1.Power in A.C Circuit Week 1
At the end of this week, the students are expected to:
Resistance
Inductance
Capacitance
i VmIm
P(t)
Average power
+
VmIm
e 2
_ R
0 t
i(t)
_ v(t)
Fig 1.1: (a) pure resistive circuit, (b) power wave form.
(b)
Inspection of the power waveform of fig 1.1 shows that its average value lies half way
between zero and its peak value of VmIm. That is
P = VmIm/2
Since V (the magnitude of the r.m.s value of voltage) is V m/√2 and I (the magnitude of
the r.m.s value of current) is Im/√2, this can be written as P = VI. Thus, power (average
power) to a purely resistive load is P = VI (watts).
(1.1)
Example 1.1: Calculate the power dissipated by the circuit of fig 1.2
+
100V
I R = 25
_
Fig 1.2 4
Solution
I = 100V/25 = 4A
P = VI = 100 x 4 = 400W
+
i
PL(t)
VI i(t)
+ v(t)
PL
V
_ 0 t
(a)
Energy Energy Energ Energy
_
release y released
d store
stored d
Fig 1.3: (a) pure inductive circuit (b) power waveform(bfo) r a purely inductive circuit
Consider fig 1.3. Energy stored during each quarter-cycle is returned during the next
quarter cycle. Thus, the average power is zero. Consequently, the only power flowing
in the circuit is reactive power. This is given by
QL = VI (VAr) (1.2)
Example 1.2: For the circuit of fig 1.4, determine the reactive power
100V I XL = 20
_
Solution
I = 100V/20 = 5A Fig 1.4
QL = VI = 100 x 5 = 500VAr
5
1.1.3 Power in A.C circuit containing capacitance only
For a purely capacitive load current leads voltage by 900. Multiplications of V times i
yield the power curve of figure 1.5
+
PC(t)
i VI
v(t)
i(t)
+
PC 0 t
(b)
V
_
1.
-VI
Energy Energy stored Energy stored
Energy released
released
2.
Fig 1.5: (a) pure capacitive circuit (b) power waveform for a pure capacitive circuit.
Consider fig 1.5. Energy stored during each quarter-cycle is returned during the next
quarter cycle. Thus, the average power is zero. Consequently, the only power flowing
in the circuit is reactive power. This is given by
QC = I2XC (1.3)
Example 1.3: With regard to fig 1.6, determine average and reactive power.
+
100V I
XC = 40
_
Fig 1.6
Solution
I = 100V/40 = 2.5A.
QC = VI = 100 x 2.5 = 250VAr.
P = 0W.
6
1.1.4 Calculations of power in A.C circuits containing R, L and C
Example 1.4: For the RL circuit of figure 1.7, I = 5A. Find the power and reactive power.
R = 3
XL = 4
P
5A
Q
Fig 1.7
Solution
P = I2R = (5)2 (3) = 75W
QL = I2XL = (5)2 (4) = 100VAr
Example 1.5: For the RC circuit of figure 1.8, determine the power consumed and the
reactive power.
+
40V 20R 80 XC
_
Fig 1.8
Solution
P = V2/R = (40)2/20 = 80W
QL = V2/XC = (40)2/80 = 20VAr
Example 1.6: A 10 resistor, a 100F capacitor and an inductor of 0.15H are connected in
series to a supply at 230V, 50Hz. Calculate the power consumed by the circuit.
Solution
XL = 2f L = 2 x 50 x 0.15 = 47.1
XC = 1 = 1 = 31.83
2fC 2 x 50 x 100 x 10-6
7
Z = √{R2 + (XL – XC)2} = √{102 + (47.1 – 31.83)2} = 18.28
I = VS = 230 = 12.58A
Z 18.28
Power consumed, P = I2R = (12.58)2 x 10 = 1582W
8
Power in A.C Circuit Week 2
At the end of this week, the students is expected to:
9
2. Static Capacitors
They are installed to improve the power factor of a group of a.c motors and are
practically loss-free. Since their capacitances are not variable, they tend to over-
compensate on light loads, unless arrangements for automatic switching off the
capacitor bank are made.
3. Phase Advancers
The power factor of induction motors is being improved by equipping the machines
with a phase advancer, which supply exciting current to the motor circuit. With the
arrangement, the phase angle between the supply voltage and current would be
decrease, thereby increasing the power factor.
10
Power Calculation in A.C Circuit Week 3
At the end of this week, the students are expected to:
Explain apparent power, reactive power and active power
Solve problems on power factor, active power apparent power reactive power and
power factor
1.4 APPARENT POWER, REACTIVE POWER AND ACTIVE
POWER
1.4.1 Apparent power I
+
S load
V
_
When a load has voltage V across it and current I through it as in figure 1.9, the power
that appears to flow to it is VI. However, if the load contains both resistance and
reactance, this product represents neither active power nor reactive power. Since VI
appears to represent power, it is called apparent power. Apparent power is given the
symbol S and units of volt-amperes (VA). Thus
S = VI (VA) (1.5)
where V and I are the magnitude of the r.m.s voltage and current respectively.
1.4.2 Reactive Power
Consider figure 1.3. During the intervals that instantaneous power P L(t) is negative,
power is being returned from the load. (This can only happen if the load contains
reactive elements: L or C.) The portion of power that flows into the load then back out
is called reactive power. Reactive power is given by the symbol Q and units of volt-
ampere reactive (VAr). Thus
Q = VIsinθ (1.6)
1.4.3 Active power
Consider again figure 1.3. Since PL represents the power flowing to the load; its average
will be the average power to the load. Denote this average by the letter P. If P has a
positive value, it represents the power that is really dissipated by the load. For
11
this reason, P is called Real power. In modern terminology, real power is also called
active power. The unit of active power is in watt (W). Thus
P = VIcosθ (W) (1.7)
1.5 SOLVED PROBLEMS ON POWER FACTOR, ACTIVE POWER,
APPARENT POWER, REACTIVE POWER AND POWER
FACTOR CORRECTIONS
R = 8
XL = 7 XC = 15
V = 100
Fig 1.10
Solution
Z = √{R2 + (XC – XL)2} = √{82 + (15 – 7)2} = 11.314
I = E = 100 = 8.84A
Z 11.314
From the phasor diagram of RLC series circuit shown in fig 1.11
VL
V
VL - VC
I
VR
Fig 1.11
VC
12
= cos-1 (70.72/100) = 450
(a) P = VIcos = 100 x 8.84 x cos450 = 625W
(b) S = VI = 100 x 8.84 = 884VA
(c) Q = VIsin = 100 x 8.84 x sin450 = 625VAr
(d) P.f = cos = cos450 = 0.707
Example 1.8: A resistor of 40 is connected in parallel with a 67.6mH inductor, the
combination being supplied by a 120V, 50Hz supply. Calculate (a) the power factor
(b) the active power (c) the apparent power (d) the reactive volt-amperes consumed
Solution
IR = VS/R = 120/40 = A
IL = VS = 120 = 5.65A
2fL 2 x 50 x 67.6 x 10-3
I = √(I 2 + I 2) = √(32 + 5.652) = 6.397A
R L
IR
VS
IL I
Fig 1.12
Example 1.9: A load of P = 1000KW with p.f = 0.5lagging is fed by a 5KV, 50Hz source. A
capacitor is added in parallel such that the power factor is improved to 0.8. Find the value of
the shunt capacitance needed to improve the power factor
13
Solution
The value of the shunt capacitance is given by
C = P(tan1 - tan2)
2fV2
Before improvement.
P = 1000KW, cos1 = 0.5, 1 = cos-1(0.5) = 600
Ptan1 = 1000K x tan600 = 1732.05KVAr
C = 1732.05 – 750.82 125F
2 x 50 x (5000)2
14
Three Phase Systems Week 4
At the end of this week, the students are expected to:
Define polyphase system
Explain the basic differences between single phase and three phase systems
Explain phase sequence of a three phase system
State the advantages of three phase circuits.
2.1 POLYPHASE SYSTEM
Circuits or system in which the ac sources operate at the same frequency but different
phases are known as polyphase systems.
2.2 BASIC DIFFERENCES BETWEEN SINGLE PHASE AND THREE
PHASE SYSTEMS
2.2.1 Single-Phase Systems
A single phase a.c power system consists of a generator connected through a pair of
wires (a transmission line) to a load. Figure 2.1 depicts a single phase two wire
system, where VP is the magnitude of the source voltage and is the phase. The
power in a single phase system is pulsating (not constant). For large motors, pulsating
power supply causes excessive vibration. Besides, it has neither delta nor star type of
connection.
Vp Φ _+ ZL
15
Vp 00 ZL1
_+a A
Vp -12 00
_
b B
ZL2
+
Vp +12 00
_
c C ZL3
+
n N
A B C
ωt
1200
2400
16
2.4 ADVANTAGES OF 3-PHASE CIRCUITS
1. The instantaneous power in a three phase system can be held constant. This
results in uniform transmission.
2. Three phase systems are more economical than single phase systems.
3. Three phase systems are more efficient
17
Three Phase Systems Week 5
At the end of this week, the students are expected to:
Explain how 3-phase e.m.fs are produced
Distinguish between star and delta three-phase system
Derive the relationship between line and phase values of voltages and currents in a
star and delta connected windings
2.5 GENERATION OF THREE PHASE E.M.F’s
B1 A C1
N
S
C B
A1
18
2.6.2 Delta-Connected 3-Phase system
1. Neutral wire is not present
Line 1
VR
VRY
VBR
VB
Vy
Line2
Line VYB
3
(a)
Fig 2.5: (a) Star connection of a 3-Φ circuit
VRY
VR
-VY -VB
300
VYB
VB
VY
-VR
VBR
19
Fig 2.6: phasor diagram of a star connected load
Consider the star connection of a three phase circuit shown in fig 2.5. It phasor
diagram is as shown in fig 2.6. To obtain the line voltages we proceed as under:
Let VRY = line voltage between red phase and yellow phase
VYB = line voltage between yellow phase and blue phase
VBR = line voltage between blue phase and red phase
VR = voltage across the red phase
VY = voltage across the yellow phase
VB = voltage across the blue phase
Thus, VYB, VBR and VYB are called line voltages, while VB, VR and VY are called
phase voltages.
The p.d between line 1 and 2 in (fig 2.5) is V RY. Hence, VRY is found by
compounding VR and VY reversed and its value is given by the diagonal of the
parallelogram of fig 2.6. Obviously, the angle between V R and VY reversed is 600. The
parallelogram is shown in fig 2.7 below.
VY VRY
300
o VR
Fig 2.7: parallelogram of fig 2.6
From fig 2.7, ox = ½ VRY (2.1)
Also, ox = VR cos 300 (2.2)
Equating (2.2) to equation (2.1) gives
VRY = 2 (VRcos300)
= √3 VR = √3 Vph
Considering that the system is balanced,
VYB = √3 Vph
also, VBR = √3 Vph
Now VRY = VYB = VBR = line voltage, say VL. Hence, in star connection
VL = √3Vph (2.3)
20
2.7.2 Line currents and phase currents in a star connected windings
R
IR
IB
Iy
2
Y
IY (IY – IR)
VYB
3 B
(IB – IY)
21
VRY
(IR – IB)
IR
-IY Φ
-IB
(IB – Iy)
Φ
Φ
IY VYB
IB
-IR
VBR
(IY – IR)
Fig 2.10 Phasor diagram of a delta connection of a three phase circuit
Consider the delta connection of a three phase circuit shown in fig 2.9. It phasor
diagram is as shown in fig 2.10. To obtain the line currents we proceed as under:
Let I1 = IR – IB
I2 = IY - IR
I3 = IB - IY
I1, I2 and I3 are called line currents
Line current I1 is also found by compounding IR and IB reversed as shown in fig 2.10. Its
value is given by diagonal of fig 2.10. The parallelogram of fig 2.10 is as shown in fig
2.11.
IR
I1
300
o IB
Fig 2.11: parallelogram of fig 2.10
From fig 2.11,
Ox = ½ I1 (2.5)
Also, ox = IB cos300 (2.6)
22
From equation (2.6) and (2.6), ½ I1 = √3/2 IB
If IR = IY = IB = phase current (Iph), then
Current in line no.1 is I1 = √3Iph
Current in line no.2 is I2 = √3Iph and
Current in line no.3 is I3 = √3 Iph
Since all the line currents are equal in magnitude, i.e I1 = I2 = I3 = IL
IL = √3Iph (2.7)
23
Three Phase Systems Week 6
At the end of this week, the students are expected to:
Derive an expression for power in a three-phase circuit (balanced and unbalanced)
Explain the two wattmeter and single wattmeter methods of measuring three-phase
power
2.8 DERIVATION FOR POWER IN A 3-PHASE CIRCUIT
(BALANCED AND UNBALANCED)
2.8.1 Power in a 3-Phase circuit (balanced-delta connection)
Consider the delta connection of a three phase circuit (fig 2.9). The total active power
in a delta connected circuit is the sum of the three phase powers. Hence,
Power per phase = VphIphcos
Total power = 3 x VphIph cos
However, Vph = VL and Iph = IL/√3. In terms of line values, the above expression for
power becomes
P = 3 x VL x IL x cos = √3 VLILcos (2.9)
√3
Similarly, total reactive power is given by
Q = √3 VLILsin (2.10)
and total apparent power of the three phase is
S = √3 VLIL (2.11)
2.8.2 Power in a three phase circuit (unbalanced star connection)
IR
Vph ZR
N
I
ZY
Vph ZB
IY
Vph
I
Consider the unbalanced three phase star connected load, where it is assumed that the
phase voltages (Vph) are equal. The line currents are obtained from ohms law.
24
Power in phase R, PR = phase voltage x Phase current x cosR, where R is the angle
between phase voltage and phase current.
PR = Vph IRcosR (2.12)
Similarly, power in phase Y is obtained as
PY = Vph IY cosY, (2.13)
Power in phase B is
PB = Vph IB cosB (2.14)
Total power in the three phase is
PT = PR + PY + PB
= Vph IRcosR + Vph IYcosY + Vph IBcosB (2.15)
are connected to the remaining phase. As shown in fig 2.12, wattmeter W 1 is inserted
in phase a and wattmeter W2 in phase c. Their potential coils are connected across a
and b, and c and b respectively. The current coil (c.c) of each wattmeter measures the
line current, while the respective potential coil (p.c) measures the line voltage. The
algebraic sum of the two wattmeter readings equals the total power absorbed by the
loads. Thus
W1 + W2
25
c.c
a W1 ia
p.c ZA
b
ZB ZC
p.c
ic
c c.c
c.c
W1
a
p.c Z
Z
Z
b
c
Fig 2.13: schematic diagram of a single-wattmeter method
26
Three Phase Systems Week 7
At the end of this week, the students are expected to:
Solve problems on
Line and phase voltages and current in a star and delta connected windings
Power in a three phase circuit
2-wattmeter and single wattmeter methods of measuring 3-phase circuits
2.10 SOLVED PROBLEMS ON LINE AND PHASE VOLTAGES AND
CURRENT IN A STAR AND DELTA CONNECTED WINDINGS,
POWER IN THREE PHASE CIRCUIT AND 2-WATTMETER AND
SINGLE WATTMETER METHOD OF MEASURING 3-PHASE POWER
Example 2.1The impedance per phase of a delta connected load is 10 per phase, the line
voltage being 230V. Determine (a) the phase current (b) the line current (c) the apparent
power of the load.
Solution
(a) Iph = Vph/Zph = 230/10 = 23A
(b) IL = √3 Iph = √3 x 23 = 39.8A
(c) S = √3 VL IL = √3 x 230 x 39.8 = 15.9KVA
The circuit arrangement is shown in fig 2.14.
Iph = 39.8A
Zph = 10
VL = 230V Iph = 23A Zph = 10
Zph = 10
27
Example 2.2An unbalanced star-connected load has balanced phase voltage of 120V and
the a.b.c sequence. The line currents are given as Ia = 1000A, Ib = 20-400A and Ic = 30-
1550A. Find the power consumed by the circuit.
Solution
Ia = 1050A, Vpa = 12000V
Ib = 20400A, Vpb = 120-1200V
Ic = 301550A, VPc = 120-2400V
Pa = VPIacosa = 120 x 10cos(0 – 0) = 1200W
Pb = VpIbcosb = 120 x 20cos{-120 –(-40)} = 416.76W
Pc = VPIccosc = 120 x 30cos{-240 – (-155)} = 313.76W
P = Pa + Pb + Pc
= 1200 + 416.76 + 313.76 1.93KW
Example 2.3: Line voltage and current of a delta connected inductive load is 160V and 40A
respectively. Power factor of load is 0.8lag. Assuming that power is being measured using
two wattmeters, find the readings of the wattmeters.
Solution
VPh = VL = 160V, IL = 40A
Total power, P = √3 VLILcos
= √3 x 160 x 40 x 0.8 = 8868W
W1 + W2 = 8868 (2.4.1)
cos = 0.8, = cos-1(0.8) = 36.90
tan = 0.75
For a lagging P.f,
tan = √3 (W1 - W2)
W1 + W2
0.75 = √3 (W1 – W2), W1 – W2 = 8868 x 0.75 = 3840
8868 √3
W1 – W2 = 3840 (2.4.2)
Adding eqtn. (2.4.1) and (2.4.2) together gives
2W1 = 12708
W1 = 12708/2 = 6354W
From eqtn. (2.4.1), W2 = 8868 – 6354 = 2514W
28
Example 2.4: The current coil of a wattmeter is connected to the red phase of a star
connected load, while the potential coil is connected between the line and the neutral. If the
phase voltage and current are respectively 20800V and 30500A, find the total power
consumed by the load.
Solution
The circuit diagram is shown in fig 2.15
c.c IR
W1
R
Vph
p.c Z
Z Z
B
Fig 2.15: schematic diagram of a single-wattmeter method
P = √3 VLILcos
where IR = IL and VL = √3 VPh = √3 x 20800 = 34.64800V P
= √3 x 34.64 x 30 cos(800 – 500) = 1558.8W
29
Time Domain Analysis Week 8
At the end of this week, the students are expected to:
Explain the meaning of transient
Derive formulae for current and voltage growth and decay in RC circuits
3.1 TRANSIENT
when a circuit possesses energy storing elements such as inductance and capacitance,
the energy state of the circuit can be disturbed by changing the position of the switch
(fig 3.1) connecting the elements to the source. There is a transitional period during
which the branch current and element voltages change from their former values to
new ones. This period is called the transient.
3.2 DERIVATIONS OF FORMULAE FOR CURRENT AND
VOLTAGE GROWTH AND DECAY IN RC CIRCUIT
3.2.1 Current and Voltage Growth in RC Circuit
Let us consider the circuit shown in figure 3.1
R C
Let the current in the circuit at any instant t be i, and capacitor voltage be v. When
switch S is closed and Kirchhoff’s law is being applied, this yield
Ri + v = V (3.1)
Since i = C(dv/dt), equation (3.1) becomes
V = RC (dv/dt) + v
V – v = RC (dv/dt)
so that dt/RC = dv/(V – v)
Integrating both sides, we have
t = -ln (V – v) + A
RC
where A is the constant of integration
when t = 0, v = 0
30
A = ln V
So that t = ln V .
RC V–v
V = e t/RC
V–v
and v = V (1 – e-t/RC) volts (3.2)
Also i = C dv = CV . d (1 – e-t/RC)
dt dt
i = V/R . e-t/RC (3.3)
R
C
By Kirchhoff’s law
iR + v = 0 or -v = C dv { i = C dv/dt}
R dt
So that dt/RC = -dv/v
Integrating both sides, we have
t = - ln v + A
RC
When t = 0, v = V, so that A = ln V. Hence
t = ln V/v
RC
So that V/v = et/RC
and v = Ve-t/RC (3.4)
Also i = -v/R
The negative sign indicates that the direction of the discharge current is the reverse of
that of the charging current
i = -V/R e-t/RC (3.5)
31
Time Domain Analysis Week 9
At the end of this week, the students are expected to:
Sketch the growth and decay curves in RC circuits
Define time constant in RC circuit
Solve problems involving transient in RC circuit
3.3 SKETCH FOR GROWTH AND DECAY CURVES OF CURRENT
AND VOLTAGE IN RC CIRCUIT
The sketch for growth of current and voltage in RC circuit is shown in figure 3.3
while the sketch for decay of current and voltage in RC circuit is as shown in fig 3.4
V
i,v
Charging current
Voltage across the capacitor
Voltage across the capacitor
T
Discharging current
t
i Fig 3.4
Fig 3.3
32
3.5 SOLVED PROBLEMS INVOLVING TRANSIENT IN RC
CIRCUIT
Example 3.1: A 20F capacitor is charged to a p.d of 400V and then discharged through a
100,000 resistor. Determine:
(a) the time constant
(b) the initial value of discharged current
Solution
(a) T = RC = 100 000 x 20 = 2s
100 000
(b) Initial value of discharge current is
V/R = 400/100 000 = 4mA
Example 3.2: An 8F capacitor is connected in series with a 0.5M resistor across a 200V
d.c supply. Calculate:
(a) the time taken for the P.d across the capacitor to grow to 160V:
(b) the current and the P.d across the capacitor 4s after it is connected to the supply
Solution
(a) T = RC = 0.5 x 106 x 8 x 10-6 = 4s
From v = V(1 – e-t/RC)
-t/4
e = 0.2
From mathematical table
t/4 = 1.61
t = 6.44s
(b) At t = 4s
-4/4
v = 200(1 – e ) = 200( 1 – 0.68) = 126.4V
and i = v/R e-t/RC
= 400 e-1 = 147A
Example 3.3: A 15F capacitor in series with a 10K resistor is connected across a 300V
d.c supply. The fully charged capacitor is disconnected from the supply and is discharged by
connecting a 11200 resistor across it terminals. Determine (i) the initial value of the
charging current, and (ii) the initial value of the discharge current.
33
Solution
(i) Initial value of charging current, I0 = V/R = 300 = 30mA
10 x 103
(ii) The initial value of discharging current is given by
i = V/R, where R = 11200
i = 300 = 26.7mA
11200
34
Time Domain Analysis Week 10
L
V
R
35
When t = 0, i = 0, so that, A = ln I.
Rt/L = -ln(I – i) + ln I
= ln I .
I–i
Hence I – i = e-Rt/L
I
i = I(1 – e-Rt/L) (3.8)
The voltage across the inductance,
VL = L di/dt
= L d/dt [ I (1 – e-Rt/L )]
VL = IR e-R/L . t (3.9)
R L
X
Switch
Y
V
Fig 3.6
0 = Ri + L di/dt
Ri = -L di/dt
The negative sign indicate a decaying current, hence
(R/L) dt = -1/t dt
Integrating both sides, we have
(R/L) t = -ln i + A
where A is the constant of integration
At the instant of closing switch, t = 0 and i = I, so that
0 = -ln I + A
(R/L) t = ln I – ln i
Hence I/i = e-Rt/L
and i = I e-Rt/L (3.10)
Also, VL = L di/dt
36
= L [d/dt {Ie-Rt/L}]
VL = -IR e-Rt/L (3.11)
Decaying current
t
VL Fig 3.8
Fig 3.7
37
Time Domain Analysis Week 11
B
E
RD
Let us consider the circuit shown in figure 3.9. A discharge resistor R D is connected in
parallel with the inductive circuit. When the switch S is connected to A, the current
becomes E/R. When the switch is moved to position B, the circuit is disconnected
from the supply.
When the position of the switch is change from A to B, the circuit in the
inductive circuit is switched off and a voltage is induced in it. Arcing is produced at
the time of charging the position of the switch and there is a possibility of damaging
the insulation because the induced voltage may be many times greater than the
applied voltage. To avoid this arcing, a discharge resistor R D is connected as shown in
figure 3.9
3.10 SOLVED PROBLEMS INVOLVING TRANSIENT IN RL
CIRCUIT
Example 3.4: A coil having a resistance of 4 and a constant inductance of 2H is switched
across a 20V d.c supply. Calculate:
(a) the time constant
(b) the final value of the current
Solution
(a) T = L/R = 2/4 = 0.5s
38
(b) I = V/R = 20/5 = 5A
1 2
R1 = 10 R = 15
10V
L = 0.1H
Fig 3.10
Solution
(a) For the switch in position 1, the time constant is
T1 = L/R1 = 0.1/10 = 10ms
-3
i = I(1 – e-t/T) = 10/10 (1 – e-t/10x10 )
1
-t/10x10 -3
= (1 – e ) amperes
(b) For the switch in position 2, the time constant is
T2 = L = 0.1 = 4ms
R1 + R 10 + 15
2 t/4x10-3
i =2 Ie-t/T = 10/10 (e- )
-3
t/4x10
= e- amperes
Example 3.6: A coil having 10 resistance and 14H inductance is connected across a
d.c voltage of 140V. After the current has reached its final value, how much time it would
take for the current to reach a value of 8A after switching off the supply.
39
Solution
-t/T
i = Ie
where i = 8A, and T = L/R = 14/10 = 1.4s
and I = V/R = 140/10 = 14A
-t/1.4
8 = 14 e
e-t/1.4 = 8/14
t = 0.783s
40
Magnetic Coupling Week 12
12
1 2
Coil 1Coil 2
Figure 4.1 shows magnetic coupling between two coils. In this case, a portion of the
magnetic flux established by one coil interlinks the other. In this case, energy is
transferred from one circuit to the other through the medium of magnetic flux that is
common to both.
From fig 4.1, 1 is the total flux produced by i 1, and 2 is the total flux
produced by i2, and 12 is the magnetic flux that linked both coils
41
4.3 DERIVATION FOR MUTUAL INDUCTANCE BETWEEN TWO
COILS
Consider fig 4.1. The induced voltage in coil 2 due to a change in flux can be written
as (by faraday’s law)
e2 = N2d12 (4.1)
dt
where N2 is the number of turns in coil 2
Also, e2 is proportional to the rate of change of i1, that is
e2 α di1 or e2 = M di (4.2)
dt dt
In equation (4.2), M is the constant of proportionality known as mutual inductance
between two coils. It is measured in Henry (H)
Equating equation (4.1) to (4.2) we have
N2 d12 = M di1 dt
dt
M = N2 d12 (4.3)
di1
42
Magnetic Coupling Week 13
M positive M negative
M negative M negative
Fig 4.2: Dot Convention
43
4.5 COEFFICIENT OF COUPLING
Coefficient of coupling is defined as the ratio of mutual inductance M to the square
root of the product of inductances of coil 1 and coil 2.
44
Magnetic Coupling Week 14
V1 load
V2
X1 I11 X2 R2I2
I1R1 P S
I1 Z1 I0
E1 E2 I2Z2
R X To load
V1 IC V2
Img
Ideal transformer
Fig 4.6: Equivalent circuit of a practical transformer
45
transformer. Similarly, inductive reactances X 1 and X2 represent the reactance of the
windings due to leakage flux in the practical transformer.
The inductive reactor X is such that it takes a reactive current equal to the
magnetizing current Img of the practical transformer. The core losses due to hysteresis
and eddy currents are allowed for, by a resistor R of such value that it takes a current
Ic equal to the core loss of the practical transformer. The resultant of I mg and Ic is Io,
which is the current the transformer take on no load.
46
Magnetic Coupling Week 15
Example 4.2: Two coils having 30 and 600turns respectively are wound side by side on a
closed iron circuit. If the mutual inductance between the coils is 0.226H, and the change of
current in the first coil is 20A in 0.02s, find the e.m.f induced in the second coil
Solution
e2 = M di/dt = 0.226 x 20/0.02 = 226V
Example 4.3: The coefficient of coupling between two coils is 0.75. There are 250turns in
coil 1. The total flux linking coil 1 is 0.4mWb, when the current in this coil is 3A. When i 1 is
changed from 3A to zero linearly in milliseconds, the voltage induced in coil 2 is 70V.
Calculate: (a) the self inductance of coil 1 (b) the mutual inductance between the two coils.
Solution
(a) L1 = N11 = 250 x 0.4 x 10-3 = 3.4 x 10-3H
i1 3
(b) e2 = M di, M = e2 dt = 70 x 3x 10-3 = 70 x 10-3H
dt di 3
Example 4.4: Two coils X and Y have self inductance of 12H and 20H respectively, the
mutual inductance between the coils being 8.5H. Find the coupling coefficient between the
two coils
Solution
K= M = 8.5 = 0.55
√(LXLY ) √(2 x 20)
47
Example 4.5: The current in the primary winding of a pair of mutually coupled coil is 5A,
and the primary flux of 6mWb links with the secondary winding. If the secondary winding
has 950turns and the primary winding current is reduced to zero in 4ms, determine: (a) the
average value of the e.m.f induced in the secondary winding (b) the mutual inductance
between the two coils
Solution
(a) e2 = N2 d2 = 950 x 6 x 10-3 = 1425V
dt 4 x 10-3
(b) M = e2 dt, whee dI1 = 5 – 0 = 5A
dI1
M = 1425 x 4 x 10-3 = 1.14H
5
48