COLD STORAGE Excel Sheet
COLD STORAGE Excel Sheet
Insulation Type
Inches Type
Ceiling 4 Styrene
Walls 4 Styrene
Floor 6 Concrete
Product Load
(a) 1000 lbs./day of Mix Vegitable to be reduced from entering
From Temp of 106 ºF. to 35 ºF. (Table 7) Temp. Drop 71 ºF.
(b) 300 lbs./day of Apples to be reduced from entering
From Temp of 106 ºF. to 35 ºF. (Table 7) Temp. Drop 71 ºF.
Miscellaneous
Motors (including all blower motors) 3 HP
Lights (assume 1 watt/sq.ft.) 7200 Watts
No. of people 100
1. Transmission Loads
Ceiling: (L) 120 x (W) 60 x Heat Load 101 (Table 1) = 727200 BTUH
North Wall: (L) 120 x (H) 15 x Heat Load 101 (Table 1) = 181800 BTUH
South Wall: (L) 120 x (H) 15 x Heat Load 101 (Table 1) = 181800 BTUH
East Wall: (L) 60 x (H) 15 x Heat Load 101 (Table 1) = 90900 BTUH
West Wall: (L) 60 x (H) 15 x Heat Load 101 (Table 1) = 90900 BTUH
Floor: (L) 120 x (W) 60 x Heat Load 350 (Table 1) = 2520000 BTUH
3. Additional Loads
Electrical Motors: 3 HP x 75000 BTU/HP/24 hr. = 225000 BTUH
Electrical Lights: 10800 Watts x 82 = 885600 BTUH
People Load: 100 People x 21480 BTU/24 hrs. (Table 12) = 2148000 BTUH
Divide by No. of Operating Hrs. (18) to obtain BTUH Cooling Requirement 462286 BTUH
Total Fresh Air Load 149310 BTUH
Total Load 611597 BTUH
Total Cooling Load 51 TON
Hyderabad - INDIA
ºF.
430920 BTUH
63900 BTUH
18531 BTUH
`