Hunt 2008
Hunt 2008
Abstract
The second harmonic inrush restraint function of transformer differential relays maintains
security of the differential protection during transformer inrush events. The typical setpoint for
the second harmonic restraint is the relay manufacturer’s default or recommended setting of 20%
of fundamental current, with some adjustment based on operating experience. However, some
operating situations may result in levels of second harmonic current lower than 20% during
inrush, and levels may be as low as 5%. This lower level of second harmonic current requires a
lower inrush restraint setting that may impact the tripping time of the differential element for
fault conditions. In addition, inrush restraint is typically performed on a per-phase basis, so a loss
of security is possible if inrush restraint performs incorrectly on only one phase of the protected
transformer.
This paper provides several examples of actual events where loss of security occurred due to
incorrect settings of the second harmonic restraint function, or due to mis-application of cross-
phase blocking. Based on the information from these events, the paper directly discusses
considerations and recommendations for setting the second harmonic restraint to maintain
security during transformer inrush including a discussion of traditional and adaptive inrush
restraint techniques. The paper also includes recommendations on when to apply cross-phase
blocking techniques such as 1-out-of-3 blocking, 2-out-of-3 blocking and Averaging blocking
methods.
A key message from this paper is the use of the actual inrush characteristic of the protected
transformer to determine optimum setpoints for the differential relay. Microprocessor relays have
the capability to, and should, capture waveforms every time a transformer is energized. This data
should be analyzed to check the adequacy of the existing second harmonic restraint settings, to
ensure no loss of security occurs.
1. Introduction
Florida Power & Light Company (FPL) is in the process of replacing existing transformer
protection panels at select locations on the FPL transmission system. The existing panels use
electro-mechanical or solid-state differential relays, and the new transformer protection panels
will use microprocessor relays with wye-connected CTs in an FPL standard protection package.
The basic protection for these transformers is differential protection where second harmonic
blocking is used to block the differential element from operating during transformer inrush
events.
As part of this replacement process, FPL used an experimental laboratory procedure along
with actual operating experiences to validate settings before placing the transformer in service.
A relay was configured to some inrush restraint function, level setting, and cross-phase blocking
method. These settings were then tested against simulated and actual fault events, by playing
oscillographic records back through a test set to the relay. These tests were repeated using
different setpoints and different restraint functions until a setting that meets FPLs’ operating
criteria was determined. These settings are then confirmed by capturing transformer in-rush
events and comparing the setpoint levels to actual second harmonic levels to confirm there is
enough margin.
One of the drivers for this process is an effort to eliminate misoperations of transformer
differential relays due to low second harmonics on inrush without sacrificing protection
capabilities. Misoperations can occur during the energization of a transformer due to failure of
the harmonic restraint function. A digital fault recorder oscillographic record that captures this
type of harmonic restraint failure was used for the testing later in this paper. This fault record
shows a failure due to the low levels of harmonic current produced during an energization. An
external fault can also trigger a misoperation during the voltage recovery period, causing the
differential relay to operate immediately after a fault is cleared from the system.
I1 I1 I1
i1 i1 i1
inrush
119
Practical Experience in Setting Transformer Differential Inrush Restraint
There are two common situations where differential protection may incorrectly declare an
internal fault condition. One condition is CT saturation for a fault outside of the transformer zone
of protection. The error in the measurement signal of the saturated CT results in a significant
error in the differential current. The erroneous differential current may result in undesired
operation of the differential element for an external fault condition. This type of event is beyond
the scope of this paper.
The second common situation is a transformer inrush event. Some operating situations
instantly change the operating flux of the transformer core, requiring a large supply of current.
This inrush of current typically occurs in only one winding of the transformer. Therefore inrush
currents may produce a differential current that results in the operation of the differential
protection. This type of event is not a fault condition, so the differential protection should
restrain from operating for this condition.
120
Practical Experience in Setting Transformer Differential Inrush Restraint
R1 X1
I1 I2
Magnetizing
Current Rm Xm
121
Practical Experience in Setting Transformer Differential Inrush Restraint
field. Once the external field is reduced, the magnetic moments maintain a net magnetization
component along by the direction of the field. This effect results in magnetic hysteresis of the
steel.[2] Transformers use grain-oriented electrical steel, where the domains tend to produce
directions of magnetization with high permeability and low core loss.
M
e M M'' M''
M' M'
iM''
iM' Time iM'' iM' iM
iM
Figure 4 shows the exciting voltage e, the core flux M, and the exciting current iM, of a
transformer. The figure also shows the flux and exciting current mapped to the corresponding
magnetic hysteresis loop. The excitation voltage drives the flux in the core. The exciting current
is needed to produce the magnetic field. The waveform of the exciting current varies from the
sinusoidal waveform of the flux due to the non-linear magnetic properties of the core.[2]
The waveforms and hysteresis loop shown in Figure 4 are typical for a transformer that is in
service supplying load. The flux requirement is very small, and therefore the exciting current is
very small. Now consider what happens when the excitation voltage increases. This voltage
drives an increase in the flux in the core. The flux characteristic is still sinusoidal in shape. The
flux may be shifted in respect to the 0-axis due to the point on the wave when the excitation
increases, and the amount of remanent flux in the core. This flux may be high enough to cause
saturation of the transformer core. The hysteresis loop becomes negligible for this case, as shown
in Figure 5. The resulting current, the magnetizing inrush current, needed to supply the flux is
very high in magnitude, and may approach the magnitude of fault currents. The magnetizing
current will eventually decay due to losses in the circuit.[3]
122
Practical Experience in Setting Transformer Differential Inrush Restraint
iM
M
e
M
saturation knee
pont
Time iM
2D radians
123
Practical Experience in Setting Transformer Differential Inrush Restraint
Voltage
angle
e M
Time
Start of event
Figure 7: Voltage angle during magnetizing inrush
It is obvious that the flux is offset with respect to the 0-axis based on the voltage angle T.
When the voltage angle T is 90q, the flux is fully offset. There is no offset when the voltage angle
T is 0q. Maximum saturation of the transformer core occurs when the flux is fully offset at the
90q voltage angle. [3]
124
Practical Experience in Setting Transformer Differential Inrush Restraint
Voltage M
angle
90o
Time
Start of event
Figure 8: Exciting voltage and flux at 90q voltage angle
M
e e
Time Time
125
Practical Experience in Setting Transformer Differential Inrush Restraint
126
Practical Experience in Setting Transformer Differential Inrush Restraint
across the system impedance. As the source impedance decreases, indicating a stronger source,
the magnitude of the inrush current increases. The resistance of the system is also a major
contributor to the decay of the inrush current over time. The change in flux over time is defined
by
t T
'M ³
t
R u i dt
D radians 2S 4S Time
127
Practical Experience in Setting Transformer Differential Inrush Restraint
Setting the midpoint of the first peak to time t=0, a cosine Fourier series may be used to
calculate the second harmonic current and fundamental frequency component. Assuming the
exciting current is truly symmetric, then the second harmonic ratio will be as high as 70.5%
when D = S/3 radians, and will be 17.1% when D = 2S /3 radians.[3]
128
Practical Experience in Setting Transformer Differential Inrush Restraint
Current
Tx 1
Tx 2
Time
R + jX
Tx 2
Time
Tx 1
Current
Figure 11: Sympathetic inrush circuit and waveforms
129
Practical Experience in Setting Transformer Differential Inrush Restraint
fundamental frequency component in the differential current. Tripping of the differential element
is blocked when this ratio exceeds an adjustable threshold.
Differential
Current
Second
SP H/ harmonic
current
Differential
trip level
H/ SP
NOT
AND
TRIP
130
Practical Experience in Setting Transformer Differential Inrush Restraint
131
Practical Experience in Setting Transformer Differential Inrush Restraint
90o
120o 60o
INHIBIT
150o 30o
210o 330o
INHIBIT
240o 300o
270o
132
Practical Experience in Setting Transformer Differential Inrush Restraint
1-out-of-3. In 1-out-of-3 mode, all three phases are restrained when a blocking
condition exists on any one phase. 1-out-of-3 mode typically reverts back to per-
phase mode after a short time delay to allow tripping in case an internal fault
occurs during energization.
These restraint modes may be explicit settings of the transformer differential element. They
may also be implemented in the flexible configuration logic of the transformer protection relay.
133
Practical Experience in Setting Transformer Differential Inrush Restraint
134
Practical Experience in Setting Transformer Differential Inrush Restraint
averaging
In addition, the 1-out-of-3 inrush restraint mode can be implemented using the
flexible configuration logic of the relay.
This test procedure uses wye-connected CTs that are typical on new installations using
microprocessor-based differential relays. Delta-connected CTs complicate inrush restraint
settings. The currents measured by the relay are phase-phase currents. The subtractive effect of
the delta connection may actually decrease the second harmonic current seen by the relay and
require a lower setting on the inrush restraint function.[9]
Therefore, the concern for setting the inrush restraint function is the ratio of the second
harmonic current to the fundamental current. Having some guidelines that predict this ratio will
help develop inrush restraint settings that are sensitive and selective.
To determine the most appropriate choice for the inrush restraint method and the inrush
restraint mode, a simple bench test experiment was devised. The
procedure was to simply choose some settings for the relay, connect the
relay to a three-phase test set, and play several oscillography files SET RELAY Function
through the relay. SET RELAY Mode
SET RELAY Level
135
Practical Experience in Setting Transformer Differential Inrush Restraint
136
Practical Experience in Setting Transformer Differential Inrush Restraint
PLAY FAULT
Y
Differential
REDUCE Level
Trip
CHANGE Mode
7. Conclusions
The traditional settings for inrush restraint for transformer differential protection are to use
harmonic restraint in a per-phase mode, with a restraint level of 20%. Experience shows that for
most transformer protection applications these settings provide high-speed clearing of
transformer faults and proper restraint for inrush events. For a few applications, lowering the
harmonic restraint setting, employing cross-blocking techniques, or a combination of both may
be necessary to ensure that transformer energizations occur successfully where very low second
harmonic inrush levels are present. Capturing energization records to confirm where these
techniques may need to be employed is essential.
Based on operating experience, FPL has a few transformer protection applications where the
traditional inrush restraint settings are not adequate. For these applications, FPL plans to use
137
Practical Experience in Setting Transformer Differential Inrush Restraint
either 2-out-of-3 or averaging mode, to provide greater security, along with a setting for the
harmonic blocking function in the range of 15 to 20%. This range, along with applying cross-
phase blocking techniques, provides a good margin of security for energization of the
transformer where the second harmonic current may fall to low levels. The belief is these settings
will also successfully restrain the differential element when faced with a fault recovery
magnetizing inrush event.
There may be some concern when setting the inrush restraint level to 15% or lower. CT
saturation during internal faults may result in the protection relay seeing a high second harmonic
current ratio and incorrectly restraining. Setting an unrestrained differential element between 8
per unit and 10 per unit provides confidence the transformer protection will trip for an internal
fault even at a lower setting for the inrush restraint.
FPL has used this process to guide the development of inrush restraint settings. The limited
experience to date with intelligent consideration of the settings has been successful. The
following event records are from two different transformer locations that used these settings. The
transformers in both cases had previously been energized, so remanent flux was present in the
transformer core. Figure 19 is for a 560MVA, 230kV/138kV three-phase autotransformer,
energized at 230kV. Figure 20 is for a 224MVA, 230kV/138kV autotransformer, energized at
230kV.
138
Practical Experience in Setting Transformer Differential Inrush Restraint
139
Practical Experience in Setting Transformer Differential Inrush Restraint
8. Symbols
The process control industry has developed symbols and diagramming formats to represent
both linear and non-linear processes. The symbols and diagramming format are commonly
known as “SAMA diagrams”, as they were originally a standard developed by the Scientific
Apparatus Makers Association. Though the Scientific Apparatus Makers Association has
declared the original standard obsolete, and no longer permits the direct association of the
organization name with the industry standard, these symbols, and the term “SAMA diagram”, are
still in common use in the process control industry. These symbols will grow increasingly useful
as protection systems migrate from traditional protection and control to automatic process
control.
Setpoint Dividing
9. References
[1] L. L. Grigsby, editor, “The Electric Power Engineering Handbook”, CRC Press LLC, Boca
Raton, FL, 2001, p. 3-29.
[2] A. E. Fitzgerald, C. Kingsley, Jr., S. D. Umans, “Electric Machinery, 4th edition”,
McGraw_Hill Book Company, New York, NY, 1983, pp. 4-24.
[3] S. H. Horowitz, A. G. Phadke, “Power System Relaying, 2nd edition”, Research Studies Press
Ltd., Somerset, England, 1995, pp. 210-214.
[4] C. E. Lin, C. L. Cheng, C. L. Huang, J. C. Yeh, “Investigation of Magnetizing Inrush
Current in Transformers Part I – Numerical Simulation”, IEEE Transactions on Power
Delivery, Vol. 8, No. 1, January, 1993, pp. 246-254.
[5] H. S. Bronzeado, P. B. Brogan, R. Yacamini, “Harmonic Analysis of Transient Currents
During Sympathetic Interaction”, IEEE Transactions on Power Systems, Vol. 11, No. 4,
November 1996.
[6] M. M. Saied, “A Study on the Inrush Current Phenomena in Transformer Substation”,
Conference Record of the 36th Annual Meeting of the IAS, 2001. pp. 1180-1187.
140
Practical Experience in Setting Transformer Differential Inrush Restraint
10. Bibliography
[B1] C. E. Lin, C. L. Cheng, C. L. Huang, J. C. Yeh, “Investigation of Magnetizing Inrush
Current in Transformers Part II – Harmonic Analysis”, IEEE Transactions on Power
Delivery, Vol. 8, No. 1, January, 1993, pp. 255-263.
[B2] GE Publication GEK-113327A, “T60 Transformer Management Relay”, Instruction
Manual, Markham, Ontario, Canada, 2006
[B3] G. Ziegler, “Numerical Differential Protection”, Publicis Corporate Publishing,
Erlangen, Germany, 2005. pp. 146-151.
Authors
Rich Hunt, Application Engineer, GE Multilin
Rich Hunt is an Application Engineer with GE Multilin, responsible for technical sales, technical
marketing, and technical support of GE Multilin products. Rich has 20 years experience in
electric utility systems, including 10 years with Virginia Power, and 10 years experience as an
Application Engineer for relay manufacturers. Rich earned the B.S.E.E. and M.S.E.E at Virginia
Tech, with a master’s thesis on applications of protective relays. He is registered Professional
Engineer in the Commonwealth of Virginia, and is a member of the Main Committee of the
IEEE Power System Relaying Committee.
Joe Schaefer, FPL
Joe Schaefer is responsible for developing and testing protective relay standards related to
generation, transmission, and distribution applications. His most recent designs include relay
protection for auto-transformers for applications up to 500kV. Previously, Joe was employed as
a protection field engineer responsible for relay equipment from 480V to 500kV applications
including nuclear plant relaying. Joe received his BSEE from University of Florida and joined
Florida Power and Light in 1987.
Bob Bentert, FPL
Bob Bentert is a Senior Engineer responsible for operations support of protective relay and
control equipment. Bob evaluates protective relays and performs in-depth analysis of protective
relay misoperations. Prior to FPL, Bob was the Customer Services Manager for GEC Alstom
Relays and worked for ASEA Protection and Control as a project manager.
141