0% found this document useful (0 votes)
14 views3 pages

Boq 2

The document outlines the electrical works for the IOM Headquarters project in Beirut, focusing on the installation of earthing systems, lightning protection systems, and surge protection devices. It details the specifications, quantities, and types of materials required for each component of the electrical works. The total cost for the project is to be calculated based on the listed items and their respective unit rates.

Uploaded by

crishina9legend
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
14 views3 pages

Boq 2

The document outlines the electrical works for the IOM Headquarters project in Beirut, focusing on the installation of earthing systems, lightning protection systems, and surge protection devices. It details the specifications, quantities, and types of materials required for each component of the electrical works. The total cost for the project is to be calculated based on the listed items and their respective unit rates.

Uploaded by

crishina9legend
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Project: IOM Headquarter Date : 11-07-2023

Systems: Lightning Protection , Earthing systems and surge arresters Location : Jnah - Beirut

ELECTRICALWORKS

Item Description Qty Unit Unit Amount


Rate US.$

EARTHING SYSTEM:

Supply and installation of complete earthing system


consisting of earth rods in the outer garder connected
to the existing earth system through an external
manhole with 70m2 stranded copper cables. System to
be complete with all necessary accessories to obtain low
connecting earth resistance less than 3 ohms. System to
be as manufactured by Wallis , Furse or equivalent.

A Copper earth rod 240cm with 20mm diameter with clamps


4 U

B Earth pit 40x40x40cm with cover. Cover to support weight


1 U
of 2tons.

C Stranded copper cable 70mm2 for the connection between


1 LS
the earth rods and the electrical room
D Earth bus bars with 8 terminals for electrical room, Server
5 U
room , UPS Room , top of roof and generators room.

E Earth bus bars with 6 terminals in each floor for data


12 LS
cabinets , SDB and UPS panel

F Earth bus bars with 6 terminals for the exit stairs in each
10 LS
floor

G PVC Green/Yellow cable 35mm2 for the earth


distributions between the main bus bars and the secondary 1 LS
bus bars
H PVC Green/Yellow cable 16mm2 for the connections
1 LS
between the secondary bus bars and the surge arresters
ELECTRICALWORKS

Item Description Qty Unit Unit Amount


Rate US.$

LIGHTNING PROTECTION SYSTEM:

Supply and install a complete set of lightning


protection system as per french norm NFC 17 102
including all the necessary fittings and fixing
accessories
A Early streamer Emission with minimum radius 35m at
level 1 including the necessary accessories 1 U

B Two down conductors PVC copper tape 25x3mm with


clamps each 33cm 1 LS.

C Test link 2 U

D Counter 1 U
E Mechanical protection of down conductor 2 U

F Earthing system should be independent from electrical


earth, and preferably embedded
using earth plates and mixture enhancer for preservation of
humidity 1 LS.

J Mast should be minimum 10m with fixation 1 U

SURGE PROTECTION.

The Surge arresters role is to protect the electrical devices form


the indirect strikes

Phase 1:

MDB Surge arrester 3 phases class B+C ( ATS output in


A electrical room)
1 U

Surge arrester 3 phases class B+C ( EDL lines in electrical


B room)
1 U

Surge arrester 3 phases class B+C ( Generators lines in


C electrical room)
1 U

D Surge arrester 3 phases class B+C ( Inside the Generators ) 3 U

E Microwave link Class D surge arrester 2 U

F Telephone line arrester classs D 1 LS.


ELECTRICALWORKS

Item Description Qty Unit Unit Amount


Rate US.$
Phase 2:

SDB Surge arrester 3 phases class B+C ( Main breaker at each


A floor)
1 LS.

UPS Panel Surge arrester 3 phases class C ( Main breaker at


B each floor)
1 LS.

C Multiple socket class D ( In the cabinets at each floor ) 1 LS.

UPS Room surge arresters 3 phases class B+C ( Input and


D output of the UPS)
1 LS.

Summary TOTAL U.S. $

TOTAL AMOUNT