TWHB 14e
TWHB 14e
Powered by
- Table of Contents -
Introduction ....................................................................................................................................... 1
Notes ............................................................................................................................................... 21
First, the structure, equivalent circuit, principle of rotation, 1.2 Diagram of the Internal Structure and Coil
and position detection of 3-phase full-wave brushless DC Connection Equivalent Circuit
motors are explained. In Figure 2, a summary diagram of the internal structure
1.1 Outer Appearance and Structure and an equivalent circuit of coil connections are
presented.
Figure 1 shows an example of the appearance and
structure of brushless DC motors.
Figure 1. Example of the appearance and structure of The summary diagram of the internal structure takes as
brushless DC motors an example a motor with a simple structure, having 2
poles (2 magnets) and 3 slots (3 coils). It is similar to the
Sources:
Photo P60_1 SOLITON 36 SPECIAL REPORT Selection and Control of Small structure of a brushed DC motor with the same numbers
Motors, Hiroshi Hagino of poles and slots, but here the coils are fixed and the
Photo P60_2 https://ja.wikipedia.org/wiki/ Brushless direct current motors magnets can rotate. Of course, there are no brushes.
In this case the coils are Y-connected, and current is (magnet) is to use hall elements.
supplied to the coils by semiconductor elements or the The coils are fixed in place; a permanent magnet or
like, to control current inflow and outflow according to the magnets (rotor) rotates on the outside.
position of the rotating magnets. In this example, Hall
1.3 Principles of Rotation
elements are used to detect the magnet position. Hall
elements are positioned between coils, and the voltages The principles of rotation of a brushless DC motor are
that they generate according to the strength of the here explained with steps ① to ⑥ in Figure 4. To aid
magnetic field are detected and used as position understanding, a permanent magnet is simplified from a
information. In the photo of the FDD spindle motor shown disc shape to two rectangular shapes.
in Figure 1, lower side, one can see Hall elements for ①: Of the 3 phase coils, coil 1 is fixed in the 12:00
position detection between the coils (on the upper side of direction (upward), coil 2 is at 4:00, and coil 3 is fixed at
the coil). 8:00. Of the 2 poles of the permanent magnet, the N pole
Hall elements are well-known magnetic sensors. They is on the left and the S pole is on the right, and the magnet
convert the magnitude of a magnetic field into a voltage can rotate.
of corresponding magnitude, and the sign of the voltage A current Io is made to flow into coil 1, causing a magnetic
indicates the orientation of the magnetic field. Figure 3 is field the S pole of which is outside coil 1. Currents Io/2
a schematic diagram illustrating the Hall effect. are caused to flow out from coils 2 and 3, generating a
magnetic field with the N pole on the outside of those coils.
Taking the vector resultant of the magnetic fields of coils
2 and 3, the magnetic field at the downward-directed N
pole occurs with an intensity that is 0.5-fold that when the
current Io flows in one coil; added to the magnetic field of
coil 1, the intensity is 1.5-fold. This creates a resultant
magnetic field at a 90° angle with respect to the
permanent magnet, so that the maximum torque can be
generated, and the permanent magnet rotates in the
clockwise direction.
Figure 3. Schematic diagram showing the Hall effect in a
When the current in coil 2 is reduced and the current in
Hall element
coil 3 is increased according to the rotation position, the
Hall elements utilize the phenomenon in which, when a resultant magnetic field also rotates clockwise, and so the
current IH flows in a semiconductor and magnetic flux B permanent magnet continues to rotate.
crosses the current at a right angle, a voltage VH occurs
②: In the state of rotation by 30°, the current Io is made
in a direction perpendicular to both the current and the
to flow into coil 1 and the current in coil 2 is reduced to
magnetic flux. This phenomenon was discovered by the
zero, while the current Io is caused to flow out of coil 3.
American physicist Edwin Herbert Hall, and so is called
the Hall effect. The equation for the generated voltage VH The S pole is then outside of coil 1, and the N pole is
is as follows. outside of coil 3. Taking the vector resultant, a magnetic
field occurs with intensity equal to √3 (≈1.72)-fold of that
V K d I B when the current Io is made to flow in one coil. This also
where KH: Hall coefficient, d: thickness of material creates a resultant magnetic field at an angle of 90° to the
traversed by the magnetic flux magnetic field of the permanent magnet, so that the
permanent magnet rotates in the clockwise direction.
As the equation indicates, when the current is increased,
the voltage also increases. This is used to detect the The current Io flowing into coil 1 is reduced according to
position of the rotor (magnets). the rotation, the current flowing into coil 2 is increased
from zero, and the current flowing out of coil 3 is
<Summary> increased to become Io; the resultant magnetic field
The coils of a 3-phase brushless DC motor are fixed to rotates clockwise, and the permanent magnet continues
a substrate, and are wound about an iron core. to rotate.
One method for detecting the position of the rotor
* If the current for each phase is represented as a The S pole is outside of coils 1 and 2, and the N pole is
sinusoidal waveform, then these current values become outside of coil 3. Taking the vector resultant, a magnetic
Io×sin( /3) = Io×√3/2. Taking the vector resultant of the field occurs equal to 1.5 times that occurring when the
magnetic field, the overall intensity is (√3 /2)2 ×2 = 1.5 current Io flows in one coil (the same as in ①). A resultant
times the magnetic field that occurs for one coil. When the magnetic field is formed that is at a 90° angle with respect
current for each phase is sinusoidal, the magnitude of the to the magnetic field of the permanent magnet, and the
vector resultant magnetic field is 1.5-fold times the permanent magnet rotates clockwise.
magnetic field that occurs for one coil regardless of the
④ to ⑥: Rotation is similar to that in ① to ③
position of the permanent magnet, and the magnetic field
is at 90° to the magnetic field of the permanent magnet. When in this way the supply of current to the coils is
switched according to the sequential positions of the
③: Having rotated another 30°, the current Io/2 is made
permanent magnet, the permanent magnet is caused to
to flow into coil 1, Io/2 is made to flow into coil 2, and Io is
rotate in one direction. If the current directions are
made to flow out from coil 3.
reversed, reversing the direction of the resultant magnetic
field, rotation is in the counterclockwise direction.
Figure 5 shows the continuous change in the current in 1.4.1 Position Detection Using Hall Elements
each of the coils through the steps ① to ⑥ in Figure 4. (Sensors)
The reader should be able to understand the relation
When using Hall elements (sensors) to detect the position
between the changes in the currents as explained above
of the rotating permanent magnet, the installed positions
and the permanent magnet rotation.
of the Hall elements are set at the midpoints between
<Summary> coils, that is, at points located at 1/2 the angles between
In 3-phase full-wave brushless DC motors, the inflow the coils (see Figure 6).
and outflow of currents into and out of three coils
change the magnet field, causing the rotor to rotate.
1.4 Position Detection
3-phase full-wave brushless DC motors rotate by
switching the drive current to the three coils, and position
detection of the rotating permanent magnets is required
to drive the motor.
There are two main methods of position detection. One is
a method using sensors; specifically, the voltages of Hall
elements are employed. In the diagrams used to explain
the principles of rotation in the previous article, though not
explicitly explained, H1, H2, and H3 are Hall elements
(sensors). The other method involves detection of the Figure 6. Relation between Hall element installation
induced voltages for each coil, and does not use sensors, position and coil position
and so is called a sensorless method.
Each of these methods is described below.
Figure 5. Continuous coil currents for each of the steps ① through ⑥ shown in Figure 4.
If the Hall element between coil 3 and coil 1 is H1, the Hall signals, motor driving current waveforms with the desired
element between coils 1 and 2 is H2, and the Hall element phase can be created.
between coils 2 and 3 is H3, then the signal waveforms In order to synthesize output current signals to reverse
of the Hall elements appear as Figure 7 relative to the the motor direction, H1 is subtracted from H2, H2 is
current waveforms for clockwise rotation. subtracted from H3, and H3 is subtracted from H1. That
In this example, when the magnetic field of the N pole is is, M1 = H2 - H1, M2 = H3 - H2, and M3 = H1 - H3, and
sensed by a Hall element, a positive (+) voltage occurs, by supplying output currents in accordance with the
and when the S pole magnetic field is sensed a negative phases of the synthesized waveforms M1, M2, M3,
(-) voltage is induced; the magnetic field strength changes reverse rotation is obtained.
sinusoidally according to the position of the rotating 1.4.2 Position Detection Using Induced Voltages
permanent magnet (the "Hall element voltage (Sensorless)
waveforms" in the lower part of the waveform diagram).
The output current waveforms for each of the phases are In the method not requiring sensors (Hall elements),
taken to be trapezoidal waves (the "current waveforms" induced voltages occurring in the coils are used. In a 3-
in the upper part of the waveform diagram). The numbers phase full-wave brushless DC motor, a permanent
① to ⑥ appearing along the time axis of the waveform magnet rotates relative to the coils and the N pole and S
diagram correspond to the numbers ① to ⑥ of the pole change in alternation, so that changes in magnetic
diagrams used in the explanation of "Principles of flux density occur at the coils, and induced voltages occur
Rotation" in the previous article. The same diagrams are in the coils themselves, generating electricity. The
used in the next section on "Position Detection Using magnetic flux density is greatest when the N pole is at a
Induced Voltages (Sensorless)", and so can be coil end and flux is entering the coil, and when the S pole
referenced there. is at a coil end and flux is leaving the coil. However, when
the magnetization of the permanent magnet is sinusoidal,
For motor driving, output current waveforms are changes in the flux density are greatest at the midpoints
synthesized from the Hall element output signal between the N pole and the S pole.
waveforms, which change according to the rotor position.
In this synthesis, the H2 voltage waveform is subtracted Figure 8 shows the relationship between coil current and
from the H1 voltage waveform, the H3 voltage waveform induced voltage waveforms. The numbers ① to ⑥ in the
is subtracted from the H2 voltage waveform, and the H1 figure indicate motor conditions and correspond to the
voltage waveform is subtracted from the H3 voltage numbers ① to ⑥ in Figure 4. State of ① to ⑥ of the motor
waveform. Through these operations, sine waves (M1, and the induced voltage waveform are shown below.
M2, M3) are obtained that lead H1, H2, H3 in phase by
30°. By generating output currents based on these
①: Coil 1 is at a midpoint between the S pole and the N Moreover, as is shown in the waveform diagram, the
pole, and because the action changes from magnetic flux induced voltage waveform and the driving current
due to the S pole leaving the outside of the coil to waveform are in phase for each of the coils.
magnetic flux due to the N pole entering the same space, By detecting zero points of the induced voltages and
the change in magnetic flux density is greatest. Hence the synthesizing output current waveforms, the motor can be
induced voltage in coil 1 is positive relative to the coil driven in rotation using the induced voltages as rotor
midpoint and is maximum. position detection signals. Hence the motor can be
②: The induced voltage in coil 1 drops, because the controlled without using Hall elements for position
change in magnetic flux density is less than before. detection.
③: The change in magnetic flux density near coil 1 further <Summary>
decreases, and so the induced voltage also drops further. For position detection in 3-phase full-wave brushless
DC motors, there are methods that use Hall elements,
④: The N pole is at the coil end, and the change in
and methods that utilize the voltages induced in the
magnetic flux density is zero, so that the induced voltage
motor coils without relying on Hall elements.
in coil 1 is zero.
2. Driving 3-Phase Full-Wave Brushless DC Motors
⑤: Because the N pole recedes from coil 1, the magnetic
flux entering the coil decreases, so that the induced Starting with this article, methods for driving 3-phase full-
voltage goes negative, but because the change in flux is wave brushless DC motors will be explained. In general,
small, the induced voltage drops a small amount. 3-phase full-wave brushless DC motors are driven by
using control and driving circuits for motor commutation.
⑥: The change in the density of magnetic flux entering
coil 1 further declines, so that the induced voltage falls Commutation methods include 120° commutation and
still further. sinusoidal commutation. Each method has its advantages
and drawbacks. To sum up, sinusoidal commutation is
Similarly in coils 2 and 3, at the midpoint when switching
superior with respect to control precision, efficiency, and
from the S pole to the N pole, the maximum positive
noise, but entails a complex system and results in
induced voltage occurs, at the midpoint when switching
increased costs. In contrast, 120° commutation is inferior
from the N pole to the S pole the maximum negative
to sinusoidal commutation with respect to control
induced voltage occurs, and when the N pole or the S
precision, efficiency, and noise, but the system for this
pole is at the coil end, the induced voltage is zero.
driving is simple, and costs are lower. Each commutation
2.2.1 Circuit Example control the gate of the output stage MOSFET, becoming
the PWM output that drives the motor coil. Such PWM
In sinusoidal commutation, driving is performed by control
conversion using a comparator and a triangular wave is a
and driver circuits designed for 3 phases, each of which
widely used technique that is employed in many circuits
has a driver comprising a high side and a low side. Figure
such as PWM generation for switching regulators.
11 is an example of a sinusoidal commutation PWM
driving circuit block using sensors.
Figure 18. Example of sensorless 120° commutation driving of 3-phase full-wave brushless DC Motors
Induced voltages occur when the permanent magnet from waveforms which have been delayed in phase by
rotates and the magnetic flux passing through a coil that 30°, the synthesized waveforms and output gate
is not passing a current changes; it cannot be detected in waveforms are generated.
coils in which current is flowing. In 120° commutation
driving, current is flowing in two out of the three phases,
and is not flowing in the third phase. An induced voltage
appears across the terminal of the phase in which current
is not flowing; by using the voltage CT at the midpoint to
detect the zero crossing point of the induced voltage, the
motor position is detected.
In one phase of a 3-phase motor, there are two off-
intervals in which current does not flow during one motor
rotation (through 360°) (two 120° intervals with current
and two 60° off intervals), and so there are six off-intervals
for the three phases. That is, position detection is possible
once every 60°. Output signals are generated on the
basis of 60° signals between zero crossing points for
each phase.
Figure 19 is a detailed explanation using a driving
waveform example. The current waveforms in coils 1, 2,
and 3 indicate that driving is by 120° commutation; that is,
current enters into a coil over 120° and is then off for 60°,
current flows out over the next 120°, and is then turned
off for another 60°. The resulting output voltage
waveforms are A1, A2, and A3.
Induced voltages used in detecting the motor position can
be detected during 60° off-intervals for each phase.
Taking coil 1 as an example, during the off intervals
indicated in red, an induced voltage appears in the output
A1, and is detected. At these times, currents are flowing
in coils 2 and 3. Upon switching to off from a state in which
current is flowing into the coil, after spike noise (a
transient voltage) occurs upon switching, the induced
voltage declines. During the transition from a current
outflowing state to off, after spike noise has appeared, the
induced voltage rises. Figure 19. Example of driving waveforms
The comparator output BE is a signal obtained by Figure 20 shows in enlargement the behavior of the
comparing the induced voltage signal occurring in the outputs A1-3 during coil-off intervals. This is an example
output and the coil midpoint signal CT (not shown); at the of a 60° interval in which coil 3 goes from a state in which
induced voltage zero crossing point, there is a H→L current is flowing out to the off state. The circuit diagram
transition when falling, and a L→H transition when rising. shows the state of the circuit at this time.
The comparator outputs BE1-3 are used to synthesize In the case of A2, the high side MOSFET is on and the
signals shifted 60° by a process called waveform section low side MOSFET is off, so that current is flowing out and
selection and synthesis, in which the additions are the voltage is at high level. In the case of A1, the low side
performed. Because these signals include spike noise, MOSFET is turned on, so that current flows from A2 and
which was not in the original induced voltages, a mask the voltage is at low level. A3 switches from the state of
signal (H parts) is used to mask the spike noise to inflowing current to the off state, so that, as the waveform
synthesize induced-voltage 60° signal waveforms, and indicates, after a momentary jump in voltage, the induced
Figure 20. Expands the behavior of outputs A1-3 during the coil-off period
voltage appears gradually and linearly. The voltage sensors can be used to ascertain the positions of the N
difference between A3 and CT at this time is shown as a and S poles of the permanent magnet (rotor) when
broken line together with the A3 voltage waveform. The stopped. Therefore, startup is performed by beginning to
CT voltage is approximately one-half the voltages of A2 pass currents through the coils so as to generate a
and A1. synthetic magnetic field at 90°, as in Figure 21.
On taking the difference between the voltages A3 and CT,
the zero crossing point of the induced voltage can be
detected, as shown on the right side, and BE3 in the
preceding timing chart transitions from L to H.
Compared with 120° commutation driving using sensors,
the broad outline is much the same, with the difference
that induced voltages are detected instead of relying on
sensor signals.
<Summary>
In sensorless driving, there is a method in which the
induced voltages in the coils are used in place of Hall
elements for motor position detection.
In this method, the signal CT at the midpoint of the three
coils is utilized.
The CT signal and the signals A1, A2, A3 are input to
the driving circuit, comparison processing is performed
by comparators, and outputs are generated. Figure 21. Rotor position and startup when with sensor
Except for the use of induced voltages, this sensorless
When sensors are not present (that is, in sensorless
driving is basically the same as driving using sensors.
driving), as explained in "2.3 Sensorless 120°
2.3.1 Problems with Startup Commutation Driving", the position detection is
As explained in "1.3 Principles of Rotation” and “1.4 performed by using the induced voltage occurring in the
Position Detection”, in startup of a 3-phase full-wave coil which is not passing a current when the permanent
brushless DC motor, when sensors are present the magnet rotates. Hence while the motor is stopped, the
position of the permanent magnet cannot be ascertained, ③, ④: However, the movement is not yet sufficient to
and so a procedure for motor startup is needed. There cause an induced voltage, and so a synthetic magnetic
are two methods for startup in the case of a sensorless field is next generated in the 7 o'clock direction. The
system. permanent magnet then similarly moves clockwise.
2.3.2 Startup Method 1: Startup on Detection of ⑤, ⑥: Next a synthetic magnetic field is generated in the
Induced Voltage from Synchronous Operation 9 o'clock direction; the permanent magnet moves still
further in the clockwise direction, and begins to rotate.
As stated previously, in sensorless driving, the position of
the permanent magnet when stopped cannot be This operation is continued, and the time until the next
determined, and so it cannot be known what currents switching is shortened little by little, so that the permanent
should be passed in the three coils upon startup. As one magnet rotation rate increases, and gradually the induced
means to deal with this, synchronous operation is used to voltage rises to a level at which detection is possible.
rotate the permanent magnet, the induced voltage that When a state is reached in which the induced voltage can
occurs is detected, and 120° commutation driving is then be detected, normal sensorless 120° communication
performed; this is explained using Figure 22. driving commences.
①: If the permanent magnet is in the position in ①, then In other words, in this method a synthetic magnetic field
ordinarily currents would be passed in the coils so as to is created in a rotation direction regardless of the position
form a synthetic magnetic field in the 6 o'clock direction; of the permanent magnet, and by switching at fixed times
but because the permanent magnet position is unknown, to start rotation of the permanent magnet, an induced
a synthetic magnetic field is generated in a direction voltage occurs and is detected, and normal control is
determined in advance (in the diagram, the 5 o'clock begun.
direction), regardless of the permanent magnet position.
In this method, if at the start the synthetic magnetic field
②: When this state is maintained for a fixed length of time, switching occurs too quickly, the permanent magnet may
the S(N) pole of the permanent magnet is drawn toward not be able to follow, and so a method must be used in
the synthetic magnetic field N(S) pole, and the permanent which the switching period begins slowly and is gradually
magnet moves (rotates) clockwise a small amount. quickened.
Figure 22. Startup detecting induced voltage from synchronous operation driving
A function block diagram for the operations is presented A startup period generation oscillator sends a ST_CLK
in Figure 23. signal to a driving basic waveform generation block, and
the signal causes a synthetic magnetic field to be
generated in a direction determined in advance,
regardless of the above-described permanent magnet
position; the synthetic magnetic field is then switched in
the direction of rotation according to the period of the
signal.
BEMF_DET is a signal used to notify detection of an
induced voltage. When this signal enters the startup
period generation oscillator, the ST_CLK signal is
stopped, BEMF_DET is input to the driving basic
waveform generation block, generation of a synthetic
magnetic field based on the induced voltage begins, and
normal control commences.
Figure 23. Function block diagram detecting induced
voltage from synchronous operation driving
Figure 24. Startup waveforms detecting induced voltage from synchronous operation driving
Figure 24 is waveform examples illustrating the series of diagram used to explain the principles and operation
operations described using Figure 22. The ST_CLK involved in detection of the permanent magnet position.
signal and BEMF_DET signal as well as the signal Using the outputs A1, A2, A3, the coils are energized such
resulting from their addition (see the block diagram), and that current flows through the coils in the six patterns ①
the output voltage waveforms A1 to A3, are relevant to the to ⑥. This energizing is for a short time duration, such
present explanation. The fact that the period of the that the permanent magnet does not rotate.
BEMF_DET signal becomes shorter and shorter indicates
that the rotation rate is increasing.
However, this startup method has the following issues.
A synthetic magnetic field is created regardless of the
position of the permanent magnet, so that depending on
the magnet state, a reverse-direction torque may act,
and for some stopped positions of the magnet, time may
Figure 25. Example of permanent magnet stop state
be required for startup.
Originally, the relative positions of the permanent
magnet and the created synthetic magnetic field should
differ by 90° in order to generate a large amount of
torque. But because the synthetic magnetic field is
created irrespective of the permanent magnet position,
motion may start from an angle such as 70° or 60°, so
that the required large startup torque is not obtained.
The other startup method that addresses these issues is
Figure 26. Schematic diagram showing the principle of
to detect the position of the permanent magnet stop and
position detection and operation of a permanent magnet
start it up.
The energizing waveforms and current waveforms (IVM)
<Summary>
for the six patterns are shown in Figure 27. A1 to A3
In the sensorless system, two types of startup methods
output voltages corresponding to the energization
are used to deal with the fact that the position of the
patterns ① to ⑥. The power supply current is of varying
permanent magnet at the stop is not known.
sizes for each of these patterns. This is because the
The first method is, a synthetic magnetic field is formed
current for each pattern differs depending on the position
in a rotation direction regardless of the position of the
of the permanent magnet; in this method, the difference
permanent magnet, and upon switching at fixed times to
in currents is used to detect the position of the permanent
start rotation of the permanent magnet and detecting
magnet.
the induced voltage that occurs, normal control is
initiated.
However, there are some problems with this method,
and if they need to be addressed, it takes the method
that the permanent magnet stop position is detected
and started it up.
2.3.3 Startup Method 2: Startup on Detection of
Permanent Magnet Stopped Position
Method 2, which includes addressing the issues of
Method 1 described in the previous section, is to detect
the stopped position of the permanent magnet and start.
Figure 27. Current waveforms of the six patterns in Figure
Figure 25 shows an example of a stopped permanent 26 and the current waveforms flowing
magnet (rotor), assuming that the S pole is stopped at the
3 o'clock position and the N pole at the 9 o'clock position. The operation is as follows. In ③, energization results in
the S pole at coil 2 and the N pole at coil 3. The permanent
Next, the circuit diagram in Figure 26 is a schematic
magnet S pole opposes coil 2, and the permanent magnet The flow of operation is as follows: (1) The six patterns
N pole opposes coil 3, so that magnetic polarization of the generated by the position detection pattern generation
coils is impeded. Hence the current rise is most gradual, block are sent to a driving basic waveform synthesis block,
and the current is small. and energization is performed by A1 to A3. The detected
power supply currents are converted into voltages by a
However, ⑥ is the opposite of ③; energization causes an
current detection resistor and an amplifier, and based on
N pole to appear at coil 2 and an S pole at coil 3. Because
(2) a sample and hold circuit and (3) a current
the permanent magnet S pole opposes coil 2 and the
comparison/maximum value pattern detection circuit, (4)
permanent magnet N pole opposes coil 3, the coil
an initial driving pattern generation block generates an
magnetic polarization is promoted. As a result, the current
initial driving pattern based on the permanent magnet
rise is most rapid, and the current is large.
position, and returns the pattern to the driving basic
In other words, by determining the energization pattern waveform synthesis block, and driving begins.
resulting in the largest or the smallest current, the
Short pulses are shown immediately after power-on in the
permanent magnet position can be detected.
output voltage waveforms A1 to A3 in the operation
To illustrate this a little more concretely, we will use an waveform diagrams in Figure 29. This represents
example of a driver circuit block and an operating energization of the six patterns for position detection. As
waveform diagram. explained above, the energization is over a short time,
The circuit block in Figure 28 is basically the method 1 and so in contrast with the other waveforms, the time is
circuit block in Figure 23 for detecting the induced voltage very short.
from synchronous operation to start the motor, to which is Immediately after power-on, the permanent magnet
added a circuit for generating the six energization position is detected, and based on the result, an initial
patterns and detecting the power supply currents, driving pattern is used for driving, so that the problems of
comparing the currents, and generating an initial driving reverse rotation and low-torque startup that occurred in
pattern. Some parts are omitted, but the blue blocks are the method of startup by detecting an induced voltage are
the outputs A1 to A3. avoided, and the motor can be rotated by a large torque
from the very beginning.
Operation after startup basically relies on the same
process as in the method of startup by detecting an
induced voltage. The timing for switching the driving
pattern during initial driving is, similarly to the method of
startup by detecting an induced voltage, based on
ST_CLK.
However, rotation is begun using a large torque from the
start, so that a sufficient induced voltage is obtained using
several patterns (in these waveform diagrams, four
ST_CLK signals), and steady-state driving is begun using
an induced voltage. That is, the problem with the method
of startup by detecting an induced voltage, that time is
required for startup, is alleviated.
<Summary>
The method of detecting the stopped position of the
permanent magnet to start the motor avoids the
problems of reverse rotation and low-torque startup of
the method in which the induced voltage from
synchronous operation is detected for startup, and so
Figure 28. Example of function block diagram for reduces the time needed for startup.
detecting permanent magnet stop position To detect the stopped position of the permanent magnet,
current is passed in six patterns over short intervals
during which the motor does not rotate, and the pattern
for which the power supply current is largest (or
smallest) is determined.
Figure 29. Example of operation waveform of permanent magnet stop position detection
Advantages Disadvantages
Minimal electrical, mechanical noise Rotor is a permanent magnet, so moment of inertia cannot be
High reliability, long lifetime decreased
Easily reaches high speeds Added costs due to complicated electronic circuits and
High efficiency sensors required for rectification function
Easily miniaturized and designed in various shapes Numerous wires needed between driving circuit and motor
Rotation speed proportional to applied voltage Tendency for torque fluctuation (when coils have iron cores)
Rotation speed falls in proportion to load
Large torque on startup and at low speeds
Torque proportional to current
Main characteristics vary linearly, making control easy
Devices Applications
HDD ・Spindles: Disc rotation → 3-phase sensorless
PCs/Game console DVD/Blu-ray drives ・Spindles: Disc rotation → 3-phase sensorless
Blu-ray recorders/players
Laser-beam printers (LBP) ・Paper feed → 3-phase sensored
PPC ・Polygon mirrors: Rotation of polygon mirrors for laser light scanning
→ 3-phase sensored, 3-phase sensorless
DC fan → 2-phase half-wave brushless, Single-phase full-wave brushless, 3-phase sensorless
Drones ・Propellors → 3-phase sensorless
・Gimbal control: Fixing camera directions → 3-phase sensorless
Machine tools ・Screwdrivers, ・Drills, ・Saws, etc.: Rotation → 3-phase sensored
Home appliances ・Air conditioners: Compressors, fans (indoor, outdoor), ・Air purifiers
・Vacuum cleaners etc., Refrigerators (Compressors, fans)
Automotive ・Air conditioners: Fans,・Battery cooling fans
・Seats: Fans etc., Pumps
Revision History
Notes
1. The information contained herein is subject to change without notice.
2. Before you use our Products, please contact our sales representative and verify the latest specifications.
3. Although ROHM is continuously working to improve product reliability and quality, semiconductors can break down
and malfunction due to various factors. Therefore, in order to prevent personal injury or fire arising from failure,
please take safety measures such as complying with the derating characteristics, implementing redundant and fire
prevention designs, and utilizing backups and fail-safe procedures. ROHM shall have no responsibility for any
damages arising out of the use of our Products beyond the rating specified by ROHM.
4. Examples of application circuits, circuit constants and any other information contained herein are provided only to
illustrate the standard usage and operations of the Products. The peripheral conditions must be taken into account
when designing circuits for mass production.
5. The technical information specified herein is intended only to show the typical functions of and examples of
application circuits for the Products. ROHM does not grant you, explicitly or implicitly, any license to use or exercise
intellectual property or other rights held by ROHM or any other parties. ROHM shall have no responsibility
whatsoever for any dispute arising out of the use of such technical information.
6. The Products specified in this document are not designed to be radiation tolerant.
7. For use of our Products in applications requiring a high degree of reliability (as exemplified below), please contact
and consult with a ROHM representative: transportation equipment (i.e., cars, ships, trains), primary communication
equipment, traffic lights, fire/crime prevention, safety equipment, medical systems, servers, solar cells, and power
transmission systems.
8. Do not use our Products in applications requiring extremely high reliability, such as aerospace equipment, nuclear
power control systems, and submarine repeaters.
9. ROHM shall have no responsibility for any damages or injury arising from non-compliance with the recommended
usage conditions and specifications contained herein.
10. ROHM has used reasonable care to ensure the accuracy of the information contained in this document. However,
ROHM does not warrant that such information is error-free, and ROHM shall have no responsibility for any damages
arising from any inaccuracy or misprint of such information.
11. Please use the Products in accordance with any applicable environmental laws and regulations, such as the RoHS
Directive. For more details, including RoHS compatibility, please contact a ROHM sales office. ROHM shall have
no responsibility for any damages or losses resulting non-compliance with any applicable laws or regulations.
12. When providing our Products and technologies contained in this document to other countries, you must abide by
the procedures and provisions stipulated in all applicable export laws and regulations, including without limitation
the US Export Administration Regulations and the Foreign Exchange and Foreign Trade Act.
13. This document, in part or in whole, may not be reprinted or reproduced without prior consent of ROHM.
Powered by