The document outlines the solution for a Single Line-to-Ground (SLG) fault at Bus A, detailing base values and per-unit system calculations for various components including cables, transformers, and a generator. It presents fault current calculations under different neutral conditions: isolated, solidly grounded, and a specific impedance value, resulting in fault currents of 0 A, 2.91 kA, and 1.26 kA respectively. A summary table consolidates the results for easy reference.

Uploaded by

kumlachewubruk94
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
24 views2 pages

SLG Fault Analysis Fixed

The document outlines the solution for a Single Line-to-Ground (SLG) fault at Bus A, detailing base values and per-unit system calculations for various components including cables, transformers, and a generator. It presents fault current calculations under different neutral conditions: isolated, solidly grounded, and a specific impedance value, resulting in fault currents of 0 A, 2.91 kA, and 1.26 kA respectively. A summary table consolidates the results for easy reference.

Uploaded by

kumlachewubruk94
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Solution for Single Line-to-Ground (SLG) Fault at Bus A

1. Base Values and Per-Unit System


------------------------------------
- Base Power (Sb): 100 MVA
- Base Voltage (Vb): 110 kV
- Base Impedance (Zb): Zb = (Vb^2) / Sb = (110 x 10^3)^2 / (100 x 10^6) = 121
Ohm

2. Per-Unit Impedances
----------------------
Cables (10 km):
- Positive/Negative Sequence:
Z1 = Z2 = j0.12 Ohm/km x 10 km = j1.2 Ohm -> j1.2 / 121 = j0.0099 pu
- Zero Sequence:
Z0 = j0.18 Ohm/km x 10 km = j1.8 Ohm -> j1.8 / 121 = j0.0149 pu

Transformer Tr1 (160 MVA):


- Positive Sequence:
Z1_Tr1 = 14.2 percent * (100 / 160) = j0.0888 pu
- Zero Sequence:
Z0_Tr1 = 6.7 percent * (100 / 160) = j0.0419 pu

Transformer Tr2 (60 MVA):


- Positive/Zero Sequence:
Z1_Tr2 = Z0_Tr2 = 14.5 percent * (100 / 60) = j0.2417 pu

Generator (60 MVA):


- Subtransient Reactance:
Xd'' = 0.2 * (100 / 60) = j0.3333 pu
- Zero Sequence (Estimated):
X0 approx 0.5Xd'' = j0.1667 pu

System (Infinite Bus, Ssc = 4500 MVA):


- Positive/Negative Sequence:
Z1 = Z2 = (100 / 4500) = j0.0222 pu
- Zero Sequence:
Z0 = Infinity

3. Fault Current Calculations


------------------------------
Case (a): Xn to Infinity (Isolated Neutral)
- Zero-sequence path is open (Z0 to Infinity):
If = 0 A

Case (b): Xn = 0 (Solidly Grounded)


- Zero-sequence impedance: Z0 = j0.2985 pu
- Fault current: If = -j5.55 pu
- If = 2.91 kA

Case (c): Xn = 45.65 Ohm


- If = 1.26 kA

Summary of Results:
| Case | Neutral Condition | Fault Current (If) |
|------|-------------------|-------------------|
| (a) | Isolated |0A |
| (b) | Solidly grounded | 2.91 kA |
| (c) | Xn = 45.65 Ohm | 1.26 kA |