22EE601 PSPC Unit 3
22EE601 PSPC Unit 3
This document is confidential and intended solely for the educational purpose of
RMK Group of Educational Institutions. If you have received this document
through email in error, please notify the system manager. This document
contains proprietary information and is intended only to the respective group /
learning community as intended. If you are not the addressee you should not
disseminate, distribute or copy through e-mail. Please notify the sender
immediately by e-mail if you have received this document by mistake and delete
this document from your system. If you are not the intended recipient you are
notified that disclosing, copying, distributing or taking any action in reliance on
the contents of this information is strictly prohibited.
22EE601- POWER SYSTEM PROTECTION
AND CONTROL
Department : EEE
Batch/Year :2022-2026/III
Created by: N M Jothi swaroopan
1.TABLE OF CONTENTS
S.N
TITLE Page No
o
UNIT-III
1 Contents 05
2 07
Course Objectives
3 08
Pre Requisites (Course names with code)
4 09
Syllabus (with Subject code, Name LPTC details)
5 10
Course outcomes
6 11-12
CO- PO/PSO Mapping
7 13
Lecture Plan
8 14
Activity based learning
9 15-37
Lecture Notes, Quiz, Links to Videos, e-book reference
10 38
Assignments
11 39
Part A Question & Answers
12 43
Part B Questions
13 44
Supportive online Certification courses
15 46
Additional topics
16 47
Assessment Schedule
17 48
Prescribed Text Books & Reference Books
18 49
Mini Project Suggestions
2. Course Objectives
TOTAL : 45 PERIODS
➢ CO1: Ability to analyze the characteristics and functions of relays
and protection schemes.
➢ CO2: Study about the apparatus protection, static and numerical
relays.
➢ CO3: Acquire knowledge on functioning of circuit breaker.
➢ CO4: Understand the significance of power system operation and
control.
➢ CO5: Acquire knowledge on real power-frequency interaction.
➢ CO6: Understand the reactive power-voltage interaction.
5.Course Outcomes
Semester: 06
Level of
Course Name: POWER SYSTEM PROTECTION AND CONTROL
(22EE601) Knowledge
PO1 PO1
CO PO1 PO2 PO3 PO4 PO5 PO6 PO7 PO8 PO9 PO10
1 2
CO1 2 1 1 1 - - - - 1 1 - -
CO2 3 2 1 1 - - - - 1 1 - -
CO3 3 2 1 1 - - - - 1 1 - -
CO4 3 2 1 1 - - - - 1 1 - -
CO5 3 2 1 1 - - - - 1 1 - -
CO6 3 2 1 1 - - - - 1 1 - -
1. Plot and analyze the load characteristics for monthly and weekly for our college
campus.
2. Measuring the unit consumed per day ,month and annually in their house. With
raw data's, forecast the load using neutral network.
3. Analyze the automatic control of water flow in the water tank.
Lecture notes
Constant Frequency
Constant frequency is to be maintained for the following functions:
➢ All the AC motors should require constant frequency supply so as to maintain
speed constant.
➢ In continuous process industry, it affects the operation of the process itself.
➢ For synchronous operation of various units in the power system network, it is
necessary to maintain frequency constant.
➢ Frequency affects the amount of power transmitted through interconnecting lines.
➢ Frequency fluctuations are harmful to electrical appliances.
➢ Speed of three phase ac motors proportional to the frequency.
(N=120f/p)
➢ The blades of turbines are designed to operate at a particular speed. Frequency
variation leads to speed variation and results in mechanical vibration
Constant Voltage
➢ Voltage Control Equipment needed to maintain Voltage at permissible limits
➢ Voltage below normal level Reduces the light Intensity and Voltage above the normal
level can reduce the life of the lamps
➢ Low voltage at motor terminal can draw more currents and cause overheat inside the
device
➢ Voltage deviation affects the performance of the device and drops the life time
➢ By adjusting the excitation of the generator at the sending end below the certain level
can cause instability problems and excitation above certain level will result in overheating
of rotor.
Q–V Control
In this control, the terminal voltage of the generator is sensed and converted into
proportionate DC signal and then compared to DC reference voltage. The error in between a
DC signal and a DC reference voltage, i.e., Δ |V | is taken as an input to the Q–V controller.
A control output ΔQ is applied to the exciter.
Generator Controllers (p–f and Q–V Controllers)
The active power P is mainly dependent on the internal angle δ and is
independent of the bus voltage magnitude |V|. The bus voltage is dependent on
machine excitation and hence on reactive power Q and is independent of the
machine angle δ. Change in the machine angle δ is caused by a momentary change
in the generator speed and hence the frequency. Therefore, the load frequency and
excitation voltage controls are non-interactive for small changes and can be modeled
and analyzed independently. Figure gives the schematic diagram of load frequency
(P–f) and excitation voltage (Q–V) regulators of a turbo-generator. The objective of
the MW frequency or the P–f control mechanism is to exert control of frequency and
simultaneously exchange of the realpower flows via interconnecting lines. In this
control, a frequency sensor senses the change in frequency and gives the signal Δf .
The P–f controller senses the change in frequency signal (Δ f) and the increments in
tie-line real powers (ΔP ), which will indirectly provide information about the
incremental state error (Δδ ). These sensor signals (Δf and ΔP ) are amplified, mixed,
and transformed into a real-power control signal ΔP . The valve control mechanism
takes ΔP as the input signal and provides the output signal, which will change the
position of the inlet valve of the prime mover. As a result, there will be a change in
the prime mover output and hence a change in real-power generation ΔP . This
entire P–f control can be yielded by automatic load frequency control (ALFC) loop.
The speed governor is the main primary tool for the LFC, whether the machine is
used alone to feed a smaller system or whether it is a part of the most elaborate
arrangement. A schematic arrangement of the main features of a speed-governing
system of the kind used on steam turbines to control the output of the generator to
maintain constant frequency is as shown in Fig.
This is the heart of the system which senses the change in speed (frequency).As the
speed increases the fly balls move outwards and the point B on linkage mechanism
moves downwards. The reverse happens when the speed decreases.
It comprises a pilot valve and main piston arrangement. Low power level pilot valve
movement is converted into high power level piston valve movement. This is necessary in
order to open or close the steam valve against high pressure steam.
ABC is a rigid link pivoted at B and CDE is another rigid link pivoted at D. This link
mechanism provides a movement to the control valve in proportion to change in speed. It
also provides a feedback from the steam valve movement.
iv)Speed Changer: It provides a steady state power output setting for the turbine.
Its downward movement opens the upper pilot valve so that more steam is admitted to
the turbine under steady conditions (hence more steady power output). The reverse
happens for upward movement of speed changer.
A brief explanation of the diagram is as follows:
Steam enters into the turbine through a pipe that is partially obstructed by a
steam admission valve. In steady state the opening valve is determined by the position
of a device called the speed changer (upper left corner in Fig.1), fixes the position of
the steam valve through two rigid rods ABC and CDE. The reference value or set point
of the turbine power in steady state is called the reference power.
When the load on the bus suddenly changes, the shaft speed is modified, and a device
called speed regulator acts through the rigid rods to move the steam valve. A similar
effect could be produced by temporarily modifying the reference power (which justifies
the name speed changer). In practice, both control schemes are used simultaneously.
Amplifying stages (generally hydraulic) are introduced to magnify the output of the
controller and produced the forces necessary to actually move the steam valve.
The link point ‘C’ will move upward because of linkage (A-B-C) action. Let it be
further, the link point ‘D’ moves the piston in pilot servo (V), resulting in higher
pressure oil flow in the upper part of the main piston. The piston moves
downward by an amount ΔXD and the steam valve opening increases. It
increases the torque developed by the turbine. This increased torque increases
the speed of generator, i.e., frequency (Δf). This change of speed results in the
outward movement of fly ball of the speed regulator. Thus the link ‘B’ moves
slightly downward a small distance ΔXB. Due to the movement of link point B,
the link point ‘C’ also moves downward by an amount ΔXC’’ which is also
proportional to Δf. Thus the net movement of link point C is
and ΔXC “ = K2 Δf
Steam turbine or hydro turbine act as a prime mover driving a generator unit. At
present, we can assume that the voltage level is constant and the torque variations
are small. Then an incremental analysis will give a relatively simple dynamic
relationship between ΔXE and ΔPG. Such an analysis reveals considerable difference,
not only between steam turbines and hydro- turbines, but also between various types
(reheat and non-reheat) of steam turbines. Therefore, the transfer function, relates
the change in the generated power output with respect to the change in the valve
position, varies with the type of the prime mover.
Speed droop is a governor function which reduces the governor reference speed as fuel
position (load) increases. All engine controls use the principle of droop to provide stable
operation. The simpler mechanical governors have the droop function built into the
control system, and it cannot be changed.
The ability to return to the original speed after a change in load is called
isochronous speed control.
All electronic controls have circuits which effectively provide a form of temporary droop
by adjusting the amount of actuator position change according to how much off speed is
sensed. Without some form of droop, engine-speed regulation would always be
unstable. A load increase would cause the engine to slow down. The governor would
respond by increasing the fuel position until the reference speed was attained. However,
the combined properties of inertia and power lag would cause the speed to recover to a
level greater than the reference.
Droop is a straight-line function, with a certain speed reference for every fuel position.
Normally, a droop governor lowers the speed reference from 3 to 5 percent of the
reference speed over the full range of the governor output. Thus a 3% droop governor
with a reference speed of 1854 rpm at no fuel would have a reference speed of 1800 rpm
at max fuel (61.8 Hz at no fuel and 60 Hz at max fuel).Most complex hydraulic governors
have adjustable droop. In these cases, droop may be set between 0% and 5%. Droop is
not adjustable in most mechanical governors.
Fig. Ideal steady state characteristics of a governor with speed droop
It is to be noted that if the frequency of two areas are to be controlled, the static
frequency drop is 50% of the isolated operation of two systems. Also, if there is
change in load in any area, half of it shared by other area.
638.5323 f = 30926.6166
f = 48.4339 Hz
Result
h = 0.9712
X = 25 – 12.5 x (0.9712)
X = 12.85MW
Extend BC to B’F
Prime movers driving the generators are fitted with governors, which are regarded as
primary control elements in the LFC system. Governors sense the change in a speed control
mechanism to adjust the opening of steam valves in the case of steam turbines
1. Most AC motors run at speeds that are directly related to frequency. The speed and
induced electro motive force (e.m.f) may vary because of the change of frequency of the
power circuit.
2. When operating at frequencies below 49.5 Hz; some types of steam turbines, certain
rotor states undergo excessive vibration.
3. The change in frequency can cause mal operation of power converters by producing
harmonics.
4. For power stations running in parallel it is necessary that frequency of the network
must remain constant for synchronization of generators.
Previous chapter derived the modelling of speed governor, turbine, and generator load
model. Combining the governor model, turbine model and generator load model, we get
the complete block diagram representation of LFC of an isolated power system which is
shown in fig.10
The basic objective of the primary ALFC loop is to maintain constant frequency in spite of
changing loads. The primary ALFC loop as shown in the fig. has one output and two
inputs. ΔPref(s) and ΔPD(s)
Consider the speed changer has a fixed setting. Under this condition ΔPC =0 and the load
demand changes. This is known s free governor operation. The block diagram is shown in
fig drawn from substituting ΔPC =0.
Fig.2
Fig.3
Static Analysis or Steady state response of controlled case
In this case, there is a step change ΔPC force for speed changer setting and the load demand
remains fixed i.e ΔPD =0.
Fig.5
Fig.6
Taking inverse Laplace transform for an expression ΔF(s) is tedious, because the
denominator will be third order. We can simplify the analysis by making the following
assumptions.
1. The action of speed governor and turbine is instantaneously compared with rest of the
power system.
Fig.8
Fig.9. Dynamic response of primary ALFC loop to a step load change
Dynamic Analysis of Controlled Case:
1. By reducing value of R it is possible to increase AFRC. Hence static frequency error may be
reduced.
2. With smaller time constant Tg and Tt, the system response shows some oscillations before
settling down with a drop in frequency. But if these time constants are neglected, response is
purely exponential.
3. If the overall closed loop system time constant is calculated from the response curve, it is
found to be much smaller than the open loop time constant of the power system.
4. For the uncontrolled system there exists a steady state frequency error as a result of increase
in load demand, however small it may be.
5. When the load demand increases speed or frequency of the system drops though initially
kinetic energy of rotating inertia may be used to meet up the demand. Eventually it will be
balanced by an increase in system generation and decrease in load as associated with the
dropping frequency.
Problems in LFC single Area
Example 1: Find the static frequency drop if the load is suddenly increased by 25 MW on a
system having the following data:
Rated capacity Pr = 500 MW
Operating Load PD = 250 MW
Inertia constant H = 5 s
Governor regulation R = 2 Hz p.u. MW
Frequency f = 50 Hz
Also find the additional generation.
Example 2 : An Isolated power system has the following parameters:
Turbine Rated output Pr = 300 MW
Load Change = 60 MW
Inertia constant H = 5 s
Governor regulation R =0.05 p.u.
Nominal Frequency f = 50 Hz
Turbine time constant = 0.5 sec
Governor time constant = 0.2 sec
The load varies by 0.8 percent for a 1 percent change in frequency; determine the steady
state frequency deviation in Hz. (June 2016 AU)
LFC of two area system:
Here, the control objective is to regulate the frequency of each area and
to simultaneously regulate the power flow through the tie line according to an inter
area power agreement.
Tie Line Modeling
In the case of an isolated control area, the zero steady state error in
frequency (i.e., Δf = 0) can be obtained by using a proportional plus integral
controller, whereas in two-control area case, proportional plus integral controller will
be installed to give zero steady state error in a tie-line power flow (i.e., ΔPTie = 0) in
addition to zero steady-state error in frequency.
For the sake of convenience, each area can be represented by an
equivalent turbine, generator, and governor system. In the case of a single control
area, the incremental power (ΔPG −ΔPD) was considered by the rate of increase of
stored KE and increase in area load caused by the increase in frequency. But as in
the case of a two-area, the tie-line power must be accounted for the incremental
power balance equation of each area, since there is power f low in or out of the area
through the tie line.
Block diagram representation of two area system
By the combination of basic block diagrams of Load frequency control of
single area network along with single area tie line support (fig 2 ) and Tie Line
model (fig 3), the composite block diagram of a two-area system can be modelled as
shown in Fig.
A 10 MW 2.5 % 7 MW
B 2 MW 4% 2 MW
Assignments
1. A single-area system has the following data: Speed regulation, R = 4 Hz/p.u. MW;
Damping coefficient, B = 0.1 p.u. MW/Hz; Power system time constant, Tp = 10 s;
Power system gain, Kp = 75 Hz/p.u. MW; When a 2% load change occurs,
determine the AFRC and the static frequency error. What is the value of the steady-
state frequency error if the governor is blocked?
(β = 0.35 MW/Hz ; ΔF = -0.571 Hz; β = 0.1 p.u MW/Hz ; ΔF = -0.2 Hz)
3. Two generating units having the capacities 600 and 900 MW and are operating at
a 50 Hz supply. The system load increases by 150 MW when both the generating
units are operating at about half of their capacity, which results in the frequency
falling by 0.5 Hz. If the generating units are to share the increased load in
proportion to their ratings, what should be the individual speed regulations? What
should the regulations be if expressed in p.u. Hz/p.u. MW?
(R1 = 0.1 p.u ; R2 =0.1 p.u Hz/ p.u MW)
Part A (Q & A)
K
S.No Part A (Q & A) COs
Level
2 The need for voltage regulation in power system is to maintain the K1 CO1
voltage at the load terminals within prescribed limits under fluctuating
load conditions by employing suitable voltage control equi
What are the steps required for designing an optimum linear
regulator?
An optimum linear regulator can be designed using the following
steps:
1. Casting the system dynamic model in a state-variable form and
3 introducing appropriate control forces. K2 CO3
2. Choosing an integral-squared-error control index, the minimization
of which is the control goal.
3. Finding the structure of the optimal controller that will minimize the
chosen control index.
How and why do you approximate the system for the dynamic
response of the uncontrolled LFC of a single area?
The characteristic equation of the LFC of an isolated power system is
third order, dynamic response that can be obtained only for a specific
4 numerical case. K2 CO3
However, the characteristic equation can be approximated as first
order by examining the relative magnitudes of the different time
constants involved
What is the criterion used for obtaining optimum values for the
control parameters?
5 Integral of the sum of the squared error criterion is the required K2 CO3
criterion
S.No Part A (Q & A) K Level COs
Explain the control area concept.
It is possible to divide a very large power system into sub-areas in
which all the generators are tightly coupled such that they swing in unison
with change in load or due to a speed-changer setting. Such an area, where
CO3
6 all the generators are running coherently, is termed the control area. In this K2
area, frequency may be same in Steady-state and dynamic conditions. For
developing a suitable control strategy, a control area can be reduced to a
single generator, a speed governor, and a load system.
26 K1 CO3
State why P–f and Q–V control loops can be treated as non-interactive?
The active power P is mainly dependent on the internal angle δ and is
independent of bus voltage magnitude |V|. The bus voltage
is dependent on machine excitation and hence on reactive power Q
and is independent of the machine angle δ. The change in the
30 machine angle δ is caused by a momentary change in the generator K1 CO3
speed and hence the frequency. Therefore, the load frequency and
excitation voltage controls are non-interactive for small changes and
can be modeled and analyzed independently.
Why is the load on the power system is variable? What are the
4 K2 CO3
effects of variable load in power system?
Solve to determine the change in frequency that occurs in this time for
100 MVA synchronous generator is running on full load at 50 Hz
21 frequency. A 40 MW Loads is suddenly removed. Due to lag in governor K3 CO3
system, the steam valve of the turbine begins to close after 0.5 sec..
Given H = 5 MW sec/ MVA of generator rating
Solve for steady-state change in frequency and tie-line power of 10 MW
change in load occurs in both areas where two control areas of 1,000 and
2,000 MW capacities are interconnected by a tie line. The speed regulations
22 of the two areas, respectively, are 4 Hz/p.u. MW and 2.5 Hz/p.u. MW.
K3 CO3
Consider a 2% change in load occurs for 2% change in frequency in each
area.
Solve to find power generation at each station and power transfer through
the line if the load on the bus of each station is 200 MW. And the two
generating stations A and B having capacities 500 and 800 MW, respectively,
are interconnected by a short line. The percentage speed regulations from
no-load to full load of the two stations are 2 and 3, respectively.
23 K3 CO3
S.No Part C K Level COs
Apply the load frequency dynamics of this area and determine the steady
state frequency deviation in Hz using Area frequency response
characteristics .The load frequency dynamics of a single area power
system whose data are given below.
Rated Capacity of area (Pr)= 1500 MW ;Nominal Operating Load = 750
1 MW ; Nominal Frequency = 50 Hz ;Inertia Constant = 5.0 K3 CO4
Speed Regulation = 3 % ;Governor time constant & Turbine constant = 0
Assume linear load frequency Characteristics which means the
connected system load is increases by 1 % if the system frequency
increases by 1 %. The area is subjected to a load increase of 30 MW.
Apply the load frequency dynamics of a single area power system whose
data are given below. Rated Capacity of area (Pr)= 1000 MW; Nominal
Operating Load = 500 MW; Inertia Constant = 5.0; Regulation = 5 Hz/ p.u
MW; Frequency = 50 Hz Load decrease by 1 % for a decrease in
frequency by 1 %
2 a. Find gain and time constant of a power system. If it is an K3 CO4
uncontrolled area then find out the change in frequency due to an
increase of load by 75 MW
b. Determine the steady state frequency by changing regulation = 4
Hz/ p.u MW nominal operating load is 750 MW and compare with
the results ‘a’
Supportive Online Certification Courses
1. Collect the monthly power and energy consumed data's for three years. With
this data's forecast the future load with help of recent optimal techniques
3. Develop advanced LFC algorithms that use real-time data from smart grids to
adjust generation and maintain the balance between load and generation, ensuring
grid stability
With neat diagram, explain the Interconnected two area grid system with tie line control.
Compare and explain the performance of Electronic Speed Governor
Study the implementation of real-time frequency regulation markets that allow for
dynamic trading of regulation services to balance supply and demand.
Address the cybersecurity challenges associated with real-time control systems, ensuring the resilience and
security of power grids against cyber threats.
Assessment Schedule
TEXT BOOKS:
2. Allen. J. Wood and Bruce F. Wollen berg, ‘Power Generation, Operation and
Control’, John Wiley & Sons, Inc., 2016.
3. Abhijit Chakrabarti and Sunita Halder, ‘Power System Analysis Operation and
Control’, PHI learning Pvt. Ltd., New Delhi, Third Edition, 2010.
REFERENCES
1. Kothari D.P. and Nagrath I.J., ‘Power System Engineering’, Tata McGraw-Hill
Education, Second Edition, 2008.
2. Hadi Saadat, ‘Power System Analysis’, McGraw Hill Education Pvt. Ltd., New
Delhi, 21st reprint, 2010.
3. Kundur P., ‘Power System Stability and Control, McGraw Hill Education Pvt. Ltd.,
New Delhi, 10th reprint, 2010.
Mini project suggestions
Disclaimer:
This document is confidential and intended solely for the educational purpose of RMK Group of
Educational Institutions. If you have received this document through email in error, please notify the
system manager. This document contains proprietary information and is intended only to the
respective group / learning community as intended. If you are not the addressee you should not
disseminate, distribute or copy through e-mail. Please notify the sender immediately by e-mail if you
have received this document by mistake and delete this document from your system. If you are not
the intended recipient you are notified that disclosing, copying, distributing or taking any action in
reliance on the contents of this information is strictly prohibited.