 (1) 1/0 - #14 67 90 90 (1) 2/0 - #14 (1) 1/0 - #14
575V 6.1 57 70 70 (1) 2/0 - #14 (1) 1/0 - #14 60 80 80 (1) 2/0 - #14 (1) 1/0 - #14
208V 24.2 155 200 200 (1) 2/0 - #14 (2) 300 - 1/0 139 175 175 (1) 2/0 - #14 (1) 3/0 - #14
230V 22.0 153 200 200 (1) 2/0 - #14 (2) 300 - 1/0 138 175 175 (1) 2/0 - #14 (1) 3/0 - #14
7.5
460V 11.0 69 90 90 (1) 2/0 - #14 (1) 1/0 - #14 67 90 90 (1) 2/0 - #14 (1) 1/0 - #14
575V 9.0 60 70 70 (1) 2/0 - #14 (1) 1/0 - #14 60 80 80 (1) 2/0 - #14 (1) 1/0 - #14
208V 7.5 147 200 200 (1) 2/0 - #14 (2) 300 - 1/0 139 175 175 (1) 2/0 - #14 (1) 3/0 - #14
230V 6.8 144 175 175 (1) 2/0 - #14 (1) 3/0 - #14 138 175 175 (1) 2/0 - #14 (1) 3/0 - #14
2.0
460V 3.4 70 90 90 (1) 2/0 - #14 (1) 1/0 - #14 67 90 90 (1) 2/0 - #14 (1) 1/0 - #14
575V 2.7 62 80 80 (1) 2/0 - #14 (1) 1/0 - #14 60 80 80 (1) 2/0 - #14 (1) 1/0 - #14
208V 10.6 150 200 200 (1) 2/0 - #14 (2) 300 - 1/0 139 175 175 (1) 2/0 - #14 (1) 3/0 - #14
230V 9.6 147 200 200 (1) 2/0 - #14 (2) 300 - 1/0 138 175 175 (1) 2/0 - #14 (1) 3/0 - #14
3.0
460V 4.8 71 90 90 (1) 2/0 - #14 (1) 1/0 - #14 67 90 90 (1) 2/0 - #14 (1) 1/0 - #14
575V 3.9 64 80 80 (1) 2/0 - #14 (1) 1/0 - #14 60 80 80 (1) 2/0 - #14 (1) 1/0 - #14
208V 16.7 156 200 200 (1) 2/0 - #14 (2) 300 - 1/0 139 175 175 (1) 2/0 - #14 (1) 3/0 - #14
AGZ060D 230V 15.2 153 200 200 (1) 2/0 - #14 (2) 300 - 1/0 138 175 175 (1) 2/0 - #14 (1) 3/0 - #14
5.0
PUMP 460V 7.6 74 100 100 (1) 2/0 - #14 (1) 1/0 - #14 67 90 90 (1) 2/0 - #14 (1) 1/0 - #14
575V 6.1 66 80 80 (1) 2/0 - #14 (1) 1/0 - #14 60 80 80 (1) 2/0 - #14 (1) 1/0 - #14
208V 24.2 164 200 200 (1) 2/0 - #14 (2) 300 - 1/0 139 175 175 (1) 2/0 - #14 (1) 3/0 - #14
230V 22.0 160 200 200 (1) 2/0 - #14 (2) 300 - 1/0 138 175 175 (1) 2/0 - #14 (1) 3/0 - #14
7.5
460V 11.0 78 100 100 (1) 2/0 - #14 (1) 1/0 - #14 67 90 90 (1) 2/0 - #14 (1) 1/0 - #14
575V 9.0 69 90 90 (1) 2/0 - #14 (1) 1/0 - #14 60 80 80 (1) 2/0 - #14 (1) 1/0 - #14
208V 30.8 170 225 225 (1) 600 - #2 (2) 300 - 1/0 139 175 175 (1) 2/0 - #14 (1) 3/0 - #14
230V 28.0 166 200 200 (1) 2/0 - #14 (2) 300 - 1/0 138 175 175 (1) 2/0 - #14 (1) 3/0 - #14
10.0
460V 14.0 81 100 100 (1) 2/0 - #14 (1) 1/0 - #14 67 90 90 (1) 2/0 - #14 (1) 1/0 - #14
575V 11.0 71 90 90 (1) 2/0 - #14 (1) 1/0 - #14 60 80 80 (1) 2/0 - #14 (1) 1/0 - #14
208V 7.5 151 200 200 (1) 2/0 - #14 (2) 300 - 1/0 143 175 175 (1) 2/0 - #14 (1) 3/0 - #14
230V 6.8 148 200 200 (1) 2/0 - #14 (2) 300 - 1/0 142 175 175 (1) 2/0 - #14 (1) 3/0 - #14
2.0
460V 3.4 72 90 90 (1) 2/0 - #14 (1) 1/0 - #14 68 90 90 (1) 2/0 - #14 (1) 1/0 - #14
575V 2.7 62 80 80 (1) 2/0 - #14 (1) 1/0 - #14 60 80 80 (1) 2/0 - #14 (1) 1/0 - #14
208V 10.6 154 200 200 (1) 2/0 - #14 (2) 300 - 1/0 143 175 175 (1) 2/0 - #14 (1) 3/0 - #14
230V 9.6 151 200 200 (1) 2/0 - #14 (2) 300 - 1/0 142 175 175 (1) 2/0 - #14 (1) 3/0 - #14
3.0
460V 4.8 73 90 90 (1) 2/0 - #14 (1) 1/0 - #14 68 90 90 (1) 2/0 - #14 (1) 1/0 - #14
575V 3.9 64 80 80 (1) 2/0 - #14 (1) 1/0 - #14 60 80 80 (1) 2/0 - #14 (1) 1/0 - #14
208V 16.7 160 200 200 (1) 2/0 - #14 (2) 300 - 1/0 143 175 175 (1) 2/0 - #14 (1) 3/0 - #14
AGZ065D 230V 15.2 157 200 200 (1) 2/0 - #14 (2) 300 - 1/0 142 175 175 (1) 2/0 - #14 (1) 3/0 - #14
5.0
PUMP 460V 7.6 76 100 100 (1) 2/0 - #14 (1) 1/0 - #14 68 90 90 (1) 2/0 - #14 (1) 1/0 - #14
575V 6.1 66 80 80 (1) 2/0 - #14 (1) 1/0 - #14 60 80 80 (1) 2/0 - #14 (1) 1/0 - #14
208V 24.2 168 200 200 (1) 2/0 - #14 (2) 300 - 1/0 143 175 175 (1) 2/0 - #14 (1) 3/0 - #14
230V 22.0 164 200 200 (1) 2/0 - #14 (2) 300 - 1/0 142 175 175 (1) 2/0 - #14 (1) 3/0 - #14
7.5
460V 11.0 79 100 100 (1) 2/0 - #14 (1) 1/0 - #14 68 90 90 (1) 2/0 - #14 (1) 1/0 - #14
575V 9.0 69 90 90 (1) 2/0 - #14 (1) 1/0 - #14 60 80 80 (1) 2/0 - #14 (1) 1/0 - #14
208V 30.8 174 225 225 (1) 600 - #2 (2) 300 - 1/0 143 175 175 (1) 2/0 - #14 (1) 3/0 - #14
230V 28.0 170 225 225 (1) 600 - #2 (2) 300 - 1/0 142 175 175 (1) 2/0 - #14 (1) 3/0 - #14
10.0
460V 14.0 82 100 100 (1) 2/0 - #14 (1) 1/0 - #14 68 90 90 (1) 2/0 - #14 (1) 1/0 - #14
575V 11.0 71 90 90 (1) 2/0 - #14 (1) 1/0 - #14 60 80 80 (1) 2/0 - #14 (1) 1/0 - #14
Note: Power block and disconnect switch sizes are minimums. Larger sizes may be used, however the lug range must be the same.
40 IM 1110-2
Electrical Information
Table 23: Electrical Data - Multi-Point (Continued)
Multiple Point Field Data - Circuit #1 Multiple Point Field Data - Circuit #2
Pump
Model Voltage Ratings Lug Range Ratings Lug Range
HP FLA MCA RFS MFS Power Block (1) Disconnect Switch [1] MCA RFS MFS Power Block (1) Disconnect Switch [1]
208V 7.5 171 225 225 (1) 600 - #2 (2) 300 - 1/0 163 225 225 (1) 2/0 - #14 (2) 300 - 1/0
230V 6.8 169 225 225 (1) 600 - #2 (2) 300 - 1/0 162 225 225 (1) 2/0 - #14 (2) 300 - 1/0
2.0
460V 3.4 76 100 100 (1) 2/0 - #14 (1) 1/0 - #14 73 100 100 (1) 2/0 - #14 (1) 1/0 - #14
575V 2.7 64 80 80 (1) 2/0 - #14 (1) 1/0 - #14 62 80 80 (1) 2/0 - #14 (1) 1/0 - #14
208V 10.6 174 225 225 (1) 600 - #2 (2) 300 - 1/0 163 225 225 (1) 2/0 - #14 (2) 300 - 1/0
230V 9.6 172 225 225 (1) 600 - #2 (2) 300 - 1/0 162 225 225 (1) 2/0 - #14 (2) 300 - 1/0
3.0
460V 4.8 78 100 100 (1) 2/0 - #14 (1) 1/0 - #14 73 100 100 (1) 2/0 - #14 (1) 1/0 - #14
575V 3.9 66 90 90 (1) 2/0 - #14 (1) 1/0 - #14 62 80 80 (1) 2/0 - #14 (1) 1/0 - #14
208V 16.7 180 250 250 (1) 600 - #2 (2) 300 - 1/0 163 225 225 (1) 2/0 - #14 (2) 300 - 1/0
AGZ070D 230V 15.2 178 225 225 (1) 600 - #2 (2) 300 - 1/0 162 225 225 (1) 2/0 - #14 (2) 300 - 1/0
5.0
PUMP 460V 7.6 81 110 110 (1) 2/0 - #14 (1) 1/0 - #14 73 100 100 (1) 2/0 - #14 (1) 1/0 - #14
575V 6.1 68 90 90 (1) 2/0 - #14 (1) 1/0 - #14 62 80 80 (1) 2/0 - #14 (1) 1/0 - #14
208V 24.2 187 250 250 (1) 600 - #2 (2) 300 - 1/0 163 225 225 (1) 2/0 - #14 (2) 300 - 1/0
230V 22.0 184 250 250 (1) 600 - #2 (2) 300 - 1/0 162 225 225 (1) 2/0 - #14 (2) 300 - 1/0
7.5
460V 11.0 84 110 110 (1) 2/0 - #14 (1) 1/0 - #14 73 100 100 (1) 2/0 - #14 (1) 1/0 - #14
575V 9.0 71 90 90 (1) 2/0 - #14 (1) 1/0 - #14 62 80 80 (1) 2/0 - #14 (1) 1/0 - #14
208V 30.8 194 250 250 (1) 600 - #2 (2) 300 - 1/0 163 225 225 (1) 2/0 - #14 (2) 300 - 1/0
230V 28.0 190 250 250 (1) 600 - #2 (2) 300 - 1/0 162 225 225 (1) 2/0 - #14 (2) 300 - 1/0
10.0
460V 14.0 87 110 110 (1) 2/0 - #14 (1) 1/0 - #14 73 100 100 (1) 2/0 - #14 (1) 1/0 - #14
575V 11.0 73 90 90 (1) 2/0 - #14 (1) 1/0 - #14 62 80 80 (1) 2/0 - #14 (1) 1/0 - #14
208V 10.6 197 250 250 (1) 600 - #2 (2) 300 - 1/0 187 250 250 (1) 600 - #2 (2) 300 - 1/0
230V 9.6 196 250 250 (1) 600 - #2 (2) 300 - 1/0 187 250 250 (1) 600 - #2 (2) 300 - 1/0
3.0
460V 4.8 85 110 110 (1) 2/0 - #14 (1) 1/0 - #14 81 110 110 (1) 2/0 - #14 (1) 1/0 - #14
575V 3.9 70 90 90 (1) 2/0 - #14 (1) 1/0 - #14 66 90 90 (1) 2/0 - #14 (1) 1/0 - #14
208V 16.7 203 250 250 (1) 600 - #2 (2) 300 - 1/0 187 250 250 (1) 600 - #2 (2) 300 - 1/0
230V 15.2 202 250 250 (1) 600 - #2 (2) 300 - 1/0 187 250 250 (1) 600 - #2 (2) 300 - 1/0
5.0
460V 7.6 88 110 110 (1) 2/0 - #14 (1) 1/0 - #14 81 110 110 (1) 2/0 - #14 (1) 1/0 - #14
575V 6.1 72 90 90 (1) 2/0 - #14 (1) 1/0 - #14 66 90 90 (1) 2/0 - #14 (1) 1/0 - #14
208V 24.2 211 250 250 (1) 600 - #2 (2) 300 - 1/0 187 250 250 (1) 600 - #2 (2) 300 - 1/0
AGZ075D 230V 22.0 209 250 250 (1) 600 - #2 (2) 300 - 1/0 187 250 250 (1) 600 - #2 (2) 300 - 1/0
7.5
PUMP 460V 11.0 92 110 110 (1) 2/0 - #14 (1) 1/0 - #14 81 110 110 (1) 2/0 - #14 (1) 1/0 - #14
575V 9.0 75 100 100 (1) 2/0 - #14 (1) 1/0 - #14 66 90 90 (1) 2/0 - #14 (1) 1/0 - #14
208V 30.8 218 250 250 (1) 600 - #2 (2) 300 - 1/0 187 250 250 (1) 600 - #2 (2) 300 - 1/0
230V 28.0 215 250 250 (1) 600 - #2 (2) 300 - 1/0 187 250 250 (1) 600 - #2 (2) 300 - 1/0
10.0
460V 14.0 95 125 125 (1) 2/0 - #14 (1) 1/0 - #14 81 110 110 (1) 2/0 - #14 (1) 1/0 - #14
575V 11.0 77 100 100 (1) 2/0 - #14 (1) 1/0 - #14 66 90 90 (1) 2/0 - #14 (1) 1/0 - #14
208V 46.2 233 300 300 (1) 600 - #2 (2) 300 - 1/0 187 250 250 (1) 600 - #2 (2) 300 - 1/0
230V 42.0 229 300 300 (1) 600 - #2 (2) 300 - 1/0 187 250 250 (1) 600 - #2 (2) 300 - 1/0
15.0
460V 21.0 102 125 125 (1) 2/0 - #14 (1) 3/0 - #14 81 110 110 (1) 2/0 - #14 (1) 1/0 - #14
575V 17.0 83 100 100 (1) 2/0 - #14 (1) 1/0 - #14 66 90 90 (1) 2/0 - #14 (1) 1/0 - #14
208V 10.6 197 250 250 (1) 600 - #2 (2) 300 - 1/0 224 300 300 (1) 600 - #2 (2) 300 - 1/0
230V 9.6 196 250 250 (1) 600 - #2 (2) 300 - 1/0 224 300 300 (1) 600 - #2 (2) 300 - 1/0
3.0
460V 4.8 85 110 110 (1) 2/0 - #14 (1) 1/0 - #14 99 125 125 (1) 2/0 - #14 (1) 3/0 - #14
575V 3.9 70 90 90 (1) 2/0 - #14 (1) 1/0 - #14 88 110 110 (1) 2/0 - #14 (1) 1/0 - #14
208V 16.7 203 250 250 (1) 600 - #2 (2) 300 - 1/0 224 300 300 (1) 600 - #2 (2) 300 - 1/0
230V 15.2 202 250 250 (1) 600 - #2 (2) 300 - 1/0 224 300 300 (1) 600 - #2 (2) 300 - 1/0
5.0
460V 7.6 88 110 110 (1) 2/0 - #14 (1) 1/0 - #14 99 125 125 (1) 2/0 - #14 (1) 3/0 - #14
575V 6.1 72 90 90 (1) 2/0 - #14 (1) 1/0 - #14 88 110 110 (1) 2/0 - #14 (1) 1/0 - #14
208V 24.2 211 250 250 (1) 600 - #2 (2) 300 - 1/0 224 300 300 (1) 600 - #2 (2) 300 - 1/0
AGZ080D 230V 22.0 209 250 250 (1) 600 - #2 (2) 300 - 1/0 224 300 300 (1) 600 - #2 (2) 300 - 1/0
7.5
PUMP 460V 11.0 92 110 110 (1) 2/0 - #14 (1) 1/0 - #14 99 125 125 (1) 2/0 - #14 (1) 3/0 - #14
575V 9.0 75 100 100 (1) 2/0 - #14 (1) 1/0 - #14 88 110 110 (1) 2/0 - #14 (1) 1/0 - #14
208V 30.8 218 250 250 (1) 600 - #2 (2) 300 - 1/0 224 300 300 (1) 600 - #2 (2) 300 - 1/0
230V 28.0 215 250 250 (1) 600 - #2 (2) 300 - 1/0 224 300 300 (1) 600 - #2 (2) 300 - 1/0
10.0
460V 14.0 95 125 125 (1) 2/0 - #14 (1) 1/0 - #14 99 125 125 (1) 2/0 - #14 (1) 3/0 - #14
575V 11.0 77 100 100 (1) 2/0 - #14 (1) 1/0 - #14 88 110 110 (1) 2/0 - #14 (1) 1/0 - #14
208V 46.2 233 300 300 (1) 600 - #2 (2) 300 - 1/0 224 300 300 (1) 600 - #2 (2) 300 - 1/0
230V 42.0 229 300 300 (1) 600 - #2 (2) 300 - 1/0 224 300 300 (1) 600 - #2 (2) 300 - 1/0
15.0
460V 21.0 102 125 125 (1) 2/0 - #14 (1) 3/0 - #14 99 125 125 (1) 2/0 - #14 (1) 3/0 - #14
575V 17.0 83 100 100 (1) 2/0 - #14 (1) 1/0 - #14 88 110 110 (1) 2/0 - #14 (1) 1/0 - #14
Note: Power block and disconnect switch sizes are minimums. Larger sizes may be used, however the lug range must be the same.
IM 1110-2 41
Electrical Information
Table 24: Electrical Data - Multi-Point (Continued)
Multiple Point Field Data - Circuit #1 Multiple Point Field Data - Circuit #2
Pump
Model Voltage Ratings Lug Range Ratings Lug Range
HP FLA MCA RFS MFS Power Block (1) Disconnect Switch [1] MCA RFS MFS Power Block (1) Disconnect Switch [1]
208V 10.6 235 300 300 (1) 600 - #2 (2) 300 - 1/0 224 300 300 (1) 600 - #2 (2) 300 - 1/0
230V 9.6 234 300 300 (1) 600 - #2 (2) 300 - 1/0 224 300 300 (1) 600 - #2 (2) 300 - 1/0
3.0
460V 4.8 104 125 125 (1) 2/0 - #14 (1) 3/0 - #14 99 125 125 (1) 2/0 - #14 (1) 3/0 - #14
575V 3.9 91 125 125 (1) 2/0 - #14 (1) 1/0 - #14 88 110 110 (1) 2/0 - #14 (1) 1/0 - #14
208V 16.7 241 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 224 300 300 (1) 600 - #2 (2) 300 - 1/0
230V 15.2 240 300 300 (1) 600 - #2 (2) 300 - 1/0 224 300 300 (1) 600 - #2 (2) 300 - 1/0
5.0
460V 7.6 107 125 125 (1) 2/0 - #14 (1) 3/0 - #14 99 125 125 (1) 2/0 - #14 (1) 3/0 - #14
575V 6.1 94 125 125 (1) 2/0 - #14 (1) 1/0 - #14 88 110 110 (1) 2/0 - #14 (1) 1/0 - #14
208V 24.2 249 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 224 300 300 (1) 600 - #2 (2) 300 - 1/0
AGZ090D 230V 22.0 246 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 224 300 300 (1) 600 - #2 (2) 300 - 1/0
7.5
PUMP 460V 11.0 110 125 125 (1) 2/0 - #14 (1) 3/0 - #14 99 125 125 (1) 2/0 - #14 (1) 3/0 - #14
575V 9.0 97 125 125 (1) 2/0 - #14 (1) 3/0 - #14 88 110 110 (1) 2/0 - #14 (1) 1/0 - #14
208V 30.8 255 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 224 300 300 (1) 600 - #2 (2) 300 - 1/0
230V 28.0 252 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 224 300 300 (1) 600 - #2 (2) 300 - 1/0
10.0
460V 14.0 113 150 150 (1) 2/0 - #14 (1) 3/0 - #14 99 125 125 (1) 2/0 - #14 (1) 3/0 - #14
575V 11.0 99 125 125 (1) 2/0 - #14 (1) 3/0 - #14 88 110 110 (1) 2/0 - #14 (1) 1/0 - #14
208V 46.2 271 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 224 300 300 (1) 600 - #2 (2) 300 - 1/0
230V 42.0 266 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 224 300 300 (1) 600 - #2 (2) 300 - 1/0
15.0
460V 21.0 120 150 150 (1) 2/0 - #14 (1) 3/0 - #14 99 125 125 (1) 2/0 - #14 (1) 3/0 - #14
575V 17.0 105 125 125 (1) 2/0 - #14 (1) 3/0 - #14 88 110 110 (1) 2/0 - #14 (1) 1/0 - #14
208V 10.6 268 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 257 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 9.6 267 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 257 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
3.0
460V 4.8 123 175 175 (1) 2/0 - #14 (1) 3/0 - #14 118 150 150 (1) 2/0 - #14 (1) 3/0 - #14
575V 3.9 110 150 150 (1) 2/0 - #14 (1) 3/0 - #14 106 150 150 (1) 2/0 - #14 (1) 3/0 - #14
208V 16.7 274 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 257 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 15.2 273 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 257 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
5.0
460V 7.6 126 175 175 (1) 2/0 - #14 (1) 3/0 - #14 118 150 150 (1) 2/0 - #14 (1) 3/0 - #14
575V 6.1 112 150 150 (1) 2/0 - #14 (1) 3/0 - #14 106 150 150 (1) 2/0 - #14 (1) 3/0 - #14
208V 24.2 282 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 257 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
AGZ100D 230V 22.0 279 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 257 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
7.5
PUMP 460V 11.0 129 175 175 (1) 2/0 - #14 (1) 3/0 - #14 118 150 150 (1) 2/0 - #14 (1) 3/0 - #14
575V 9.0 115 150 150 (1) 2/0 - #14 (1) 3/0 - #14 106 150 150 (1) 2/0 - #14 (1) 3/0 - #14
208V 30.8 288 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 257 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 28.0 285 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 257 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
10.0
460V 14.0 132 175 175 (1) 2/0 - #14 (1) 3/0 - #14 118 150 150 (1) 2/0 - #14 (1) 3/0 - #14
575V 11.0 117 150 150 (1) 2/0 - #14 (1) 3/0 - #14 106 150 150 (1) 2/0 - #14 (1) 3/0 - #14
208V 46.2 304 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 257 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 42.0 299 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 257 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
15.0
460V 21.0 139 175 175 (1) 2/0 - #14 (1) 3/0 - #14 118 150 150 (1) 2/0 - #14 (1) 3/0 - #14
575V 17.0 123 150 150 (1) 2/0 - #14 (1) 3/0 - #14 106 150 150 (1) 2/0 - #14 (1) 3/0 - #14
208V 10.6 284 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 274 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 9.6 283 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 274 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
3.0
460V 4.8 120 150 150 (1) 2/0 - #14 (1) 3/0 - #14 115 125 125 (1) 2/0 - #14 (1) 3/0 - #14
575V 3.9 98 110 110 (1) 2/0 - #14 (1) 3/0 - #14 94 110 110 (1) 2/0 - #14 (1) 3/0 - #14
208V 16.7 290 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 274 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 15.2 289 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 274 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
5.0
460V 7.6 123 150 150 (1) 2/0 - #14 (1) 3/0 - #14 115 125 125 (1) 2/0 - #14 (1) 3/0 - #14
575V 6.1 100 125 125 (1) 2/0 - #14 (1) 3/0 - #14 94 110 110 (1) 2/0 - #14 (1) 3/0 - #14
208V 24.2 298 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 274 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
AGZ110D 230V 22.0 296 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 274 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
7.5
PUMP 460V 11.0 126 150 150 (1) 2/0 - #14 (1) 3/0 - #14 115 125 125 (1) 2/0 - #14 (1) 3/0 - #14
575V 9.0 103 125 125 (1) 2/0 - #14 (1) 3/0 - #14 94 110 110 (1) 2/0 - #14 (1) 3/0 - #14
208V 30.8 305 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 274 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 28.0 302 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 274 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
10.0
460V 14.0 129 150 150 (1) 2/0 - #14 (1) 3/0 - #14 115 125 125 (1) 2/0 - #14 (1) 3/0 - #14
575V 11.0 105 125 125 (1) 2/0 - #14 (1) 3/0 - #14 94 110 110 (1) 2/0 - #14 (1) 3/0 - #14
208V 46.2 320 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 274 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 42.0 316 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 274 300 300 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
15.0
460V 21.0 136 150 150 (1) 2/0 - #14 (1) 3/0 - #14 115 125 125 (1) 2/0 - #14 (1) 3/0 - #14
575V 17.0 111 125 125 (1) 2/0 - #14 (1) 3/0 - #14 94 110 110 (1) 2/0 - #14 (1) 3/0 - #14
Note: Power block and disconnect switch sizes are minimums. Larger sizes may be used, however the lug range must be the same.
42 IM 1110-2
Electrical Information
Table 25: Electrical Data - Multi-Point (Continued)
Multiple Point Field Data - Circuit #1 Multiple Point Field Data - Circuit #2
Pump
Model Voltage Ratings Lug Range Ratings Lug Range
HP FLA MCA RFS MFS Power Block (1) Disconnect Switch [1] MCA RFS MFS Power Block (1) Disconnect Switch [1]
208V 10.6 284 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 321 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 9.6 283 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 321 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
3.0
460V 4.8 120 125 125 (1) 2/0 - #14 (1) 3/0 - #14 159 200 200 (1) 2/0 - #14 (2) 300 - 1/0
575V 3.9 98 110 110 (1) 2/0 - #14 (1) 3/0 - #14 125 150 150 (1) 2/0 - #14 (1) 3/0 - #14
208V 16.7 290 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 321 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 15.2 289 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 321 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
5.0
460V 7.6 123 150 150 (1) 2/0 - #14 (1) 3/0 - #14 159 200 200 (1) 2/0 - #14 (2) 300 - 1/0
575V 6.1 100 125 125 (1) 2/0 - #14 (1) 3/0 - #14 125 150 150 (1) 2/0 - #14 (1) 3/0 - #14
208V 24.2 298 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 321 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
AGZ125D 230V 22.0 296 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 321 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
7.5
PUMP 460V 11.0 126 150 150 (1) 2/0 - #14 (1) 3/0 - #14 159 200 200 (1) 2/0 - #14 (2) 300 - 1/0
575V 9.0 103 125 125 (1) 2/0 - #14 (1) 3/0 - #14 125 150 150 (1) 2/0 - #14 (1) 3/0 - #14
208V 30.8 305 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 321 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 28.0 302 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 321 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
10.0
460V 14.0 129 150 150 (1) 2/0 - #14 (1) 3/0 - #14 159 200 200 (1) 2/0 - #14 (2) 300 - 1/0
575V 11.0 105 125 125 (1) 2/0 - #14 (1) 3/0 - #14 125 150 150 (1) 2/0 - #14 (1) 3/0 - #14
208V 46.2 320 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 321 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 42.0 316 350 350 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 321 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
15.0
460V 21.0 136 150 150 (1) 2/0 - #14 (1) 3/0 - #14 159 200 200 (1) 2/0 - #14 (2) 300 - 1/0
575V 17.0 111 125 125 (1) 2/0 - #14 (1) 3/0 - #14 125 150 150 (1) 2/0 - #14 (1) 3/0 - #14
208V 10.6 332 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 321 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 9.6 331 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 321 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
3.0
460V 4.8 164 200 200 (1) 2/0 - #14 (2) 300 - 1/0 159 200 200 (1) 2/0 - #14 (2) 300 - 1/0
575V 3.9 129 150 150 (1) 2/0 - #14 (1) 3/0 - #14 125 150 150 (1) 2/0 - #14 (1) 3/0 - #14
208V 16.7 338 400 400 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1 321 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 15.2 336 400 400 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1 321 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
5.0
460V 7.6 167 200 200 (1) 2/0 - #14 (2) 300 - 1/0 159 200 200 (1) 2/0 - #14 (2) 300 - 1/0
575V 6.1 131 150 150 (1) 2/0 - #14 (1) 3/0 - #14 125 150 150 (1) 2/0 - #14 (1) 3/0 - #14
208V 24.2 345 400 400 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1 321 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
AGZ130D 230V 22.0 343 400 400 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1 321 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
7.5
PUMP 460V 11.0 170 200 200 (1) 600 - #2 (2) 300 - 1/0 159 200 200 (1) 2/0 - #14 (2) 300 - 1/0
575V 9.0 134 150 150 (1) 2/0 - #14 (1) 3/0 - #14 125 150 150 (1) 2/0 - #14 (1) 3/0 - #14
208V 30.8 352 400 400 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1 321 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 28.0 349 400 400 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1 321 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
10.0
460V 14.0 173 200 200 (1) 600 - #2 (2) 300 - 1/0 159 200 200 (1) 2/0 - #14 (2) 300 - 1/0
575V 11.0 136 150 150 (1) 2/0 - #14 (1) 3/0 - #14 125 150 150 (1) 2/0 - #14 (1) 3/0 - #14
208V 46.2 367 450 450 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1 321 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 42.0 363 450 450 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1 321 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
15.0
460V 21.0 180 200 200 (1) 600 - #2 (2) 300 - 1/0 159 200 200 (1) 2/0 - #14 (2) 300 - 1/0
575V 17.0 142 175 175 (1) 2/0 - #14 (2) 300 - 1/0 125 150 150 (1) 2/0 - #14 (1) 3/0 - #14
208V 16.7 346 400 400 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1 329 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 15.2 344 400 400 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1 329 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
5.0
460V 7.6 171 200 200 (1) 600 - #2 (2) 300 - 1/0 163 200 200 (1) 2/0 - #14 (2) 300 - 1/0
575V 6.1 134 150 150 (1) 2/0 - #14 (1) 3/0 - #14 128 150 150 (1) 2/0 - #14 (1) 3/0 - #14
208V 24.2 353 400 400 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1 329 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 22.0 351 400 400 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1 329 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
7.5
460V 11.0 174 200 200 (1) 600 - #2 (2) 300 - 1/0 163 200 200 (1) 2/0 - #14 (2) 300 - 1/0
575V 9.0 137 150 150 (1) 2/0 - #14 (1) 3/0 - #14 128 150 150 (1) 2/0 - #14 (1) 3/0 - #14
208V 30.8 360 400 400 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1 329 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
AGZ140D 230V 28.0 357 400 400 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1 329 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
10.0
PUMP 460V 14.0 177 200 200 (1) 600 - #2 (2) 300 - 1/0 163 200 200 (1) 2/0 - #14 (2) 300 - 1/0
575V 11.0 139 150 150 (1) 2/0 - #14 (1) 3/0 - #14 128 150 150 (1) 2/0 - #14 (1) 3/0 - #14
208V 46.2 375 450 450 (2) 500 - #6 (2) 500 - 3/0 329 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 42.0 371 450 450 (2) 500 - #6 (2) 500 - 3/0 329 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
15.0
460V 21.0 184 225 225 (1) 600 - #2 (2) 300 - 1/0 163 200 200 (1) 2/0 - #14 (2) 300 - 1/0
575V 17.0 145 175 175 (1) 2/0 - #14 (2) 300 - 1/0 128 150 150 (1) 2/0 - #14 (1) 3/0 - #14
208V 59.4 388 450 450 (2) 500 - #6 (2) 500 - 3/0 329 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
230V 54.0 383 450 450 (2) 500 - #6 (2) 500 - 3/0 329 400 400 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1
20.0
460V 27.0 190 225 225 (1) 600 - #2 (2) 300 - 1/0 163 200 200 (1) 2/0 - #14 (2) 300 - 1/0
575V 22.0 150 175 175 (1) 2/0 - #14 (2) 300 - 1/0 128 150 150 (1) 2/0 - #14 (1) 3/0 - #14
Note: Power block and disconnect switch sizes are minimums. Larger sizes may be used, however the lug range must be the same.
IM 1110-2 43
Electrical Information
Table 26: Electrical Data - Multi-Point (Continued)
Multiple Point Field Data - Circuit #1 Multiple Point Field Data - Circuit #2
Pump
Model Voltage Ratings Lug Range Ratings Lug Range
HP FLA MCA RFS MFS Power Block (1) Disconnect Switch [1] MCA RFS MFS Power Block (1) Disconnect Switch [1]
208V 16.7 346 400 400 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1 415 500 500 (2) 500 - #6 (2) 500 - 3/0
230V 15.2 344 400 400 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1 415 500 500 (2) 500 - #6 (2) 500 - 3/0
5.0
460V 7.6 171 200 200 (1) 600 - #2 (2) 300 - 1/0 196 225 225 (1) 600 - #2 (2) 300 - 1/0
575V 6.1 134 150 150 (1) 2/0 - #14 (1) 3/0 - #14 176 225 225 (1) 600 - #2 (2) 300 - 1/0
208V 24.2 353 400 400 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1 415 500 500 (2) 500 - #6 (2) 500 - 3/0
230V 22.0 351 400 400 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1 415 500 500 (2) 500 - #6 (2) 500 - 3/0
7.5
460V 11.0 174 200 200 (1) 600 - #2 (2) 300 - 1/0 196 225 225 (1) 600 - #2 (2) 300 - 1/0
575V 9.0 137 150 150 (1) 2/0 - #14 (1) 3/0 - #14 176 225 225 (1) 600 - #2 (2) 300 - 1/0
208V 30.8 360 400 400 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1 415 500 500 (2) 500 - #6 (2) 500 - 3/0
AGZ160D 230V 28.0 357 400 400 (2) 500 - #6 (1) 600 - #1 & (2) 250 - #1 415 500 500 (2) 500 - #6 (2) 500 - 3/0
10.0
PUMP 460V 14.0 177 200 200 (1) 600 - #2 (2) 300 - 1/0 196 225 225 (1) 600 - #2 (2) 300 - 1/0
575V 11.0 139 150 150 (1) 2/0 - #14 (1) 3/0 - #14 176 225 225 (1) 600 - #2 (2) 300 - 1/0
208V 46.2 375 450 450 (2) 500 - #6 (2) 500 - 3/0 415 500 500 (2) 500 - #6 (2) 500 - 3/0
230V 42.0 371 450 450 (2) 500 - #6 (2) 500 - 3/0 415 500 500 (2) 500 - #6 (2) 500 - 3/0
15.0
460V 21.0 184 225 225 (1) 600 - #2 (2) 300 - 1/0 196 225 225 (1) 600 - #2 (2) 300 - 1/0
575V 17.0 145 150 150 (1) 2/0 - #14 (2) 300 - 1/0 176 225 225 (1) 600 - #2 (2) 300 - 1/0
208V 59.4 388 450 450 (2) 500 - #6 (2) 500 - 3/0 415 500 500 (2) 500 - #6 (2) 500 - 3/0
230V 54.0 383 450 450 (2) 500 - #6 (2) 500 - 3/0 415 500 500 (2) 500 - #6 (2) 500 - 3/0
20.0
460V 27.0 190 225 225 (1) 600 - #2 (2) 300 - 1/0 196 225 225 (1) 600 - #2 (2) 300 - 1/0
575V 22.0 150 150 150 (1) 2/0 - #14 (2) 300 - 1/0 176 225 225 (1) 600 - #2 (2) 300 - 1/0
208V 16.7 471 500 500 (2) 500 - #6 (2) 500 - 3/0 454 500 500 (2) 500 - #6 (2) 500 - 3/0
230V 15.2 430 500 500 (2) 500 - #6 (2) 500 - 3/0 415 500 500 (2) 500 - #6 (2) 500 - 3/0
5.0
460V 7.6 212 250 250 (1) 600 - #2 (2) 300 - 1/0 204 250 250 (1) 600 - #2 (2) 300 - 1/0
575V 6.1 182 225 225 (1) 600 - #2 (2) 300 - 1/0 176 225 225 (1) 600 - #2 (2) 300 - 1/0
208V 24.2 478 600 600 (2) 500 - #6 (2) 500 - 3/0 454 500 500 (2) 500 - #6 (2) 500 - 3/0
230V 22.0 437 500 500 (2) 500 - #6 (2) 500 - 3/0 415 500 500 (2) 500 - #6 (2) 500 - 3/0
7.5
460V 11.0 215 250 250 (1) 600 - #2 (2) 300 - 1/0 204 250 250 (1) 600 - #2 (2) 300 - 1/0
575V 9.0 185 225 225 (1) 600 - #2 (2) 300 - 1/0 176 225 225 (1) 600 - #2 (2) 300 - 1/0
208V 30.8 485 600 600 (2) 500 - #6 (2) 500 - 3/0 454 500 500 (2) 500 - #6 (2) 500 - 3/0
AGZ180D 230V 28.0 443 500 500 (2) 500 - #6 (2) 500 - 3/0 415 500 500 (2) 500 - #6 (2) 500 - 3/0
10.0
PUMP 460V 14.0 218 250 250 (1) 600 - #2 (2) 300 - 1/0 204 250 250 (1) 600 - #2 (2) 300 - 1/0
575V 11.0 187 225 225 (1) 600 - #2 (2) 300 - 1/0 176 225 225 (1) 600 - #2 (2) 300 - 1/0
208V 46.2 500 600 600 (2) 500 - #6 (2) 500 - 3/0 454 500 500 (2) 500 - #6 (2) 500 - 3/0
230V 42.0 457 500 500 (2) 500 - #6 (2) 500 - 3/0 415 500 500 (2) 500 - #6 (2) 500 - 3/0
15.0
460V 21.0 225 250 250 (1) 600 - #2 (2) 300 - 1/0 204 250 250 (1) 600 - #2 (2) 300 - 1/0
575V 17.0 193 225 225 (1) 600 - #2 (2) 300 - 1/0 176 225 225 (1) 600 - #2 (2) 300 - 1/0
208V 59.4 513 600 600 (2) 500 - #6 (2) 500 - 3/0 454 500 500 (2) 500 - #6 (2) 500 - 3/0
230V 54.0 469 500 500 (2) 500 - #6 (2) 500 - 3/0 415 500 500 (2) 500 - #6 (2) 500 - 3/0
20.0
460V 27.0 231 250 250 (1) 600 - #2 (2) 300 - 1/0 204 250 250 (1) 600 - #2 (2) 300 - 1/0
575V 22.0 198 225 225 (1) 600 - #2 (2) 300 - 1/0 176 225 225 (1) 600 - #2 (2) 300 - 1/0
208V 16.7 478 600 600 (2) 500 - #6 (2) 500 - 3/0 462 500 500 (2) 500 - #6 (2) 500 - 3/0
230V 15.2 438 500 500 (2) 500 - #6 (2) 500 - 3/0 423 500 500 (2) 500 - #6 (2) 500 - 3/0
5.0
460V 7.6 216 250 250 (1) 600 - #2 (2) 300 - 1/0 208 250 250 (1) 600 - #2 (2) 300 - 1/0
575V 6.1 185 225 225 (1) 600 - #2 (2) 300 - 1/0 179 225 225 (1) 600 - #2 (2) 300 - 1/0
208V 24.2 486 600 600 (2) 500 - #6 (2) 500 - 3/0 462 500 500 (2) 500 - #6 (2) 500 - 3/0
230V 22.0 445 500 500 (2) 500 - #6 (2) 500 - 3/0 423 500 500 (2) 500 - #6 (2) 500 - 3/0
7.5
460V 11.0 219 250 250 (1) 600 - #2 (2) 300 - 1/0 208 250 250 (1) 600 - #2 (2) 300 - 1/0
575V 9.0 188 225 225 (1) 600 - #2 (2) 300 - 1/0 179 225 225 (1) 600 - #2 (2) 300 - 1/0
208V 30.8 492 600 600 (2) 500 - #6 (2) 500 - 3/0 462 500 500 (2) 500 - #6 (2) 500 - 3/0
AGZ190D 230V 28.0 451 500 500 (2) 500 - #6 (2) 500 - 3/0 423 500 500 (2) 500 - #6 (2) 500 - 3/0
10.0
PUMP 460V 14.0 222 250 250 (1) 600 - #2 (2) 300 - 1/0 208 250 250 (1) 600 - #2 (2) 300 - 1/0
575V 11.0 190 225 225 (1) 600 - #2 (2) 300 - 1/0 179 225 225 (1) 600 - #2 (2) 300 - 1/0
208V 46.2 508 600 600 (2) 500 - #6 (2) 500 - 3/0 462 500 500 (2) 500 - #6 (2) 500 - 3/0
230V 42.0 465 500 500 (2) 500 - #6 (2) 500 - 3/0 423 500 500 (2) 500 - #6 (2) 500 - 3/0
15.0
460V 21.0 229 250 250 (1) 600 - #2 (2) 300 - 1/0 208 250 250 (1) 600 - #2 (2) 300 - 1/0
575V 17.0 196 225 225 (1) 600 - #2 (2) 300 - 1/0 179 225 225 (1) 600 - #2 (2) 300 - 1/0
208V 59.4 521 600 600 (2) 500 - #6 (2) 500 - 3/0 462 500 500 (2) 500 - #6 (2) 500 - 3/0
230V 54.0 477 500 500 (2) 500 - #6 (2) 500 - 3/0 423 500 500 (2) 500 - #6 (2) 500 - 3/0
20.0
460V 27.0 235 250 250 (1) 600 - #2 (1) 600 - #1 & (2) 250 - #1 208 250 250 (1) 600 - #2 (2) 300 - 1/0
575V 22.0 201 250 250 (1) 600 - #2 (2) 300 - 1/0 179 225 225 (1) 600 - #2 (2) 300 - 1/0
Note: Power block and disconnect switch sizes are minimums. Larger sizes may be used, however the lug range must be the same.
44 IM 1110-2
Electrical Information
Table 27: Electrical Data, Pumps Only (for field-wired pumps)
Note 1: Use above data when field wiring pumps separately from the chiller unit. Data is for individual pump. Include a field supplied
circuit breaker.
Note 2: Consult chiller catalog or installation manual for unit electrical data.
IM 1110-2 45
Pump Operation
Pump Operation
Pump Start Control (MicroTech® III) This option does not have the desirable automatic duty/standby
attribute normally associated with dual pumps. In case of a
The standard arrangement is for the MicroTech III unit pump failure, the second pump must be started manually on
controller pump output signal to automatically start and stop the selector switch.
the pump(s). The specific starting method is determined by the
Evap Pump Control setpoint. This setting allows the following Pump Operating Control
configurations:
Constant Flow
• #1 only - Pump A will always be used
The pumps will run at constant speed and will start and stop
• #2 only - Pump B will always be used
automatically with the chiller unit. When the chiller is enabled
• Auto - The primary pump is the one with the least run hours; to run by having its MicroTech III unit controller in the Auto
the other is used as a backup state or by a signal from a BAS (not necessarily with
• #1 Primary - Pump A used normally; pump B is backup compressors running based on availability of a cooling load),
the pump panel will receive a signal to start. When there is
• #2 Primary - Pump B used normally; pump A is backup
sufficient flow to close the flow switch within a timed period
#1 Only or #2 Only (recirc timer), a proof-of-flow signal is sent to the chiller and
the pump is in the Run state. If there is a call for cooling based
Selecting [#1 only] or [#2 only] will run only the pump on the chilled water temperature, the chiller will commence its
selected; the other is unavailable. This mode is useful for compressor startup procedure. If there is no call for cooling,
running only one pump if the other is out of service. [#1 only] the chiller will be on stand-by, waiting for load.
is the factory default setting when there is only one pump on
the pump package. If the flow switch does not see flow, the pump remains in the
Start state until flow is established, at which time the pump
Primary/Standby Pump Staging will be in the Run state. Flow is recognized when the flow
The pump designated as primary will start first. If the switch indicates flow for longer than the recir timer setpoint.
evaporator state is START for a time greater than the The Run state is a control condition established by satisfying
RECIRCULATE TIMEOUT setpoint and there is no flow, then certain conditions. The Start state means that a digital signal
the primary pump will be deenergized and the standby pump has been sent to the pump for it to start running.
will start. When the evaporator is in the RUN state, if flow is
lost for more than half of the FLOW PROOF setpoint value, If say, a chilled water valve is closed, the pump may receive a
the primary pump will shut off and the standby pump will Start signal and will run dead-headed but not actually be in the
start. Once the standby pump is started, the FLOW LOSS Run state as defined by the controller. No alarm is given in
alarm logic will apply if flow cannot be established in the this condition. When the valve is opened, the flow switch will
evaporator START state, or if flow is lost in the see flow, will signal this to the chiller controller, and the pump
EVAPORATOR RUN state. will go to the official Run state.
When starting the chiller, it is prudent to be sure there is flow
Auto Control so the chiller compressors will be able to start based on a call
AUTO pump control is the factory default on two-pump units; for cooling due to high chilled water temperature. Observing
the primary/standby logic above is in effect. When the water pressure gauges can confirm flow.
evaporator is not in the RUN state, the run hours of the pumps
Flow interruption will open the flow switch, sending a signal
will be compared. The pump with the least hours will be
to the chiller to shut down and also de-energize the pump. If
designated as the primary at this time.
the chiller is turned off, the pump will shut off after a timed
Optional Local Control at Pump Panel period to allow water circulation during refrigerant
pumpdown.
This control method can be selected at time of order placement
and provides for one start output from the MicroTech III unit Operation of the evaporator pump is controlled by the Pump
controller to start or stop pumps and two non-VFD pumps. Transition diagram in Figure 18. The pump will start on a
Pump operation is controlled by a selector switch located on signal from the chiller controller when either the chilled water
the door of the pump control panel. Pump #1 and Pump #2 will leaving or entering temperature reaches the chiller freeze point
run the respective pump exclusively, with no duty/standby setting to help prevent freeze up.
feature. The Auto position will alternate pump selection
through an alternating relay, changing pump with each start.
46 IM 1110-2
Pump Operation
Figure 18: Pump Transition Diagram
RUN START
TEST : Flow OK for
Evap Recirc Time
Variable Flow
There are four possible pump operating modes when the pump reduced, the pump automatically reduces the head developed
package is equipped with the variable frequency drive (VFD) according to the pre-set control curve. It is often found that
option: using a remote differential pressure sensor to sense the
1 Sensorless Pressure Control
pressure across a remote load could theoretically result in
loads close to the pump being under-pumped. The situation
2 BAS Control
would be where the load at a loop extremity is satisfied and the
3 Remote Sensor Control
control valve closes while a load close to the pump needs full
4 Locally SElected Constant Speed Control flow. The probability of this occurring is remote but it is
Sensorless Pressure Control is the factory default setting. possible. One answer to this is to move the sensor closer to the
Sensorless Pressure Control pump (two-thirds out in the system is a popular
recommendation) although physically re-positioning the
Speed and pressure is adjusted to match the system load. The
sensor at commissioning stage can be a costly exercise. With
control curve is designed to replicate sensor positions at
Sensorless pump control it is possible to replicate the moving
varying distances from the pump. Sensorless control is an
of a sensor by adjusting the head setting 'Hmin'.
innovative concept in circulating pumps. Pump performance
and characteristic curves for ten different speeds are embedded Figure 19: Pump Control Curve
in the memory of the speed controller during manufacture.
This data includes power, pressure and flow across the flow
range of the pump. NOTE: Sensorless operation is only
allowed for single chiller systems. Systems with parallel
chiller operation must use one of the other control methods.
These measurements enable the pump to continuously identify
the head and flow at any point in time, giving accurate
pressure control without the need for external feedback
signals. Patented software technology within the controller
ensures trouble-free operation in all conditions.
Incorporating the pump's hydraulic data into the controller and
removing sensors results in true integration of all components
and removes the risk of remote sensor failure.
The default control mode for Sensorless pumps 'Quadratic BAS Control
Pressure Control' where the controller is set to control the The pump will speed up or slow down based on an input from
speed according to a 'control curve' between max and min flow the BAS. The pump control protocol is the same as ordered for
(seeFigure 19). Fitting a differential pressure sensor at the the chiller unit.
most remote load, across the supply piping and return piping
encompassing the valve and coil set, is generally the best Remote Sensor Control
installation scheme for energy efficiency. The VFD is wired to pressure differential switch(s) mounted in
the chilled water piping system. This is the standard VFD
Sensorless control can replicate this control without the need
control when a sensorless VFD is not used
for the remote sensor. As the flow required by the system is
IM 1110-2 47
Pump Operation
Locally Selected Constant Speed Control to two variables when not in status mode and in the case of
This mode is selected by pressing the Hand on key. Operation Alarm/ Warning. The number of the Active Set-up (Sensorless
of the pump at a constant speed as selected on the VFD control mode being setup 1) is shown.
panel. This mode allows selecting a pump speed to match the Line 1-2: Operator data lines displaying data and variables
system curve. defined or chosen by the user. By pressing the [Status] key, up
to one extra line can be added. It shows up to 5 variables with
Operating the VFD Controller
related unit, regardless of status. In case of alarm/warning, the
The VFD incorporates an integrated graphic local display and warning is shown instead of the variables. Normal setup is to
keypad to select mode, change parameters and view status and show feet of head and gpm.
alarms. A diagram of the controller and explanation of its
Status line: Status shows the state of the inverter such as Run
operation begins on page 86.
OK, Running on Auto Remote Running
The unit is shipped in the sensorless mode. If this mode is to
Operating variables on the data lines (b) will vary depending
be used, no programming is required.
on the operating mode.
Figure 20: Graphical Local Control Panel (GLCP) • Sensorless: displays gpm and head
• External Sensor: displays gpm and head
(a) Status Line
• BAS: configured by the BAS
(b) Data Lines • Hand: displays Hz
Status Display II
See the operating variables (1.1, 1.2, 1.3, and 2) shown in the
display in Figure 21.
Control Functions
1 Graphical display with Status lines.
2 Menu keys and indicator lights (LED's) - selecting mode,
changing parameters and switching between display
functions.
3 Navigation keys and indicator lights (LEDs).
4 Operation keys and indicator lights (LEDs).
Graphical Display In the example, Speed, Motor current, Motor power and
Frequency are selected as variables in the first and second
The LCD-display is back-lit with a total of 6 alpha-numeric lines.1.1, 1.2 and 1.3 are shown in small size. 2 is shown in
lines. All data is displayed on the LCP which can show up to large size.
five operating variables while in [Status] mode.
Display Contrast Adjustment
Graphic Display Lines
Press [status] and [?] for darker display
Status line: The status line is programmable with the normal
setup displaying hertz on the left, Pump kw in the middle and Press [status] and [?] for brighter display
rpm on the right. Showing the status when in status mode or up
48 IM 1110-2
Pump Operation
Indicator Lights Back Cancel Info
Figure 22: LED Indicator Lights These keys are only used for programming
If certain threshold values are
Navigation Keys
exceeded, the alarm and/or
warning LED lights up (See The four navigation arrows (up, down, right, and left) are used
Figure 22). A status and alarm to navigate between the different screen choices. Use the keys
text appear on the control to move the cursor.
panel. The On LED is Figure 25: Navigation Keys
activated when the frequency
converter receives power
from mains voltage, a DC bus
terminal, or an external 24V
supply. At the same time, the
back light is on.
• Green LED/On: Control section is working.
• Yellow LED/Warn.: Indicates a warning, may turn into
Alarm.
OK
• Flashing Red LED/Alarm: Indicates an alarm.
Is used for choosing a parameter marked by the cursor and for
CONTROL KEYS enabling the change of a parameter.
Menu Keys
Pump Control Keys
The menu keys are divided into functions. The keys below the
Operation Control Keys for local control are found at the
display and indicator lamps are used for parameter set-up,
bottom of the control panel. The key in use will have an LED
including choice of display indication during normal
illuminated above it.
operation.
Figure 26: Pump Control Keys
Figure 23: Menu Keys
Hand On
Status
Enables control of the pump speed via the graphic keypad. It
Three different readouts can be chosen by pressing the [Status] will over-ride any other mode setting. Raise or lower the
key repeatedly. Normal display is as shown in Figure 21. frequency (speed) using the up and down arrow keys. The
Quick Menu pump will run even without a start signal from the chiller. If
selected when in the Auto mode, it will start operation at the
Used for programming only. current speed, from which the speed can be changed. When
Main Menu going back to auto, it will be at the last Hand on speed, but
Used for programming all parameters. quickly return to the correct automatic speed.
Alarm Log NOTE: The low water device (flow switch) input must be
Displays an Alarm list of the ten latest alarms (numbered A1- made for the pump to start in either hand mode or auto mode.
A10). To obtain additional details about an alarm, use the Off
arrow keys to maneuver to the alarm number and press [OK]. Stops the pump in any operating mode.
Information is displayed about the condition of the frequency
Auto-On
converter before it enters the alarm mode.
Enables the pump to be controlled by either the sensorless
The Alarm log button on the LCP allows access to both Alarm control, the BAS or by the remote pressure sensor, depending
log and Maintenance log. on which operating mode is being used. When a start signal is
Back/Cancel/Info Keys applied on the control terminals the pump will start.
Figure 24: Back/Cancel/Info Keys NOTE: For the pump to operate in either Sensorless mode or
any other automatic control mode it is necessary to have
pressed the [Auto on] button.
Reset
Used for resetting the frequency converter after an alarm (trip).
IM 1110-2 49
Pump Operation
Warnings and Alarms WARNING/ALARM 9 - Inverter overloaded
The inverter is about to cut out because of an overload (too
A warning or an alarm is signaled by the relevant LED on the
high current for too long). The counter for electronic, thermal
front of the GLCP and indicated by a code on the display. A
inverter protection gives a warning at 98% and trips at 100%,
warning remains active until its cause is no longer present.
while giving an alarm. You cannot reset the inverter until the
Under certain circumstances operation of the pump may still
counter is below 90%.The fault is that the inverter is
be continued. Warning messages may be critical, but are not
overloaded by more than nominal current for too long.
necessarily so. Warnings should be attended to ASAP as they
can revert to an Alarm-shutting down the unit. WARNING/ALARM 10 - Motor ETR over temperature
Viewing Warnings & Alarms According to the electronic thermal protection (ETR), the
motor is too hot. You can choose if you want the inverter to
To view the warning or alarm details, press the Alarm Log give a warning or an alarm when the counter reaches 100% in
key in the middle of the GLCP. Go to the Alarm Log line and programming par. 1-90 Motor Thermal Protection. The fault is
press OK. Navigate to the appropriate alarm number, press that the motor is overloaded by more than nominal current for
OK and view the alarm description, number and date-time too long. Check that the motor in programming par. 1-24
stamp. A detailed description with some corrective measures Motor Current is set correctly.
is below in the section titled Warning/Fault Messages.
WARNING/ALARM 11 - Motor thermistor over temp
Resetting Alarms The thermistor or the thermistor connection is disconnected.
You can choose if you want the inverter to give a warning or
In the event of an alarm, the inverter will have tripped. Alarms an alarm in par. 1-90 Motor Thermal Protection. Check that the
must be reset to restart operation once their cause has been thermistor is connected correctly between terminal 53 or 54
rectified. In many cases the auto reset function will restart the (analog voltage input) and terminal 50 (+ 10 Volts supply), or
pump. Alternatively the [RESET] button on the control panel between terminal 18 or 19 (digital input PNP only) and
can be pressed. terminal 50. If a KTY sensor is used, check for correct
NOTE: After a manual reset using the [RESET] button on the connection between terminal 54 and 55.
control panel, the [AUTO ON] button must be pressed to
restart the pump. WARNING/ALARM 13 - Over Current
The inverter peak current limit (approx. 200% of the rated
If an alarm cannot be reset, the reason may be that its cause
current) is exceeded. The warning will last approx. 8-12 sec,
has not been rectified, or the alarm is trip-locked (see also
then the inverter trips and issues an alarm. Turn off the inverter
table on following page).
and check if the motor shaft can be turned and if the motor size
Alarms that are trip-locked offer additional protection, means matches the inverter.
that the mains supply must be switched off before the alarm
can be reset. After being switched back on, the inverter is no ALARM 14 - Earth fault
longer blocked and may be reset as described above once the There is a discharge from the output phases to earth, either in
cause has been rectified. the cable between the inverter and the motor or in the motor
Alarms that are not trip-locked can also be reset using the itself. Turn off the inverter and remove the earth fault.
automatic reset function Reset Mode (Note: automatic wake-
ALARM 16 - Short-circuit
up is possible!)
There is short-circuiting in the motor or on the motor
Selected warning and fault messages follow.
terminals. Turn off the inverter and remove the short-circuit.
Warning/Fault Messages
WARNING 23 - Internal fans
WARNING/ALARM 3 - No motor External fans have failed due to defective hardware or fans not
No motor has been connected to the output of the inverter. mounted.
50 IM 1110-2
Pump Operation
ALARM 30 - Motor phase U missing fan speed is increased to the maximum in case the power part
Motor phase U between the frequency converter and the motor or control card is very hot. If the temperature is below 15 °C
is missing. Turn off the frequency converter and check motor the warning will be present.
phase U.
ALARM 68 - Safe Stop
ALARM 31 - Motor phase V missing Safe Stop has been activated. To resume normal operation,
Motor phase V between the inverter and the motor is missing. apply 24 VDC to terminal 37 then send a Reset signal (via
Turn off the inverter and check motor phase V. Bus, Digital I/O or by pressing [Reset]).
Motor phase W between the inverter and the motor is missing. Power card over temperature.
Turn off the frequency converter and check motor phase W.
ALARM 92 - No Flow
ALARM 33 - Inrush fault A no load situation has been detected for the system. See
Too many power ups have occurred within a short time period. parameter group 22-2*.
This warning/alarm is only active if the supply voltage to the A no flow and high speed indicates that the pump has run dry.
inverter is lost and par. 14-10 Mains Failure is NOT set to See parameter group 22-2*.
OFF. Possible correction check the fuses to the frequency
ALARM 96 - Start Delayed
converter
Start of the motor has been delayed due to short cycle
WARNING/ALARM 37 - Phase Imbalance protection is active. See parameter group 22-7*.
There is a current imbalance between the power units. VFD Operation
WARNING 49 - Speed limit The VFD constantly monitors the chilled water system's state.
The speed has been limited by range in par. 4-11 Motor Speed When the building cooling load drops, air side controls will
Low Limit [RPM] and par. 4-13 Motor Speed High Limit start to close in order to control the space temperature. At that
[RPM]. instant in time, the pump power draw will start to drop. The
drive will notice this and slow down the pump (Hz output will
ALARM 50 - AMA calibration failed decrease), which then triggers a decrease in flow and head
Contact Daikin Applied service. since the pump impeller rpm is dropping.
ALARM 51 - AMA check Unom and Inom The reverse is true, when the load increases (valves open), the
power draw will increase and the drive will speed up (Hz goes
The setting of motor voltage, motor current, and motor power up) and the flow and head increases.
is presumably wrong. Check the settings.
Both flow and head will fluctuate and since they are being read
WARNING 59 - Current limit instantaneously, as opposed to an averaged value, even the
The current is higher than the value in par. 4-18 Current Limit. slightest change is registered on the screen. This gives the
readings a jumpy appearance.
WARNING 60 - External Interlock A building's cooling load tends to change slowly and it may be
External Interlock has been activated. To resume normal difficult to discern load changes by merely observing the VFD
operation, apply24 V DC to the terminal programmed for display. However, the pump rpm, Hz and kW can be noted
External Interlock and reset the inverter (via Bus, Digital I/O over time and used for reference. A given building load will
or by pressing [Reset]). have a discrete reading.
WARNING 66 - Heatsink Temperature Low Observing the pump kW power input at various cooling loads
will indicate the large amount of electrical energy saved by the
The heat sink temperature is measured as 0 °C. This could VFD.
indicate that the temperature sensor is defective and thus the
IM 1110-2 51
Start-up and Shutdown
Start-up and Shutdown
In addition to making any settings required, it is often Check rotation of the pump by bumping it. It should be
desirable to run the pumps without the chiller running to check clockwise when viewed from the top of the motor looking
the chilled water circuit. De-energize the compressors by down at the fan rotation.
turning off the three switches located in the unit left-hand
Do not run the pump without fluid in the system. Fluid is
control panel (SW1, PS1 and PS2). Energize the unit by
required to cool and lubricate the pump.
closing the main disconnect located in the right-hand panel
door. Non-VFD pumps can then be operated using the switch Before starting pump(s) and with water in the pump, purge the
located on the door of the pump control panel. Use the dispay seal flush line by cracking the vent valve until water appears.
keypad on VFD unit for operation. Press the Hand on key and The valve will protrude from the pump insulation. The seal is
use the ? or ? key to regulate the pump speed and flow. The the highest point in the pump and requires water for sealing
VFD should be changed to the Auto mode for normal and lubrication.
operation.
VFD equipped pumps are shipped with the pump VFD
Setting the Operating Mode controller in the AUTO mode. Confirm this by checking the
VFD controller and pressing the Auto key if necessary. The
For convenience, the operating parameters for each of the three AUTO ON button is located at the bottom on the controller.
operating modes have pre-programmed setups. See Figure 20, page 48.
Setup #1 Sensorless
The pump control is factory set for this mode and no field Check that the "Y" strainer
valve is open (horizontal Vent
changes or programming is required. Valve
position) and the triple-
Setup #2 External Sensor duty valve is open.
Normally a differential pressure sensor. Hold-down Bolts
Setup #3 BAS Start Up
Occasionally the impeller may be temporarily bound up and
Hand On
will not turn at start up. If this is the case, loosen the insulation
Manual operation - not programmed. and loosen the hold-down bolts holding the motor assembly to
the pump casing (do not remove them) and bump the pump.
Change from the sensorless default setup #1 to setup #2 or #3
on the graphic keypad display as follows. See Figure 20, The pump package is shipped with three strainers:
page 48 for key locations. • A "Y" type strainer at the unit inlet connection
1 Press the OFF key. The keypad display will remain • A perforated strainer located in the inlet guide assembly at
powered. the inlet of the pump.
2 Press the MAIN MENU key. Should show parameter "0- • A fine mesh temporary start-up strainer located in the inlet
** Operations/Display". guide.
3 Press OK.
The "Y" strainer has a finer mesh than the inlet guide strainer
4 Press ▼ key to 0-1 "Set UP Operations". and should catch most debris before it reaches the inlet guide
5 Press "OK". Display goes to 0-10 "Active Setup" strainer, which also functions as suction flow direction device.
6 Press "OK". Display will show boxed #1, #2, or #3 No special attention need be paid to the suction guide strainer
7 Press ▼ or ▲ key to select either mode #2 or #3. #1 is at initial start-up. It will strain the pumped fluid and stabilize
factory default. the flow into the pump suction automatically.
8 Press OK. The upper right-hand corner of the display Removing Temporary Strainer
should show 2(2) or 3(3) depending on the choice.
The temporary strainer must be removed following system
9 Press AUTO for normal operation. clean up as follows:
10 Press STATUS to return to the normal operating screen. After all debris has been removed from the system, or a
maximum of 24 running hours, stop the pump and close the
Pre-start Up
pump isolation valves. Drain the suction guide by removing
Follow the chiller start-up procedure outlined in the current the drain plug or opening the blowdown valve, if installed.
chiller installation and operating manual, available on Remove the insulation disc held on with Velcro (the disc has a
www.DaikinApplied.com. In addition, check that the pump "CAUTION Remove Startup Strainer After 24 Hours” sticker).
package is operating normally in accordance with its sequence Remove the suction guide cover and remove the strainer
of operation. assembly from the valve body.
52 IM 1110-2
Start-up and Shutdown
The temporary fine-mesh start-up strainer is tack-welded to the Seasonal Shutdown
permanent stainless steel strainer. This temporary strainer
should now be removed from the permanent strainer. The fine- Follow the instructions in the chiller unit for seasonal
mesh strainer is designed to remove small particulate from shutdown procedures. In addition for the pump package:
new piping systems and could easily clog with debris if left in No components or piping on the pump package are heat traced.
place. This will be detrimental to the operation of the pump. If heat tracing is field installed, carefully remove the factory
Replace the permanent strainer into the fitting body, once the insulation, install the heat tracing and carefully replace the
temporary strainer is removed. insulation, being careful to seal it against moisture penetration.
Inspect the cover O-ring and replace if necessary. Replace the If draining the chilled water system, see diagrams beginning
cover into the body. Ensuring that the strainer is properly on page 5 for the location of drain points in the piping and
seated, tighten the cover bolts diagonally, evenly and firmly. pumps, both of which must be thoroughly drained.
The seal may drip at initial start up as it breaks in. If the drip
continues for more than a few hours, service may be required.
IM 1110-2 53
Setup for BAS Integration
Introduction Configuring the VFD Controller for BACnet
Setup for BAS Integration
The VFD pump supports an optional interface that allows MS/TP Communication
control by a Building Automation System (BAS). The pump This following section assumes you are using a BACnet
can be integrated to a BAS via BACnet® MS/TP, Option Card in conjunction with the AGZ-D pump package
LONWORKS® or Modbus network protocols. The frequency converter (see Figure 28). It is also assumed that the
appropriate MicroTech® III communication module must be VFD pump controller is connected to a "master" BAS or PC
selected as a factory-installed option on the AGZ-D chiller. equipped with a serial communication card supporting all the
The chiller communication module determines the BACnet communication services required by your application,
corresponding protocol of the VFD pump package frequency and that all requirements stipulated in the BACnet standard, as
converter. The VFD pump controller ships from the factory well as those pertaining to the VFD pump controller are
with the protocol option that matches the communication strictly observed as well as all limitations therein fully
module selected with the chiller. Note that while BACnet IP is respected.
offered as a factory-installed option on the AGZ-D chiller, The BACnet Option Card is designed to communicate with
BACnet IP is not offered on the VFD frequency converter. If a any master complying with the BACnet standard. Familiarity
chiller unit is ordered with BACnet IP, the VFD will be with the PC used as a master in the system is assumed.
provided with BACnet MS/TP. The VFD controller comes
Light Emitting Diodes (LEDs)
with an attached "option card" for BACnet and LonWorks.
Two bi-colored LEDs indicate communication activity and
The VFD controller is a native Modbus device and does not
status of BACnet communications. These indicators can be
require an "option card" for the Modbus protocol.
seen when the BACnet Option Card is connected to the VFD
Network parameters are set using the VFD controller's pump controller. Descriptions of the two LEDs are
graphical interface. The following sections describe the summarized in Table 29 and Table 30.
parameters that are required to enable communications from
the VFD pump directly to the BAS via BACnet MS/TP, Figure 28: BACnet Option Card
LONWORKS, or Modbus. Selecting a specific
communication protocol changes various default parameter
settings to match that protocol's specifications along with
making additional protocol-specific parameters available from
the BAS.
54 IM 1110-2
Setup for BAS Integration
Table 28: BACnet MS/TP Network Configuration Parameters
Parameter Setting for BACnet; Note Default Value
FC Port [1]
Option A [3] ; During initial power-up, the frequency
8-02 Control Source converter automatically sets this parameter to Option A
Note: This parameter cannot be adjusted while
[3] if it detects a valid fieldbus option installed in slot A
the motor is running.
8-30 Protocol BACnet Digital and control word
0-127; This value must be unique throughout the
8-31 Address FC RS485
MSTP trunk
9600/19,200/38,400/76,800 baud;
8-32 Baud Rate All devices on the MSTP trunk must be set to the same 9600 baud
baud rate
0-4194303; This value must be unique throughout the
8-70 BACnet Device Instance 1
entire BACnet network.
1-127; Dependent on the Number of Masters in the
8-72 MS/TP Max Masters 127
system
1-65534; Defines how many info/data frames the
8-73 MS/TP Max Info Frames device is 1
allowed to send while holding the token
IM 1110-2 55
Setup for BAS Integration
Table 30: LED 2 - BACnet Option Card Activity
Configuring the VFD Controller for LON- Figure 30: LONWORKS Connection
WORKS Communication
Introduction
This following section assumes you are using a LONWORKS
Option Card in conjunction with the AGZ-D pump package
frequency converter (see Figure 30, LONWORKS
Connection). The LONWORKS Option Card is LonMark 3.4
certified. It is designed to communicate with any system
complying with the FTT-10A and 78kbps LONWORKS
standard. Familiarity with this technology is assumed.
The LONWORKS communications structure is similar to that
of a local area network (LAN) in that messages are continually
exchanged between a number of processors. A LONWORKS
system is a local operating network (LON). LON technology
offers a means for integrating various distributed systems that
perform sensing, monitoring, control, and other automated
functions. A LON allows these intelligent devices to
communicate with one another through a variety of Service Pin Switch
communications media using a standard protocol. LON The service pin generates a service-pin message that contains
technology supports distributed, peer-to-peer communications. the Neuron® ID and the program code identification of the
That is, individual network devices can communicate directly node. A service-pin message is a network message that is
with one another without the need for a central control system. generated by a node and broadcast on the network. It can be
Data are transported by means of standard network variable used to commission the VFD controller to the LONWORKS
types (SNVTs) which provide the interface for communication network. The service pin switch is located on the lower right-
between devices from different manufacturers. LONWORKS- hand corner of the LonWorks Option Card. See Figure 30 for
defined functional profiles determine the functionality and location of the service pin.
network variables for a particular family of devices (e.g.
Light Emitting Diodes (LEDs)
frequency converters, pumps etc.) are also available, and
supported by the LONWORKS option. Two LEDs indicate communication activity and status of the
LonWorks Option Card. These indicators can be seen when the
The VFD controller typically does not involve network LonWorks Option Card is connected to the VFD pump
addressing to enable BAS communication. However, there are controller. Descriptions of the two Service LEDs are
several basic steps required for LONWORKS integration, summarized in and Table 32
which are described in the following section. Additionally, the
available network parameters are available via the graphical Steps for LONWORKS Configuration
interface as shown in Table 31. 1 Commission the VFD controller by pressing the service
pin (see Figure 30). Doing so generates a service-pin
message, which is broadcast on the network and contains
the Neuron ID and the program code identification of the
node.
56 IM 1110-2
Setup for BAS Integration
2 Cycle power to the unit controller after 1) 4 Verify connection from VFD to BAS - terminals 79 (Net
commissioning a device, 2) de-commissioning an A) and 80 (Net B) on top of LONWORKS Option Card.
existing device, and 3) subsequent re-commissioning of See Figure 30 for terminal locations.
an existing device. 5 The VFD controller is now ready for network
3 Review the LONWORKS network parameters as configuration from the BAS. Refer to the LONWORKS
described in Table 31 below. It is recommended that Operations Manual for the AGZ-D VFD Controller,
remaining items in menus 8-* and 11-* remain at factory which is available on www.DaikinApplied.com, for a
defaults. See VFD installation manual, available on complete points list and additional configuration
www.DaikinApplied.com for further details. information.
Table 31: LONWORKS Network Parameters
Param eter Value (Range)/Definition Default Value
Option A [3]/During initial pow er-up, the frequency converter
8-02 Control Source automatically sets this parameter to Option A [3] if it detects a FC Port [1]
valid fieldbus option installed in slot A
Variable/This item w ill be
11-0 Neuron ID Variable/This is the neuron ID of the Lonw orks module. blank if the communication
module is not commissioned.
VSD Profile [0]/This parameter indicates the LONMARK
11-10 Drive Profile VSD Profile [0]
functional profile
(0-FFFF)/This parameter contains LON specific w arnings.
Bit Status
0 Internal Fault
1 Internal Fault
2 Internal Fault
3 Internal Fault
4 Internal Fault
5 Reserved
6 Reserved
11-15 LON Warning Word N/A
7 Reserved
8 Reserved
9 Invalid type change for changeable types
10 Initialization error
11 Internal communication error
12 Softw are revision mismatch
13 Bus not active
14 Option not present
15 LON input (nvi/nci) exceeds limits
0 N/A/This parameter contains the version of the external
11-17 XIF Revision 0 N/A
interface file on the Neuron C chip on the LON option
0 N/A/This parameter contains the softw are version off the
11-18 LonWorks Revision 0 N/A
application program on the Neuron C chip on the LON option.
IM 1110-2 57
Setup for BAS Integration
Table 32: MS: Service LED (Red)
Situation LED Activity Description
Configured state ½ sec. ON, then The node is configures and running
(normal operation) continuously OFF normally.
Node is not configures but has an
Non-configured state Flashing ½ Hz
application. Proceed w ith loading node.
Configuring the VFD Controller for Modbus interface. The Modbus network address and data transmission
Communication rate (Baud Rate) are available via the local control panel. At a
minimum, you must set the network address and verify the
Introduction correct baud rate before establishing network communication
between the VFD controller and the BAS. Change remaining
The VFD controller (frequency controller) is a native Modbus
parameters as required for your network.
device. In other words, it does not require any additional
communication card or other hardware for integration into a 1 Set the Modbus network parameters as described in
building automation system (BAS) via the Modbus network. Table 21. It is recommended that remaining items in
The configuration process is described in the following menus 8-* remain at factory defaults. See VFD
section. It is assumed that the user is familiar with Modbus installation manual, available on
technology and terminology. www.DaikinApplied.com for further details.
Standard Modbus network rules apply. The network is a daisy- 2 Cycle power to the VFD controller for changes to take
chain of unit controllers including the master (in this case, the effect.
BAS) and all slaves (VFD controller). The Modbus standard 3 Verify connection from BAS to VFD - terminals 68 (+)
recommends that the network be terminated on each end with and 69 (-) on the main control board of the frequency
the characteristic impedance of the network (about 120 ohms). converter. Refer to Figure 35.
Follow the guidelines stated in the Modbus specifications. 4 The VFD controller is now ready for network
configuration from the BAS. Refer to the Modbus
Steps for Modbus Configuration
Operations Manual for the AGZ-D VFD Controller,
Configurable Parameters which is available on www.DaikinApplied.com, for a
Table 33 defines the network parameters of the Modbus complete points list and additional configuration
information.
Communication Module that are available via the graphical
58 IM 1110-2
Setup for BAS Integration
Table 33: Modbus Network Parameters
Param eter Value (Range)/Definition Default Value
8-02 Control Source FC Port [1]/ On-board RS-485 port FC Port [1]
Note: Note: Remaining items in menus 8-* should likely remain at factory defaults. See VFD installation manual for further details.
IM 1110-2 59
System Maintenance
System Maintenance
DANGER
Electric equipment can cause electric shock with a risk of severe personal injury or death. Turn off, lock out and tag all power
before continuing with following service. Panels can have more than one power source.
CAUTION
Service must be performed by trained, experienced refrigeration personnel familiar with equipment operation, maintenance,
correct servicing procedures, and the safety hazards inherent in this work. Causes for repeated tripping of equipment protection
controls must be investigated and corrected.
60 IM 1110-2
System Maintenance
Pump Removal 6 Remove the adapter/casing bolts and lift the rotating
The 4392 pump must be shut down and drained in order to assembly (motor, adapter, impeller, etc) out of the casing.
remove either pump's rotating assembly. If it is desired to run 7 Remove the existing gasket and ensure the gasket
the remaining pump during the replacement procedure, a surfaces on the adapter and casing are smooth & clean.
blanking plate and gasket can be installed to seal off the 8 Insert the 4392 blanking plate fit and cross-tighten bolts
removed pump cavity. The removal procedure is as follows: evenly (to 50 ft-lbs)
1 Stop, isolate and drain the 4392 unit, in the usual manner • 6-inch impeller (PN 427804-0612 - Plate with Gasket).
2 For the pump to be serviced: • 8-inch impeller (PN 427804-0812 - Plate with Gasket)
3 Isolate and disconnect the motor cable. 9 Open system isolation valves and re-start the duty pump.
4 Close the flush / vent line valve and disconnect the 10 Reverse process when repaired rotating assembly is
tubing from the adapter fitting. ready for installation.
5 Line mark the parts (Casing /Adapter & Adapter Motor)
to confirm re-assembly locations.
IM 1110-2 61
Daikin Applied Training and Development
Now that you have made an investment in modern, efficient Daikin Applied equipment, its care should be a high priority. For
training information on all Daikin Applied HVAC products, please visit us at www.DaikinApplied.com and click on Training, or
call 540-248-9646 to speak with the Training Department.
Warranty
All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product Warranty.
Consult your local Daikin Applied sales representative for warranty details. To find your local Daikin Applied representative, go
to www.DaikinApplied.com.
Aftermarket Services
To find your local parts office, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787).
To find your local service office, visit www.DaikinApplied.com or call 800-432-1342.
This document contains the most current product information as of this printing. For the most up-to-date product information,
please go to www.DaikinApplied.com.