0% found this document useful (0 votes)
5 views2 pages

Numerical

The kVA rating of the inverter is calculated to be 5 kVA based on a 3 kW load with a power factor of 0.6. The wattage of the rectifier required to supply the inverter is approximately 3093 W, considering an inverter efficiency of 97%. For a 60-minute backup time, the battery needs an AH capacity of about 129 AH at a voltage of 24 V DC.

Uploaded by

vinaysikarwar199
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
5 views2 pages

Numerical

The kVA rating of the inverter is calculated to be 5 kVA based on a 3 kW load with a power factor of 0.6. The wattage of the rectifier required to supply the inverter is approximately 3093 W, considering an inverter efficiency of 97%. For a 60-minute backup time, the battery needs an AH capacity of about 129 AH at a voltage of 24 V DC.

Uploaded by

vinaysikarwar199
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 2

To solve for the kVA rating of the inverter, wattage of the rectifier, and AH capacity of the battery for a

60-minute backup time:

1. **kVA Rating of the Inverter**:

- The load is 3 kW at a power factor of 0.6 lagging.

- Apparent power (kVA) = Real power (kW) / Power factor

\[

\text{kVA} = \frac{3 \text{ kW}}{0.6} = 5 \text{ kVA}

\]

2. **Wattage of the Rectifier**:

- The inverter efficiency is 97%, so the input power (DC) to the inverter is:

\[

\text{Input Power} = \frac{3 \text{ kW}}{0.97} \approx 3093 \text{ W}

\]

- This is the power the rectifier must supply to the inverter.

3. **AH Capacity of the Battery**:

- Battery voltage = 24 V DC.

- Current drawn from the battery:

\[

\text{Current} = \frac{3093 \text{ W}}{24 \text{ V}} \approx 128.87 \text{ A}

\]

- For 60-minute (1 hour) backup:

\[

\text{AH} = 128.87 \text{ A} \times 1 \text{ hour} \approx 129 \text{ AH}

\]

### Final Answer


The kVA rating of the inverter is \boxed{5} kVA, the wattage of the rectifier is \boxed{3093} W, and the
AH capacity of the battery is \boxed{129} AH.