Selectivity Diagram For QA 6 and QA 0 in Normal Operation Operating Mode

The document details the selectivity diagram for circuit breakers QA 6 and QA 0, indicating total selectivity in normal operation. It provides technical specifications including ratings, trip unit settings, and calculation results in accordance with CENELEC TR50480. Additionally, it warns users about the risk of inaccurate data results and emphasizes the importance of proper software configuration and input verification.

Uploaded by

seifessam69209
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
9 views3 pages

Selectivity Diagram For QA 6 and QA 0 in Normal Operation Operating Mode

The document details the selectivity diagram for circuit breakers QA 6 and QA 0, indicating total selectivity in normal operation. It provides technical specifications including ratings, trip unit settings, and calculation results in accordance with CENELEC TR50480. Additionally, it warns users about the risk of inaccurate data results and emphasizes the importance of proper software configuration and input verification.

Uploaded by

seifessam69209
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Page 1/3

Selectivity diagram for QA 6 and QA 0 in Normal Operation


operating mode
QA 6 : NSX160B - TM-D - 125 A
QA 0 : NSX630F - Micrologic 5.3 E - 630 A

Selectivity status : Total Selectivity

__ Utility Curve __ Damage Curve __ Inrush Curve

Ib Ik3Max Ik1min Iefmin


115A 13.77 kA 6.84 kA 4.87 kA

QA 6 QA 0
Range ComPacT NSX ComPacT NSX
Designation/fuse technology NSX160B NSX630F
Circuit breaker/fuse rating 160 630
Trip unit TM-D Micrologic 5.3 E
Trip unit rating 125 630
Long delay settings
Ir (A) 125 611
Tr (s) 0 16
Short delay settings
Isd (A) 1250 916
Tsd (s) 0 0.1
Instantaneous tripping
Ii (A) OFF 6930

Project: EPM432s_2000309_Lab[2] 12/04/2025


Page 2/3

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Project: EPM432s_2000309_Lab[2] 12/04/2025


Page 3/3

NOTICE

RISK OF INACCURATE DATA RESULTS.

• Configure the software correctly to get accurate reports and/or data results.
• Do not rely solely on software messages and reports to determine if the
system is functioning correctly.
• Make sure that you have entered the correct inputs for the required
components.
• Review the calculated results and solutions provided by the software before
submitting the report.

Failure to follow these instructions can result in incorrect bill of material and
loss of business.

Project: EPM432s_2000309_Lab[2] 12/04/2025

You might also like