Frimware Upgrade Via Serial
Frimware Upgrade Via Serial
BEFORE YOU BEGIN THE DOWNLOAD PROCESS, ENSURE THAT WHILE THE
DOWNLOAD AND FIRMWARE UPDATE ARE IN PROGRESS, THERE ARE NO
INTERRUPTIONS TO THE COMMUNICATIONS, OR THE POWER SUPPLY TO THE METER,
THE RS485 ADAPTER OR THE COMPUTER
Performing a proper download and update process requires a level of competency on working
with hardware and software tools. If you believe you are not confident in performing the update
by yourself, please contact Schneider technical support for help.
It is essential that your meter has a tested and verified RS485 serial or Ethernet connection
(via EGX Gateway) to a computer prior to running this procedure. If your device does not
have this setup, you must obtain this before proceeding.
Connect the SMD meter communications port to the RS485 serial adapter. Connect the RS485
adapter to appropriate serial port of your computer and power on the meter and the adapter.
On your computer, open the DLF3000 program. The following window appears:
Under Enter New System Name, type a name of choice and click “OK”
In the following window, click on “Add”
Now, there are two ways to upgrade meter firmware, in this case we will choose through serial
RS485 (MODBUS):
Protocol: Modbus
Address: <Respective device address>*
Baud Rate: 19200
Parity: Even
* For every device that is daisy-chain connected for simultaneous firmware download, make
sure each of them has a unique “Address” in its communication configuration. For our example,
we will connect a single meter and set its “Address” as 1.
Enter a Communications Connection Name of choice, for Communications Driver select “Serial
Driver” and click “Continue”
In the next window, set the fields as shown below, selecting the appropriate Serial Port
according to your configuration:
In the window that follows, in the Devices Defined section select “Add”
In the pop-up, type a device name of choice, set the “Device Type” as per below rule and click
“OK”:
In the following window, under Download Candidate Devices select your Communications
Connection Name (which was set as “COMM” earlier in this tutorial) and then click on the “>>”
button
The contents should move to the Download Target Devices section now, as shown below:
In the health check window that appears, click on the “Health Check” button
If everything has been configured correctly, the communications is running and the meter is
responding as expected, you should get the currently installed Firmware Revision number (not
necessarily the same as shown in below picture) and a Passed message in the Health Status,
as shown below:
If you get an error in this stage, please go back to previous steps to check for incorrect
configurations and/or check the wiring and the supply to the meter and the adapter Once
the health check is passed, the meter is ready to accept the firmware update
As the download starts, the SMD meter will go into OS download mode and information
regarding the ongoing download can be seen on the screen of the meter, as well as in the
window below:
After the downloading is finished, the meter will self-restart. Wait for the following status in the
download window:
When you get the above status in the Download Firmware window, the meter has been
successfully updated with the selected firmware and is ready for use
You may connect another meter and click on “Re queue” to repeat the update process, or you
may click on “Finished” and exit the program
Once you have used the DLF3000 on a computer and created a download profile using the
above steps, you can run the DLF3000 anytime and select the same profile to repeat the
firmware update process for SMD. This way you do not need to go through setting all the
parameters every time you run the software.