Building Code
Building Code
RULE I
RULE II
RULE III
RULE IV
Note: It must use fire-resistive techniques such as fire retardants chemical/incombustible construction.
Rule IV
Exterior bearing and non-bearing walls Types II and III - 1 hr fire resistive
Types IV and V - 4 hr fire resistive
Interior bearing walls, partitions, floors, and roofs Types II, III and IV - 1 hr fire resistive
Type V - 3 hr fire resistive
Rule V.
Type of Assembly and Material Minimum thickness (in millimeter) for the
given fire resistance
Floor Construction
Solid R.C. slab
- Average cover to reinforcement 25 25 20 15
- Overall Depth 150 150 125 100
Partitions
- Solid concrete 175 175 150 125 175
- Solid masonry 200 175 150 125 200
- Hollow unit masonry 300 250 200 150 300
Rule VII
RULE V
RULE VI
RULE VII
RULE
15
RULE IX - SANITATION
Section 901: General Requirements ● Buildings for human habitation must have
potable water, plumbing, wastewater
treatment/disposal, storm drainage, pest
control, and noise abatement as per
health and safety standards.
Section 903: Wastewater Disposal System ● Discharge sewage to city sewer systems;
comply with DENR and sanitation codes.
● Where no sewer system exists, use septic
tanks, absorption fields, or treatment
plants.
● Plumbing installations must follow the
Revised National Plumbing Code.
Section 904: Storm Drainage System ● Rainwater must not enter sanitary sewers.
● Provide drainage for low-lying areas.
● Installations must follow the Revised
National Plumbing Code.
Section 905: Pest and Vermin Control ● Rat-proof hollow or wood constructions.
● Garbage bins must prevent pest entry.
● Screen public dining areas without
artificial ventilation.
Section 906: Noise Pollution Control ● Use noise abatement devices for
industrial equipment per DOLE and
DENR standards.
● Construction noise and vibrations must
meet DENR limits.
Section 907: Pipe Materials ● All pipe materials must comply with BPS-
DTI standards.
FIRE CODE
RULE 10
Chapter 2
DIVISION 1 Scope
● This deals with life safety from fire and like emergencies in buildings, structures and
facilities.
● To minimize danger to life from fire, smoke, vapor and fumes before buildings are
vacated.
● It also discusses procedures and guidelines in fire drills required for all types of
occupancies to prevent panic in times of emergencies.
● Assembly: For gatherings of 50+ people (e.g., theaters, gyms, libraries). Smaller
restaurants (<50) are "mercantile."
● Educational: Buildings for instruction with 6+ people (e.g., schools, universities).
● Day Care: Facilities caring for 4+ clients (<24 hours) (e.g., daycare centers).
● Health Care: For medical care where occupants cannot self-preserve (e.g., hospitals).
● Residential Board and Care: Lodging for 4+ residents with personal care services (e.g.,
group homes).
● Detention and Correctional: Housing under restraint (e.g., prisons, rehab centers).
● Residential: Sleeping accommodations (e.g., hotels, dormitories).
● Mercantile: For displaying/selling merchandise (e.g., malls, supermarkets).
● Business: For transactions or offices (e.g., BPOs, call centers).
● Industrial: For processing or repairing goods (e.g., factories of all kinds, power plants).
● Storage: For storing goods, vehicles, or animals (e.g., warehouses, parking garages).
● Mixed Occupancies: Buildings with multiple types of uses; strictest safety standards
apply.
● Special Structures: Unique buildings following general and specific safety guidelines.
● Conflict Resolution: Classification disputes handled by the C/MFM (City/Municipal Fire
Marshal).
● the degree of hazard shall be the relative danger of the start and spread of fire,
occurrences potentially endangering the lives and safety of the occupants of the
building.
● The degree of fire hazard shall be determined by the C/MFM
DIVISION 5
Doors
● All door construction and designs must ensure a clear and direct exit travel
● Self-closing or automatic-closing, and comply with NFPA 80 Standard for Fire Doors
and Windows
● Doors for egress must be side-hinged or pivoted-swinging, capable of swinging to full
width, and swing in egress direction for rooms with 50 or more occupants.
● Door swings in egress direction in exit enclosures or high hazard areas, leaving 1/2
width unobstructed and projecting 178mm when fully open. Doors must have a
landing.
● Doors must open easily from the occupied side
● Locks should require no key or tool for operation
○ Locks should have a simple, visible releasing mechanism.
● Bears a sign stating "FIRE EXIT, KEEP DOOR CLOSED"
● 4-or more-storey buildings must have a re-entry mechanism every 4 floors, not
allowing re-entry marked with the nearest door
○ NO RE – ENTRY
○ PROCEED TO ________ FLOOR
○ AND _________ FLOOR
● Installation or maintenance of any panic hardware device on doors that prevents or
intends to prevent egress is prohibited
For double doors At least one door must have a minimum clear
width of 710 mm.
Thresholds or floor changes over 6 mm Must have a beveled slope no steeper than
1:2.
Force to release the door latch Not more than 7 kgf in the direction of exit
travel.
Releasing device (bar or panel) Must extend at least two-thirds (2/3) of the
door’s width.
Placed between 760 mm to 1,120 mm above
the floor.
Revolving Doors ● Revolving doors are not allowed for egress from the floor of
discharge directly to the outside, except in certain Chapter
Divisions..
● They must be approved and not exceed the number of
swinging doors within 6m. Must be equipped with measures
to prevent rotation at too rapid rates for orderly egress.
Turnstiles ● Should not obstruct egress except for approved ones over
910mm
○ Ones that freely turn in exit direction and follow door
requirements
● Should not be placed in exits unless adjacent to, 6.1m away
from, swinging doors or gates, Should be rated the same as
revolving doors in terms of exit width and travel rates.
Horizontal Sliding Doors ● Door can be operated from either side without special
knowledge or effort.
● Operation force for egress is ≤ 7 kgf.
● Operation force for exit travel is ≤ 15 kgf for setting the door
in motion and 7 kgf for closing or opening.
● Door assembly complies with fire protection rating and is
self-closing or automatic-closing with smoke detection.
● Installation is in accordance with NFPA 80, Standard for Fire
Doors and Windows.
Winders Winders in stairs, permitted in Division 8-20, must have a tread depth of
150-280mm at a point 305mm from the narrowest edge.
Enclosure Interior stairways must be enclosed, except for open ones allowed by
para A.2 of Section 10.2.6.5*. Exit enclosures must be usable, and open
spaces should not interfere with egress.
Monumental Stairs Accepted as required exits if all requirements are met, except
for curved stairs that are accepted with radius of ≥ 7.5 meters
at the inner edges.
Outside Stairs Any permanently installed stairs outside the building for egress.
Separated from interior of buildings with the same fire-resistance ratings
for walls, openings are protected by fire doors and fixed wired glass
windows
Wall construction should extend vertically to a point 3,050 mm above the
topmost landing of the stairs or to the roofline.
Horizontally for at least 3,050 mm.
*Section 10.2.6.5 Protection Of Vertical Opening And Combustible Concealed Spaces
● Handrail Details:
Above upper surface on the tread 760-865 mm
Additional handrail for children’s use Placed lower than the main handrail
● Guard Details:
Guard height 1.06 m
Subdivide or fill guard area from floor, riser, or Min. required height
curb
● Enclosure walls and guards must be designed for loads transmitted by handrails or resist 75
kg horizontal force per lineal meter applied at the top, whichever produces maximum stress.
● Intermediate rails, balusters, and panel fillers must withstand a uniform load of 122 kg/m 2
over the guard's gross area, without adding reactions to the main supporting members.
Smoke-proof Enclosures***
Ramp
A. Dimensional Criteria
B. Protective Enclosure
● Ramps used as an exit or exit component inside a building must be separated from other
parts of the building as per Section 10.2.5.2, para "B."
● Fixed wired glass panels in steel sash are permitted for buildings with approved,
supervised sprinkler systems.
● No usable enclosed space or open space under ramps in an exit enclosure can be used
for any purpose.
C. Other Details
● Live load design: Minimum 488 kg/m², with non slip surfaces.
● Uniform slope: Slope should not vary between landings, and landings must be level.
Direction changes should only occur at landings.
● Noncombustible material: Required for ramps in buildings over 3 storeys or any height
in noncombustible/fire-resistive constructions. The ramp floor and landings must be
solid, without perforations.
● Guards and handrails: Must comply with Section 10.2.5.4, para "H," except for Class A
ramps where handrails are not required.
● Impediment-free arrangement: Outside ramps should avoid any barriers. For ramps
over 3 storeys high, this arrangement should have a height of at least 1.22 meters.
● Water accumulation: Surfaces of outside ramps and landings should be designed to
minimize water buildup.
Exit Passageways
A. Application
● Hallways, corridors, passages, or tunnels can be designated as an exit passageway
when they comply with the requirements of Section 10.2.5.2, along with additional
provisions in this section.
1. Exit passageways must be separated from other parts of the building as per Section
10.2.5.2, para “B.”
2. Fixed wired glass panels in steel sash can be installed in the separation for buildings
with an Automatic Sprinkler System.
C. Width
● The width must be sufficient to accommodate the total capacity of all exits discharging
into the passageway.
D. Floor
Occupancy (Resident user categories for application of life safety requirements in this Division)
Use Condition I - Free Occupants have free movement from sleeping areas and other
Egress spaces to the exterior via compliant means of egress.
Use Condition II - Zoned Free movement is allowed between sleeping areas and other
Egress smoke compartments.
Use Condition III - Zoned Movement is allowed within individual smoke compartments (e.g.,
Impeded Egress residential units with sleeping rooms and activity spaces), with
egress to other compartments controlled by remote release
mechanisms.
Special Requirements
● Use Conditions III and IV:
Emergency egress mechanisms must be accessible, secure, and operable by minimum
available staff at all times.
● Use Condition I Exception:
Facilities may follow Use Condition II standards given that Use Condition I facilities are
provided with a twenty-four hour (24-hr) on-duty staff.
Occupant Load
● Means of egress must accommodate the maximum intended occupants on any floor.
● Minimum standard: 1 person per 11.1 m² gross floor area.
A. Types of Exits
Permissible exit types include:
1. Doors
2. Stairs and smoke-proof enclosures
3. Horizontal exits
4. Exit passageways
B. Capacity of Exits
● Exit capacity is calculated in accordance with para “C” of Section 10.2.5.2 of this RIRR.
C. Number of Exits
● Each floor or fire section must have at least two (2) exits, remote from each other.
● Exit access travel permitted to be common path not exceeding thirty meters (30 m).
D. Access to Exits
● All access points (aisles, passageways, corridors, etc.) must comply with Section
10.2.5.2 of this RIRR.
B. Interior Finish
● Interior finishes must be Class A or Class B.
D. Extinguishment Requirements
● Buildings must have supervised automatic sprinkler systems.
● Sprinklers must integrate with fire alarm systems.
● Portable fire extinguishers and standpipe systems must be installed, with exceptions for
locked or staff-access-only locations.
F. Hazardous Areas
Occupant Load Not more than 200 residents per smoke compartment.
Travel Distance a. Distance from any room door to exit access: ≤ 45 meters
Net Area per Occupant Not less than 0.56 m² per occupant on each side of the smoke
barrier for all occupants in adjoining compartments.
Doors Resistance Doors must provide resistance to smoke passage, and swinging
doors must be self-latching or have 22 Newtons (22 N) resistance.
Door Requirements Doors must comply with egress requirements and have
locking/release arrangements.
Vision Panels Must be provided where the barrier crosses an exit access corridor
for visibility.
Chapter 3
DIVISION 4
Chapter 5
DIVISION 1
DIVISION 2