(A) General Requirements (D.) Reinforced Concrete: CHB Wall 2 - 12MM TOP and Bottom Bars

The document outlines general requirements and specifications for structural materials and work, emphasizing compliance with the National Structural Code of the Philippines (NSCP 2015). It details the requirements for reinforced concrete, structural steel, foundations, masonry, and drainage, including specific dimensions, strengths, and safety measures. Additionally, it emphasizes the contractor's responsibility for safety and obtaining prior approval for any changes to the working drawings.

Uploaded by

axislain15
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
18 views1 page

(A) General Requirements (D.) Reinforced Concrete: CHB Wall 2 - 12MM TOP and Bottom Bars

The document outlines general requirements and specifications for structural materials and work, emphasizing compliance with the National Structural Code of the Philippines (NSCP 2015). It details the requirements for reinforced concrete, structural steel, foundations, masonry, and drainage, including specific dimensions, strengths, and safety measures. Additionally, it emphasizes the contractor's responsibility for safety and obtaining prior approval for any changes to the working drawings.

Uploaded by

axislain15
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

(A) GENERAL REQUIREMENTS (D.

) REINFORCED CONCRETE
3. LINTEL BEAMS SHALL BEAR AT LEAST 200MM (8") ON EACH SIDE OF MASONRY
1. ALL STRUCTURAL MATERIALS AND WORK SHALL CONFORM TO THE 1. CONCRETE SHALL BE MIXED, PROPORTIONED, CONVEYED AND PLACED IN WALL OPENING.
REQUIREMENTS OF THE LATEST EDITION OF THE NATIONAL STRUCTURAL CODE OF ACCORDANCE WITH THE PROVISIONS SET BY THE NSCP 2015.
THE PHILIPPINES (NSCP 2015). 4. WALL REINFORCEMENTS SHALL BE AS FOLLOWS:
2. ALL CONCRETE SHALL DEVELOP A MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS WALL THICKNESS: VERTICAL BARS: HORIZONTAL BARS:
2. VERIFY ALL DIMENSIONS, ELEVATIONS AND SITE CONDITIONS BEFORE STARTING WITH CORRESPONDING MAXIMUM SLUMP AND MAXIMUM SIZE AGGREGATE AS 8" (200MM 12MM∅ @400MM 10MM∅ @600MM
WORKS, NOTIFY THE ENGINEER IMMEDIATELY OF ANY DISCREPANCIES. FOLLOWS: 6" (150MM 10MM∅ @400MM 10MM∅ @600MM
4" (100MM 10MM∅ @400MM 10MM∅ @600MM
3. NOTES AND DETAILS ON THE DRAWINGS TAKE PRECEDENCE OVER THE GENERAL STRUCTURAL MEMBER 28 DAY STRENGTH MAX SLUMP MAX. SIZE AGG.
NOTES AND TYPICAL DETAILS IN CASE OF CONFLICT. SLAB ON GRADE 20.7MPA (3000PSI) 100MM (4") 25MM (1") 5. BLOCK WALL REINFORCING BARS SHALL BE LAPPED OF 30 BAR DIAMETERS WHERE
FOOTING 20.7MPA (3000PSI) 100MM (4") 19MM (3/4") SPLICED, HORIZONTAL/VERTICAL DOWELS FROM FOOTINGS, COLUMNS/WALLS OR
4. WHERE CONSTRUCTION DETAILS ARE NOT SHOWN OR NOTED FOR ANY PART OF COLUMNS 27.6MPA (4000PSI) 100MM (4") 19MM (3/4") SLABS SHALL EXTEND INTO THE BLOCK WALL A MINIMUM OF 30 BAR DIAMETERS
THE WORK, SUCH DETAILS SHALL BE THE SAME AS FOR SIMILAR WORK SHOWN ON BEAMS & SLAB 27.6MPA (4000PSI) 100MM (4") 19MM (3/4") OR A MINIMUM OF 400MM WHICHEVER IS LONGER AND DOWELS TO MATCH
THE DRAWINGS. VERTICAL REINFORCEMENTS OF WALL.

5. PIPES, DUCTS, SLEEVES, CHASES, ETC. SHALL NOT BE PLACED IN SLABS, BEAMS, OR 3. ALL REINFORCING STEEL BARS SHALL CONFORM TO ASTM A615 GRADE 40 FOR (G) STRUCTURAL STEEL
WALLS UNLESS SPECIFICALLY SHOWN OR NOTED NOR SHALL ANY STRUCTURAL 12MM∅ & SMALLER BARS WHILE BARS 16MM∅ & LARGER SHALL BE GRADE 60.
MEMBER BE CUT FOR PIPES, DUCTS, ETC. UNLESS SPECIFICALLY SHOWN. OBTAIN 1. ALL STRUCTURAL STEELS SUCH AS ANGLES, WIDE FLANGE SECTIONS, PIPES,
PRIOR WRITTEN APPROVAL FROM THE ENGINEER FOR INSTALLATION OF ANY 4. ALL FABRICATION, DETAILING AND PLACING SHALL CONFORM TO THE PROVISIONS STIFFENER PLATES, BASE PLATES, ETC. SHALL CONFORM TO ASTM A-36.
ADDITIONAL PIPES, DUCTS, ETC. SET BY THE NSCP 2015 EDITION
2. ALL STRUCTURAL STEEL SHALL BE DETAILED, FABRICATED AND ERECTED BASED ON
6. LOCATE AND PROTECT UNDERGROUND OR CONCEALED CONDUIT, PLUMBING OR 5. CLEAR DISTANCE SPACING BETWEEN PARALLED BARS IN A LAYER SHALL NOT BE THE SPECIFICATION FOR DESIGN, FABRICATION, AND ERECTION OF STRUCTURAL
OTHER UTILITIES WHERE NEW WORK IS BEING PERFORMED LESS THAN 1.50 TIMES THE NOMINAL DIAMETER OF THE BAR, OR 1.33 TIMES STEEL GIVEN BY THE NATIONAL STRUCTURAL CODE OF THE PHILIPPINES (NSCP).
MAXIMUM SIZE AGGREGATE, NOR LESS THAN 38MM (1 1/2").
7. TAKE NECESSARY PRECAUTIONS TO MAINTAIN AND INSURE THE INTEGRITY OF THE 3. CONNECTION BOLTS ( 3/4 ROUND, UNLESS SHOWN OTHERWISE) SHALL CONFORM
STRUCTURE DURING CONSTRUCTION. NEITHER THE OWNER NOR 6. MAINTAIN MINIMUM CONCRETE COVER FOR REINFORCING STEEL AS FOLLOWS: TO ASTM A-325. ANCHOR BOLTS (EMBEDDED IN MASONRY OR CONCRETE) SHALL
ARCHITECT/ENGINEER WILL ENFORCE SAFETY MEASURES OR REGULATIONS. IT FOOTING (CAST AGAINST & EXPOSED TO EARTH) 75MM (3") CONFORM TO ASTM A307 UNLESS NOTED OTHERWISE ON THE DRAWINGS.
SHALL BE THE CONTRACTORS RESPONSIBILITY TO PROVIDE ADEQUATE SHORING EXPOSED TO EARTH BUT POURED AGAINST FORMS 50MM (2")
AND BRACING OF THE STRUCTURE FOR ALL THE LOADS THAT MAYBE IMPOSED SLAB ON GRADE 40MM (1 1/2") 4. ALL STRUCTURAL STEEL SHALL BE CLEAN, RUST FREE AND SHOP COATED WITH THE
DURING CONSTRUCTION. FURTHER, THE CONTRACTOR SHALL DESIGN, CONSTRUCT COLUMN TIES OR SPIRALS AND BEAM STIRRUPS 40MM (1 1/2") APPROPRIATE PAINT. STRUCTURAL STEEL AND ANCHOR BOLTS SHALL BE MINIMUM
AND MAINTAIN ALL SAFETY DEVICES AND SHALL BE SOLELY RESPONSIBLE FOR ASTM A-36 DOMESTIC, LATEST REVISION.
CONFORMING TO ALL SAFETY AND HEALTH STANDARDS, LAWS AND REGULATIONS 7. SPLICES SHALL BE SECURELY WIRED TOGETHER AND SHALL LAP AT LEAST 40 TIMES
DIAMETER OR 600MM WHICHEVER IS GREATER. STAGGER BOTTOM AT LEAST 1.50M 5. NON - SHRINK GROUT - PRE-MIXED, NON-METALLIC, CEMENT-BASED GROUT,
8. OBTAIN PRIOR WRITTEN APPROVAL FROM THE ENGINEER IN CASE OF CHANGES TO FROM SPLICES IN OTHER BOTTOM REINFORCEMENT. STAGGER SPLICES FOR TOP MEETING THE REQUIREMENT OF ASTM C827, ASTM C109 & CRD-C621, WITH A
THE WORKING DRAWINGS REINFORCEMENT SIMILARLY. MINIMUM COMPRESSIVE STRENGTH OF 7000PSI AT 28 DAYS.4

(B.) DESIGN CRITERIA 8. ALL ANCHOR BOLTS, DOWELS, AND OTHER INSERTS SHALL BE PROPERLY POSITION 6. PROVIDE MISCELLANEOUS PLATES, ANGLES AND ANCHORS AS SHOWN OR NOTED
AND SECURED IN PLACE PRIOR TO PLACING OF CONCRETE. ON DRAWINGS.
REFER TO STRUCTURAL COMPUTATIONS
9. ALL CONCRETE SHALL BE KEPT MOIST FOR A MINIMUM OF 7 CONSECUTIVE DAYS 7. ALL CUTTING AND BLOCKING OF STEEL SHALL BE SHOWN ON SHOP DRAWINGS
IMMEDIATELY AFTER POURING BY THE USE OF CURING COMPOUNDS, OR OTHER AND PERFORMED IN SHOP.
(C.) FOUNDATION APPROVED METHODS.
8. PROVIDE TEMPORARY BRACING AS REQUIRED FOR A SAFE STRUCTURE UNTIL ALL
1. FOOTINGS SHALL BEAR ON SOLID UNDISTURBED EARTH (CONTROLLED, FINAL CONNECTIONS ARE MADE.
10. STRIPPING OF FORMS AND SHORES:
COMPACTED STRUCTURAL FILL OR BOTH) AT LEAST 450MM BELOW LOWEST
FOUNDATION............................................................................24 HRS.
ADJACENT FINISHED GRADE.
BEAMS....................................................................................14 DAYS
0.20
0.20 l 0.20 l 0.20
2 - 12MM∅ TOP
2. ALL STRUCTURAL MEMBERS IN THE BUILDING SUBSTRUCTURE IS DESIGNED FOR CHB WALL
ASSUMED ALLOWABLE PRESSURE OF 144KPA (3,000PSI). (E) CAMBER REQUIREMENTS AND BOTTOM BARS

2 - 12MM∅ TOP
3. SUB-GRADE PREPARATION INCLUDING DRAINAGE, EXCAVATION, COMPACTION, 1. UNLESS OTHERWISE NOTED ON THE PLANS OR SPECIFICATIONS CAMBER ALL RC AND BOTTOM BARS
AND FILLING REQUIREMENTS, SHALL CONFORM STRICTLY WITH THE BEAMS AT LEAST 10MM FOR EVERY 4000MM OF CLEAR SPAN EXCEPT CANTILEVERS
RECOMMENDATIONS GIVEN IN THE SOILS REPORT OR AS DIRECTED BY THE SOIL WHICH SHALL BE 50MM FOR EVERY 3000MM OF CLEAR SPAN.
ENGINEER.
2. UNLESS OTHERWISE NOTED ON THE PLANS OR SPECIFICATIONS CAMBER ALL
CHB WALL
4. THE CONTRACTOR SHALL NOTIFY THE ENGINEER AFTER FOOTING EXCAVATION SLABS 8MM PER 3000MM OF SHORTER SPAN AND 14MM FOR EVERY 2000MM OF
SLABS CANTILEVER SPAN WINDOW
HAVE BEEN COMPLETED AND PRIOR TO CONCRETING TO CONFIRM THE DESIGN OPENING
FOUNDATION CAPACITY.
DOOR

2.10
5. ROOF AND AREA DRAINAGE SHALL BE DIRECTED AWAY FROM THE FOUNDATIONS. (F) MASONRY AND CONCRETE BLOCKS OPENING

6. EXCAVATIONS SHALL BE PROPERLY BACKFILLED. BACKFILL FOR WALLS SHALL BE 1. CONCRETE HOLLOW BLOCKS, UNLESS OTHERWISE SPECIFIED SHALL BE 150MM
PERVIOUS MATERIAL ACCEPTABLE TO THE GEOTECHNICAL ENGINEER. DO NOT THICK LOAD BEARING BLOCKS SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH
PLACE BACKFILL BEHIND WALLS BEFORE THEY HAVE ATTAINED THEIR DESIGN OF 750 PSI (5.175 MPa) WHILE NON-LOAD BEARING SHALL HAVE A MINIMUM
STRENGTH. SHORE AND PROTECT WALLS FROM LATERAL LOADS UNTIL THE COMPRESSIVE STRENGTH OF 400 PSI (2.76 MPa).
SUPPORTING MEMBERS ARE IN PLACE AND HAVE DEVELOPED SPECIFIED
STRENGTHS 2. PROVIDE 1-16MMØ VERTICAL BARS AT CORNERS, INTERSECTIONS, END OF WALLS,
16MM∅ DRB VERTICAL BAR 16MM∅ DRB VERTICAL BAR
EACH SIDE OF OPENINGS.

LICENSED PROFESSIONAL: PRC REG. NO.: DATE ISSUED: PROJECT TITLE: R.A. 9266, ARTICLE IV, SECTION 33 SHEET CONTENT: SHEET NO.:

0163590 KORONADAL CITY DRAWINGS AND SPECIFICATIONS DULY SIGNED OR STAMPED AS INSTRUMENTS OF SERVICE, ARE THE

EXP: 10/22/2024

PTR NO.: PLACE ISSUED:


PROPOSED ONE-STOREY THREE-BEDROOM RESIDENTIAL BUILDING

LOCATION:
INTELLECTUAL PROPERTY AND DOCUMENTS OF THE ARCHITECT, WHETHER THE SUBJECT FOR WHICH THEY ARE
MADE FOR IS EXECUTED OR NOT. IT SHALL BE UNLAWFUL FOR ANY PERSON WITHOUT THE WRITTEN CONSENT
OF THE ARCHITECT OR AUTHOR OF SAID DOCUMENTS TO DUPLICATE OR MAKE COPIES OF SAID DOCUMENT
FOR USE IN REPETITION OF OR FOR OTHER PROJECTS OR BUILDINGS WHETHER EXECUTED PARTLY OR IN
WHOLE (REAFFIRMS THE PERTINENT PROVISIONS OF RA 8293 OR THE INTELLECTUAL PROPERTY CODE OF THE
S-1
PHILIPPINES).
ENGR. KIM TYRONE P. CARDENAS, RMP MS. MERLYN C. JARREL
CIVIL ENGINEER
4709863

DATE ISSUED: 01/03/2022


KORONADAL CITY
SUENO SUBDIVISION, KORONADAL CITY, SOUTH COTABATO
WORKS OF ART, ARCHITECTURE, MODELS AND DESIGN ARE CREATIVE WORKS AND CONSIDERED PART OF THE
INTELLECTUAL PROPERTY OF THE AUTHOR DULY PROTECTED BY PD 49 OR THE DECREE ON INTELLECTUAL
PROPERTY.
OWNER 05 12