The DeltaV whitepaper discusses a technique for reducing controller loading in boiler control systems by replacing Sequential Function Charts (SFCs) with function blocks. It outlines the advantages and disadvantages of both SFCs and function blocks, emphasizing that function blocks can lead to lower processor consumption. The paper provides a case study on a wood waste boiler project, demonstrating the successful implementation of function blocks for improved control efficiency.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
38 views19 pages

Deltav Loading Reduction For Sequential

The DeltaV whitepaper discusses a technique for reducing controller loading in boiler control systems by replacing Sequential Function Charts (SFCs) with function blocks. It outlines the advantages and disadvantages of both SFCs and function blocks, emphasizing that function blocks can lead to lower processor consumption. The paper provides a case study on a wood waste boiler project, demonstrating the successful implementation of function blocks for improved control efficiency.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 19

DeltaV Whitepaper

August 2010 – Page 1 Loading Reduction for Sequential Logic

DCS Cont rolle r Loa ding Re duc t ion for


Se que nc e Logic - A Boile r Cont rol
Proje c t Ca se St udy
A technique was developed for programming DeltaV systems for boiler control that replaces SFCs with function
blocks and may result in lower controller loading.

www.EmersonProcess.com/DeltaV
DeltaV Whitepaper
August 2010 – Page 2 Loading Reduction for Sequential Logic
Table of Contents

Introduction.............................................................................................................................. 3

Sequential Function Charts .................................................................................................... 3

Advantages of SFCs ............................................................................................................ 4

Disadvantages of SFCs........................................................................................................ 4

Where SFCs are appropriate ............................................................................................... 4

Function Blocks ....................................................................................................................... 4

Advantages of Function Blocks ............................................................................................ 4

Disadvantages of Function Blocks ....................................................................................... 4

Types of function blocks ....................................................................................................... 4

Description of BoP Implementation ....................................................................................... 8

BoP Performance Results .................................................................................................. 10

SWOT Analysis toward using BoP Modules on Projects .................................................... 11

Summary ................................................................................................................................ 12

For further reading.............................................................................................................. 12

Figures.................................................................................................................................... 13

Author, Contributors, and References................................................................................. 19

www.EmersonProcess.com/DeltaV
DeltaV Whitepaper
August 2010 – Page 3 Loading Reduction for Sequential Logic

Introduction
For many years the sequential control tasks in DCS and PLC control system programming have been handled
using Sequential Function Charts (SFCs, defined in IEC 848). In DeltaV, for example, phase modules are
generally set up using SFCs. These, which contain built in features derived from ISA S88, are often used in
equipment modules. Phase classes have state transition diagram logic built in.

Yet while they make for convenient and easy-to-understand programming, often SFC implementations have a
serious drawback: low free processor time in the controller(s) that contain the running SFC logic. However, if a
higher scan time is used to use less free memory, the control logic may not execute fast enough to meet process
requirements. This gives engineers unpleasant choices: put up with the low free time, create alternative control
implementations (e.g. increase scan times or change the location of multiple modules), or purchase more
computing power. Of course there are a few tricks available — in one case the fix was to use a CALC block — but
that is abstract and makes troubleshooting more difficult for the customer.

A technique was developed for programming DeltaV systems for boiler control that replaces SFCs with function
blocks and may result in lower overall processor consumption. This white paper will explain how this is done,
using as an example a wood waste boiler project that used standard DeltaV function block tools in Control Studio
to satisfy the sequence requirements outside the boiler combustion controls and flame safety system (hereafter
referred to as the Balance of Plant or BoP module). This made the BoP module fit well with the common practice
of using only function blocks in boiler controls.

Sequential Function Charts


A sequential function chart consists of a series of steps linked by transitions. A step is essentially a state of the
system, and can be active or inactive (idle); the initial step is always active at start-up. Some steps have actions
associated with them (open a valve, close a gate, etc.) that will be performed only if the step is active. Fig. 1
shows a simple linear SFC in generalized form, while Fig. 2 shows a specific application (note that in some SFC
representations a transition is shown as a single heavy line segment, rather than the way it is shown here).

A transition is enabled when the step preceding it is active and the logical condition(s) for the transition are
satisfied. When a transition is enabled the step preceding it becomes idle and the one following it becomes active.

It is possible for a single step to branch to two transitions (Fig. 3) by using a sequence select divergence, or for
two transitions to lead to one step (Fig. 4) using a sequence select convergence. A single transition can lead to
two simultaneous, or parallel, sequences by using a parallel divergence, as shown in Fig. 5.

In DeltaV programming, SFCs are deployed in phase modules, which contain built in features derived from ISA
S88, and are often used in equipment modules.

www.EmersonProcess.com/DeltaV
DeltaV Whitepaper
August 2010 – Page 4 Loading Reduction for Sequential Logic
Advantages of SFCs
Sequential function charts have a number of advantages. First of all, they are easy to understand, because they
clearly and simply represent the steps of the process. They work well for high-level programming of control
1
sequences. They are familiar to many people, because SFC is one of the languages specified in IEC 61131-3 , i

and they are frequently used in programming PLCs. And SFCs are self-documenting and easy to troubleshoot
and debug.

Disadvantages of SFCs
While SFCs are very useful in PLC programming, when used in a DCS they have several drawbacks. For one
thing, in DeltaV applications an SFC can cause low free processor time in the controllers that contain the running
SFC logic. Also, the effects of running multiple SFCs at a time need to be taken into account, especially with
cases of using one controller for independent sequences or if recipe(s) may be executed.

Despite its seeming simplicity, an SFC requires a program structure that is not suitable for every application. Also,
the effects of running multiple SFCs at a time need to be taken into account, especially in cases of using one
controller for independent sequences or if recipe(s) may be executed.

Finally, it can take considerable preparation and planning before program writing can begin, and an SFC cannot
2
be converted automatically to other languages, although a method has been developed for converting SFCs to
ii

ladder diagrams (suitable for PLCs but not really applicable to DCSs).

Where SFCs are appropriate


SFCs are most useful in cases where equipment operation follows a definite sequence, where equipment
operation is most easily understood as a series of states of operation, and where it’s important for other people to
be able to understand the programming quickly and easily.

Function Blocks
Function blocks, which are defined by IEC 61499, cover a broad range of applications. They are traditionally used
for continuous control, but work quite well for discrete control, which is how they are used in the example
presented in this paper.

Advantages of Function Blocks


Function blocks are easy to use, help reduce training requirements, allow reuse of programming elements, and
3
help to reduce downtime . And, as pointed out in the rest of this paper, they can also reduce processor loading
iii

compared to SFCs.

Disadvantages of Function Blocks


The main disadvantage cited for function blocks is that they cannot capture all the different aspects of today’s
4
distributed control applications .

Types of function blocks


Each function block contains standard process control algorithms (which can range from simple input conversions
to complex control strategies) and parameters that customize the algorithm. A function blocks uses parameter
data supplied by the user, by the function block itself, or by other function blocks to perform its calculations and

www.EmersonProcess.com/DeltaV
DeltaV Whitepaper
August 2010 – Page 5 Loading Reduction for Sequential Logic
logic functions and to supply an output value to other function blocks or to field devices. Some function blocks
also detect alarm conditions. The function blocks used in DeltaV systems are grouped into six categories:

 Input/Output (I/O) Blocks — Scale, convert, and filter input and output signals for use in other function
blocks or field devices

 Math Blocks — Perform mathematical functions for conversion, integration, and totalizing

 Timer/Counter Blocks — Perform timing and counting functions for control and sequencing

 Logical Blocks — Perform logic functions for sequencing, scheduling, and interlocking

 Analog Control Blocks — Perform simple and complex algorithms for comprehensive analog control

 Energy Metering Blocks — Perform mathematical flow calculations for natural gases, steam, and other
fluids

 Advanced Control Blocks — Perform complex algorithms for advanced process control

In this white paper we will limit the discussion of function blocks to the main ones deployed in the BoP module in
the boiler example, all of which are classified as Logical Blocks. These include the Condition (CND) Function
Block, Device Control (DC) Function Block, and Action (ACT) Function Block. The Boolean Fan Input (BFI) and
OR (OR) Function Blocks are also used.

Condition Function Block

The CND block (Fig. 6) is used to confirm a condition as a prerequisite for further control system actions. In the
case of the BoP module, CND blocks will confirm that sequence actions have completed, like transition
confirmations in SFCs. If the CND belongs to an inactive sequence, the DISABLE parameter is set to true. Also,
the timer function can be used to delay the next action from executing.

OUT_D is the discrete output value and status.

Parameters of the CND function block are shown in Table 1.

Table 1: Parameters of the CND Function Block

Parameter Units Description


ALGO_OPTS None Algorithm options. When selected, the expression algorithm will abort after a
read error. The Algorithm option is AbortOnReadErrors. When the Condition
block expression aborts, the value and status of PRE_OUT_D and OUT_D
remain unchanged.
BLOCK_ERR None The summary of active error conditions associated with the block. The block
error for the Condition function block is:
• Configuration Error - The expression is empty

www.EmersonProcess.com/DeltaV
DeltaV Whitepaper
August 2010 – Page 6 Loading Reduction for Sequential Logic
Parameter Units Description
ERROR_OPT None Specifies how the block behaves when a read error occurs. The value of
PRE_OUT_D will be False (default), True, or the last value prior to the read
error as defined in ERROR_OPT (unless 'Abort on Read Errors' is set in
ALGO_OPTS, in which case ERROR_OPT does not apply). The status of
PRE_OUT_D is BadNoComm when a read error occurs.
DESC None User-specified description of the expression.
DISABLE None Enables/disables the block logic (True = disable, False = enable).
OUT_D None The discrete output value and status.
PRE_OUT_D None The internal value set when the expression evaluates to True for the period
defined by TIME_DURATION. PRE_OUT_D ignores the DISABLE value.
TIME_DURATION Seconds Specifies the time the expression must be True to set OUT_D.
TIMER Seconds The time the expression is True.

Device Control Function Block

The DC block (Fig. 7) is traditionally used to interpret a device state via discrete input(s), and set discrete
output(s) in accordance with a setpoint value. The block compares the requested state (setpoint) to the actual
state reported from the device and, after allowing time for the device to change state, detects alarm limits on any
error. The basic functionality is augmented by an assortment of interlocks and device control options to customize
the block's operation for a particular application.

The DC block supports mode control, setpoint tracking, simulation, and alarm limit detection. Options are
available to specify the control strategy used in the block.

The setpoint requests the device to go to one of two or three supported states: Passive, Active 1 and Active 2
(optional). The Passive state is the power failure (safe) state, such as OFF or CLOSED. An Active state usually
requires energy (or allows energy to flow), such as OPEN, RUN, FORWARD, or REVERSE or OFF/LOW/HIGH.

The DC block uses as many as eight discrete I/O channels to command a device to the requested setpoint state
and to read back its confirmation contacts. Discrete I/O is associated with the Passive and Active states by means
of a mask for each state that allows each bit to be defined as True (1), False (0), or not used. The user can
configure four bits as outputs to the device and four bits as the contacts that confirm the device state. The confirm
contacts must be maintained because the block is designed to alarm on loss of confirmation.

The DC block supports two modes: Automatic (Auto) and Cascade (Cas). Note that the Cas mode is not to be
confused with CAS_IN_D, which is the discrete value and status of a setpoint from another block used when the
block is in Cascade mode.

www.EmersonProcess.com/DeltaV
DeltaV Whitepaper
August 2010 – Page 7 Loading Reduction for Sequential Logic
In the BoP module, the DC block is used for interface, permissive, and interlock support with no physical discrete
I/O. The DC block is used in combination with the standard DeltaV faceplate DL_fp to allow the operator to
change the sequence setpoint value and get feedback confirmation of the sequence status. And because the DC
block supports the Auto and Cas modes, and DL_fp enables and disables the setpoint push buttons in Auto and
Cas respectively, the operators are guided to not inadvertently stop a sequence. Table 2 shows a matrix used to
determine the sequence’s state:

Table 2: BoP Assessment of Status (two-state DC block)

DC Block Mode DC Block Feedback BoP Sequence State


Cas RUNNING Currently in a startup sequence
Cas STOPPED Currently in a shutdown sequence
Auto RUNNING Finished the startup sequence, in normal operation
Auto STOPPED Finished the shutdown sequence, in idle state

The DC Block Feedback value above is calculated based on the input(s) that go to the DC block, then the DC
block displays if it is in the Active or Passive state. In the BoP case, the control module logically creates the input
signals based on the actions in the ENABLE_START and ENABLE_STOP Action blocks, which are triggered by
the START_ENABLED and STOP_ENABLED CND blocks respectively. The blocks are shown in Figure 11 and
the expressions are shown in Table 3.

Action Function Block

The ACT block (Fig. 8) is used to complete an action expression, which usually involves writing a value to a
parameter. In the case of the BoP module, ACT blocks will contain sequence actions and can be analogous to
step actions in SFCs.

IN_D is the discrete input value and status that initiates expression evaluation.

Boolean Fan Input Function Block

The BFI block (Fig. 9) generates a discrete output based on the weighted binary sum, binary coded decimal
(BCD) representation, transition state, or logical OR of one to sixteen discrete inputs. The block supports signal
status propagation. It includes no modes or alarm detection.

Inputs and outputs are as follows:

 RESET_IN, when True (1), clears FIRST_OUT.

 IN_D1 through IN_Dn are the discrete input values and statuses (as many as 16 inputs).

 OUT_INT is the unsigned 32-bit binary weighted output value that represents the bit combination of the inputs
(IN_Dn).

 OUT_D is the output value that represents the logical OR of the inputs (IN_Dn).

www.EmersonProcess.com/DeltaV
DeltaV Whitepaper
August 2010 – Page 8 Loading Reduction for Sequential Logic
 FIRST_OUT is the binary weighted output that represents the bit combination of the discrete input value or
values (IN_Dn) that are set when OUT_INT transitions from zero to non-zero and while ARM_TRAP is non-
zero.

OR Function Block

The OR function block (Fig. 10) generates a discrete output value based on the logical OR of two to sixteen
discrete inputs. When one or more of the inputs is True (1), the output is set to True. The block supports signal
status propagation. It includes no modes or alarm detection.

IN_D1 through IN_D[n] are the discrete input values and statuses (as many as 16 inputs).

OUT_D is the discrete output value and status.

Description of BoP Implementation


The BoP module is broken into two main sections: the Sequence Control Initiation area shown in Fig. 11 and the
Control Sequence Operation and Shutdown area shown in Fig. 12. The sections intend to clearly delineate where
the sequence setpoint is determined and where the sequence actions and confirmations are in order to provide
for better troubleshooting. We will focus on the B1_LIMEINJ_CNTL module for the description of the specific
implementation.

Table 3: Configuration of Select Parameters in B1_LIMEINJ_CNTL

Name Configuration
B1_LIMEINJ_CNTL Module Scan Rate: 1 sec
Faceplate Display: DL_fp
Detail Display: DL_dt8
Parameter Download Behavior: Use configured values
DC1 DEVICE_OPTS: Permissive, SP Track, Interlock checked
DC_STATE Named Set: states_mtr2
FV_D and PV_D Named Set: mtr2-pv
SP_D Named Set: mtr2-sp
STATE_MASKS: Active 1, Input 1 and Active 1, Output 1 checked
START_ENABLED ('^/DC1/PERMISSIVE_D.CV' = 1) AND
('^/DC1/SP_D.CV' = 'mtr2-sp:START') AND
('^/START_FLAG.CV' = FALSE)

www.EmersonProcess.com/DeltaV
DeltaV Whitepaper
August 2010 – Page 9 Loading Reduction for Sequential Logic
Name Configuration
ENABLE_START '^/START_FLAG.CV' := TRUE;
'^/DC1/MODE.TARGET' := CAS;
'^/CAS_IN_D.CV' := 1;
'^/DC1/F_IN_D1.CV' := 1;
'^/ESHTDWN_CONFIRM1/DISABLE.CV' := 1;
'^/CSHTDWN_CONFIRM1/DISABLE.CV' := 1;
'^/CSHTDWN_CONFIRM2/DISABLE.CV' := 1;
'^/CSHTDWN_CONFIRM3/DISABLE.CV' := 1;
'^/STOP_ENABLED/DISABLE.CV' := 0;
'^/START_ENABLED/DISABLE.CV' := 1
STOP_ENABLED (('^/DC1/INTERLOCK_D.CV' = 0) OR
('^/DC1/SP_D.CV' = 'mtr2-sp:STOP')) AND
('^/START_FLAG.CV' = TRUE)
ENABLE_STOP '^/START_FLAG.CV' := FALSE;
'^/DC1/MODE.TARGET' := CAS;
'^/CAS_IN_D.CV' := 0;
'^/DC1/F_IN_D1.CV' := 0;
'^/START_CONFIRM1/DISABLE.CV' := 1;
'^/START_CONFIRM2/DISABLE.CV' := 1;
'^/START_CONFIRM3/DISABLE.CV' := 1;
'^/START_ENABLED/DISABLE.CV' := 0;
'^/STOP_ENABLED/DISABLE.CV' := 1
START_STOP '^/DC1/DC_STATE.CV' = 'states_mtr2:Confirmed Running'
START_ACTION4 '^/DC1/MODE.TARGET' := AUTO;
START_MESSAGE := LOGEVENT("Limestone Injection Startup Complete");
'^/START_CONFIRM1/DISABLE.CV' := 1;
'^/START_CONFIRM2/DISABLE.CV' := 1;
'^/START_CONFIRM3/DISABLE.CV' := 1

The Sequence Control Initiation area comprises a motor control template with the added function blocks
START_ENABLED, ENABLE_START, STOP ENABLED, and ENABLE_STOP to handle DC1 initial mode
changing to CAS; DC1 feedback status of RUNNING or STOPPED; and initialization of the sequence CND
function blocks.

www.EmersonProcess.com/DeltaV
DeltaV Whitepaper
August 2010 – Page 10 Loading Reduction for Sequential Logic
The Control Sequence Operation and Shutdown area comprises the START_STOP block linked to the DC block
running status; it starts a startup or shutdown sequence based on a positive edge trigger output and negative
edge trigger output respectively. Then a progression of ACT blocks and CND blocks implement the sequence
actions and confirmations. Note that in the case of the BoP modules created in this project positive edge triggers
were used between the CND and ACT function blocks. The last ACT block of the sequence would then set the
DC1 block to AUTO mode and disable the CND blocks of the sequence. An implementation might instead use
expressions in each ACT block to disable the previous CND block. As a result, the implementation would be more
analogous to SFCs and positive edge triggers wouldn’t be needed.

As a way to make normal sequence troubleshooting easier when using the BoP module, the BoP implementer
may choose to create top level Input Parameters in the BoP module and connect them to the respective
sequence CND blocks’ DISABLE parameters via Internal References. As a result, a BoP sequence troubleshooter
will be able to easily see the DISABLE value of the CND blocks at the top level of the BoP CM rather than having
to click on each CND block individually.

What’s believed to be unique is the combination of the two areas that can handle failure detection (through the
use of interlock and permissive functions of the DC block), using a standard interface of DL_fp, the connection
between the two areas, and the sequence logic contained in a top-down format that’s easy to read in comparison
to a single CALC block with the action and confirmation expressions.

BoP Performance Results


The BoP module was originally created to avoid SFCs, which may or may not have merit depending on the end
user requirements. What may have more value are the possible benefits to processor free time and sequence
execution performance.

The BoP module may take up less space in DeltaV Controllers compared to traditional SFC implementation (i.e.
command driven EM, phase). This effect is perhaps due to the smaller amount of background logic associated
with SFCs vs. CND/ACT/DC function blocks, all of which need to be loaded on the controller at the beginning of
the sequence regardless. As a result, the smaller amount of loading allows the memory to be used for essential
communication between the controller and other computers on the DeltaV network, and decreases the risk of
getting into a situation of adding another controller and changing control logic configuration.

A direct comparison study of the BoP module and a corresponding SFC implementation has not been completed.
Instead, performance data of a controller (B1_FH) with 22 conveyance motors, 129 control modules, and four
BoP modules has been collected. The significance of this example is:

Conveyance applications are traditionally covered by PLCs.

The control logic and function block number of the BoP modules is significant and comparable to a medium sized
process.

The testing was done with DeltaV version 9.3.1.5251.xr and a MDPlus controller with hardware revision 5.50. The
results may vary if any sequence is running. Also, the CAT completed with the B1_FH control modules executing
at one second scan rates.

www.EmersonProcess.com/DeltaV
DeltaV Whitepaper
August 2010 – Page 11 Loading Reduction for Sequential Logic
Table 4: Free Time vs. Scan Rate for BoP Modules

Scan Rate (ms) Free Time (%)


100 53
200 73
500 86
1000 89
2000 91

If the B1_FH BoP modules and the motor control modules were to execute at 200 ms, the processor free time
would decrease to 21-23%, which is generally considered a borderline acceptable free time. The result shows that
the performance approaches PLC scan rates with complex sequencing requirements.

SWOT Analysis toward using BoP Modules on Projects


To illustrate a qualitative evaluation of the potential end state of using BoP modules below is a Strengths,
Weaknesses, Opportunities, Threats (SWOT) Analysis:

Strengths Weaknesses
Easy implementation learning curve due to use of Programming is more complex, potentially resulting
well known function blocks in DeltaV. in longer project timelines and cost.
May have a competitive edge against traditional SX/MX controller may make solution less appealing
PLC applications. or unneeded.
May allow for standardization on engineering Function block approach deviates from increasing
training and expertise to function blocks alone usage of SFCs (e.g. SYNCADE with recipe
depending on industry. authoring).
Presentation not as straightforward as SFCs.

Opportunities Threats
Allows for better control system integrity, Potentially uses more controller memory compared
especially for controllers with multiple, to a SFC if multiple sequences are always executed
independent sequences. on a single controller with no overlap.
Graphical interface is identical to that of a motor, Users may view implementation as foreign
allowing for faster Operator training on interface. depending on background with DeltaV.
Potentially uses less controller memory compared
to a SFC for multiple, overlapping sequences

www.EmersonProcess.com/DeltaV
DeltaV Whitepaper
August 2010 – Page 12 Loading Reduction for Sequential Logic
Summary
The application of using the standards developed for the BoP module to possibly increase controller free times
and the rate of sequence execution is being proposed.

We believe the most favorable use of this type of module is with controllers that require fast scan times on
multiple units/independent sequences running on a single controller. However, there are numerous
implementation disadvantages to the widespread use of this type of module. Actions may be done within the
DeltaV software to streamline programming and make the presentation easier for Emerson integrators to interpret
and configure. Also, further research needs to be conducted to determine if the hardware benefits with using this
approach are worthwhile. Nevertheless, the BoP module has proved to be a robust method for the sequencing
requirements found in the wood waste boiler project (i.e. nine Functional Descriptions involving different UO), and
the controllers used on the project have good free processor times. As a result, the BoP module should be
successful for select applications/projects with sequencing requirements and should help to reach the end goal of
getting projects completed on time; on budget; and within quality specifications.

For further reading


More information on DeltaV configuration and other topics can be found at
http://www.easydeltav.com/BOL/MasterBOL.htm. A non-javascript version is at
http://www.easydeltav.com/bol/whnjs.htm. Also see http://www.easydeltav.com/bol/MasterBOL.htm.

For more information on IEC 61499, see http://knol.google.com/k/iec-61499#.

www.EmersonProcess.com/DeltaV
DeltaV Whitepaper
August 2010 – Page 13 Loading Reduction for Sequential Logic
Figures

Figure 1: Linear SFC

Figure 2: SFC Application

www.EmersonProcess.com/DeltaV
DeltaV Whitepaper
August 2010 – Page 14 Loading Reduction for Sequential Logic

Figure 3: Sequence Select Divergence

Figure 4: Sequence Select Convergence

Figure 5: Parallel Divergence

www.EmersonProcess.com/DeltaV
DeltaV Whitepaper
August 2010 – Page 15 Loading Reduction for Sequential Logic

Figure 6: Condition Function Block

Figure 7: Device Control Function Block

Figure 8: Action Function Block

www.EmersonProcess.com/DeltaV
DeltaV Whitepaper
August 2010 – Page 16 Loading Reduction for Sequential Logic

Figure 9: Boolean Fan Input Function Block

Figure 10: OR Function Block

www.EmersonProcess.com/DeltaV
DeltaV Whitepaper
August 2010 – Page 17 Loading Reduction for Sequential Logic

Figure 11: BoP Sequence Control Initiation Area

www.EmersonProcess.com/DeltaV
DeltaV Whitepaper
August 2010 – Page 18 Loading Reduction for Sequential Logic

Figure 12: BoP Control Sequence Operation and Shutdown Area

www.EmersonProcess.com/DeltaV
DeltaV Whitepaper
August 2010 – Page 19 Loading Reduction for Sequential Logic
Author, Contributors, and References

By Shawn Zadeh, Process Automation Engineer, Emerson Process Management

The following people contributed to development of the BoP Module:


Mark Durica, Sr. Principal Engineer, Emerson Process Management
Barbara Hamilton, Industrial Energy Consultant, Emerson Process Management

1
Ted Thayer, “Speaking in Tongues: Understanding the IEC 61131-3 Programming Languages,” Control
Engineering, January, 2009
2
Eric Anderson, white paper: “Sequential Function Chart to PLC Ladder Logic Translation”, DMC Corp.
(http://www.dmcinfo.com/Portals/0/State%20Transition%20Diagram%20to%20PLC%20Ladder%20Logic%20Tran
slation%20Whitepaper.pdf), Sept 8, 2009.
3
Rob Spiegel, “Quick & Simple PLC Programming”, Automation World, April 2006 p.43
4
Kleanthis Thramboulidis, “Design Alternatives in the IEC 61499 Function Block Model”, IEEE Int. Conf. on
Emerging Technologies and Factory Automation, (ETFA’06), Sept 2006.

To locate a sales office near you, visit our website at: For large power, water, and wastewater applications
www.EmersonProcess.com/DeltaV contact Power and Water Solutions at:
Or call us at: www.EmersonProcess-powerwater.com
Asia Pacific: 65.777.8211 Or call us at:
Europe, Middle East: 41.41.768.6111 Asia Pacific: 65.777.8211
North America, Latin America: +1 800.833.8314 or Europe, Middle East, Africa: 48.22.630.2443
+1 512.832.3774 North America, Latin America: +1 412.963.4000

© Emerson Process Management 2010. All rights reserved. For Emerson Process Management trademarks and service marks, go to:
http://www.emersonprocess.com/home/news/resources/marks.pdf.

The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be
construed as warrantees or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed
by our terms and conditions, which are available on request. We reserve the right to modify or improve the design or specification of such products at any time
without notice.

www.EmersonProcess.com/DeltaV