INTRODUCTION OPERATION
The ANSUL AUTOMAN Il-C Releasing Device is for use with When energized by a fire condition, a solenoid mounted on
ANSUL fire suppression systems. Model Il-C provides the actuator trips the release mechanism puncturing the
automatic-pneumatic actuation of fixed nozzle fire cartridge. The solenoid operates approximately 50 milli-
suppression systems. seconds after energized. Then actuation gas from the
cartridge is directed through piping to pneumatically activate
DESCRIPTION the fire suppression system.
The Model Il-C is comprised of a metal enclosure which Manual actuation is provided by means of an integral
contains a spring-loaded puncture pin release mechanism, STRIKE button at the release enclosure which may be
an actuation cartridge, and an explosion-proof electrical supplemented by use of a remote manual cable pull station.
solenoid. Knockouts for the connection of conduit are
provided in the top, bottom and sides of the steel enclosure.
The enclosure also contains four surface mounting holes.
INSTALLATION INSTRUCTIONS
E 62842 6-1-11 Page 2
Install Release
1. Select a shock and vibration free surface in a clean dry
area for mounting the ANSUL AUTOMAN release. The
mounted release should be completely visible and 1/4 IN. CLOSE NIPPLE
accessible for maintenance. 45° ELBOW, 1/4 IN.
Note: The bottom of the release must be located
no higher than 50 in. (127 cm) from the floor to
3/8 IN. X 1/4 IN.
enable manual actuation of STRIKE button. If the REDUCING BUSHING 90° ELBOW, 1/4 IN.
release cannot be mounted in this manner,
a remote manual pull station (cable type or
electric) should be installed to facilitate manual FIGURE 3
actuation. 001805
2. Open the release cover and secure the enclosure at 5. Use one of the 1/2 in. (13 mm) knockouts provided in
location utilizing the four mounting holes. Use lag the top and bottom or side of the release enclosure to
screws or toggle bolts depending on the mounting exit the pipe and install balance of pipe, fittings and
surface. Figure 2 provides detailed mounting data. pressure relief valve as shown in Figure 4. Wrench
tighten all pipe joints to prevent leakage of gas.
MOUNTING DATA
PRESSURE
RELIEF VALVE*
4 3/16 IN.
(106 mm) 5/16 IN.
(8 mm) DIA.
9 7/8 IN. HOLES
1 1/8 IN.
(29 mm) (229 mm) 1 1/4 IN.
(32 mm)
21 1/2 IN.
(546 mm)
FIGURE 4
001806
*In some systems, the actuation line vent is used rather than
the pressure relief valve.
6. Proceed with wiring instructions beginning on the next
page. DO NOT INSTALL CARTRIDGE.
SURFACE KNOCKOUTS ON
MOUNTING 4 SIDES OF BOX
FIGURE 2
001804
INSTALLATION INSTRUCTIONS
E 62842 6-1-11 Page 3
WIRING DATA
NOTES:
INPUT POWER: NOTED ON SOLENOID LABEL
PART NO.: 31492 ( 24 VDC)
32525 (120 VAC)
32526 (240 VAC)
ALL INTERCONNECTING WIRING NUMBER 18 AWG
MIN. ENCLOSED IN CONDUIT SUITABLE FOR HAZARD-
OUS LOCATIONS. ANSUL AUTOMAN Il-C
FOR HAZARDOUS LOCATIONS,
DISCONNECT POWER CIRCUIT BEFORE DECOUPLING PART NO. (SEE NOTES)
EXPLOSION PROOF FITTINGS.
SOL1
N.O. ALARM
RELEASING CONTACTS
POWER SOURCE
FOR RELEASE
FIGURE 5
001802
INSTALLATION INSTRUCTIONS
E 62842 6-1-11 Page 4
MAINTENANCE
ANSUL AUTOMAN Il-C release is a mechanical device. It
requires periodic care. Maintenance to provide maximum
assurance that your release will operate effectively and
FIGURE 7 safely should be conducted at six month intervals in accor-
001801
dance with Steps 1 through 13 listed under “Test Activation
4. Return detector/alarm control system to normal supervi- Of Extinguisher(s).” Inspection to provide reasonable assur-
sory operation, reset the ANSUL AUTOMAN release ance that your release is charged and operable should be
and install ring pin as illustrated in Figure 7 to safety the conducted at more frequent intervals by visually determining
release puncture pin mechanism. that the ring pin is properly inserted and sealed in the
STRIKE button and that the reset lever is in the up (Armed)
TEST ACTIVATION OF EXTINGUISHER(S)
position.
Depending upon the hazard’s requirements, the activation
system design for the agent tank assembly will differ. For Note: Every ANSUL engineered fixed nozzle system is
this reason, the operational test of the actuation/activation subject to a mandatory inspection upon completion of
system must be performed by an authorized ANSUL your system’s installation. This inspection must be
distributor. performed by an authorized ANSUL distributor to
ensure that the complete system is installed properly
1. Refer to the installation, operation and maintenance
and is ready for service.
instruction manual(s) furnished with the ANSUL Fire
Suppression System and prepare the agent tank
assembly activation mechanism for test firing.
INSTALLATION INSTRUCTIONS
E 62842 6-1-11 Page 5
SEE
DETAIL “A”
1/2 IN.
DETAIL “A”
FIGURE 8
001800
TYCO FIRE PROTECTION PRODUCTS Copyright ©2011 Tyco Fire Protection Products
ONE STANTON STREET All rights reserved.
MARINETTE, WI 54143-2542 +1-715-735-7411 Part No. 31496-02