1. Define the power quality (PQ) problem from measurement parameter and end user perspectives.
5. A switchgear busbar is subjected to voltage variations of +-15% from its nominal value lasting for up to 0.20 seconds due to the
operation of an automatic welding machine. (i) Argue, whether a device that is compliant with the ITIC curve shown above could
tolerate these voltage deviations. (ii) By referring to the ITIC curve, deduce the impact if the duration of the voltage swings lasts for 2
seconds
3
Chapter 1: Introduction to Power Quality
(PQ)
1.1 Definition
1.2 PQ issues
1.3 Sources of PQ problems
1.4 Effects of PQ
1.5 CBEMA CURVES
1.6 PQ Standards
4
WITH WISDOM WE EXPLORE
Chapter 1: Introduction to Power Quality
(PQ)
5
WITH WISDOM WE EXPLORE
Power quality definitions (contd…)
What is PQ?
Different perspectives
Equipment designer
Electrical utility Industrial/ end-user
or manufacturer
“A perfect
“The power that
sinusoidal wave,
works for
with no variations
“V availability or whatever
in the V, and no
outage.” equipment the
noise present on
end-user is
the grounding
applying.”
system.”
6
Power quality definitions (contd…)
More concise
definition:
IEEE Definition:
“PQ is asset of
“The concept of electrical boundaries
powering and that allows a piece of
grounding sensitive equipment to function
electronic equipment in its intended
in a manner suitable manner without
for the equipment.” significant loss of
performance or life
expectancy.”
7
Power quality definitions (contd…)
Roger Dugan,
Gerry Heydt: Mark
“Measure, analysis, McGranaghan,
and improvement of and Wayne Beaty:
bus voltage, usually a
load bus voltage, to “Any power problem
maintain that voltage manifested in V, I, and
to be a sinusoid at f deviations that result
rated voltage and in failure or mis
frequency.” operation of customer
equipment.”
8
Power quality definitions (contd…)
SUPPLY/ UTILITY
What PQ?
PQ=Reliability
Why PQ?
- Loss of production
- Product damages Voltage
- Maintenance
Quality Current and PQ
- Hidden cost
frequency Quality
CONSUMERS/
LOADS
9
Power Frequency (PF) Disturbance
10
Reasons for concern with PQ
11
Recent sources of PQ problems
High efficiency
Modern load & adjustable-speed
Increased awareness
equipments are more motor drives and
of the PQ issues by
sensitive to PQ shunt capacitors
the end users.
variations. results in increasing
harmonic levels.
12
Internal Cause External Cause
• Approximately 80% of electrical • About 20% of PQ problems
disturbances originate within a originate with the utility
business facility. transmission and distribution
• E.g. Large equipment start-up system.
or shutdown, Improper wiring • E.g. The most common cause is
and grounding, Overloaded a lightning strike; others
circuits or Harmonics Equipment failure, Neighboring
business, and even Normal
operation of utility equipment
13
Sources of PQ problems causing Transients
Distribution System
• External:
• Lightning
• Car hitting poles
• Internal
• Switching Operations (Breakers,
Capacitors,…)
• Fault Clearing/Breaker Operations
Consumers / Loads
• External
• Lightning
• Internal:
• Arcing Devices
• Starting & Stopping Motors
• Breaker Operations
• Capacitor Switching
14
14
Typical types of PQ (PQ Issues)
Typical
Power
Quality
Voltage Voltage Voltage
Harmonics Transients
Flicker Sag/Dip Swell
15
Typical types of PQ (PQ Issues)
16
Typical types of PQ (PQ Issues)
Interruption
The complete loss of voltage for a period of time.
17
Typical types of PQ (PQ Issues)
Overvoltage
An RMS increase in the ac V, at the power f, for a duration greater than a few seconds.
18
Typical types of PQ (PQ Issues)
Undervoltage
An RMS decrease in the ac V, at the power f, for a duration greater than a few seconds.
19
Typical types of PQ (PQ Issues)
Voltage Swell
An RMS increase in the ac V, at the power f, for durations from a half-cycle to a few seconds.
20
Typical types of PQ (PQ Issues)
Voltage Sag
An RMS reduction in the ac V, at the power f, for durations from a half-cycle to a few seconds.
21
Typical types of PQ (PQ Issues)
Flicker
A repetitive variation of input voltage sufficient in duration to allow visual observation of a change
in electric light source intensity.
22
Typical types of PQ (PQ Issues)
Impulse Transient
A sudden, non-power frequency change in the steady state voltage or current, which has a
unidirectional polarity (nsec to msec).
23
Typical types of PQ (PQ Issues)
Oscillatory Transient
Sudden, non-power frequency change in the steady state voltage or current, that includes
both positive and negative polarity values (5 usec to 3 msec).
24
Typical types of PQ (PQ Issues)
Low Frequency Oscillatory Transient
Sudden, non-power frequency (300 Hz and 900 Hz) change in the steady-state voltage or
current, that includes both positive and negative polarity values – usually caused by utility
capacitor switching (0.5 to 3 cycles).
25
26
26
Sources of PQ Problems
High Frequency!
27
27
Sources of PQ Problems
Low Frequency!
28
28
Sources of PQ Problems
High Frequency!
29
29
Sources of PQ Problems
Low Frequency!
30
30
Sources/Causes of PQ Problems and
Their respective Solutions
Power Quality Typical Causes Example Solutions
Impulse Transient Lightning, Electrostatic Surge arresters, Filters,
discharge, Load switching. Isolation transformers.
Oscillatory Transient Line/ Cable switching, Surge arresters, Filters,
Capacitor switching. Isolation transformers.
Voltage Sags/ Swells Remote system faults. Ferroresonant
transformers, UPS.
Under/ Over Voltage Motor starting, Load variation. Voltage regulators,
Ferroresonant
transformers.
Harmonics Distortion Nonlinear load, System Active/ Passive Filters,
resonance. Transformer with zero
sequence components.
Voltage Flicker Intermittent loads, Motor Static Var systems.
starting, Arc Furnaces.
31
Effects of PQ problems (Broadly)
Increased Outside
Equipment costs from consultant
malfunctions downtime expense
Excessive Increased
wear & tear maintenance,
or repair time
premature and expenses
failure of
equipment
32
33
33
Why PQ Standards?
• To provide guidelines, recommendations, and limits to help and assure
compatibility between end use equipment and the system where it is
applied.
• To protect the utility and end user equipment from failing or mis-
operating when the V, I, or f deviates from normal.
34
Role of Standards (contd…)
Standards
Organizatio
ns (IEEE,
Power ANSI)
Conditionin Research
g Organizatio
Equipment n
Manufactur
ers
Utility
Customer
Manufacturer
Architects/E
Consultants ngineerings
Facility
Monitoring Designers
Equipment
Manufactur
ers
35
PQ
Standards
https://www.mytnb.com.my/residential/get-electricity/tnb-electricity-system
36
IEEE:
37
IEC:
- Coined in 1980
- Members 43 countries
38
ANSI:
39
IEEE 1159-2009
Standard
Table 2 —Categories and
typical characteristics of
power system
electromagnetic
phenomena
40
IEC Standard
41
In the 1970s, the Computer Business Equipment Manufacturers
Association (CBEMA) developed the curve
42
43
44
45
1. Define the power quality (PQ) problem from measurement parameter and end user perspectives.
3. List the organizations responsible for developing PQ standards from inside and outside of the US.
5. A switchgear busbar is subjected to voltage variations of +-15% from its nominal value lasting for up to 0.20 seconds due to the
operation of an automatic welding machine. (i) Argue, whether a device that is compliant with the ITIC curve shown above could
tolerate these voltage deviations. (ii) By referring to the ITIC curve, deduce the impact if the duration of the voltage swings lasts for 2
seconds
46
END