0% found this document useful (0 votes)
62 views2 pages

Typical 2000kVA Transformer

The document is a data sheet for a 2000 kVA transformer manufactured by Wilson Power Solutions Ltd, compliant with IEC 60076 standards. It details specifications such as voltage ratings, insulation classes, cooling type, losses, and dimensions. Additional information includes accessories, testing requirements, and the manufacturer's contact details.

Uploaded by

akamsingh56
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
62 views2 pages

Typical 2000kVA Transformer

The document is a data sheet for a 2000 kVA transformer manufactured by Wilson Power Solutions Ltd, compliant with IEC 60076 standards. It details specifications such as voltage ratings, insulation classes, cooling type, losses, and dimensions. Additional information includes accessories, testing requirements, and the manufacturer's contact details.

Uploaded by

akamsingh56
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

TRANSFORMER DATA SHEET

Project Name: ‐‐
Quote Number: ‐‐
Manufacturer: Wilson Power Solutions Ltd
Applicable Standard: IEC 60076
General Arrangement Dwg #: WPS‐T2‐2000‐AL‐GA
Transformer Rating: kVA 2000
Rated High Voltage @ No Load: Volts 11000
Rated Low Voltage @ No Load: Volts 433
Minimum Insulation class HV LI: kV 75
Minimum Insulation class HV AC: kV 28
Minimum Insulation class LV LI: kV ‐
Minimum Insulation class LV AC: kV 3
Insulating Fluid: Mineral Oil
Fans: No
Pumps: No
Type of Cooling: ONAN
Number of Phases: 3
Frequency: Hz 50
Vector Group: Dyn11
Impedance Voltage (Z): % 6
Core Material: CRGO steel
No Load Losses: W 1305
Load Losses @ 75⁰C: W 15000
Losses as per EU Regulation No.
548/2014 Meets Tier‐2 Requirement
Resistance % 0.75
Reactance % 5.95
Regulation type: DETC
Tapping on HV: % +5.0, +2.5, 0.0, ‐2.5, ‐5
Design Ambient Temperature: ⁰C 40
Temp Rise of Top Oil: ⁰C 60
Temp Rise of Winding: ⁰C 65
Altitude: m <1000
Pollution class: C4
Sound Power Level: dB(A) 61
HV Conductor Material: Aluminium
LV Conductor Material: Aluminium
Paint Finish Colour: Dark Admiralty Grey(BS 632 shade)
Free Breathing, bolted cover, tank attached cooler
Transformer Type: bank
Cable Box ‐ 12kV, 3‐Pole, (Facing‐'E' BS:2562)
HV termination type: with 1 take off per phase

Wilson Power Solutions Limited, Westland Works, Westland Square, Leeds LS11 5SS
Tel: +44 (0)113 271 7588
Registered office Westland Works, Westland Square, Leeds LS11 5SS
Cable box ‐ 1.1kV, 4‐Pole, (Facing‐'F', BS:2562) with
LV termination type: 4 take off per phase & Neutral
Neutral: Located inside ‐ cable box
Harmonic distortion: THD% <5%
Accessories:
Draining & Sampling Valve Yes
Radiator Valves No
Dehydrating Breather Yes
Pressure Relief Device No
Oil Temperature Indicator No
Buchholz unit No
Winding Temperature Indicator No
Magnetic Liquid Level Indicator No
Conservator No
HV CTs No
LV CTs No
Neutral CTs No
Disconnecting links HV No
Disconnecting links LV No
Marshalling box No
Bund No
Overall Dimensions:
Length mm 1828
Width mm 1769
Height mm 1821
Oil L 1110
Weight: kg 5125
Testing Requirement:
Routine tests Yes
Lighting Impulse No
Chopped impulse No
Temperature rise test No
Noise test No
Dissolved gas analysis No
Frequency response analysis No
CT checks No
Other information
Comments: All losses, dimensions & weights are provisional only subject to confirmation

Wilson Power Solutions Limited, Westland Works, Westland Square, Leeds LS11 5SS
Tel: +44 (0)113 271 7588
Registered office Westland Works, Westland Square, Leeds LS11 5SS

You might also like