Controller for temperature control - EKC 202

REFRIGERATION AND AIR CONDITIONING

Manual

Introduction
Anvendelse Application The controller is used for temperature control refrigeration appliances and cold room in supermarkets Control of defrost, fans, alarm and light For front panel mounting Principle The controller contains a temperature control where the signal can be received from one temperature sensor. The sensor is placed in the cold air ow after the evaporator or in the warm air ow just before the evaporator. The controller controls the defrost with either natural defrost or electric defrost. Renewed cutin after defrost can be accomplished based on time or temperature. A measurement of the defrost temperature can be obtained directly through the use of a defrost sensoro. Two to four relays vwill cut the required functions in and out the application determines which: Refrigeration (compressor or solenoid valve) Defrost Fan Alarm Light The dierent applications are described on next page. Advantages Integrated refrigeration-technical functions Defrost on demand in 1:1 systems Buttons and seal imbedded in the front IP65 density from the front panel Digital input for either: - Door contact function with alarm - Defrost start - Start/stop of regulation - Night operation - Change-over between two temperature reference - Case cleaning function Instant programming via programming key HACCP Factory calibration that will guarantee a better measuring accuracy than stated in the standard EN 441-13 without subsequent calibration (Pt 1000 ohm sensor) Extra module The controller can afterwards be tted with an insertion module if the application requires it. The controller has been prepared with plug, so the module simply has to be pushed in - Battery and buzzer module The module guarantees voltage to the controller if the supply voltage should drop out for more than four hours. The clock function can thus be protected during a power failure. - Data communication If you require operation from a PC, a data communication module has to be placed in the controller. - Coordinated defrost via data communication

Manual

RS8DZ402

Danfoss

02-2006

EKC 202

EKC 202A Controller with two relay outputs, two temperature sensors and digital input. Temperature control at start/stop of compressor / solenoid valve Defrost sensor Electrical defrost / gas defrost

Alarm function If an alarm function is required, relay number two may be used for it. Defrost is performed here with circulation of the air as the fans are operating continuously.

EKC 202B Controller with three relay outputs, two temperature sensors and digital input. Temperature control at start/stop of compressor / solenoid valve Defrost sensor Electrical defrost / gas defrost Relay output 3 is used for control of fan.

EKC 202C Controller with four relay outputs, two temperature sensors and digital input. Temperature control at start/stop of compressor / solenoid valve Defrost sensor Electrical defrost / gas defrost Control of fan Relay output 4 can be used for an alarm function or for a light function.

EKC 202

Manual

RS8DZ402

Danfoss

02-2006

Start of defrost A defrost can be started in dierent ways Interval: Defrost is started at xed time intervals, say, every eighth hour Refrigeration time: Defrost is started at xed refrigeration time inter vals, in other words, a low need for refrigeration will postpone the coming defrost Contact Defrost is started here with a pulse signal on a digital input. Manual: An extra defrost can be activated from the controllers lower-most button S5-temp. In 1:1 systems the eciency of the evaporator can be followed. Icing-up will start a defrost. Schedule Defrost here can be started at xed times of the day and night. But max. six defrosts Network A defrost can be started via data communication All the mentioned methods can be used at random if just one them is activated a defrost will be started. When the defrost starts the defrost timers are set at zero

A pulse signal starts the defrost

Digital input The digital input can be used for the following functions: - Door contact function with alarm if the door has been open for too long. - Defrost start - Start/stop of regulation - Change-over to night operation - Case cleaning - Change to another temperature reference - Inject on/o Case cleaning function This function makes it easy to steer the refrigeration appliance through a cleaning phase. Via three pushes on a switch you change from one phase to the next phase. The rst push stops the refrigeration the fans keep working Later: The next push stops the fans Still later: The next push restarts refrigeration The dierent situations can be followed on the display. There is no temperature monitoring during case cleaning. On the network a cleaning alarm is transmitted to the system unit. This alarm can be logged so that proof of the sequence of events is provided.

1 2 3

+ +

+ + +

C Fan O C

Defrost on demand 1 Based on refrigeration time When the aggregate refrigeration time has passed a xed time, a defrost will be started. 2 Based on temperature The controller will constantly follow the temperature at S5. Between two defrosts the S5 temperature will become lower the more the evaporator ices up (the compressor operates for a longer time and pulls the S5 temperature further down). When the temperature passes a set allowed variation the defrost will be started. This function can only be used in 1:1 systems

Manual

RS8DZ402

Danfoss

02-2006

EKC 202

Operation
Display The values will be shown with three digits, and with a setting you can determine whether the temperature are to be shown in C or in F. Examples Set menu 1. Push the upper button until a parameter r01 is shown 2. Push the upper or the lower button and nd that parameter you want to change 3. Push the middle button until the parameter value is shown 4. Push the upper or the lower button and select the new value 5. Push the middle button againt to enter the value. Cutout alarm relay / receipt alarm/see alarm code Push briey the upper button If there are several alarm codes they are found in a rolling stack. Push the uppermost or lowermost button to scan the rolling stack. Set temperature 1. Push the middle button until the temperature value is shown 2. Push the upper or the lower button and select the new value 3. Push the middle button to select the setting Manuel start or stop of a defrost Push the lower button for four seconds. The buttons When you want to change a setting, the upper and the lower buttons will give you a higher or lower value depending on the button you are pushing. But before you change the value, you must have access to the menu. You obtain this by pushing the upper button for a couple of seconds - you will then enter the column with parameter codes. Find the parameter code you want to change and push the middle buttons until value for the parameter is shown. When you have changed the value save the new value by once more pushing the middle button See the temperature at the other temperature sensor Push briey the lower button If no sensor has been mounted, non will appear.

Light-emitting diodes (LED) on front panel There are LEDs on the front panel which will light up when the belonging relay is activated. = Refrigeration = Defrost = Fan The light-emitting diodes will ash when there is an alarm. In this situation you can download the error code to the display and cancel/sign for the alarm by giving the top button a brief push.

100% tight The buttons and the seal are imbedded in the front. A special moulding technique unites the hard front plastic, the softer buttons and the seal, so that they become an integral part of the front panel. There are no openings that can receive moisture or dirt.

EKC 202

Manual

RS8DZ402

Danfoss

02-2006

Menu survey
SW = 1.2x
Parameters Function Codes Normal operation Temperature (set point) --Thermostat Dierential r01 Max. limitation of setpoint setting r02 r03 Min. limitation of setpoint setting Adjustment of temperature indication r04 Temperature unit (C/F) r05 Correction of the signal from Sair r09 Manual service(-1), stop regulation(0), start regulation (1) r12 Displacement of reference during night operation r13 Activation of reference displacement r40 r39 Value of reference displacement (activation by r39 or DI) r40 Alarm Delay for temperature alarm A03 Delay for door alarm A04 Delay for temperature alarm after defrost A12 High alarm limit A13 Low alarm limit A14 Alarm delay DI1 A27 High alarm limit for condenser temperature (o69) A37 Compressor Min. ON-time c01 Min. OFF-time c02 Compressor relay must cutin and out inversely (NC-function) c30 Defrost Defrost method (none/EL/gas) d01 Defrost stop temperature d02 Interval between defrost starts d03 Max. defrost duration d04 Displacement of time on cutin of defrost at start-up d05 Drip o time d06 Delay for fan start after defrost d07 Fan start temperature d08 Fan cutin during defrost d09 Defrost sensor (0=time, 1=S5, 2=Sair) d10 Max. aggregate refrigeration time between two defrosts d18 Defrost on demand - S5 temperatures permitted variation during frost build-up. On d19 central plant choose 20 K (=o ) Fans Fan stop at cutout compressor F01 Delay of fan stop F02 Fan stop temperature (S5) F04 Real time clock Six start times for defrost. t01-t06 Setting of hours. 0=OFF t11-t16 Six start times for defrost. Setting of minutes. 0=OFF t07 Clock - Setting of hours Clock - Setting of minute t08 Clock - Setting of date t45 Clock - Setting of month t46 Clock - Setting of year t47 Miscellaneous Delay of output signals after start-up o01 Input signal on DI1. Function: o02 0=not used. 1=status on DI1. 2=door function with alarm when open. 3=door alarm when open. 4=defrost start (pulse-pressure). 5=ext.main switch. 6=night operation 7=change reference (r40 will be activated) 8=alarm function when closed. 9=alarm function when open. 10=case cleaning (pulse pressure). 11=Inject o when open. o03 Network address On/O switch (Service Pin message) o04 Access code 1 (all settings) o05 Used sensor type (Pt /PTC/NTC) o06 Display step = 0.5 (normal 0.1 at Pt sensor) o15 Max hold time after coordinated defrost o16 Conguration of light function (relay 4) o38 1=ON during night operation. 2=ON / OFF via data communication. 3=ON follows the DI-function, when DI is selected to door function or to door alarm Activation of light relay (only if o38=2) o39 Case cleaning. 0=no case cleaning. 1=Fans only. 2=All output O. o46 Access code 2 (partly access) o64 Save the controllers present settings to the programming key. Select your own number. o65 Load a set of settings from the programming key (previously saved via o65 function) Can o66 only be set when regulation is stopped (r12=0) o67 Replace the controllers factory settings with the present settings Controller EKC EKC EKC 202A 202B 202C Min.value -50C 0,1 K -49C -50C -20 K C -10 K -1 -10 K OFF -50 K 0 min 0 min 0 min -50C -50C 0 min 0C 0 min 0 min 0 / OFF no 0C 0 hours 0 min 0 min 0 min 0 min -15C no 0 0 hours 0K no 0 min -50C 0 hours 0 min 0 hours 0 min 1 1 0 0s 0 Max.value 50C 20 K 50C 49C 20 K F 10 K 1 10 K on 50 K 240 min 240 min 240 min 50C 50C 240 min 99C 30 min 30 min 1 / on gas 25C 48 hours 180 min 240 min 60 min 60 min 0C yes 2 48 hours 20 K yes 30 min 50C 23 hours 59 min 23 hours 59 min 31 12 99 600 s 11 Factory setting 2C 2K 50C -50C 0.0 K C 0K 1 0K OFF 0K 30 min 60 min 90 min 8C -30C 30 min 50C 0 min 0 min 0 / OFF EL 6C 8 hours 45 min 0 min 0 min 0 min -5C yes 0 0 hours 20 K no 0 min 50C 0 hours 0 min 0 hours 0 min 1 1 0 5s 0 Actual setting

0 OFF 0 Pt no 0 min 1 OFF 0 0 0 0 OFF

240 ON 100 ntc yes 60 min 3 ON 2 100 25 25 On

0 OFF 0 Pt no 20 1 OFF 0 0 0 0 OFF

Manual

RS8DZ402

Danfoss

02-2006

EKC 202

Re alternative application for the S5 sensor (maintain the setting at 0 if it is used as defrost sensor, otherwise 1 = product sensor and 2 = condenser sensor with alarm) Select application for relay 4: 1=defrost/light, 2= alarm Service Temperature measured with S5 sensor Status on DI1 input. on/1=closed Status on night operation (on or o ) 1=closed Read the present regulation reference Status on relay for cooling (Can be controlled manually, but only when r12=-1) Status on relay for fans (Can be controlled manually, but only when r12=-1) Status on relay for defrost. (Can be controlled manually, but only when r12=-1) Temperature measured with Sair sensor Status on relay 4 (alarm, defrost, light).(Can be controlled manually, but only when r12=-1)

o70 o72 u09 u10 u13 u28 u58 u59 u60 u69 u71 defrost / Alarm Light / Alarm

0 1

2 2

0 2

Factory setting If you need to return to the factory-set values, it can be done in this way: - Cut out the supply voltage to the controller - Keep upper and lower button depressed at the same time as you reconnect the supply voltage

Fault code display E1 Fault in controller E6 Change battery + check clock E 27 S5 sensor error E 29 Sair sensor error

Alarm code display A1 High temperature alarm A2 Low temperature alarm A4 Door alarm A5 Max. Hold time A 15 DI 1 alarm A 45 Standby mode A 59 Case cleasning A 61 Condenser alarm

Status code display S0 Regulating S1 Waiting for end of the coordinated defrost S2 ON-time Compressor S3 OFF-time Compressor S4 Drip-o time S10 Refrigeration stopped by main switch S11 Refrigeration stopped by thermostat S14 Defrost sequence. Defrosting S15 Defrost sequence. Fan delay S16 Refrigeration stopped because of open DI input S17 Door open (open DI input) S20 Emergency cooling S25 Manual control of outputs S29 Case cleaning S32 Delay of output at start-up non The defrost temperature cannot be displayed. There is stop based on time -dDefrost in progress / First cooling after defrost PS Password required. Set password

Start-up:

Regulation starts when the voltage is on. 1 Go through the survey of factory settings. Make any necessary changes in the respective parameters. 2 For network. Set the address in o03 and then transmit it to the gateway/ system unit with setting o04.

EKC 202

Manual

RS8DZ402

Danfoss

02-2006

Functions
Here is a description of the individual functions. A controller only contains this part of the functions. Cf. the menu survey. Function Normal display Normally the temperature value from thermostat sensor Sair is displayed. Thermostat Set point Regulation is based on the set value plus a displacement, if applicable. The value is set via a push on the centre button. The set value can be locked or limited to a range with the settings in r02 and r 03. The reference at any time can be seen in u28 Temp. ref Dierential When the temperaure is higher than the reference + the set dierential, the compressor relay will be cut in. It will cut out again when the temperature comes down to the set reference. Display air (u69) Thermostat control Cutout C Para- Parameter by operation via data meter communication

r01

Dierential

Ref.

Dif.

Setpoint limitation The controllers setting range for the setpoint may be narrowed down, so that much too high or much too low values are not set accidentally - with resulting damages. To avoid a too high setting of the setpoint, the max. allowable reference value must be lowered. To avoid a too low setting of the setpoint, the min. allowable reference value must be increased. Correction of the displays temperature showing If the temperature at the products and the temperature received by the controller are not identical, an oset adjustment of the shown display temperature can be carried out. Temperature unit Set here if the controller is to show temperature values in C or in F. r02 r03 r04 Max cutout C Min cutout C Disp. Adj. K

r05

Temp. unit C=0. / F=1 (Only C on AKM, whatever the setting) Adjust Sair Main Switch 1: Start 0: Stop -1: Manual control of outputs allowed

Correction of signal from Sair Compensation possibility through long sensor cable Start / stop of refrigeration With this setting refrigeration can be started, stopped or a manual override of the outputs can be allowed. Start / stop of refrigeration can also be accomplished with the external switch function connected to the DI input. Stopped refrigeration will give a Standby alarm. Night setback value The thermostats reference will be the setpoint plus this value when the controller changes over to night operation. (Select a negative value if there is to be cold accumulation.) Activation of reference displacement When the function is changed to ON the thermostat dierential will be increased by the value in r40. Activation can also take place via input DI(dened in o02).

r09 r12

r13

Night oset

r39

Th. oset

Value of reference displacement The thermostat reference and the alarm values are shifted the following number of degrees when the displacement is activated. Activation can take place via r39 or input DI

r40

Th. oset K

Night setbck (start of night signal)

Manual

RS8DZ402

Danfoss

02-2006

EKC 202

Alarm The controller can give alarm in dierent situations. When there is an alarm all the light-emitting diodes (LED) will ash on the controller front panel, and the alarm relay will cut in. Alarm delay (short alarm delay) If one of the two limit values is exceeded, a timer function will commence. The alarm will not become active until the set time delay has been passed. The time delay is set in minutes. Time delay for door alarm The time delay is set in minutes. The function is denered in o02. Time delay for cooling (long alarm delay) This time delay is used during start-up, during defrost, immediately after a defrost. There will be change-over to the normal time delay (A03) when the temperature has dropped below the set upper alarm limit. The time delay is set in minutes. Upper alarm limit Here you set when the alarm for high temperature is to start. The limit value is set in C (absolute value). The limit value will be raised during night operation. The value is the same as the one set for night setback, but will only be raised if the value is positive. The limit value will also be raised in connection with reference displacement r39. Lower alarm limit Here you set when the alarm for low temperature is to start. The limit value is set in C (absolute value). The limit value will also be raised in connection with reference displacement r39. Delay of a DI alarm A cut-out/cut-in input will result in alarm when the time delay is passed. The function is dened in o02. High alarm limit for condenser temperature If the S5 sensor is used for monitoring the condensers temperature you must set the value at which the alarm is to become activated. The value is set in C. The denition of S5 as condenser sensor is accomplished in o70. The alarm is zeroset again 10 K below the set temperature. Compressor The compressor relay works in conjunction with the thermostat. When the thermostat calls for refrigeration will the compressor relay be operated. Running times To prevent irregular operation, values can be set for the time the compressor is to run once it has been started. And for how long it at least has to be stopped. The running times are not observed when defrosts start. Min. ON-time (in minutes) Min. OFF-time (in minutes) Reversed relay function for compressor relay 0: Normal function where the relay cuts in when refrigeration is demanded 1: Reversed function where the relay cuts out when refrigeration is demanded (this wiring produces the result that there will be refrigeration if the supply voltage to the controller fails). Defrost The controller contains a timer function that is zeroset after each defrost start. The timer function will start a defrost if/when the interval time is passed. The timer function starts when voltage is connected to the controller, but it is displaced the rst time by the setting in d05. If there is power failure the timer value will be saved and continue from here when the power returns. This timer function can be used as a simple way of starting defrosts, but it will always act as safety defrost if one of the subsequent defrost starts is not received. The controller also contains a real-time clock. By means of settings of this clock and times for the required defrost times, defrost can be started at xed times of the day. If there is a risk of power failure for periods longer than four hours, a battery module should be mounted in the controller. Defrost start can also be accomplished via data communication, via contact signals or manual start-up. c01 c02 c30 A03

Alarm settings With data communication the importance of the individual alarms can be dened. Setting is carried out in the Alarm destinations menu. Alarm delay

A04 A12

DoorOpen del Pulldown del

A13

HighLim Air

A14

LowLim Air

A27 A37

AI.Delay DI Condtemp Al.

Reset alarm Compressor control

Min. On time Min. O time Cmp relay NC

Defrost control

EKC 202

Manual

RS8DZ402

Danfoss

02-2006

All starting methods will function in the controller. The dierent functions have to be set, so that defrosts do not come tumbling one after the other. Defrost can be accomplished with electricity, hotgas or brine. The actual defrost will be stopped based on time or temperature with a signal from a temperature sensor. Defrost method Here you set whether defrost is to be accomplished with electricity or "non". During defrost the defrost relay will be cut in. When gas defrosting the compressor relay will be cut in during defrost. Defrost stop temperature The defrost is stopped at a given temperature which is measured with a sensor (the sensor is dened in d10). The temperature value is set. Interval between defrost starts The function is zeroset and will start the timer function at each defrost start. When the time has expired the function will start a defrost. The function is used as a simple defrost start, or it may be used as a safeguard if the normal signal fails to appear. If master/slave defrost without clock function or without data communication is used, the interval time will be used as max. time between defrosts. If a defrost start via data communcation does not take place, the interval time will be used as max. time between defrosts. When there is defrost with clock function or data communication, the interval time must be set for a somewhat longer period of time than the planned one, as the interval time will otherwise start a defrost which a little later will be followed by the planned one. In connection with power failure the interval time will be maintained, and when the power returns the interval time will continue from the maintained value. The interval time is not active when set to 0. Max. defrost duration This setting is a safety time so that the defrost will be stopped if there has not already been a stop based on temperature or via coordinated defrost. (The setting will be the defrost time if d10 is selected to be 0) Time staggering for defrost cutins during start-up The function is only relevant if you have several refrigeration appliances or groups where you want the defrost to be staggered in relation to one another. The function is furthermore only relevant if you have chosen defrost with interval start (d03). The function delays the interval time d03 by the set number of minutes, but it only does it once, and this at the very rst defrost taking place when voltage is connected to the controller. The function will be active after each and every power failure. Drip-o time Here you set the time that is to elapse from a defrost and until the compressor is to start again. (The time when water drips o the evaporator). Delay of fan start after defrost Here you set the time that is to elapse from compressor start after a defrost and until the fan may start again. (The time when water is tied to the evaporator). Fan start temperature The fan may also be started a little earlier than mentioned under Delay of fan start after defrost, if the defrost sensor S5 registers another allowable value than the one set here. Fan cut in during defrost Here you can set whether fan is to operate during defrost. Defrost sensor Here you dene the defrost sensor. 0: None, defrost is based on time 1: S5 2: Sair Defrost on demand aggregate refrigeration time Set here is the refrigeration time allowed without defrosts. If the time is passed, a defrost will be started. With setting = 0 the function is cut out. Defrost on demand S5 temperature The controller will follow the eectivity of the evaporator, and via internal calculations and measurements of the S5 temperature it will be able to start a defrost when the variation of the S5 temperature becomes larger than required. Here you set how large a slide of the S5 temperature can be allowed. When the value is passed, a defrost will start. The function can only be used in 1:1 systems when the evaporating temperature will become lower to ensure that the air temperature will be maintained. In central systems the function must be cut out. With setting = 20 the function is cut out d01 Def. method

d02

Def. Stop Temp

d03

Def Interval (0=o )

d04

Max Def. time

d05

Time Stagg.

d06 d07 d08

DripO time FanStartDel FanStartTemp

d09 d10

FanDuringDef DefStopSens.

d18

MaxTherRunT

d19

CutoutS5Dif.

10

Manual

RS8DZ402

Danfoss

02-2006

EKC 202

If you wish to see the temperature at the S5 sensor, push the controllers lowermost button. If you wish to start an extra defrost, push the controllers lowermost button for four seconds. You can stop an ongoing defrost in the same way

Defrost temp. Def Start Here you can start a manual defrost. Hold After Def Shows ON when the controller is operating with coordinated defrost. Fan control Fan stop CO (Yes = Fan stopped) Fan del. CO

Fan Fan stopped at cut-out compressor Here you can select whether the fan is to be stopped when the compressor is cut out Delay of fan stop when compressor is cut out If you have chosen to stop the fan when the compressor is cut out, you can delay the fan stop when the compressor has stopped. Here you can set the time delay. Fan stop temperature The function stops the fans in an error situation, so that they will not provide power to the appliance. If the defrost sensor registers a higher temperature than the one set here, the fans will be stopped. There will be re-start at 2 K below the setting. The function is not active during a defrost or start-up after a defrost. With setting +50C the function is interrupted. Real-time clock The controller can accommodate one insertion module which may either be a data communcation module or a battery moduel for the real-time clock. The battery module is used in conjunction with the real-time clock and will keep the clock going during lengthy power failures. Real-time clock You can set up to six individual times for defrost starts for each 24-hour period. There is also a date indication used for registration of temperature measurements. Defrost start, hour setting Defrost start, minute setting (1 and 11 belong together, etc.) When all t01 to t16 equal 0 the clock will not start defrosts. Clock: Hour setting Clock: Minute setting Clock: Date setting Clock: Month setting Clock: Year setting Miscellaneous Delay of output signal after start-up After start-up or a power failure the controllers functions can be delayed so that overloading of the electricity supply network is avoided. Here you can set the time delay. Digital input signal - DI The controller has a digital input which can be used for one of the following functions: O: The input is not used 1) Status display of a contact function 2) Door function. When the input is open it signals that the door is open. The refrigeration and the fans are stopped. When the time setting in A04 is passed, an alarm will be given and refrigeration will be resumed. 3) Door alarm. When the input is open it signals that the door is open. When the time setting in A04 is passed, there will be alarm. 4) Defrost. The function is started with a pulse pressure. The controller will register when the DI input is activated. The controller will then start a defrost cycle. If the signal is to be received by several controllers it is important that ALL connections are mounted the same way (DI to DI and GND to GND). 5) Main switch. Regulation is carried out when the input is short-circuited, and regulation is stopped when the input is put in pos. OFF. 6) Night operation. When the input is short-circuited, there will be regulation for night operation. 7) Reference displacement when DI1 is short-circuited. Displacement with r40. 8) Separate alarm function. Alarm will be given when the input is short-circuited. 9) Separate alarm function. Alarm will be given when the input is opened. (For 8 and 9 the time delay is set in A27) 10) Case cleaning. The function is started with a pulse pressure. Cf. also description on page 4. 11) Inject on/o. O when DI is open. EKC 202 Manual RS8DZ402 Danfoss 02-2006

F01 F02

F04

FanStopTemp.

(Times cannot be set via data communication. Settings are only relevant when there is no data communication).

t01-t06 t11-t16 t07 t08 t45 t46 t47 o01 Miscellaneous DelayOfOutp.

o02

DI 1 Cong. Denition takes place with the numerical value shown to the left. (0 = o )

DI state (Measurement) The DI inputs present status is shown here. ON or OFF.

11

Address If the controller is built into a network with data communication, it must have an address, and the master gateway of the data communication must then know this address. These settings can only be made when a data communcation module has been mounted in the controller and the installation of the data communication cable has been nished. This installation is mentioned in a separate document RC8AC. The address is set between 1 and 240, gateway determined The address is sent to the gateway when the menu is set in pos. ON Access code 1 (Access to all settings) If the settings in the controller are to be protected with an access code you can set a numerical value between 0 and 100. If not, you can cancel the function with setting 0. (99 will always give you access). Sensor type Normally a Pt 1000 sensor with great signal accuracy is used. But you can also use a sensor with another signal accuracy. That may either be a PTC sensor (1000 ohm at 25C) or an NTC sensor (5000 Ohm at 25C). All the mounted sensors must be of the same type. Display step Yes: Gives steps of 0.5 No: Gives steps of 0.1 Max. standby time after coordinated defrost When a controller has completed a defrost it will wait for a signal which tells that the refrigeration may be resumed. If this signal fails to appear for one reason or another, the controller will itself start the refrigeration when this standby time has elapsed. Conguration of light function 1) The relay cuts in during night operation 2) The relay to be controlled via data communication 3) The relay to be controlled by the door switch dened in either o02 where the setting is selected to either 2 or 3. When the door is opened the relay will cut in. When the door is closed again there will be a time delay of two minutes before the light is switched o. Activation of light relay The light relay can be activated here (if 038=2) Case cleaning The status of the function can be followed here or the function can be started manually. 0 = Normal operation (no cleaning) 1 = Cleaning with fans operating. All other outputs are O. 2 = Cleaning with stopped fans. All outputs are O. If the function is controlled by a signal at the DI input, the relevant status can be seen here in the menu. Access code 2 (Access to adjustments) There is access to adjustments of values, but not to conguration settings. If the settings in the controller are to be protected with an access code you can set a numerical value between 0 and 100. If not, you can cancel the function with setting 0. If the function is used, access code 1 (o05) must also be used. Copy the controllers present settings With this function the controllers settings can be transferred to a programming key. The key can contain up to 25 dierent sets. Select a number. All settings except for Address (o03) will be copied. When copying has started the display returns to o65. After two seconds you can move into the menu again and check whether the copying was satisfactory. Showing of a negative gure spells problems. See the signicance in the Fault Message section. Copy from the programming key This function downloads a set of settings earlier saved in the controller. Select the relevant number. All settings except for Address (o03) will be copied. When copying has started the display returns to o66. After two seconds you can move back into the mennu again and check whether the copying was satisfactory. Showing of a negative gure spells problems. See the signicance in the Fault Message section. Save as factory setting With this setting you save the controllers actual settings as a new basic setting (the earlier factory settings are overwritten). Other application for S5 sensor Maintain the setting at 0 if the sensor has been dened as defrost sensor in D10. If D10 has been set at 0 or 2 the S5 input can be used as product sensor or condenser sensor. Here you dene which: 0: Defrost sensor 1: Product sensor 2: Condenser sensor with alarm 12 Manual RS8DZ402 Danfoss 02-2006

After installation of a data communication module the controller can be operated on an equal footing with the other controllers in ADAP-KOOL refrigeration controls.

o03 o04 o05 -

o06

SensorCong Pt = 0 PTC = 1 NTC = 2 Disp. Step = 0.5 Max HoldTime

o15 o16

o38

Light cong

o39 o46

Light remote Case clean

o64

o65

o66

o67 o70

S5 Cong

EKC 202

Relay 4 Here you dene the application for relay 4: 1: Defrost (EKC 202A) or Light (EKC 202C) 2: Alarm

o72

DO4 Cong

- - - Night Setback 0=Day 1=Night Service Temperature measured with S5 sensor Status on DI input. on/1=closed Status on night operation (on or o ) 1=closed Read the present regulation reference * Status on relay for cooling * Status on relay for fan * Status on relay for defrost * Temperature measured with Sair sensor * Status on relay 4 (alarm, defrost or light function) *) Not all items will be shown. Only the function belonging to the selected application can be seen. Fault message In an error situation the LEDs on the front will ash and the alarm relay will be activated. If you push the top button in this situation you can see the alarm report in the display. If there are futher push again to see them. There are two kinds of error reports - it can either be an alarm occurring during the daily operation, or there may be a defect in the installation. A-alarms will not become visible until the set time delay has expired. E-alarms, on the other hand, will become visible the moment the error occurs. (An A alarm will not be visible as long as there is an active E alarm). Here are the messages that may appear: A1: High temperature alarm A2: Low temperature alarm A4: Door alarm A5: Information. Parameter o16 is expired A15: Alarm. Signal from DI input A45: Standby position (stopped refrigeration via r12 or DI input) A59: Case cleaning. Signal from DI input A61: Condenser alarm E1: Faults in the controller E6: Fault in real-time clock. Check the battery / reset the clock. E27: Sensor error on S5 E29: Sensor error on Sair When copying settings to or from a copying key with functions o65 or o66, the following information may appear: 0: Copying concluded and OK 4: Copying key not correctly mounted 5: Copying was not correct. Repeat copying 6: Copying to EKC incorrect. Repeat copying 7: Copying to copying key incorrect. Repeat copying 8: Copying not possible. Order number or SW version do not match 9: Communication error and timeout 10: Copying still going on (The information can be found in o65 or o66 a couple of seconds after copying has been started). Alarm destinations The importance of the individual alarms can be dened with a setting (0, 1, 2 or 3) Service S5 temp. DI1 status Night Cond. Temp. ref. Comp1/LLSV Fan relay Def. relay Sair temp DO4 status

u09 u10 u13 u28 u58 u59 u60 u69 u71

Alarms

1 = alarm High t. alarm Low t. alarm Door Alarm Max Hold Time DI1 alarm Standby mode Case cleaning Cond. alarm EKC error S5 error Sair error

EKC 202

Manual

RS8DZ402

Danfoss

02-2006

13

Connections
EKC 202A EKC 202B EKC 202C

or

or

Power supply 230 V a.c. Sensors Sair is thermostat sensors. S5 is a defrost sensor and is used if defrost has to be stopped based on temperature. It may however also be used as product sensor or condenser sensor. Digital On/O signal A cut-in input will activate a function. The possible functions are described in menu o02.

Relays The general connections are: Refrigeration. The contact will cut in when the controller demands refrigeration Defrost. Fan. Alarm. The relay is cut out during normal operation and cuts in in alarm situations and when the controller is dead (de-energised) Light. The contact will cut in when the controller demands light. Electric noise Cables for sensors, DI inputs and data communication must be kept separate from other electric cables: - Use separate cable trays - Keep a distance between cables of at least 10 cm - Long cables at the DI input should be avoided

Data communication If data communication is used, it is important that the installation of the data communication cable is performed correctly. See separate literature No. RC8AC.. The controller cannot be hooked up with a monitoring unit type m2.

14

Manual

RS8DZ402

Danfoss

02-2006

EKC 202

Data
Supply voltage Sensors 230 V a.c. +10/-15 %. 1,5 VA Pt 1000 or PTC (1000 ohm / 25C) or NTC-M2020 (5000 ohm / 25C) Measuring range -60 to +99C 1 K below -35C Controller 0,5 K between -35 to +25C 1 K above +25C 0.3 K at 0C Pt 1000 sensor 0.005 K per grad LED, 3 digits Signal from contact functions Requirements to contacts: Gold plating Cable length must be max. 15 m Use auxiliary relays when the cable is longer Max.1,5 mm2 multi-core cable on supply and relays. Power current terminals are mounted on the circuit board. Max. 1 mm2 on sensors - and DI inputs. Low current terminals are with plugs DO1 SPDT, Imax. = 10 A ohmic/ (Refrigeration) 6 A AC 15* inductive SPST NO, Imax. = 10 A ohmic/ DO2 6 A AC 15* inductive SPST NO, Imax. = 6 A ohmic/ DO3 3 A AC 15* inductive SPDT, Imax. = 4 A ohmic/ DO4 1 A AC 15* inductive Imin. = 1 mA at 100 mV** 0 to +55C, During operations -40 to +70C, During transport 20 - 80% Rh, not condensed No shock inuence / vibrations IP 65 from front. Buttons and packing are imbedded in the front. 4 hours EU Low Voltage Directive and EMC demands re CEmarking complied with LVD tested acc. EN 60730-1 og EN 60730-2-9, A1, A2 EMC tested acc. EN50082-1 og EN 60730-2-9, A2

Accuracy

Display Digital inputs

Electrical connection cable

Weight = 200 g

Relays

Environments

Density Escapement reserve for the clock Approvals

* AC 15 load to EN 60947-5-1 ** Gold plating ensures make function wiht small contact loads DO1 and DO2: It is a 16 A relay, but printed circuit and derating means that the 10 A must not be exceeded.

Ordering
Type EKC 202A EKC 202B EKC 202C EKA 179A Function Refrigeration controller Refrigeration controller with fan function Refrigeration controller for electric defrost Data communication module RS 485 Battery and buzzer module that will protect the clock in case of lengthy power failure Battery module that will protect the clock in case of lengthy power failure Code no. 084B8521 084B8522 084B8523 084B8565

EKA 181A

084B8566

EKA 181C

084B8577

EKA 182A

Copy key EKC - EKC

084B8567

Temperature sensors: please refer to lit.no. RK0YG EKC 202 Manual RS8DZ402 Danfoss 02-2006 15

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specications already agreed. All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

16

Manual

RS8DZ402

Danfoss

02-2006

EKC 202