Selectivity Diagram For QA 6 and QA 0 in Normal Operation Operating Mode
Selectivity Diagram For QA 6 and QA 0 in Normal Operation Operating Mode
QA 6 QA 0
Range ComPacT NSX ComPacT NSX
Designation/fuse technology NSX160B NSX630F
Circuit breaker/fuse rating 160 630
Trip unit TM-D Micrologic 5.3 E
Trip unit rating 125 630
Long delay settings
Ir (A) 125 611
Tr (s) 0 16
Short delay settings
Isd (A) 1250 916
Tsd (s) 0 0.1
Instantaneous tripping
Ii (A) OFF 6930
NOTICE
• Configure the software correctly to get accurate reports and/or data results.
• Do not rely solely on software messages and reports to determine if the
system is functioning correctly.
• Make sure that you have entered the correct inputs for the required
components.
• Review the calculated results and solutions provided by the software before
submitting the report.
Failure to follow these instructions can result in incorrect bill of material and
loss of business.