FP0 Hardware
FP0 Hardware
Hardware Manual
PROGRAMMABLE CONTROLLER
FP0
Hardware Manual
Matsushita Electric Works, Ltd.
ACGM0084END V3.4 5/2001
LIMITED WARRANTY
If physical defects caused by distribution are found, Matsushita Electric Works, Ltd.,
will replace/repair the product free of charge. Exceptions include:
Installation
environment
Do not use the unit where it will be exposed to the following:
D Direct sunlight and ambient temperatures
outside the range of 0_C to 55_C/32_F to
131_F.
D Ambient humidity outside the range of 30% to
85% RH and sudden temperature changes
causing condensation.
D Inflammable or corrosive gas.
D Excessive vibration or shock.
D Excessive airborne dust or metal particles.
D Water in any form including spray or mist.
D Benzine, paint thinner, alcohol or other
organic solvents or strong alkaline solutions
such as ammonia or caustic soda.
D Influence from power transmission lines, high
voltage equipment, power cables, power
equipment, radio transmitters, or any other
equipment that would generate high switching
surges.
Static electricity
D In dry locations, excessive static electricity
can cause problems. Before touching the unit,
always touch a grounded piece of metal in
order to discharge static electricity.
Cleaning
D Do not use thinner–based cleaners because
they deform the unit case and cause the
colors to fade.
Power supplies
D An insulated power supply with an internal
protective circuit should be used. The power
supply for the FP0 control unit operation is a
non-insulated circuit, so if an incorrect
voltage is directly applied, the internal circuit
may be damaged or destroyed. If using a
power supply without a protective circuit,
power should be supplied through a
protective element such as a fuse.
Power supply
sequence
D Have the power supply sequence such that
the power supply of the FP0 control unit turns
OFF before the power supply for I/O.
D If the power supply for I/O is turned OFF
before the power supply of FP0 control unit,
the FP0 control unit will detect the input
fluctuations and may begin an unscheduled
operation.
Before turning
ON the power
When turning ON the power for the first time, be sure to take the
precautions given below.
D When carrying out assembly, check to make
sure that there are no scraps of wiring,
particularly conductive fragments, adhering to
the unit.
D Verify that the power supply wiring, I/O wiring,
and power supply voltage are all correct.
D Sufficiently tighten the installation screws and
terminal screws.
D Set the mode switch to PROG. mode.
Important Symbols
The following symbols are used in this manual:
Example:
Contains an illustrative example of the previous text section.
next page
Indicates that the text will be continued on the next page.
Table of Contents
Chapter 1 Overview
Chapter 8 Installation
Chapter 9 Wiring
Appendix D Dimensions
Index
Record of Changes
Overview
Overview FP0 Hardware
Terminal type
10 points with 14 points with
10 points 14 points RS232C port
RS232C
( Input:
Relay output: 4 )
6
( Input:
Relay output: 6 )
8
MIL type
( Input:
Transistor output: 8 )
8
(Input:
Transistor output: 8 )
8
( Input: 16
Transistor output: 16 )
( Input:
Transistor output: 16 )
16
8 points 16 points
( Input:
Relay output: 4 )
4
( Input:
Relay output: 8 )
8
FP0-E8RS FP0-E16RS
MIL type
16 points 32 points
(Input:
Transistor output: 8 )
8
(Input:
Transistor output: 16 )
16
8 inputs 16 inputs
FP0-E8X FP0-E16X
FP0-A21
The FP0 I/O Link Unit works as the slave station of a remote I/O system. The FP0 I/O
Link Unit exchanges I/O information with the master unit.
FP0–IOL
OUTPUT
+
+
+
–
–
–
INPUT
FP0–PSA2
FP0–PSA2
Notes
A maximum of three expansion I/O units, analog I/O units, or
I/O link units can be connected to one control unit.
Control unit First Second Third
(CPU) expansion unit expansion unit expansion unit
14 14
Input: 8 Output: 6 = Input: 8 Output: 6
18 10 + 8
Input: 10 Output: 8 = Input: 6 Output: 4 Input: 4 Output: 4
22 14 + 8
Input: 12 Output: 10 = Input: 8 Output: 6 Input: 4 Output: 4
26 10 + 16
Input: 14 Output: 12 = Input: 6 Output: 4 Input: 8 Output: 8
= 10 + 8 + 8
Input: 6 Output: 4 Input: 4 Output: 4 Input: 4 Output: 4
30 14 + 16
Input: 16 Output: 14 = Input: 8 Output: 6 Input: 8 Output: 8
= 14 + 8 + 8
Input: 8 Output: 6 Input: 4 Output: 4 Input: 4 Output: 4
34 10 + 16 + 8
Input: 18 Output: 16 = Input: 6 Output: 4 Input: 8 Output: 8 Input: 4 Output: 4
10 + 8 + 8 + 8
= Input: 6 Output: 4 Input: 4 Output: 4 Input: 4 Output: 4 Input: 4 Output: 4
38 14 + 16 + 8
Input: 20 Output: 18 = Input: 8 Output: 6 Input: 8 Output: 8 Input: 4 Output: 4
= 14 + 8 + 8 + 8
Input: 8 Output: 6 Input: 4 Output: 4 Input: 4 Output: 4 Input: 4 Output: 4
42 10 + 16 + 16
Input: 22 Output: 20 = Input: 6 Output: 4 Input: 8 Output: 8 Input: 8 Output: 8
= 10 + 16 + 8 + 8
Input: 6 Output: 4 Input: 8 Output: 8 Input: 4 Output: 4 Input: 4 Output: 4
46 14 + 16 + 16
Input: 24 Output: 22 = Input: 8 Output: 6 Input: 8 Output: 8 Input: 8 Output: 8
= 14 + 16 + 8 + 8
Input: 8 Output: 6 Input: 8 Output: 8 Input: 4 Output: 4 Input: 4 Output: 4
50 10 + 16 + 16 + 8
Input: 26 Output: 24 = Input: 6 Output: 4 Input: 8 Output: 8 Input: 8 Output: 8 Input: 4 Output: 4
54 14 + 16 + 16 + 8
Input: 28 Output: 26 = Input: 8 Output: 6 Input: 8 Output: 8 Input: 8 Output: 8 Input: 4 Output: 4
58 10 + 16 + 16 + 16
Input: 30 Output: 28 = Input: 6 Output: 4 Input: 8 Output: 8 Input: 8 Output: 8 Input: 8 Output: 8
62 14 + 16 + 16 + 16
Input: 32 Output: 30 = Input: 8 Output: 6 Input: 8 Output: 8 Input: 8 Output: 8 Input: 8 Output: 8
32 32
Input: 16 Output: 16 = Input: 16 Output: 16
16 + 16
= Input: 8 Output: 8 Input: 8 Output: 8
48 32 + 16
Input: 24 Output: 24 = Input: 16 Output: 16 Input: 8 Output: 8
16 + 32
= Input: 8 Output: 8 Input: 16 Output: 16
16 + 16 + 16
= Input: 8 Output: 8 Input: 8 Output: 8 Input: 8 Output: 8
64 32 + 32
Input: 32 Output: 32 = Input: 16 Output: 16 Input: 16 Output: 16
32 + 16 + 16
= Input: 16 Output: 16 Input: 8 Output: 8 Input: 8 Output: 8
16 + 32 + 16
= Input: 8 Output: 8 Input: 16 Output: 16 Input: 8 Output: 8
16 + 16 + 16 + 16
= Input: 8 Output: 8 Input: 8 Output: 8 Input: 8 Output: 8 Input: 8 Output: 8
80 32 + 32 + 16
Input: 40 Output: 40 = Input: 16 Output: 16 Input: 16 Output: 16 Input: 8 Output: 8
32 + 16 + 16 + 16
= Input: 16 Output: 16 Input: 8 Output: 8 Input: 8 Output: 8 Input: 8 Output: 8
16 + 32 + 32
= Input: 8 Output: 8 Input: 16 Output: 16 Input: 16 Output: 16
16 + 32 + 16 + 16
= Input: 8 Output: 8 Input: 16 Output: 16 Input: 8 Output: 8 Input: 8 Output: 8
96 32 + 32 + 32
Input: 48 Output: 48 = Input: 16 Output: 16 Input: 16 Output: 16 Input: 16 Output: 16
32 + 32 + 16 + 16
= Input: 16 Output: 16 Input: 16 Output: 16 Input: 8 Output: 8 Input: 8 Output: 8
16 + 32 + 32 + 16
= Input: 8 Output: 8 Input: 16 Output: 16 Input: 16 Output: 16 Input: 8 Output: 8
112 32 + 32 + 32 + 16
Input: 56 Output: 56 = Input: 16 Output: 16 Input: 16 Output: 16 Input: 16 Output: 16 Input: 8 Output: 8
16 + 32 + 32 + 32
= Input: 8 Output: 8 Input: 16 Output: 16 Input: 16 Output: 16 Input: 16 Output: 16
128 32 + 32 + 32 + 32
Input: 64 Output: 64 = Input: 16 Output: 16 Input: 16 Output: 16 Input: 16 Output: 16 Input: 16 Output: 16
Notes
1) When FP programmers (AFP1112A/AFP1114) are used, reading
and writing of the following FP0 instructions are not possible
and the functions cannot be used.
– High–speed counter function (related
instructions: F166/F167)
– Pulse output function (related instructions:
F168/F169)
– PWM output function (related instruction: F170)
– 1ms unit timer instruction (TML)
– 32–bit auxiliary timer instruction (F183)
– Changing the communication baud rate to
19,200bps (factory setting is 9600bps)
2) If the FP PC cable (AFC8513) is to be connected to a computer
(IBM PC/AT compatible), use a commercially available 9 pin –
25 pin port adapter.
Control Units
Control Units FP0 Hardware
1 EXPANSION 8
CONNECTOR
9
4
10
11 17
15 21
12 18
16 22
13 19
14 20
23
LED Description
RUN (green) Illuminates when in the RUN mode and indicates the execution of a program. It flashes during
forced input/output.
PROG. (green) Illuminates when in the PROG. mode and indicates that operation has stopped.
ERROR/ALARM Flashes when an error is detected during the self-diagnostic function. Illuminates if a
(red) hardware error occurs, or if operation slows because of the program, and the watchdog timer
is activated.
When performing remote switching from the programming tool, the position of the mode
switch and the actual mode of operation may differ. Verify the mode with the status
indicator LED. Otherwise, restart the FP0 and change the mode of operation with the
mode switch.
Pin assignment
2.2 Specifications
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
30% to 85% RH (non-condensing)
Ambient temperature
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0°C to +55°C/32°F to +131°F
Allowed
momentary power
off time
C10/C14
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
5ms at 21.6V, 10ms at 24V
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
C16/C32/T32 10ms at 21.6V, 10ms at 24V
Breakdown voltage
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
500V AC for 1 minute between I/O terminal and power supply/ground terminal
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1500V AC for 1 minute between I/O terminal and power supply/ground
terminal (relay output type only)
Insulation resistance
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
min. 100MΩ (measured with a 500V DC megger)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
between I/O terminal and ground terminal
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Noise immunity 1,000Vp-p with pulse widths 50ns and 1µs (based on in-house measurements)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Operating condition Free from corrosive gases and excessive dust
Operating voltage range 21.6V to 26.4V DC
Rated operating voltage
Rated current consumption ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
24V DC
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
300mA or less (see page 2-6)
Shock resistance
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Shock of 98m/s2 or more, 4 times on 3 axes
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Storage humidity 30% to 85% RH (non-condensing)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Storage temperature –20°C to +70°C/–4°F to +158°F
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Vibration resistance 10Hz to 55Hz, 1 cycle/min: double amplitude of 0.75mm/ 0.030in., 10min. on 3
axes
2.2.2 Weight
Type
ÁÁÁÁÁÁÁÁÁ
Weight
C10RS/C10CRS
ÁÁÁÁÁÁÁÁÁ
approx. 100g/3.53oz
C14RS/C14CRS
ÁÁÁÁÁÁÁÁÁ
approx. 105g/3.70oz
C16T/C16CT/C16P/C16CP
C32T/C32CT/C32P/C32CP ÁÁÁÁÁÁÁÁÁ
approx. 85g/3.00oz
ÁÁÁÁÁÁÁÁÁ
approx. 115g/4.06oz
ÁÁÁÁÁÁÁÁÁ
T32CP approx. 130g/4.59oz.
ÁÁÁÁÁÁÁÁÁ
E8RS/E8RM approx. 90g/3.17oz
ÁÁÁÁÁÁÁÁÁ
E8X/E8YT/E8YP approx. 65g/2.29oz
E16RS/E16RM approx. 105g/3.70oz
E16T/E16P/E16X/E16YT/E16YP
ÁÁÁÁÁÁÁÁÁ
approx. 70g/2.47oz
E32T/E32P
ÁÁÁÁÁÁÁÁÁ
approx. 85g/3.00oz
ÁÁÁÁÁÁÁÁÁÁ
Type Current consumption
(at 24V DC)
Control unit C10RS, C10CRS
C14RS, C14CRS ÁÁÁÁÁÁÁÁÁÁ
100mA or less
ÁÁÁÁÁÁÁÁÁÁ
100mA or less
ÁÁÁÁÁÁÁÁÁÁ
C16T, C16CT, C16P, C16CP 40mA or less
ÁÁÁÁÁÁÁÁÁÁ
C32T, C32CT, C32P, C32CP, T32CP 60mA or less
ÁÁÁÁÁÁÁÁÁÁ
Expansion I/O unit E8X 10mA or less
ÁÁÁÁÁÁÁÁÁÁ
E8YT, E8YP 15mA or less
ÁÁÁÁÁÁÁÁÁÁ
E8RS, E16RS, E16X 20mA or less
E16YT, E16YP, E16T, E16P 25mA or less
ÁÁÁÁÁÁÁÁÁÁ
20mA or less
ÁÁÁÁÁÁÁÁÁÁ
FP Programmer II Ver. 2 (AFP1114V2) 50mA or less
ÁÁÁÁÁÁÁÁÁÁ
C-NET adapter S2 type (AFP15402) 50mA or less
Type
ÁÁÁÁÁÁÁÁÁ
Current consumption
ÁÁÁÁÁÁÁÁÁ
(at 24V DC)
ÁÁÁÁÁÁÁÁÁ
Expansion I/O unit E8RS 50mA
E16RS 100mA
Analog I/O unit A21
ÁÁÁÁÁÁÁÁÁ
100mA
Type
FP0 E16RS ÁÁÁÁÁÁÁÁ
Current consumption
ÁÁÁÁÁÁÁÁ
100mA
Type
ÁÁÁÁÁÁÁÁ
Current consumption
FP0 C14RS
ÁÁÁÁÁÁÁÁ
100mA
FP0 E32T
ÁÁÁÁÁÁÁÁ
40mA
ÁÁÁÁÁÁÁÁ
FP Programmer II Ver. 2 FP0 E16T 25mA
ÁÁÁÁÁÁÁÁ
FP0 E16RS 20mA
ÁÁÁÁÁÁÁÁ
FP Programmer II Ver. 2 50mA
Total current consumption 235mA or less
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
T32CP
C10CRS C14CRS C16P C32P
C16CP C32CP
Programming method/Control method
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
Relay symbol/Cyclic operation
Controllable I/O points Control unit only
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁ
total: 10
ÁÁÁÁÁ ÁÁÁÁÁÁ
ÁÁÁÁ
Input: 6
ÁÁÁÁÁÁ
Output: 4
total: 14
Input: 8
Output: 6
total: 16
Input: 8
Output: 8
total: 32
Input: 16
Output: 16
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
unit is the same
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
output type as the
control unit
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
When the expansion max. 106 max. 110 max. 112 max. 128
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
unit is a transistor
output type
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Program memory Built in EEPROM (no back-up battery required) RAM,
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
battery
back–up
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
Program capacity 2,720 steps 5,000 10,000
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
steps steps
Numbers of instruction Basic instruction 83 types
High-level
instruction ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
114 types
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
115 types
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Operation speed 0.9µs/step (basic instruction)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
I/O update time and Base time Without expansion: 0.3ms
With expansion: 0.3ms + (1 × Number of expansion unit) ms
Operation Relays Internal relay (R)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1,008 points (R0 to R62F)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
memory
points Special internal 64 points (R9000 to R903F)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
relay (R)
Timer/Counter (T/C) 144 points (initial setting is 100 timer points, T0 to T99 / 44
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
counter points, C100 to C143 (see notes)
Timer range: 1ms, 10ms, 100ms, 1s; selected by instruction
Note
The proportion of timer points to counter points can be changed
using system register 5. See FP0 Programming Manual.
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
C16CP C32CP
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
Operation Memory Data register 1,660 words 6,144 words 16,383
memory areas (DT) (DT0 to DT1659) (DT0 to words
points
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ DT6143) (DT0 to
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
DT16382)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Special data 112 words (DT9000 to DT9111, for T32CP DT90000 to DT90111)
register (DT)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Index registers 2 words
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(IX, IY)
Differential points Unlimited number of points
Master control relay points (MCR)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
32 points
ÁÁÁÁ
Number of labels (JP and LOOP)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
64 labels
ÁÁÁÁ 255 labels
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Number of step ladders 128 stages 704 stages
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Number of subroutines 16 subroutines 100 sub–
routines
Number of interrupt programs
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
7 programs (external: 6, internal: 1)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Self-diagnostic function
Memory Timer
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Such as watchdog timer, program syntax check, run–time error
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ ÁÁÁÁ
Non-hold type: all points Set with
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
backup system
Counter Non-hold type From set value to C139 From set
(see notes) registers 5
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
value to C127
(border
Hold type 4 points (elapsed values) C140 to C143 16 points between
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
(elapsed timer and
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
values) C128 counter)
to C143 and 6
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
Internal Non-hold type 976 points (R0 to R60F) 880 points
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
relay 61 words (WR0 to WR60) (R0 to R54F)
55 words
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
(WR0 to Set with
WR54) system
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
register 7
Hold type 32 points (R610 to R62F) 128 points
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
2 words (WR61 to WR 62) (R550 to
R62F)
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
8 words
(WR55 to
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ WR62)
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
Data Non-hold type 1652 words (DT0 to DT1651) 6112 words
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
registers (DT0 to Set with
DT6111) system
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
register 8
Hold type 8 words (DT1652 to DT1659) 32 words
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
(DT6112 to
DT6143)
Notes
The program, system registers and the hold type areas
(internal relay, data register and counter) are backed up by the
built in EEPROM.
For T32CP, all data registers are backed up by storage battery.
Once charged (at least 22 hours), back–up lasts for 15 days at
25°C/77°F.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
C16CP C32CP
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Special Pulse catch input Total 6 points
functions µ
X0 and X1: 50µs
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Interrupt input X2 to X5: 100µs
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Baud rate:
FP0-C10CRS, C10CRM, C14CRS, C14CRM,
C16CT, C16CP, C32CT, C32CP, and T32CP
300, 600, 1200, 2400. 4800, 9600, and 19200bps
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Transmission distance: 3m/9.84ft.
Terminal block: 3-pin, made by Phoenix Contact Co.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(product number: MKDS 1/3-3.5)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Communication method: half-duplex
Periodical interrupt 0.5ms to 30s interval
Constant scan
High-speed counter function ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Available
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Counter mode: Addition/subtraction (one phase)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(see notes 2, 3) S Input point number: 4 channels maximum
S Maximum counting speed: 10kHz maximum for all
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
4 channels (see note 4)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
S Input contacts used:
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
X0: count input (ch 0)
X1: count input (ch 1)
X2: reset input (see note 5)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
X3: count input (ch 2)
X4: count input (ch 3)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
X5: reset input (see note 5)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
S Minimum input pulse width: X0, X1.. 50µs <10kHz>
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
X3, X4 ..100µs <5kHz>
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Counter mode: Two-phase/individual/direction decision
(two phase)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
S Input point number: 2 channels maximum
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
S Maximum counting speed: kHz maximum for all 2
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
channels
S Input contacts used: X0: count input (ch 0)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
X1: count input (ch 0)
X2: reset input
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
X3: count input (ch 2)
X4: count input (ch 2)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
S Minimum input pulse width: X0, X1.. 50µs <10kHz>
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
output number Y1)
function (No interpolation function)
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
(see note
3) Output frequency —————— 40Hz to 10kHz
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
(Y0/Y1: one-point output)
40Hz to 5kHz
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
(Y0/Y1: two-point output)
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
Special PWM Output point —————— Two points (Y0 and Y1)
functions output number
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
function
Output frequency —————— Frequency: 0.15Hz to 38Hz
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
(see note
3) (see note 6)
Duty: 0.1% to 99.9%
Notes
1) When using the RS232C port for communication,
retransmission is recommended.
The driver IC for the RS232C port conforms completely to
EIA/TIA-232E and CCITT V28 standards.
2) The combinations 1 phase 2 channels and 2 phases 1
channel are also possible for the high-speed counter.
3) For details and limitations on the high-speed counter, pulse
output, and PWM output functions. See FP0 Programming
Manual.
4) The max. counting speed (10kHz) is the counting speed with a
rated input voltage of 24V DC and an ambient temperature of
25°C/77°F. The counting speed (frequency) will decrease
depending on the voltage and temperature.
5) If the unit is equipped with both reset inputs X0 and X1, X2
serves as the reset input for X1. If X3 and X4 are used, X5
serves as the reset input for X4.
6) With control unit’s CPU that is Ver.2.0 or a subsequent
version, the frequency will be 0.15Hz to 1kHz.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
21.6 to 26.4V DC
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Input points per C10RS, 6 points/common
common C10CRS
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(see note 1)
C14RS, 8 points/common
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
C14CRS
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
C16T, C16CT, 8 points/common
C16P, C16CP
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
C32T, C32CT, 16 points/common
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
C32P, C32CP,
T32CP
ON voltage/ON current
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
19.2V or less/3mA or less
OFF voltage/OFF current
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
2.4V or more/1mA or more
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Response time OFF ↔ ON 50µs or less (at X0, X1) (see note 2)
(at 24V DC and 100µs or less (at X2 to X5) (see note 2)
25°C/66°F)
25 C/66 F)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
2ms or less (at X6 to XF)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ON ↔ OFF the same as above
Operating mode indicator LED
Notes
1) Either positive or negative polarity is possible for the input
voltage supply.
FP0–C14RS/C14CRS
at 24V DC
Number of 8 at 26.4V DC
input points
per common
which are 5
simultaneously 3
ON
FP0–C16T/C16CT/C16P/C16CP
at 26.4V DC
Number of 8
at 24V DC
input points
per common
which are 4
simultaneously
ON
FP0–C32T/C32CT/C32P/C32CP/T32CP
at 26.4V DC
Number of 16 at 24V DC
input points
per common
which are 8
simultaneously 6
ON
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Item Description
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Output type Normally open (1 Form A) relay output
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Rated control capacity 2A 250V AC, 2A 30V DC (4.5A maximum per common)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Output points per C10RS, 2 points/common + 1 point/common + 1 point/common
common C10CRS
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
C14RS, 4 points/common + 1 point/common + 1 point/common
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
C14CRS
Response time OFF → ON approx. 10ms
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
20,000,000 operations or more
Electrical life time
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
100,000 operations or more
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Surge absorber None
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Operating mode indicator LED
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Insulation method optical coupler
Output type open collector
Rated load voltage
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
NPN open collector type: 5 to 24V DC (see notes)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
PNP open collector type: 24V DC
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Operating load voltage range NPN open collector type: 4.75 to 26.4V DC (see notes)
PNP open collector type: 21.6 to 26.4V DC
Max. load current
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0.1A
Max. surge current
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0.3A
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Output points per C16T, C16CT, 8 points/common
common C16P, C16CP
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
C32T, C32CT, 16 points/common
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
C32P, C32CP,
T32CP
OFF state leakage current
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
100µA or less
ON state voltage drop
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1.5V or less
External power Voltage
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
21.6 to 26.4V DC
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
supply for driving
internal circuit Current Y0 and Y1: 5mA/1 point, except Y0 and Y1: 3mA/1 point
Response time OFF → ON
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1ms or less (Y0 and Y1 only: 50µs or less)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ON → OFF 1ms or less (Y0 and Y1 only: 50µs or less)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Surge absorber Zener diode
Operating mode indicator LED
Notes
The T32CP control unit uses only the PNP open collector.
FP0-C10RS/C10CRS/C14RS/C14CRS
Input side
5.6kΩ X0
Internal
(see note 1)
circuit
5.6kΩ
Xn
Output side Y0
Load
Internal
circuit
Yn
Load
Internal
circuit
COM
Power
supply
Notes
1) The resistor in the control unit is 2kW for X0 through X5, and
1kW for X6 and X7.
2) Either positive or negative polarity is possible for the input
voltage supply.
FP0-C16T/C16CT/C32T/C32CT
Input side
5.6kΩ
X0
5.6kΩ Xn
Internal Load
circuit Y0
Yn
Internal Load
circuit
(–)
Notes
1) The resistor in the control unit is 2kW for X0 through X5, and
1kW for X6 through XF.
2) Either positive or negative polarity is possible for the input
voltage supply.
When the load voltage differs from the 24V DC external power supply for the driving the
internal circuit
Other than 24V DC load voltage, 5V DC and 12V DC and other load voltages can be
connected.
FP0-C16T/C16CT/C32T/C32CT
Input side
5.6kΩ X0
Internal
(see note 1)
circuit
5.6kΩ X1
Internal
(see note 1)
circuit
5.6kΩ
Xn
Output side
(+)
Notes
1) The resistor in the control unit is 2kW for X0 through X5, and
1kW for X6 through XF.
2) Either positive or negative polarity is possible for the input
voltage supply.
Input side
5.6kΩ X0
5.6kΩ Xn
Internal Load
circuit Y0
Yn
Internal Load
circuit
24V DC
(+) (Load voltage and
external power
supply)
Notes
1) The resistor in the control unit is 2kW for X0 through X5, and
1kW for X6 through XF.
2) Either positive or negative polarity is possible for the input
voltage supply.
2.4.1 C10RS/C10CRS
Inputs X0–5
X0
X0–5 X0
X1
X2
X3
X4 X5
X5
(NC) COM
(NC) Y0
COM
(see note) Y0–3
Outputs Load
Y0
Load Y3
Y1
(NC) COM
Y0–3
(NC)
COM Power supply
Y2 Load
COM
Y3 Load
COM Power supply
2.4.2 C14RS/C14CRS
X0–7
Inputs X0
X1 X0–7 X0
X2
X3
X4
X5
X7
X6 COM
X7
COM
Y0
Y4 Load
COM Power supply
Y5 Load
COM Power supply
Note
Either positive or negative polarity is possible for the input
voltage supply.
2.4.3 C16T/C16CT
Inputs
A X0–7
X0 X1
X2 X3 X0 X1
X4 X5
X6 X7
COM COM COM COM
(see note 1)
Outputs
Y0 Y1
A Y0–7
Load Y0 Y1 Load
Load Y2 Y3 Load (+) (–)
Load Y4 Y5 Load
Load Y6 Y7 Load
(+) (–)
Notes
1) Either positive or negative polarity is possible for the input
voltage supply.
2) The two COM terminals of input terminal (X0–7) are connected
internally, however they should be externally connected as
well.
2.4.4 C16P/C16CP
Inputs
A X0–7
X0 X1
X2 X3 X0 X1
X4 X5
X6 X7
COM COM COM COM
A Y0–7
Load Y0 Y1 Load
Load Y2 Y3 Load (+) (–)
Load Y4 Y5 Load
Load Y6 Y7 Load
(+) (–)
Notes
1) Either positive or negative polarity is possible for the input
voltage supply.
2.4.5 C32T/C32CT
Inputs Inputs
X0 X1 X8 X9
COM COM
(see note 1)
Outputs Outputs Y0 Y1 Y8 Y9
Notes
1) Either positive or negative polarity is possible for the input
voltage supply.
2) The four COM terminals of input terminals (X0–7 and X8–F) are
connected internally, however they should be externally
connected as well.
3) The (+) terminals of output terminals (Y0–7) and output
terminals (Y8–F) are connected internally, however they
should be externally connected as well.
4) The (–) terminals of output terminals (Y0–7) and output
terminals (Y8–F) are connected internally, however they
should be externally connected as well.
2.4.6 C32P/C32CP/T32CP
Inputs Inputs
X0 X1 X8 X9
COM COM
(see note 1)
Outputs Outputs Y0 Y1 Y8 Y9
Notes
1) Either positive or negative polarity is possible for the input
voltage supply.
2) The four COM terminals of input terminals (X0–7 and X8–F) are
connected internally, however they should be externally
connected as well.
3) The (+) terminals of output terminals (Y0–7) and output
terminals (Y8–F) are connected internally, however they
should be externally connected as well.
4) The (–) terminals of output terminals (Y0–7) and output
terminals (Y8–F) are connected internally, however they
should be externally connected as well.
2 4 6
3 5 7
10
11
12 13
14 15
3.2 Specifications
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
optical coupler
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Rated input voltage 24V DC
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Rated input current approx. 4.3mA (at 24V DC)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Input impedance approx. 5.6kΩ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Operating voltage range 21.6 to 26.4V DC
Input points per E8RS 4 points/common
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
common (see note)
E16RS, E16T, 8 points/common
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
E16P, E8X
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
E32T, E32P, 16 points/common
E16X
ON voltage/ON current
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
19.2V or less/3mA or less
OFF voltage/OFF current
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
2.4V or more/1mA or more
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Response time OFF ↔ ON 2ms or less
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(at 24V DC and
25°C/66°F) ON ↔ OFF the same as above
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Operating mode indicator LED
Note
Either positive or negative polarity is possible for the input
voltage supply.
at 24V DC
Number of 8 at 26.4V DC
input points
per common 6
which are
simultaneously
ON
47/ 55/
116.6 131
Ambient temperature (C/F)
FP0–E16T/E16P/E8X
at 26.4V DC
Number of 8
input points at 24V DC
per common
which are 5
simultaneously4
ON
FP0–E32T/E32P/E16X
at 26.4V DC
Number of 16 at 24V DC
input points
per common
which are 9
8
simultaneously
ON
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
common
E16RS 8 points/common
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Response time OFF ↔ ON approx. 10ms
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ON ↔ OFF approx. 8ms
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Mechanical life time 20,000,000 operations or more
Electrical life time 100,000 operations or more
Item
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Description
Surge absorber
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
None
Operating mode indicator
FP0 transistor output types: E16T, E16P, E32T, E32P, E8YT, E8YP, E16YT, E16YP
Item
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Description
Insulation method
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
optical coupler
Output type
Rated load voltage ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
open collector
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
NPN open collector type: 5 to 24V DC (see note)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
PNP open collector type: 24V DC
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Operating load voltage range NPN open collector type: 4.75 to 26.4V DC
PNP open collector type: 21.6 to 26.4V DC
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Max. load current 0.1A
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Max. surge current 0.3A
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Output points per E16T, E16P, 8 points/common
common E8YT, E8YP
E32T, E32P,
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
16 points/common
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
E16YT, E16YP
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
OFF state leakage current 100µA or less
ON state voltage drop 1.5V or less
External power Voltage
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
21.6 to 26.4V DC
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
supply for driving
Current Y0 and Y1: 5mA/1 point, except Y0 and Y1: 3mA/1 point
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
internal circuit
Response time OFF → ON 1ms or less (Y0 and Y1 only: 50µs or less)
ON → OFF
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1ms or less (Y0 and Y1 only: 50µs or less)
Surge absorber
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Zener diode
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Operating mode indicator LED
Note
For NPN open collector type, able to be used with different
voltages for the load voltage and the external power supply for
driving the internal circuit.
External power supply for
driving internal circuit
(+)
(21.6V to 26.4V DC)
Rated load voltage
Yn (5V to 24V DC)
Internal Load
circuit
Ground for load voltage and for
(–) external power supply for driving
internal circuit
FP0-E8RS/E16RS
Input side
5.6kΩ X20
Internal
1kΩ
circuit
5.6kΩ
X2n
Internal 1kΩ
circuit
COM
Internal
circuit
Y2n
Load
Internal
circuit
COM
Power
supply
Notes
Either positive or negative polarity is possible for the input
voltage supply.
The I/O number given above is the I/O number when the
expansion I/O unit is installed as the first expansion unit
(see page 7 - 4).
FP0-E16T/E32T
Input side
5.6kΩ
X20
Internal 1kΩ
circuit
5.6kΩ X2n
Internal 1kΩ
circuit 24V DC
COM (see notes)
Y20
Internal Load
circuit
Y2n
Internal Load
circuit
(–)
Notes
Either positive or negative polarity is possible for the input
voltage supply.
The I/O number given above is the I/O number when the
expansion I/O unit is installed as the first expansion unit
(see page 7 - 4).
When the load voltage differs from the 24V DC external power supply for driving
the internal circuit
Other than 24V DC load voltage, 5V DC and 12V DC and other load voltages can be
connected.
FP0-E16T/E32T
5.6kΩ X20
Internal 1kΩ
circuit
5.6kΩ X21
Internal 1kΩ
circuit
5.6kΩ
X2n
(+)
Y21
Internal Load (for 5 V )
circuit
Notes
Either positive or negative polarity is possible for the input
voltage supply.
The I/O number given above is the I/O number when the
expansion I/O unit is installed as the first expansion unit
(see page 7 - 4).
FP0-E16P/E32PT
Input side
5.6kΩ X20
Internal 1kΩ
circuit
5.6kΩ X2n
Y20
Internal Load
circuit
Y2n
Internal Load
circuit
24V DC
(+)
Notes
Either positive or negative polarity is possible for the input
voltage supply.
The I/O number given above is the I/O number when the
expansion I/O unit is installed as the first expansion unit
(see page 7 - 4).
FP0-E8X/E16X
Input side
5.6kΩ
X20
Internal 1kΩ
circuit
5.6kΩ X2n
Internal 1kΩ
circuit
COM
24V DC ( notes)
Notes
Either positive or negative polarity is possible for the input
voltage supply.
The input number given above is the input number when the
expansion input unit is installed as the first expansion unit
(see page 7 - 4).
FP0-E8YT/E16YT
Internal Y20
Load
circuit
Internal Y2n
Load
circuit
(–)
24V DC
(External power supply and
load voltage)
Note
The output number given above is the output number when the
expansion output unit is installed as the first expansion unit
(see page 7 - 4).
When the load voltage differs from the 24V DC external power supply for driving
the internal circuit
Other than 24V DC load voltage, 5V DC and 12V DC and other load voltages can be
connected.
FP0-E8YT/E16YT
Y20
Internal circuit Load (for 5V )
Y21
Load (for 5V )
Internal circuit
Y2n
Internal circuit Load (for 24V DC)
5V DC 24V DC
(Rated load (External
(–) voltage) power supply
for driving
internal circuit)
Note
The output number given above is the output number when the
expansion output unit is installed as the first expansion unit
(see page 7 - 4).
Y20
Internal Load
circuit
Y2F
Internal Load
circuit
24V DC
(+)
Note
The output number given above is the output number when the
expansion output unit is installed as the first expansion unit
(see page 7 - 4).
3.4.1 E8RS
Inputs
X20 X0–3 X20
X21
X22 X23
X23
(NC)
(NC) COM
(NC)
(NC)
COM Y0–3
Y20
(see notes)
Y23
Outputs
Y20 Load
Y21 Load COM
Y22 Load
Y23 Load
(NC)
(NC)
(NC)
(NC)
Power
COM supply
Notes
Either positive or negative polarity is possible for the input
voltage supply.
The I/O number given above is the I/O number when the
expansion I/O unit is installed as the first expansion unit.
The I/O numbers for the expansion I/O units will differ
depending on the location where they are installed
(see page 7 - 4).
3.4.2 E16RS
Inputs
X20 X20
X21
X22
X23
X24 X27
X25 COM
X26
X27
COM Y20
(see notes)
Outputs
Y20 Load Y27
Y21 Load COM
Y22 Load
Y23 Load
Y24 Load
Y25 Load
Y26 Load
Y27 Load
COM Power
supply
Notes
Either positive or negative polarity is possible for the input
voltage supply.
The I/O number given above is the I/O number when the
expansion I/O unit is installed as the first expansion unit.
The I/O numbers for the expansion I/O units will differ
depending on the location where they are installed
(see page 7 - 4).
3.4.3 E16T
Inputs
A
X20 X21
X22 X23 X20 X21
X24 X25
X26 X27
COM COM COM COM
(see note 1)
Outputs
Y20 Y21
A
Load Y20 Y21 Load
Load Y22 Y23 Load (+) (–)
Load Y24 Y25 Load
Load Y26 Y27 Load
(+) (–)
Notes
1) Either positive or negative polarity is possible for the input
voltage supply.
2) The two COM terminals of input terminals are connected
internally, however they should be externally connected as
well.
3) The I/O number given above is the I/O number when the
expansion I/O unit is installed as the first expansion unit.
The I/O numbers for the expansion I/O units will differ
depending on the location where they are installed
(see page 7 - 4).
3.4.4 E16P
Inputs
A
X20 X21
X22 X23 X20 X21
X24 X25
X26 X27
COM COM COM COM
(see note 1)
Outputs
Y20 Y21
A
Load Y20 Y21 Load
Load Y22 Y23 Load (+) (–)
Load Y24 Y25 Load
Load Y26 Y27 Load
(+) (–)
Notes
1) Either positive or negative polarity is possible for the input
voltage supply.
2) The two COM terminals of input terminals are connected
internally, however they should be externally connected as
well.
3) The I/O number given above is the I/O number when the
expansion I/O unit is installed as the first expansion unit.
The I/O numbers for the expansion I/O units will differ
depending on the location where they are installed
(see page 7 - 4).
3.4.5 E32T
Inputs Inputs
X20 X21 X28 X29
X20 X21 X28 X29
X22 X23 X2A X2B
X24 X25 X2C X2D
X26 X27 X2E X2F
COM COM COM COM
COM COM
(see note 1)
Notes
1) Either positive or negative polarity is possible for the input
voltage supply.
2) The four COM terminals of input terminals are connected
internally, however they should be externally connected as
well.
3) The two (+) terminals of output terminals are connected
internally, however they should be externally connected as
well.
4) The two (–) terminals of the output terminals are connected
internally, however they should be externally connected as
well.
5) The I/O number given above is the I/O number when the
expansion I/O unit is installed as the first expansion unit.
The I/O numbers for the expansion I/O units will differ
depending on the location where they are installed
(see page 7 - 4).
3.4.6 E32P
Inputs Inputs
X20 X21 X28 X29
X20 X21 X28 X29
X22 X23 X2A X2B
X24 X25 X2C X2D
X26 X27 X2E X2F
COM COM COM COM
COM COM
(see note 1)
Notes
1) Either positive or negative polarity is possible for the input
voltage supply.
2) The four COM terminals of input terminals are connected
internally, however they should be externally connected as
well.
3) The two (+) terminals of output terminals are connected
internally, however they should be externally connected as
well.
4) The two (–) terminals of the output terminals are internally
connected, however they should be externally connected as
well.
5) The I/O number given above is the I/O number when the
expansion I/O unit is installed as the first expansion unit.
The I/O numbers for the expansion I/O units will differ
depending on the location where they are installed
(see page 7 - 4).
3.4.7 E8X
X20 X21
Inputs
A
X20 X21
X22 X23
X24 X25
X26 X27 COM COM
COM COM
(see note 1)
Notes
1) Either positive or negative polarity is possible for the input
voltage supply.
2) The two COM terminals of input terminals are connected
internally, however they should be externally connected as
well.
3) The input number given above is the input number when the
expansion input unit is installed as the first expansion unit.
The input numbers for the expansion input units will differ
depending on the location where they are installed
(see page 7 - 4).
3.4.8 E16X
Inputs X20 X21 X28 X29
(see note 1)
Notes
1) Either positive or negative polarity is possible for the input
voltage supply.
2) The four COM terminals of input terminals are connected
internally, however they should be externally connected as
well.
3) The input number given above is the input number when the
expansion input unit is installed as the first expansion unit.
The input numbers for the expansion input units will differ
depending on the location where they are installed
(see page 7 - 4).
3.4.9 E8YT
Outputs
A
Load Y20 Y21 Load Y20 Y21
Load Y22 Y23 Load
Load Y24 Y25 Load
Load Y26 Y27 Load
(+) (–) (–)
(+)
3.4.10 E8YP
Outputs
A
Load Y20 Y21 Load Y20 Y21
Load Y22 Y23 Load
Load Y24 Y25 Load
Load Y26 Y27 Load
(+) (–)
(+) (–)
Note
The output number given above is the output number when the
expansion output unit is installed as the first expansion unit. The
output numbers for the expansion output units will differ
depending on the location where they are installed
(see page 7 - 4).
3.4.11 E16YT
Outputs Outputs
Notes
The two (+) terminals of the output terminals are connected
internally, however they should be externally connected as
well.
The two (–) terminals of the output terminals are connected
internally, however they should be externally connected as
well.
The output number given above is the output number when
the expansion output unit is installed as the first expansion
unit. The output numbers for the expansion output units will
differ depending on the location where they are installed
(see page 7 - 4).
3.4.12 E16YP
Outputs Outputs
Y20 Y21 Y28 Y29
A A
Load Y20 Y21 Load Load Y28 Y29 Load
Load Y22 Y23 Load Load Y2A Y2B Load
Load Y24 Y25 Load Load Y2C Y2D Load
(+)
Load Y26 Y27 Load Load Y2E Y2F Load (–)
(+) (–) (+) (–)
Notes
The two (+) terminals of the output terminals are connected
internally, however they should be externally connected as
well.
The two (–) terminals of the output terminals are connected
internally, however they should be externally connected as
well.
The output number given above is the output number when
the expansion output unit is installed as the first expansion
unit. The output numbers for the expansion output units will
differ depending on the location where they are installed
(see page 7 - 4).
Mode Switch
Range
number
Analog K type thermo– J type thermo– T type thermo–
0 to 5V
input –10 to +10V couple (see notes couple (see notes couple (see notes
0 to 20mA
range 3, 4) 3, 4) 3, 4)
switching 1 to 3, 5 No With No aver– With av– Temper– –100°C Temper– –100°C Temper– –100°C
averaging averaging aging eraging ature of to ature of to ature of to
(see (see (see (see terminal temper– terminal temper– terminal temper–
note 1) note 2) note 1) note 2) to ature of to 750°C ature of to 350°C ature of
1000°C terminal terminal terminal
1
2
3
5
ON
Analog 0 to –10 to
output 4
20mA +10V
range
switching
4
ON
Notes
1) No averaging: Conversion data is set for the specified input
contact point area for each A/D conversion, on each channel.
2) With averaging: On each channel, for each A/D conversion,
the maximum and minimum values from the data of the last
ten times are excluded, and the data from the other eight times
is averaged, and the result set (see page 4-17).
3) If a thermocouple setting is used, averaging is carried out,
regardless of the switch settings (see page 4-18).
4) After turning on the analog unit, 20 minutes are required for
the transient state to reach a measurement accuracy of 99%.
During this time, deviations of 10C can occur.
measurement
accuracy
99%
10C
time
20 min.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Pin number Name Description
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1 IN/V 0 Analog input (channel 0), voltage input
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
2 IN/I 0 Analog input (channel 0), current input
3 IN/COM Analog input (channel 0 and 1), analog input common
4
5
IN/V 1
IN/I 1 ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Analog input (channel 1), voltage input
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Analog input (channel 1), current input
6
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Ground for analog cable
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
7 OUT/V Voltage output
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
8 OUT/I Current output
9 OUT/COM Analog output common
4.2 Specifications
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Item Description
Rated operation voltage 24V DC
Operating voltage range
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
21.6 to 26.4V DC
Rated current consumption
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
100mA or less (see page 2-6)
Allowed momentary power off time
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
10ms
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Ambient temperature 0°C to +55°C/32°F to +131°F
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Storage temperature –20°C to +70°C/–4°F to +158°F
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Ambient humidity 30% to 85% RH (non-condensing)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Storage humidity 30% to 85% RH (non-condensing)
Breakdown voltage 500V AC for 1 minute between I/O terminal and power supply/ground
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
terminal
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
500V AC for 1 minute between input and output terminals
Insulation resistance min. 100MΩ (measured with a 500V DC megger) for between I/O terminal
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
and power supply/ground terminal
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
min. 100MΩ (measured with a 500V DC megger) for between input and
output terminals
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Vibration resistance 10Hz to 55Hz, 1 cycle/min: double amplitude of 0.75mm/ 0.030in., 10min. on
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
3 axes
Shock resistance Shock of 98m/s2 or more, 4 times on axes
Noise immunity
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1,000Vp-p with pulse widths 50ns and 1µs (based on in-house
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
measurements)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Operating condition Free from corrosive gases and excessive dust
Weight appox. 100g/3.53oz
Digital output
Thermocouple range
0 to 5V/ 0 to 20mA ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
K, J and T type thermocouples
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
K0 to K4000 (H0 to H0FA0)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
–10 to +10V K – 2000 to K + 2000 (HF830 to H07D0)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Thermo– K type K (temperature of terminal) to K1000 (see note 1)
couple K – 100 to K (temperature of terminal) (see note 2)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(units in °°C)
J type K (temperature of terminal) to K750 (see note 1)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
K – 100 to K (temperature of terminal) (see note 2)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
T type K (temperature of terminal) to K350 (see note 1)
K – 100 to K (temperature of terminal) (see note 2)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
When disconnected: K 20000
Resolution
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1/4000
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Conversion Voltage/ 1ms/channel (see note 3)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
speed current range
Thermocouple range 560ms (fixed)
Item
Overall Voltage/ ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Description
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±1% F.S. or less (0 to 55°C/32 to 131°F)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
precision current range ±0.6% F.S. or less (25°C/77°F)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Thermocouple range Offset error (0 to 55°C/32 to 131°F):
±2% F.S. or less (K type thermocouple) (see note 4)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±2.7% F.S. or less (J type thermocouple) (see note 4)
±5.8% F.S. or less (T type thermocouple) (see note 4)
Input
impedance
Voltage range ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Linearity error: ±1% F.S. or less(0 to 55°C/32 to 131°F)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
1MΩ or more
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Current range 250Ω
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Absolute Voltage range ±15V
maximum input
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Current range +30mA
Insulation method (see note 5) Between analog input terminal to FP0 internal circuit:
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
photocoupler insulation (non-insulated between analog inputs)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Between analog input terminal to analog I/O unit external power supply:
insulation-type DC/DC converter
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Between analog input terminal to analog output terminal: insulation-type
DC/DC converter
Number of input contact points
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
32 input contact points:
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
16 points for 1st half: analog input CH0 data (WX2) (see note 6)
16 points for last half: analog input CH1 data (WX3) (see note 6)
Notes
1) A temperature lower than the terminal temperature of the
analog I/O unit cannot be measured.
2) A temperature higher than the terminal temperature of the
analog I/O unit cannot be measured.
3) The time noted below is required before the analog data is
reflected in the control unit input.
10V
0V
Analog input
K2000
WX2 K0
Refresh Refresh
Conversion
standby 1ms × number of
time: (1ms)
0ms to expansion units
scan time
DC/DC converter
insulation
+5V
Photocoupler
insulation Analog output
6) The number for the input contact point being used varies
depending on the expansion location (see page 7 - 5).
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Output range Voltage range –10 to +10V
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Current range 0 to 20mA
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Digital input –10 to +10V K – 2000 to K + 2000 (HF830 to H07D0)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
0 to 20mA K0 to K4000 (H0 to H0FA0)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Resolution 1/4000
Conversion speed 500µs (see note 1)
Overall precision
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±1% F.S. or less (0 to 55°C/32 to 131°F)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
±0.6% F.S. or less (25°C/77°F)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Output impedence Voltage range 0.5Ω
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Maximum output Voltage range ±10mA
current
Allowable output Current range
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
300Ω or less
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
load resistance
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Insulation method (see note 2) Between analog output terminal to FP0 internal circuit:
Photocoupler insulation
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Between analog output terminal to analog I/O unit external power supply:
insulation-type DC/DC converter
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Between analog output terminal to analog input terminal:
insulation-type DC/DC converter
Number of output contact points
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
16 output contact points: analog output data (WY2) (see note 3)
Notes
1) The time noted below is required before the analog data is
reflected in the control unit output.
K2000
K0
WY2
10V
0V
Analog output
Refresh Waiting for Conversion time
1ms × number of processing (500µs)
expansion units 0ms to
scan time
3000
5.0 1000
2000
7.5 1500
10.0 2000
1000 12.5 2500
15.0 3000
0 17.5 3500
5 10 15 20(mA)
20.0 4000
Analog input range
3000
1.0 800
1.5 1200
2000 2.0 1600
2.5 2000
1000 3.0 2400
3.5 2800
0
4.0 3200
1 2 3 4 5(V) 4.5 3600
Analog input range
5.0 4000
Voltage range: –10 to +10V DC input Corresponding table of A/D conversion values
(K)
Input voltage (V) A/D conversion value
2000
–10.0 –2000
A/D conversion value
–7.5 –1500
1000
–5.0 –1000
0 –2.5 –500
–10 –5 5 10 (V)
0.0 0
–1000 +2.5 +500
+5.0 +1000
–2000 +7.5 +1500
Analog input range
+10.0 +2000
Thermocouple input
Setting a temperature higher than the temperature of the terminal using the analog
mode switch (see page 4-3)
(K type
(K)
thermocouple) Corresponding table of A/D conversion values
1000
Temperature (°C) A/D conversion value
(J type
A/D conversion value
Thermocouple input
Setting a temperature lower than the temperature of terminal using the analog mode
switch (see page 4-3)
Thermocouple input range
Corresponding table of A/D conversion values
–100(°C) –75 –50 –25 Temp. of
terminal
Temperature (°C) A/D conversion value
0
Temp. of Temperature of terminal Temperature of terminal
terminal
Voltage range: –10 to +10V DC output Corresponding table of D/A conversion values
(V)
10 Digital input value Output voltage (V)
–2000 –10.0
Output signal range
5 –1500 –7.5
–1000 –5.0
0
–500 –2.5
–2000 –1000 1000 2000(K)
0 0.0
–5
+500 +2.5
+1000 +5.0
–10
+1500 +7.5
Digital input
+2000 10.0
15 1000 5.0
1500 7.5
10 2000 10.0
2500 12.5
5 3000 15.0
3500 17.5
4000 20.0
0
1000 2000 3000 4000 (K)
Digital input
Processing if the range is exceeded
Digital input value Analog output value
Negative value Constant (value just
before negative value is
input)
4001 or more Constant (value just
before 4001 is input)
4.5 Wiring
Input instrument V
V
(CH1) OUT I
OUT I Input instrument
COM
COM (CH1)
Connect input instrument between IN/V and First, connect both IN/V terminal and IN/I terminal.
IN/COM terminal. And then connect input instrument between it and
IN/COM terminal.
Thermocouple Thermocouple
V (CH1) V (CH1)
OUT I OUT I
COM COM
Connect IN/V terminal to the (+) side of the Connect IN/V terminal to the (–) side of the
thermocouple, and connect IN/COM terminal to the (–) thermocouple, and connect IN/COM terminal to the
side of the thermocouple. (+) side of the thermocouple.
V0 V0
I0 I0
IN COM IN COM
V1 V1
I1 Output I1 Output
instrument instrument
V V
OUT I OUT I
COM COM
Connect output instrument between OUT/V and Connect output instrument between OUT/I and
OUT/COM terminal. OUT/COM terminal.
Notes
Always make sure the switch settings and the terminal base
wiring connections match. For output, in particular, if the
settings and the wiring connections are wrong, the control
unit will output values like those shown below, even in the
PROG. mode. (For information on switch settings,
see page 4-3)
ÁÁÁÁÁÁ
Item Output terminal (OUT)
ÁÁÁÁÁÁ
Current terminal (I) Voltage terminal (V)
ÁÁÁÁÁÁ
0mA output based on current range
0mA –10V
setting
0V output based on voltage range
setting
Example:
Offset error
Temperature (C)
200
of terminal
Logical
Value
100
Measured value
K100 K107 K200 K207
Digital value (WX2)
In the above case, seven should be subtracted from the value of WX2.
R9010
F27 (–), WX2, K7, DT100
The value with the offset value of “7” subtracted is stored at DT100.
Note
We recommend initiating correction using the offset value taken
approximately 5 minutes after power is turned ON in order to
take into consideration the heat generated by the unit itself.
Reading 18msec
time 1m 1m 1m 1m
sec sec sec sec
ch1 ch1 ch1 ch1 ch1 ch1 ch1 ch1 ch1 ch1 ch1 ch1 ch1 ch1 ch1 ch1 ch1 ch1
ch0 ch0 ch0 ch0 ch0 ch0 ch0 ch0 ch0 ch0 ch0 ch0 ch0 ch0 ch0 ch0 ch0 ch0
100 90 110 100 1800 1850 1900 1830 1870 1910 1780 1810 1950
(110+100+1800+1850+1900+1830+
90 110 100 1800 1850 1900 1830 1870 1910 1780 1870+1780)÷8=1405
min max
(110+1800+1850+1900+1830+
110 100 1800 1850 1900 1830 1870 1910 1780 1810 1870+1780+1810)÷8=1618.75
min max
(1800+1850+1900+1830+
100 1800 1850 1900 1830 1870 1910 1780 1810 1950 1870+1910+1780+1810)÷8
min max =1843.75
Digital K1843
K1618
output value K1405
for ch0 K1195
18msec
Starting with the most recent data, the data from the last ten times is taken. The
maximum and minimum values are deleted, and then averaging is carried out on the
remaining eight items. The value obtained from the most recent averaging is normally
used as the value output at this time. (If a fraction results from the calculation, it is
rounded off.)
When the input range is set to a thermocouple (K, J or T type), processing like that
shown below is carried out internally in the analog I/O unit.
560msec
Starting from the most recent data, the data from the last five times is taken. The
maximum and minimum values are deleted, and then averaging is carried out on the
remaining three items. The value obtained from the most recent averaging is normally
used as the value output at this time. (If a fraction results from the calculation, it is
rounded off.)
Note
In the read timing, the minimum and maximum values are
subtracted from the data from the last ten times, just as in
averaging processing on page 4-17, and the data from the
remaining eight times is used for the averaging.
70msec 70msec
ch1 ch1
ch0
STATION
COM.
Operating condition
Station number
0
No.
display LEDs
selection switches ALARM
0
1
2
MODE
Operation mode 3
selection switch 4
OFF ON
RS485
+
RS485 transmission
line terminals – Sunken terminal
fixing screws
–
FP0–IOL
No.
– Sets the station number of the FP0 I/O Link Unit.
– The working range is 01–32 .
0
lower – If the switches are not within this range, a selection error will
occur and communication will be impossible.
Note
In case of a selection error, the ALARM LED will flash.
Notes
Switches 1 and 2 must always be set the same (ON or OFF).
In case I/O Link error flag is valid, the MSB (most significant
bit) of the 2 words allocated [32 bit: WX (n, n+1)] is assigned
as an error flag to the Control Unit (0: normal, 1: abnormal).
5.3 Specifications
Note
If the I/O Link error flag is on (valid), there are 63 I/O points (Input
31 points + Output 32 points).
Cable Cross–section
Twisted pair shield jacket
with shield
conductor insulator
VCTF molding
jacket
conductor insulator
Notes
1) The electric characteristic of polyvinyl chloride is inferior to
polyethylene, so the maximum communication distance is
short.
2) Twisted pair cable should be a shielded type.
3) Use only one type of communication cable, i.e. do not mix
cable types.
4) Twisted pair cable should especially be used in an
environment with extensive noise.
5) If AFP3740, AFP87441, AFP87442, AFP3741 are in the network,
the communication distance should be limited as stated
above.
Communication Communication
FG cable Communication FG
cable
cable
When connecting the communication cable, be sure to connect the side terminal of
a slave station to the side terminal of the FP0 I/O Link Unit, and the side terminal
of a slave station to the side terminal of the FP0 I/O Link Unit. No more than two pairs
of cables should be connected to one RS485 port.
slave station
Correct
slave station slave station slave station slave station slave station slave station
Be sure to follow the wiring diagram and the terminal symbol sheet when setting up your
system.
Tightening torque for both terminals and fixing screws must be 0.5 to 0.6 Nm (5.1 to 6.1
kgfcm).
Parallel connection
(multi–conductor cable)
FP0 FP0
Using the serial connector, the FP0 I/O Link Unit works as the slave station of the
Remote I/O System. The FP0 I/O Link Unit exchanges I/O information with the
FP3/FP10SH. Use a two–conductor cable to connect the FP3/FP10SH and the FP0 I/O
Link Unit. To connect the FP0 I/O Link Unit and the FP0 Control Unit or FP0 Expansion
Unit, use an expansion connector. The FP0 I/O Link Unit functions as a buffer. The
output from the FP3/FP10SH is sent to the input of the FP0 through the FP0 I/O Link
Unit. The output from the FP0 is sent to the input of the FP3/FP10SH from the FP0 I/O
Link Unit. Be sure to connect the FP0 I/O Link Unit with one FP3/FP10SH Master Unit.
Without a master station, the slave station (including FP0 I/O Link Unit) will not work.
FP3/FP10SH
Master Unit
Serial connection
(two–conductor cable)
I/O I/O
Link Link
Unit Unit
FP0 FP0
To connect the FP0 I/O Link Unit to the FP0, add an expansion unit to the main (or
another) unit. Three FP0 I/O Link Units can be connected to one FP0 Control Unit.
WX2,3,WY2,3
one–unit FP0 FP0
expansion: Control Unit I/O Link Unit
Notes
This flag indicates the state of the communication condition
between the FP0 I/O Link Unit and the Master Unit. If a
communication error occurs at other slave stations while the
Master Unit’s operation mode switch No. 7 (communication
error operation mode) is set to ”0” (operation stop mode), this
flag turns on.
This flag is assigned the MSB (most significant bit) of Input 2
words [32bits: WX (n, n+1)] in the FP0 I/O Link Unit. For
details, see page 5-11, Example 1.
Example 1:
Below is an example of the Remote I/O System connected to
the FP0 I/O Link Unit. (I/O link error flag is invalid.)
FP3/FP10SH
Power supply
Master Unit
next page
Accordingly, the I/O number of the individual FP0 I/O Link Unit
identified by the FP3/FP10SH is determined by the base word
number of the Master Unit and the station number of the FP0
I/O Link Unit.
In the remote I/O map, the Input numbers are allocated first.
For example, in the drawing shown above, when the FP0 I/O
Link Unit of station no. 1 is connected to a Master Unit whose
base word number is 64, the input number from the
FP3/FP10SH to the FP0 I/O Link Unit is WX64 and 65 (X640 to
65F), and the output number is WY66 and 67 (Y660 to 67F).
When the FP0 I/O Link Unit of station no. 2 is connected in the
same manner, the input number from FP3/FP10SH to the FP0
I/O Link Unit is WX68 and 69 (X680 to 69F), and the output
number is WY70 and 71 (Y700 to 71F).
The relationship between the input/output of the FP3/FP10SH
and that of the FP0 from the illustration above is shown below:
FP3/FP10SH I/O map I/O Link Unit FP0 I/O map
WY2,3 (Y20 to 3F) Output
Input WX64,65 (X640 to 65F) WX2,3 (X20 to 3F) Input
Output WY66,67 (Y660 to 67F) Station No. 1
(first expansion)
Input WX68,69 (X680 to 69F)
Output WY70,71 (Y700 to 71F) WY2,3 (Y20 to 3F) Output
WX2,3 (X20 to 3F) Input
Station No. 2
(first expansion)
For example, when the Y20 in the FP0 at station no. 1 turns
ON, the X640 in the FP3/FP10SH turns ON. When the Y660 in
the FP3/FP10SH turns ON, the X20 in the FP0 at station no. 1
turns ON. Similarly, when the Y20 in the FP0 at station no. 2
turns ON, the X680 in the FP3/FP10SH turns ON. When the
Y700 in the FP3/FP10SH turns ON, the X20 in the FP0 at
station no. 2 turns ON. In this way, the FP0 I/O Link Unit can
exchange I/O information between the FP3/FP10SH and the
FP0.
Example 2:
Remote I/O system in which the FP0 Control Unit has one FP0
I/O Link Unit. (I/O Link error flag is valid.)
FP3/FP10SH
Power supply
Master Unit
The base word number that the Master Unit
I/O
CPU at the left can control is 64.
As this X3F is allocated as the I/O Link error flag in the FP0 I/O
map, Y67F and Y71F in the FP3/FP10SH I/O map are invalid.
Example 3:
Remote I/O system in which the FP0 Control Unit has 3 FP0 I/O
Link Units.
Power supply FP3/FP10SH
Master Unit
CPU
The base word number that the Master Unit at the left can
I/O
control is 64.
To other slave
Communication cable stations
FP0 FP0
Control I/O Link I/O Link I/O Link Control I/O Link
Unit Unit Unit Unit Unit Unit
I/O Number
at FP0 WY2,3 WY4,5 WY6,7 WY2,3
Control WX2,3 WX4,5 WX6,7 WX2,3
Unit
I/O Number
at Remote WY64,65 WY68,69 WY72,73 WY76,77
Master WX66,67 WX70,71 WX74,75 WX78,79
Unit
Here the Remote I/O Master Unit recognizes I/O numbers such
that 2 words of input are allocated first. A total of 4 words are
allocated per station.
Each FP0 Control Unit can be expanded by three FP0 I/O Link
Units. All exchanges between the Master Unit and FP0 I/O Link
Unit are carried out via allocated Inputs and Outputs.
6.2 Specifications
Performance Specifications
Primary Rated operating voltage 115/230V AC
Side
Operating voltage range 85 to 265V AC
Rated operating frequency 50/50Hz
Operating frequency range 40 to 70Hz
Inrush current <50A at 55C/131_F
Current consumption 145mA (at 230V and 0.7A output current)
Over voltage protection PROTECTED
Secondary Rated output voltage 24V DC
Side
Output voltage range 23.5V to 24.5V DC
Nominal output current 0.7A
Output current range 0 to 0.7A
Output ripple <60mVpp
Short circuit protected electronic, automatic restart mode
Over voltage protected Yes
Over load protected Yes (switch off at ~0.8A and more)
Holding time min. 20ms at 230V AC
General Specifications
Characteristics primary switched, temperature and current peak controlled
Ambient temperature 0C/32_F to +55C/131_F
Storage temperature –20C/–4_F to +70C/158_F
Ambient humidity 5 to 95% non condensing
Storage humidity 5 to 95% non condensing
Vibration resistance 10 to 55Hz, 1 cycle/min., double amplitude of 0.75mm, 10 min.
on 3 axes
Shock resistance 10g min., 4 times on 3 axes
Life time min. 7 years at nom. load, 25C/77_F ambient temperature, 20000h
at 55C/131_F with full load/continuous operation
Mounting DIN rail or FPO flat attachment plate
Size 90× 60× 30.4mm
Input connector AC side MC connector, 2 pin
Output connector DC connector, 6 pin, 3 pins for “+” and 3 pins for “–”
Status display LED (green) at the front side for the secondary voltage indica-
tion
Note
Before you turn the power on, see page 10 - 2.
I/O Allocation
I/O Allocation FP0 Hardware
Example:
External input relay (X)
X0, X1 . . . . . . . . . . . . . . . . . . . . . . . . XF
X10, X11 . . . . . . . . . . . . . . . . . . . . . . X1F
Decimal X20, X21 . . . . . . . . . . . . . . . . . . . . . . X2F
1, 2, 3 . . . . . . . .
Hexadecimal
0, 1, 2, 3 . . . . . . . . A,B . . . . F
ÁÁÁÁÁ
ÁÁÁÁÁ
Type I/O number
ÁÁÁÁÁ
C10RS, C10CRS Input: 6 points X0 to X5
Output: 4 points Y0 to Y3
C14RS, C14CRS Input: 8 points
ÁÁÁÁÁ
X0 to X7
Output: 6 points
ÁÁÁÁÁ
Y0 to Y5
C16T, C16CT, C16P, C16CP Input: 8 points
Output: 8 points ÁÁÁÁÁ
X0 to X7
ÁÁÁÁÁ
Y0 to Y7
ÁÁÁÁÁ
C32T, C32CT, C32P, C32CP, T32CP Input: 16 points X0 to XF
Output: 16 points Y0 to YF
I/O number
ÁÁÁÁÁ ÁÁÁÁÁ
ÁÁÁÁÁ
Type First Second Third
expansion expansion expansion
E8RS Input: 4 points
Output: 4 points ÁÁÁÁÁ ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
X20 to X23
ÁÁÁÁÁ
Y20 to Y23
X40 to X43
Y40 to Y43
X60 to X63
Y60 to Y63
E8X Input: 8 points
ÁÁÁÁÁ ÁÁÁÁÁ
ÁÁÁÁÁ
X20 to X27 X40 to X47 X60 to X67
ÁÁÁÁÁ ÁÁÁÁÁ
ÁÁÁÁÁ
E8YT/E8YP Output: 8 points Y20 to Y27 Y40 to Y47 Y60 to Y67
ÁÁÁÁÁ ÁÁÁÁÁ
ÁÁÁÁÁ
E16RS/E16T/E16P Input: 8 points X20 to X27 X40 to X47 X60 to X67
ÁÁÁÁÁ ÁÁÁÁÁ
ÁÁÁÁÁ
Output: 8 points Y20 to Y27 Y40 to Y47 Y60 to Y67
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
E16X Input: 16 points X20 to X2F X40 to X4F X60 to X6F
E16YT/E16YP Output: 16 points Y20 to Y2F Y40 to Y4F Y60 to Y6F
E32T/E32P Input: 16 points
ÁÁÁÁÁ ÁÁÁÁÁ
ÁÁÁÁÁ
X20 to X2F X40 to X4F X60 to X6F
Output: 16 points
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Y20 to Y2F Y40 to Y4F Y60 to Y6F
Third expansion
Second expansion
First expansion
Control unit
I/O number
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
Type First Second Third
expansion expansion expansion
A21
ÁÁÁÁÁÁ
Input channel 0:
ÁÁÁÁÁ
WX2
ÁÁÁÁÁÁ WX4 WX6
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
16 points (X20 to X2F) (X40 to X4F) (X60 to X6F)
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
Input channel 1: WX3 WX5 WX7
16 points (X30 to X3F) (X50 to X5F) (X70 to X7F)
ÁÁÁÁÁÁ
Output: 16 points
ÁÁÁÁÁ
WY2
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
(Y20 to Y2F)
WY4
(Y40 to Y4F)
WY6
(Y60 to Y6F)
Third expansion
Second expansion
First expansion
Control unit
Installation
Installation FP0 Hardware
Notes
Avoid installing the unit in the following locations:
– Ambient temperatures outside the range of 0°C to
55°C/32°F to 131°F
– Ambient humidity outside the range of 30% to 85% RH
– Sudden temperature changes causing condensation
– Inflammable or corrosive gases
– Excessive airborne dust or metal particles
– Benzine, paint thinner, alcohol or other organic
solvents or strong alkaline solutions such as
ammonia or caustic soda
– Excessive vibration or shock
– Direct sunlight
– Water in any form including spray or mist
Avoid noise interference from the following items:
– Influence from power transmission lines, high voltage
equipment, power cables, power equipment, radio
transmitters, or any other equipment that would
generate high switching surges
– If noise occurs in the power supply line even after the
above countermeasures are taken, it is recommended
to supply power through an insolated transformer,
noise filter, or the like.
Measures regarding heat discharge
– Always install the unit orientated with the tool port
facing outward on the bottom in order to prevent the
generation of heat.
Tool port
ÉÉÉÉÉÉÉÉÉÉÉ
ÉÉÉÉÉÉÉÉÉÉÉ 50mm/1.97in. or more
FP0
ÉÉÉÉÉÉÉÉÉÉÉ
50mm/1.97in. or more
ÉÉÉÉÉÉÉÉÉÉÉ
– Maintain a minimum of 100mm/3.937in. between
devices to avoid adverse affects from noise and heat
when installing a device or panel door to the front of
the FP0 unit.
ÉÉ 100mm/3.937in.
ÉÉ
ÉÉ or more
ÉÉ
ÉÉ
ÉÉ ÉÉ
ÉÉ
ÉÉ ÉÉ
Other device or panel door
ÉÉ ÉÉ
FP0
ÉÉ ÉÉ
ÉÉ
ÉÉ ÉÉ
ÉÉ
ÉÉ ÉÉ
– Keep the first 100mm/3.937in. from the front surface of
the FP0 control unit open in order to allow room for
programming tool connections and wiring.
Seal
When peeling the seal on the side of the initial lot products, the shaded
part is exposed. Cut off the shaded part with a pair of nippers or similar
tool so that the internal connector is exposed.
Shaded part
Cut here.
When removing the shaded part, use a sharp cutting object, making sure
that the shaded part is removed leaving a smooth surface. Note that
failure to remove the shaded part completely can result in damage to the
connector.
3. Align the pins and holes in the four corners of the control
unit and expansion unit, and insert the pins into the holes
so that there is no gap between the units.
Control unit
Expansion unit
FP0 unit
DIN rail
2
FP0 unit
DIN rail
3
1 2
Slotted screwdriver
Screw
6.0mm/0.236in.
Procedure:
1. Fit the upper hook of the FP0 unit onto the FP0 slim type
mounting plate.
2. Without moving the upper hook, press on the lower hook to
fit the FP0 unit into position.
1
FP0 slim type
mounting plate
FP0 unit
When using an expansion unit, tighten the screws after joining all of the FP0 slim type
mounting plate to be connected. Tighten the screws at each of the four corners.
Dia. 5.0/0.197
Dia. 5.0/0.197
60.0/2.362
Procedure:
1. Raise the expansion hooks on the top and bottom of the
unit.
2. Install the FP0 unit on the FP0 flat type mounting plate.
3. Align the expansion hooks with the plate and press the
hooks back down.
1
3
FP0 flat type mounting
plate
3
1
Notes
The FP0 flat type mounting plate (AFP0804) cannot be used for
an expansion unit.
An FP0 unit with an attached FP0 flat type mounting plate can
also be installed sideways on a DIN rail.
DIN rail
Wiring
Wiring FP0 Hardware
Note
When stopping the operation of FP0, also have the I/O devices
turned OFF after the FP0 has stopped operating.
Green:
Function earth
(Frame ground)
Blue: 0V
Brown:
24V DC
Item Descriptions
Rated voltage 24V DC
Operating voltage range 21.6 to 26.4V DC
Notes
To minimize adverse effects from noise, twist the brown and
blue wires of the power supply cable.
To protect the system against erroneous voltage from the
power supply line, use an insulated power supply with an
internal protective circuit.
The regulator on the FP0 unit is a non-insulated type.
If using a power supply device without an internal protective
circuit, always make sure power is supplied to the unit
through a protective element such as a fuse.
Motor
devices
Insulated
DC I/O devices
power
supply
Insulated
DC
FP0
power
supply
9.3 Grounding
Under normal conditions, the inherent noise resistance is sufficient. However, in
situations of excess noise, ground the instrument to increase noise suppression.
For grounding purposes, use wiring with a minimum of 2mm2. The grounding
connection should have a resistance of less than 100W.
Other Other
FP0 device FP0 device
CORRECT
Notes
The point of grounding should be as close to the FP0 control
unit as possible. The ground wire should be as short as
possible.
If two devices share a single ground point, it may produce an
adverse effect. Always use an exclusive ground for each
device.
Depending on the surroundings in which the equipment is
used, grounding may cause problems.
Example:
Since the power supply line (24V DC and GND terminal) of the
FP0 power supply connector is connected to the frame ground
(F.G.) through a varistor, the varistor may be shorted out if
there is an irregular potential between the power supply line
(24V DC and GND) and ground.
Power supply connector of FP0
control unit
24V DC
Power supply
lines
GND
Varistor Varistor (39V DC)
F.G.
Notes
Be sure to select the thickness (dia.) of the input wires while
taking into consideration the required current capacity.
Arrange the wiring so that the input and output wiring are
separated, and so that the input wiring is separated from the
power wiring, as much as possible. Do not route them through
the same duct or wrap them up together.
Separate the input wires from the power and high voltage
wires by at least 100mm/3.937in.
In this section you find some examples for wiring sensors, an LED-equipped reed
switch, a two-wire type sensor and a LED-equipped limit switch.
9.4.1 Sensors
Relay output type NPN open collector output type
Sensor
FP0
COM
Internal
circuit
Power supply for input
Input
terminal
LED-equipped 19.2V DC
reed switch or more FP0
COM
24V DC
Input terminal
Two-wire Bleeder
type sensor resistor FP0
COM
Internal
circuit
The OFF voltage of the FP0 input is 2.4V, therefore, select an R value so that the voltage between the
COM terminal and the input terminal will be less than 2.4V.
Input
LED-equipped terminal
limit switch
Bleeder FP0
resistor
COM
Internal circuit
Notes
There is no fuse protection built into the output circuit.
Therefore, in order to protect against overheating of the output
circuitry caused by possible short circuits, install an external
fuse at each point. However, in case of a short circuit, the
control unit itself may not be protected.
Be sure to select the thickness (dia.) of the output wires while
taking into consideration the required current capacity.
Arrange the wiring so that the input and output wiring are
separated, and so that the output wiring is separated from the
power wiring, as much as possible. Do not route them through
the same duct or wrap them up together.
Separate the output wires from the power and high voltage
wires by at least 100mm/3.937in.
Protect the outputs as described below.
COM
AC inductive load
Varistor
Output
terminal
FP0
COM
AC inductive load
Output
terminal
FP0
COM
DC inductive load
(*) Diode:
Reverse voltage (VR): 3 times the load voltage
Average rectified forward current (I0): Load current or more
Inductor
Output
Load
terminal
FP0
COM
Suitable wire
When tightening the terminals of the terminal block socket, use a screwdriver (Phoenix
Contact Co., Product no. 1205037) with a blade size of 0.4 × 2.5. The tightening torque
should be 0.22 to 0.25Nm (2.3 to 2.5kgfcm) or less.
Procedure:
1. Remove a portion of the wire’s insulation.
Suitable wire
7mm/0.276in.
Wire
Notes
When removing the wire’s insulation, be careful not to scratch
the core wire.
Do not twist the wires to connect them.
Do not solder the wires to connect them. The solder may
break due to vibration.
After wiring, make sure stress is not applied to the wire.
In the terminal block socket construction, if the wire closes
upon counter-clockwise rotation, the connection is faulty.
Disconnect the wire, check the terminal hole, and then
re-connect the wire.
Clockwise Counter
clockwise
Wire
Wire
CORRECT INCORRECT
4. When all wires has been inserted, fit the semi-cover into
place.
semi-cover
Note
If using a MIL connector for flat cables, please specify the order
number AXM110915.
Item Specification
Baud rate 300/600/1200/2400/4800/9600/19
200bps
Transmission 3m/9.84ft.
distance
Terminal block Made by Phoenix Contact Co.
(3-pin)
Product number: MKDS 1/3-3.5
Communication half-duplex
method
RS232C port
Settings when shipped from the factory
terminal layout
These are changed using system registers
412 to 414. The settings in effect when the
unit is shipped from the factory are noted
below.
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
412 RS232C port is not used.
SG: Signal Ground
ÁÁÁÁÁÁÁÁÁÁÁÁ
413 Character bit: 8 bits
RD: Receive Data Parity check: odd
ÁÁÁÁÁÁÁÁÁÁÁÁ
Stop bit: 1 bit
SD: Send Data Header: without STX code
ÁÁÁÁÁÁÁÁÁÁÁÁ
Terminator: CR
414 Baud rate: 9600bps
Suitable wire
7mm/0.276in.
2. Insert wire into the RS232C port until it contacts the back of
the RS232C port.
RS232C port
Suitable wire
Clockwise
Notes
When removing the wire’s insulation, be careful not to scratch
the core wire.
Do not twist the wires to connect them.
Do not solder the wires to connect them. The solder may
break due to vibration.
After wiring, make sure stress is not applied to the wire.
In the RS232C port terminal construction, if the wire closes
upon counter-clockwise rotation, the connection is faulty.
Disconnect the wire, check the terminal hole, and then
re-connect the wire.
Clockwise Counter
clockwise
Wire
Wire
CORRECT INCORRECT
Trial Operation
Trial Operation FP0 Hardware
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Item Description
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Unit mounting status S Does the unit type match the device list during the design stage?
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
S Are all of the units firmly attached?
Power supply
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
S Is operating voltage supplied correctly?
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
S Is the power supply cable properly connected?
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
S Are both voltage and polarity connected correctly for each
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
connection?
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
S Protection against excess current: when overloaded, output voltage
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
lowers. Although the output voltage will return to normal when the
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
load returns to normal, be careful as long overloads or shortcircuits
will cause deterioration or destruction of internal elements. (see
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
note)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
S When output voltage decreases due to a generation of excess
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
voltage within the power supply, turn off the AC input for at least
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
one minute. After that turn the input on again. (see note)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
S Attaching additional power supply units in parallel is not allowed! It
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
may destroy internal elements and the load of the power supply.
(see note)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Check input/output terminals S Does the wiring of connector and terminal match?
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
S Is the operating voltage of I/O correct?
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
S Are the connectors of I/O properly connected?
Note
These precautions concern the FP0–PSA2 power supply unit
specifically.
Status
indicator
LEDs
Program
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ ÁÁÁÁ
LED status
Condition Description execution
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ ÁÁÁÁ
RUN PROG. ERROR/ALARM status
ÁÁÁÁÁ ÁÁÁÁÁ
ÁÁÁÁÁ ÁÁÁÁ
Normal operation in RUN
ON OFF OFF Operation
mode
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ ÁÁÁÁ
Normal Normal operation in PROG.
condition OFF ON OFF Stop
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ ÁÁÁÁ
mode
Blink OFF OFF Forcing ON/OFF in RUN mode Operation
Abnormal ÁÁÁÁÁ
ON
ÁÁÁÁÁ
ÁÁÁÁÁ ÁÁÁÁÁ
ÁÁÁÁÁ
OFF
ÁÁÁÁÁ
OFF
ON
Blink
Blink
When a self-diagnostic error
occurs ÁÁÁÁ
Operation
ÁÁÁÁ
Stop
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ ÁÁÁÁ
condition When a system watchdog
Varies Varies ON Stop
timer error occurs
11.2 Troubleshooting
<Condition>
The self-diagnostic error occurs.
<Procedure 1 >
Check the error code using the programming tool.
Using NPST-GR software
In the ONLINE mode, select “STATUS DISPLAY.” At the bottom of the “STA-
TUS DISPLAY” window, you can find the error code.
SLF DIAGN ERR CD ( ) [ ]
Error code is 1 to 9
<Condition>
There is a syntax error in the program.
<Procedure 1 >
Change to PROG. mode and clear the error.
<Procedure 2>
Execute a total-check function to determine the location of the syntax error.
Refer to your software manual for details about the total-check method.
<Procedure 1 >
Use the programming tool in PROG. mode to clear the error.
D In the PROG. mode, the power supply can be turned OFF and then ON
again to clear the error, but all of the contents of the operation memory
except hold type data are cleared.
D An error can also be cleared by executing a self-diagnostic error set
instruction F148 (ERR).
<Procedure 2>
Follow the procedures described in the table of error codes (see page 11-12).
Note
When an operation error (error code 45) occurs, the address at
which the error occurred is stored in special data registers
DT9017 and DT9018. If this happens, monitor the address at
which the error occurred before cancelling the error.
<Condition>
The system watchdog timer has been activated and the operation of FP0 has been
stopped.
<Procedure 1 >
Set the mode switch from RUN to PROG. and turn the power OFF and then ON.
<Procedure 2>
Set the mode switch from PROG. to RUN.
If the ERROR/ALARM LED is turned ON, the program execution time is too long.
Check:
D if instructions such as JP or LOOP are programmed in such a way
that a scan can never finish.
D that interrupt instructions are executed in succession.
<Procedure 1 >
Check the power supply wiring.
<Procedure 2>
Check if the power supplied to the FP0 control unit is in the range of the rating.
Be sure to check the fluctuation in the power supply.
<Procedure 3>
Disconnect the power supply wiring to the other devices if the power supplied to the
FP0 control unit is shared with them.
If the LEDs on the FP0 control unit turn ON at this moment, the capacity of the
power supply is not enough to control other devices as well.
Prepare another power supply for other devices or increase the capacity of the
power supply.
<Procedure 2>
Check if the power is properly supplied to the loads.
If the output monitored is turned ON, there is probably a duplicated output error.
<Procedure 2>
Forcing ON the output using a programming tool.
<Procedure 2>
Check that the power is properly supplied to the input terminals.
If the power is properly supplied to the input terminal, there is probably an abnor-
mality in the FP0’s input circuit. Please contact your dealer.
If the power is not properly supplied to the input terminal, there is probably an
abnormality in the input device or input power supply. Check the input device and
input power supply.
If the input monitored is OFF, there is probably an abnormality in the FP0’s input
circuit. Please contact your dealer.
If the input monitored is ON, check the program again.
Also, check the leakage current at the input devices (e.g., two-wire type sensor)
and check for the duplicated use of output or the program flow when a control in-
struction such as MC or JP is used.
Check the settings of the I/O allocation.
In this window, you can find the baud rate as shown below:
TRNS RATE (bps) [115k / 57k / 38k /19200 / 9600 / 4800 / 2400 ]
Select a baud rate (9600), press <F1> and select “SAVE DISK? YES” to regis-
ter this change onto the disk.
Using FPWIN GR
Option –> Communication Settings
Using FPWIN Pro
Online –> Communication Parameters
Settings on the FP0 side
The baud rate of the FP0 control unit is factory set to 9,600bps.
<Procedure 2>
Check the FP PC cable and RS232C port adapter.
<Procedure 3>
Confirm the setting of the computer referring to the manual for your computer.
Using FPWIN GR
Tool –> Set PLC Password
<Procedure >
Execute a total-check function to determine the location of the syntax error.
Refer to your software manual for details about the total-check method.
System Registers
System Registers FP0 Hardware
Moreover in FPWIN Pro, there is an “Additional Information” column for each System
Register that briefly explains its use.
Using FPWIN GR
For more details about system register settings, see “Control FPWIN GR
Operational Guide Book.”
Using FP programmer II
Procedure:
1. Set the mode of the FP0 control unit to PROG.
2. Press the keys on the FP programmer II,
as shown on the right. ACLR
(–)
OP
5 0 ENT
is changed from PROG. to RUN. With regard to the modem connection setting, when
the power is turned on or when the mode is changed from PROG. to RUN, the controller
sends a command to the modem which enables it for reception.
When the initialized operation is performed, all set system register values (parameters)
will be initialized.
Setting example
To increase the number of timers to 120, change the value of system register 5 to K120.
MIN (0): All counter
0
Hold types and non–hold type settings (System registers 6 to 8 and 14)
With the FP0, the areas held in the event of a power supply interruption are fixed at the
areas shown in the table below, and the settings for system registers 6 to 8 and 14, will
be invalid.
C10/C14/C16 series
Timer Non-hold type: All points
Counter Non-hold type: From the set value to C139
Hold type: 4 points (elapsed values)
C140 to C143
Internal relay Non-hold type: 976 points (R0 to R60F)
61 words (WR0 to WR60)
Hold type: 32 points (R610 to R62F)
2 words (WR61 to WR62)
Data register Non-hold type: 1652 words (DT0 to DT1651)
Hold type: 8 words (DT1652 to DT1659)
C32 series
Timer Non-hold type: All points
Counter Non-hold type: From the set value to C127
Hold type: 16 points (elapsed values)
C128 to C143
Internal relay Non-hold type: 880 points (R0 to R54F)
55 words (WR0 to WR54)
Hold type: 128 points (R550 to R62F)
8 words (WR55 to WR62)
Data register Non-hold type: 6112 words (DT0 to DT6111)
Hold type: 32 words (DT6112 to DT6143)
Note
For more information on performance specifications, also for the
T32CP unit, see page 2-8.
Default
Address Name of system register Set value (parameter)
value
Allocation 0 Sequence program area The set values are fixed and cannot be
of user capacity changed.
memory The stored values vary depending on the
model and type.
K3: 3 K words (FP0 C10, C14, C16)
K5: 5 K words (FP0 C32)
1 to 3 Unused
Hold/ 5 Timer and counter division K100 K0 to K144
Non– (setting of leading counter For detailed information, see page A-4.
hold number)
6 to 8 Unused With the FP0, values set with the program-
ming tool become invalid.
9 to 13 Unused
14 Unused With the FP0, values set with the program-
ming tool become invalid.
15 Unused
Action on 20 Disable or enable setting for K0 K0: Disable (will be syntax error)
error duplicated output K1: Enable (will not be syntax error)
21, 22 Unused
23 Operation setting when an I/O K0 K0: Stop
verification error occurs K1: Continuation
24, 25 Unused
26 Operation setting when an K0 K0: Stop
operation error occurs K1: Continuation
27 to 29 Unused
4 Unused With the FP0, values set with the program-
ming tool become invalid.
Default
Address Name of system register Set value (parameter)
value
Time 30 Unused
setting
31 Wait time setting for K2600 K4 to K32760: 10ms to 81900ms
multi-frame communication (6500ms) Use of default setting (K2600/ 6500ms) is
recommended.
set value × 2.5ms = Wait time setting for mul-
ti–frame communica-
tion (ms)
Default
Address Name of system register Set value (parameter)
value
Input 400 High-speed Setting by H0 CH0 0: Do not set input X0 as high-speed count-
setting counter mode FPWIN Pro, er.
settings (X0 to NPST-GR Ver. 1: 2-phase input (X0, X1)
X2) 4, or FPWIN
GR 2: 2-phase input (X0, X1),
Reset input (X2)
3: Incremental input (X0)
4: Incremental input (X0),
Reset input (X2)
5: Decremental input (X0)
6: Decremental input (X0),
Reset input (X2)
7: Individual input (X0, X1)
8: Individual input (X0, X1),
Reset input (X2)
9: Direction decision (X0, X1)
10:Direction decision (X0, X1),
Reset input (X2)
CH1 0: Do not set input X1 as high-speed count-
er.
3: Incremental input (X1)
4: Incremental input (X1),
Reset input (X2)
5: Decremental input (X1)
6: Decremental input (X1),
Reset input (X2)
Notes
If the operation mode is set to 2–phase, individual, or direction
differentiation, the setting for CH1 is invalid.
If reset input settings overlap, the setting of CH1 takes
precedence.
If system register 400 to 403 have been set simultaneously for
the same input relay, the following precedence order is
effective: [High–speed counter] –> [Pulse catch] –> [Interrupt
input].
Default
Address Name of system register Set value (parameter)
value
Input 400 High-speed Setting by FP H0 CH0/ 0: Do not use high-
setting counter mode programmer II CH1 H 0 0 speed counter.
settings (X0 to 1: 2-phase input (X0,
x2) X1)
2: 2-phase input (X0,
X1), Reset input
(X2)
3: Incremental input
(X0)
4: Incremental input
(X0), Reset input
(X2)
5: Decremental input
(X0)
6: Decremental input
(X0), Reset input
(X2)
7: Individual input (X0,
X1)
8: Individual input (X0,
X1), Reset input
(X2)
9: Direction dicision
(X0, X1)
A: Direction dicision
(X0, X1), Reset
input (X2)
0: Do not use high-
speed counter.
3: Incremental input
(X1)
4: Incremental input
(X1), Reset input
(X2)
5: Decremental input
(X1)
6: Decremental input
(X1), Reset input
(X2)
Notes
If the operation mode is set to 2–phase, individual, or direction
differentiation, the setting for CH1 is invalid.
If reset input settings overlap, the setting of CH1 takes
precedence.
If system register 400 to 403 have been set simultaneously for
the same input relay, the following precedence order is
effective: [High–speed counter] –> [Pulse catch] –> [Interrupt
input].
Default
Address Name of system register Set value (parameter)
value
Input 401 High-speed Setting by H0 CH2 0: Do not set input X3 as high-speed
setting counter mode FPWIN Pro, counter.
settings (X3 to NPST-GR Ver. 1: 2-phase input (X3, X4)
X5) 4, or FPWIN GR 2: 2-phase input (X3, X4), Reset input (X5)
3: Incremental input (X3)
4: Incremental input (X3), Reset input (X5)
5: Decremental input (X3)
6: Decremental input (X3), Reset input
(X5)
7: Individual input (X3, X4)
8: Individual input (X3, X4), Reset input
(X5)
9: Direction decision (X3, X4)
10:Direction decision (X3, X4), Reset input
(X5)
CH3 0: Do not set input X4 as high-speed
counter.
3: Incremental input (X4)
4: Incremental input (X4), Reset input (X5)
5: Decremental input (X4)
6: Decremental input (X4), Reset input
(X5)
Notes
If the operation mode is set to 2–phase, individual, or direction
differentiation, the setting for CH3 is invalid.
If reset input settings overlap, the setting of CH3 takes
precedence.
If system register 400 to 403 have been set simultaneously for
the same input relay, the following precedence order is
effective: [High–speed counter] –> [Pulse catch] –> [Interrupt
input].
Default
Address Name of system register Set value (parameter)
value
Input 401 High-speed Setting by FP H0 CH2/ 0: Do not use
setting counter mode programmer II CH3 H 0 0 high-speed
settings (X3 to counter.
X5) 1: 2-phase input (X3,
X4)
2: 2-phase input (X3,
X4),
Reset input (X5)
3: Incremental input
(X3)
4: Incremental input
(X3),
Reset input (X5)
5: Decremental input
(X3)
6: Decremental input
(X3),
Reset input (X5)
7: Individual input
(X3, X4)
8: Individual input
(X3, X4),
Reset input (X5)
9: Direction dicision
(X3, X4)
A: Direction dicision
(X3, X4),
Reset input (X5)
0: Do not use
high-speed
counter.
3: Incremental input
(X4)
4: Incremental input
(X4),
Reset input (X5)
5: Decremental input
(X4)
6: Decremental input
(X4),
Reset input (X5)
Notes
If the operation mode is set to 2–phase, individual, or direction
differentiation, the setting for CH3 is invalid.
If reset input settings overlap, the setting of CH3 takes
precedence.
If system register 400 to 403 have been set simultaneously for
the same input relay, the following precedence order is
effective: [High–speed counter] –> [Pulse catch] –> [Interrupt
input].
Default
Address Name of system register Set value (parameter)
value
Input 402 Pulse catch input function H0 X5 X4 X3 X2 X1 X0
setting 0: Standard input
settings 0 0 0 0 0 0 1: Pulse catch input
15 0
402: 00011000
X5 X4 X3 X2 X1 X0
H1 H8
Input H18
In the case of FP0, settings X6 and X7 are
invalid.
15 0
403: 000011 0011 11
X5 X4 X3 X2 X1 X0 X5 X4 X3 X2 X1 X0
H0 H3 H0 HF
Input H30F
404 to Unused With the FP0, values set with the program-
407 ming tool become invalid.
Notes
With the NPST–GR, “0” or “1” is set for each bit on the screen
in the setting for system register 403.
If system register 400 to 403 are set simultaneously for the
same input relay, the following precedence order is effective:
Default
Address Name of system register Set value (parameter)
value
Tool port 410 Unit number setting for tool K1 K1 to K32 (Unit No. 1 to 32)
setting port (when connecting
C–NET)
411 Communication format H0 Using FPWIN Pro or NPST–GR
setting for tool port Select items from the menu.
Using FP programmer II
Setting item Specify the setting contents using H
S Default setting value constants.
S Modem communication: 15 6 0
Disabled
S Data length (character bits):
8 bits
Modem communication
0: Disabled
1: Enabled
Data length
(character bits)
0: 8 bits
1: 7 bits
When connecting a modem, set the unit num-
ber to 1 with system resister 410.
414 Baud rate Setting by H0 0: 9600 bps
setting for tool FPWIN Pro 1: 19200 bps
port or NPST–GR
ver. 4
Tool port/ 414 Baud rate Setting by H1
RS232C setting for tool FP
H 0 0
port port and programmer
setting RS232C port II
RS232C port
Tool port
H0: 19200 bps
H0: 9600 bps
H1: 9600 bps
H1: 19200 bps
H2: 4800 bps
If anything other
H3: 2400 bps
than H0 or H1 is set
for the tool port baud H4: 1200 bps
rate, the baud rate H5: 600 bps
will be 9600 bps.
H6: 300 bps
Default
Address Name of system register Set value (parameter)
value
RS232C 412 Communication method K0 Using FPWIN Pro or NPST–GR, select
port setting for RS232C port items from the menu.
setting Using FP programmer II:
K0: RS232C port is not used.
K1: Computer link mode (when connecting
C–NET)
K2: Serial data communication mode (gener-
al port)
413 Communication format setting H3 Using FPWIN Pro or NPST–GR, select items
for RS232C port from the menu.
Setting item/Default setting Using FP programmer II:
value Specify the setting contents using H
– Start code: None constants.
– Terminal code: CR 15 6 0
– Stop bit: 1 bit
– Parity check: With odd
– Data length: 8 bits Start code 0: No STX 1: STX
Note
Used by the system.
Addresses Description
T32CP Other Types
DT90000 DT9000 Self–diagnostic error code
The self-diagnostic error code is stored here when a self-diagnostic
error occurs. Monitor the error code using decimal display.
For detailed information, see page 11-10.
DT90010 DT9010 I/O verify error unit
The position of the I/O for which an error occurred is stored in bits 0 to 3.
DT90014 DT9014 Auxiliary register for operation
One shift-out hexadecimal digit is stored in bit positions 0 to 3 when an F105 (BSR)
or F106 (BSL) instruction is executed.
DT90015 DT9015 Auxiliary register for operation
The divided remainder (16-bit) is stored in DT9015 when an F32 (%) or F52 (B%)
instruction is executed.
DT90016 DT9016
The divided remainder (32-bit) is stored DT9015 and DT9016 when an F33 (D%) or
F53 (DB%) instruction is executed.
DT90017 DT9017 Operation error address (hold)
After commencing operation, the address where the first operation error occurred is
stored. Monitor the address using decimal display.
DT90018 DT9018 Operation error address (non-hold)
The address where a operation error occurred is stored. Each time an error occurs,
the new address overwrites the previous address. At the beginning of scan, the ad-
dress is 0. Monitor the address using decimal display.
DT90019 DT9019 2.5 ms ring counter
The data stored here is increased by one every 2.5 ms. (H0 to HFFFF)
Difference between the values of the two points (absolute value) × 2.5 ms = Elapsed
time between the two points.
Addresses Description
T32CP Other Types
DT90022 DT9022 Scan time (current value) ( see note 1)
The current scan time is stored here. Scan time is calculated using the formula:
Scan time (ms) = stored data (decimal) × 0.1
K50 indicates 5 ms.
DT90023 DT9023 Scan time (minimum value) ( see note 1)
The minimum scan time is stored here. Scan time is calculated using the formula:
Scan time (ms) = stored data (decimal) × 0.1
K50 indicates 5 ms.
DT90024 DT9024 Scan time (maximum value) ( see note 1)
The maximum scan time is stored here. Scan time is calculated using the formula:
Scan time (ms) = stored data (decimal) × 0.1
K125 indicates 12.5 ms.
DT90025 DT9025 Mask condition monitoring register for interrupts(INT 0 to 5)
The mask conditions of interrupts using ICTL instruction can be moni-
tored here. Monitor using binary display.
15 11 7 3 0 (Bit No.)
23 19 16 (INT No.)
Notes
1) Scan time display is only possible in RUN mode, and shows
the operation cycle time. The maximum and minimum values
are cleared when each the mode is switched between RUN
mode and PROG. mode.
2) Used by the system.
Addresses Description
T32CP Other Types
DT90038 DT9038 Work 2 for F96 (SRC) instruction
The position of the first matching data, counting from the starting 16-bit area, is
stored here when an F96 (SRC) instruction is executed.
DT90039 to DT9039 to Not used
DT90043 DT9043
DT90044 DT9044 High-speed counter elapsed value for ch0
The elapsed value (24–bit data) for the high–speed counter is stored here. Each time
the ED instruction is executed, the elapsed value for the high–speed counter is auto-
DT90045 DT9045 matically transferred to the special registers DT9044 and DT9045.
The value can be written by executing a DMV (F1) instruction.
DT90046 DT9046 High-speed counter target value for ch0
The target value (24–bit data) of the high–speed counter specified by the high–speed
counter instruction is stored here.
DT90047 DT9047 Target values have been preset for the various instructions, to be used when the
high–speed counter related instruction F166 to F170 is executed. These preset val-
ues can only be read, and cannot be written.
DT90048 DT9048 High-speed counter elapsed value area for ch1
The elapsed value (24–bit data) for the high–speed counter is stored here. Each time
the ED instruction is executed, the elapsed value for the high–speed counter is auto-
DT90049 DT9049 matically transferred to the special registers DT9048 and DT9049.
The value can be written by executing a DMV (F1) instruction.
DT90050 DT9050 High-speed counter target value area for ch1
The target value (24–bit data) of the high–speed counter specified by the high–speed
counter instruction is stored here.
DT90051 DT9051 Target values have been preset for the various instructions, to be used when the
high–speed counter related instruction F166 to F170 is executed. These preset val-
ues can only be read, and cannot be written.
Addresses Description
T32CP Other Types
DT90052 DT9052 High-speed counter control flag
A value can be written with an MV (F0) instruction to reset the high-speed counter,
disable counting, stop high-speed counter instruction (F168), and clear the high-
speed counter.
Control code setting
Control code = (Binary)
Software reset
0: Yes / 1: No
Count
0: Enable / 1: Disable
Hardware reset
0: Enable / 1: Disable
High–speed counter clear
0: Continue / 1: Clear
Software is not reset: H0 (0000)
Perform software reset: H1 (0001)
Disable count: H2 (0010)
Disable hardware reset: H4 (0100)
Stop pulse output (clear instruction): H8 (1000)
Perform software reset and stop pulse output: H9 (1001)
bit 15 12 11 8 7 4 3 0
DT9052
A hardware reset disable is only effective when using the reset inputs (X2 and X5). In
all other cases it is ignored.
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
When using pulse output, a hardware reset input is equivalent to an home point proxi-
mate input.
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
DT90053 Clock/calendar monitor (hour/minute)
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
(see note) Hour and minute data of the clock/calendar are stored here. This data is
read-only data; it cannot be overwritten.
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
Higher 8 bits Lower 8 bits
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
Hour data Minute data
H00 to H23 (BCD) H00 to H59 (BCD)
Note
An expansion memory unit is necessary.
Addresses Description
T32CP Other Types
DT90054 DT90054, Clock/calendar monitor and setting (minute/second)
(see note) DT90055, Clock/calendar monitor and setting (day/hour)
DT90056, Clock/calendar monitor and setting (year/month)
DT90057, Clock/calendar monitor and setting (day-of-the-week)
The year, month, day, hour, minute, second, and day-of-the-week data for
the calendar timer is stored. The built-in calendar timer will operate cor-
rectly through the year 2099 and supports leap years. The calendar timer
can be set (the time set) by writing a value using a programming tool or a
DT90055 program that uses the F0 (MV) transfer instruction.
(see note)
Higher 8 bits Lower 8 bits
DT90057
(see note)
Note
An expansion memory unit is necessary.
Addresses Description
T32CP
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
Other Types
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
DT90058 Clock/calendar time setting and 30s correction
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
(see note ) The clock/calendar is adjusted as follows.
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
When setting the clock/calendar by program that uses F0 (MV)
instructions
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
By setting the the highest bit of DT90058 to 1, the time becomes that
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
written to DT90054 to DT90057 by F0 (MV) instruction. After the time is
set, DT90058 is cleared to 0. (Cannot be performed with any instruction
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
other than F0 (MV) instruction.)
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
Example: FPWIN GR
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
Set the time to 12:00:00 on the 5th day when the X0 turns ON.
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
X0
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
( DF ) 1
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
[ F0 MV, H 0, DT90054 ] . . . Inputs 0 minutes
1
and 0 seconds
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
[ F0 MV, H 512, DT90055 ] . . . Inputs 12th hour
5th day
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
Note
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
If you changed the values of DT90054 to DT90057 with the data
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
monitor functions of NPST-GR software, the time will be set
when the new values are written. Therefore, it is unnecessary to
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
write to DT90058.
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
When the correcting times less than 30 seconds
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
By setting the lowest bit of DT90058 to 1, the value will be moved up or
down and become exactly 0 seconds. After the correction is completed,
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
DT90058 is cleared to 0.
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
Example: FPWIN GR
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
Correct to 0 seconds with X0 turns ON
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
X0
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
( DF ) 1
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
[ F0 MV, H 1, DT90058 ] Correct to 0
1
second.
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
At the time of correction, if between 0 and 29 seconds, it will be moved
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
down, and if the between 30 and 59 seconds, it will be moved up. In the
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
example above, if the time was 5 minutes 29 seconds, it will become 5
minutes 0 second; and, if the time was 5 minutes 35 seconds, it will
ÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑÑ
become 6 minutes 0 second.
Note
An expansion memory unit is necessary.
Addresses Description
T32CP Other Types
DT90059 DT9059 Serial communication error code
bit 15 12 11 8 7 4 3 0
DT90059/DT9059
Addresses Description
T32CP Other Types
DT90060 DT9060 Process Step ladder process
number: Indicates the startup condition of the step ladder process. When the
0 to 15 proccess starts up, the bit corresponding to the process number turns
on “1”.
DT90061 DT9061 Process
number: Monitor using binary display.
16 to 31
15 11 7 3 0 (Bit No.)
DT90062 DT9062 Process
number:
DT9060
32 to 47 15 11 7 3 0 (Process No.)
DT90063 DT9063 Process 0: not–executing
number: 1: executing
48 to 63
DT90064 DT9064 Process A programming tool can be used to write data.
number:
64 to 79
DT90065 DT9065 Process
number:
80 to 95
DT90066 DT9066 Process
number:
96 to 111
DT90067 DT9067 Process
number:
112 to 127
DT90104 DT9104 High-speed counter elapsed value area for ch2
The elapsed value (24–bit data) for the high–speed counter is stored here. Each time
the ED instruction is executed, the elapsed value for the high–speed counter is auto-
DT90105 DT9105 matically transferred to the special registers DT9104 and DT9105.
The value can be written by executing a DMV (F1) instruction.
DT90106 DT9106 High-speed counter target value area for ch2
The target value (24–bit data) of the high–speed counter specified by the high–speed
counter instruction is stored here.
DT90107 DT9107 Target values have been preset for the various instructions, to be used when the
high–speed counter related instruction F166 to F170 is executed. These preset val-
ues can only be read, and cannot be written.
DT90108 DT9108 High-speed counter elapsed value area for ch3
The elapsed value (24–bit data) for the high–speed counter is stored here. Each time
the ED instruction is executed, the elapsed value for the high–speed counter is auto-
DT90109 DT9109 matically transferred to the special registers DT9108 and DT9109.
The value can be written by executing a DMV (F1) instruction.
DT90110 DT9110 High-speed counter target value area for ch3
The target value (24–bit data) of the high–speed counter specified by the high–speed
counter instruction is stored here.
DT90111 DT9111 Target values have been preset for the various instructions, to be used when the
high–speed counter related instruction F166 to F170 is executed. These preset val-
ues can only be read, and cannot be written.
Dimensions
Dimensions FP0 Hardware
D.1 C10RS–10CRS–14RS–14CRS/E8RS–16RS
(8.5/0.335)
3.5/0.138 Approx. 100.0/3.937
25.0/0.984
60.0/2.362 60.0/2.362
90.0/3.543
Approx. 130.0/5.118
90.0/3.543
(9/0.354)
(7.5/0.295)
DIN rail
(DIN EN50022, 35/1.378) attachment gap
(unit: mm/in.)
D.2 C16T–16CT–16P–16CP/E16T–16P–8X–8YT–8YP
(18/0.709)
3.5/0.138 Approx. 78.0/3.071
25.0/0.984
60.0/2.362 60.0/2.362
90.0/3.543
90.0/3.543
(3.5/0.138)
(unit: mm/in.)
D.3 C32T–32CT–32P–32CP/E32T–32P–16X–16YT–16YP
(18/0.709)
3.5/0.138 Approx. 78.0/3.071
60.0/2.362 30.0/1.181 60.0/2.362
90.0/3.543
90.0/3.543
(3.5/0.138)
(unit: mm/in.)
(unit: mm/in.)
(unit: mm/in.)
90.0/3.543
4,5/0.177
(unit: mm/in.)
67.5/2.657
60.0/2.362
A B C D
27.5/1.083
DIN rail
35.0/1.378
90.0/3.543
27.5/1.083
(unit: mm/in.)
Note
A + B +C + D dimensions (Unit: mm/in.)
60.0/2.362
2.5/0.098
100/3.937 75.0/2.953
25.0/ 25.0/ 25.0/
0.984 0.984 0.984
90.0/3.543
60.0/2.362
60.0/2.362
dir. 5.0/0.197
dir. 5.0/2.362
dir. 10.0/0.394 After joining all of the FP0 slim type mounting
plates to be connected, tighten the corner
screws.
Figure 2 : Four plates in series
(unit: mm/in.)
Figure 3 : Mounting hole dimensions
70.0/2.756
60.0/2.362
(unit: mm/in.)
6.2/2.441 60.0/2.362
60.0/2.362
90.0/3.543
dir. 5.0/
0.197
4.0/0.157
dir. 10.0/0.394
A
B
A B
Unit type
(mm/in.) (mm/in.)
C10RS
C10CRS
C14RS
C14CRS
60.0/2.362
31.2/1.23 25/0.98
C16T
C16CT
C16P
90.0/3.543
C16CP
C32T
C32CT
36.2/1.43 30/1.18
C32P
C32CP
dir. 5.0/0.197
Note
Cannot be used if system is expanded
C Expansion units, 1 - 3
Expansion, 1 - 6
Communication error, 11 - 8
Control units, 1 - 2
current consumed, 2 - 6
F
input specifications, 2 - 11 FP0 I/O link unit, 5 - 2
internal circuit diagram, 2 - 15 cables, 5 - 6
relay output type, 2 - 15
DIP switches, 5 - 3
transistor output type, 2 - 16
LEDs, 5 - 2
LEDs, 2 - 3, 2 - 4
mode switches, 5 - 3
MIL type, 1 - 2
specifications, 5 - 5
mode switch, 2 - 3, 2 - 4
station number selection switches,
output specifications, 2 - 13 5-3
relay output, 2 - 13
terminal pin layout, 5 - 7
transistor output type, 2 - 13
parts and terminology, 2 - 2
performance specifications, 2 - 8 G
pin layouts, 2 - 19
RS232C port, 2 - 4 Grounding, 9 - 6
specifications, 2 - 5
I R
I/O allocation Relay output units, combinations, 1 - 7
analog unit, 7 - 5 RS232C port
control units, 7 - 3 baud rate, 9 - 16
expansion units, 7 - 4 wires, 9 - 16
I/O number, 7 - 2–7 - 5 wiring, 9 - 16
I/O points, 1 - 6, 1 - 7, 1 - 8
Installation, 8 - 1 S
expansion units, 8 - 5
Safety instructions, wiring, 9 - 2
Intelligent unit, 1 - 4
Self–diagnostic error, 11 - 11
Self–diagnostic error code, C - 2
L
Self–diagnostic error codes, 11 - 12
Link unit, 1 - 4 Self–diagnostic error flag, B - 2
Self–diagnostic function, 11 - 2
M Sensors, wiring, 9 - 7
Special data registers, C - 2
MIL connector, wiring, 9 - 14
Special internal relays, B - 2
Mounting plate
flat type, 8 - 9 Syntax check error, 11 - 10
slim type, 8 - 8 Syntax check error codes, 11 - 11
System registers, A - 2
hold type, A - 4
N
non–hold type, A - 4
Noise, 9 - 6
T
O
Terminal block socket
Operation error flag, B - 2 wires, 9 - 12
wiring, 9 - 12
Transistor output units, combinations,
P 1-8
Power failures, 9 - 2 Troubleshooting, 11 - 3
Power supply unit, 1 - 5, 6 - 2
specifications, 6 - 3 W
Pressure connection tool, 9 - 14
Watchdog timer, 11 - 5
Programming tools, 1 - 9
Wiring
PROTECT ERROR, 11 - 9
input, 9 - 7
output, 9 - 10
power supply, 9 - 4
AGGM0084END V3.2 Sept. 1999 FP0 I/O Link Unit information added
ACGM0084END V3.3 Feb. 2000 System registers, special internal relays, and special data
registers added
ACGM0084END V3.4 May 2001 Error removal, product updates.
I.O.P. connection information deleted. For information on
I.O.P.s, see the relevant GT or GK series manuals.
Important note added for thermocouple setting using the
analog mode ( see page 4-3).
GLOBAL NETWORK
Europe
H Austria Matsushita Electric Works Austria GmbH
Stojanstraße 12, 2344 Maria Enzersdorf, Austria, Tel. (02236) 2 68 46, Fax (02236) 46133, http://www.matsushita.at
H Benelux Matsushita Electric Works Benelux B. V.
De Rijn 4, (Postbus 211), 5684 PJ Best, (5680 AE Best), Netherlands, Tel. (0499) 37 2727, Fax (0499) 372185, http://www.matsushita.nl
H France Matsushita Electric Works France S.A.R.L.
B.P. 44, 91371 Verrières le Buisson CEDEX, France, Tel. 01 60 13 57 57, Fax 01 60 13 57 58, http://www.matsushita–france.fr
H Germany Matsushita Electric Works Deutschland GmbH
Rudolf–Diesel–Ring 2, 83607 Holzkirchen, Germany, Tel. (08024) 648–0, Fax (08024) 648–555, http://www.matsushita.de
H Ireland Matsushita Electric Works Ltd., Irish Branch Office
Waverley, Old Naas Road, Bluebell, Dublin 12, Republic of Ireland, Tel. (01) 460 09 69, Fax (01) 460 11 31
H Italy Matsushita Electric Works Italia s.r.l.
Via del Commercio 3–5 (Z.I. Ferlina), 37012 Bussolengo (VR), Italy, Tel. (045) 675 27 11, Fax (045) 670 04 44, http://www.matsushita.it
H Portugal Matsushita Electric Works Portugal, Portuguese Branch Office
Avda 25 de Abril, Edificio Alvorada 5º E, 2750 Cascais, Portugal, Tel. (351) 1482 82 66, Fax (351) 1482 74 21
H Scandinavia Matsushita Electric Works Scandinavia AB
Sjöängsvägen 10, 19272 Sollentuna, Sweden, Tel. +46 8 59 47 66 80, Fax (+46) 8 59 47 66 90, http://www.mac–europe.com
H Spain Matsushita Electric Works España S.A.
Parque Empresarial Barajas, San Severo, 20, 28042 Madrid, Spain, Tel. (91) 329 38 75, Fax (91) 329 29 76
H Switzerland Matsushita Electric Works Schweiz AG
Grundstrasse 8, 6343 Rotkreuz, Switzerland, Tel. (041) 799 70 50, Fax (041) 799 70 55, http://www.matsushita.ch
H United Kingdom Matsushita Electric Works UK Ltd.
Sunrise Parkway, Linford Wood East, Milton Keynes, MK14 6LF, England, Tel. (01908) 231 555, Fax (01908) 231 599,
http://www.matsushita.co.uk
Asia
H China Matsushita Electric Works, Ltd. China Office
2013, Beijing Fortune, Building 5, Dong San Huan Bei Lu, Chaoyang District, Beijing, China, Tel. 86–10–6590–8646, Fax 86–10–6590–8647
H Hong Kong Matsushita Electric Works Ltd. Hong Kong
Rm1601, 16/F, Tower 2, The Gateway, 25 Canton Road, Tsimshatsui, Kowloon, Hong Kong, Tel. (852) 2956–3118, Fax (852) 2956–0398
H Japan Matsushita Electric Works Ltd. Automation Controls Group
1048 Kadoma, Kadoma–shi, Osaka 571–8686, Japan, Tel. 06–6908–1050, Fax 06–6908–5781, http://www.mew.co.jp/e–acg/
H Singapore Matsushita Electric Works Pte. Ltd. (Asia Pacific)
101 Thomson Road, #25–03/05, United Square, Singapore 307591,Tel. (65) 255–5473, Fax (65) 253–5689