MEE - Unit 4 - Notes
MEE - Unit 4 - Notes
Polarity marking in case of single phase transformer is required for connecting two
or more transformers in parallel
While in case of three phase transformer. Polarity marking of each phase winding is
necessary for connecting it in required transformer grouping such as star/star,
delta/star etc
As per ISS-1962 the terminal marking of three-phase and single –phase T/f should
be as shown in figs
Instead if the voltmeter reads voltage equal to supply voltage and secondary emf
the polarity marking given is reversed on secondary and it is termed as additive (see
fig)
In case of transformer, subtractive polarity making is preferred because by chance
any two adjacent terminals i.e A1 a1 or A2 a2 get shored, the voltage available across
the windings will be less than supply voltage, hence will not cause any harm to the
insulation of transformer windings.
Another method of marking polarity is as shown in fig. in this case also, secondary
terminals are marked arbitrarily(randomly) with respect to primary terminals
The primary and secondary terminals are
connected in series as shown in fig
If the voltage V1 across the primary is less
than supply voltage polarity is correct or
subtractive
In case of subtractive polarity marking a any
instant the direction of induced e.m.f.s In
both primary and secondary will be the
same i.e either From A2 to A1 and a2 to a1 or
A1 to A2 and a1 to a2
It also means that both winding are wound on the core in the same direction and
their staring ad finishing ends ae marked by same suffixes
If the voltage V1 across the primary is addition of supply voltage and secondary
e.m.f than polarity is reversed or additive.
2.) Phasing out test (I):-
This test is carried out to identify primary & secondary windings belonging to
same phase. This test is required only in case of three phase transformer.
In this test, generally the L.V winding is connected to rated voltage at rated
frequency
As the high voltage may not be available in the laboratory for testing purpose
This test can be carried out on transformers complete with winding and fitted in
tank with oil
For normal for low flux densities the reading of the wattmeter (low P.F) will represent
i.) core loss of transformer
ii.) L.V copper loss at no load which is negligible
Neglecting other losses which are very small the wattmeter represents core losses
The reason for connecting voltage to H.V side in this test is that the voltage required for
conducting the test is nearly five percent of rated voltage which will be available in the
laboratory
But the current required for L.V is much more in comparison to full load H.V current which
may not be available or may cause disturbance to the distribution system at the time of
testing
the reading of the wattmeter voltmeter and ammeter are recorded
Generally current flowing through H.V. winding is adjusted to its full load value at this time
the reading of wattmeter indicates full load copper loss and iron losses being negligible
The voltage applied under this condition say Vsc is called as impedance voltage or
impedance voltage drop as this voltage is utilized in a drop across the impedance of the
transformer winding and no voltage is available across the short circuited L.V winding
235.5 + 75
𝑊𝑠𝑐 𝑎𝑡 750 𝐶(𝐹. 𝐿 𝑐𝑢. 𝑙𝑜𝑠𝑠 𝑎𝑡 750 𝐶) = 𝑊𝑠𝑐 x
235.5 + 𝑡1
235.5 + 75
𝑅01 𝑎𝑡 750 𝐶 = 𝑅01 𝑎𝑡 𝑡1 x
235.5 + 𝑡1
𝑋01 𝑎𝑡 750 𝐶 𝑖𝑠 𝑠𝑎𝑚𝑒 𝑎𝑠 𝑋01 𝑎𝑡 𝑡1
From this test results and test results of open circuit test the performance characteristics such
as efficiency of transformer by loss summation can be found. Similarly regulation can also be
determined:-
400V 2 500 V
11 kV 50 1000 V
33 kV 150 2500 V
132 kV 500 2500 V
The test should be conducted immediately after the heat run test on the transformer. The
insulation resistance is measured between
transformer windings and core between
transformer windings between core and
core clamping bolts etc as shown in fig
During the test the handle of the megger
should be moved at a constant speed
otherwise it will give misleading results
However high value of insulation
resistance does not mean high value of
dielectric strength
For example if there is a small air gap in
between windings it will show high
insulation resistance
But will break down when few kilovolts are applied across the windings Insulation
If insulation which as wrinkles or damaged mechanically will show high insulation resistance
but will fail at very low voltage applied across it
However it does not appear in the ammeter, voltmeter and wattmeter W1 and
connected in primary side,
So the current taken from the supply side is only the total no load current of two
transformer
The wattmeter reading connected W1 in the primary side indicates total no load loss
or iron loss of two transformer
The wattmeter W2 connected in secondary side indicate that copper loss or load
loss of two transformer caused by circulating current since both the losses are
known, than efficiency of the transformer can be easily determined
To measure the temperature rise two transformers are kept under rated load
conditions for several hours till maximum steady state temperature is reached.
Observation table:-
Sr Primary Side Secondary Side
No V1 (volts) I1 (amps) W1 (watts) V2 (volts) I2 (amps) W2 (watts)
1 Rated primary
I0 W0 Vsc Isc (Ifl) WSC
voltage (V0)
𝑋02 = √(𝑍02
2 2
− 𝑅02 )
The load is adjusted in such a way that ammeter on secondary records full load
current at this time primary current also will be full load current neglecting no load
current as ampere turns of primary and ampere turns of secondary are equal
The condition is maintained still final steady-state temperature is reached the load
is then removed supply disconnected and winding resistance measured
immediately.
From initial resistance i.e resistance at ambient temperature and resistance at full
load conditions, the temperature rise is calculated as
𝑅𝑡1 = (𝑖𝑛𝑖𝑡𝑖𝑎𝑙) 𝑟𝑒𝑠𝑖𝑠𝑡𝑎𝑛𝑐𝑒 𝑎𝑡 𝑎𝑚𝑏𝑖𝑒𝑛𝑡 𝑡𝑒𝑚𝑝𝑒𝑟𝑎𝑡𝑢𝑟𝑒 𝑖. 𝑒 𝑡10 𝐶
𝑡10 𝐶 = 𝑡𝑒𝑚𝑝𝑒𝑟𝑎𝑡𝑢𝑟𝑒 𝑎𝑡 𝑡ℎ𝑒 𝑡𝑖𝑚𝑒 𝑜𝑓 𝑡𝑒𝑠𝑡𝑖𝑛𝑔(𝑎𝑚𝑏𝑖𝑒𝑛𝑡).
𝑅𝑡2 = 𝑟𝑒𝑠𝑖𝑠𝑡𝑎𝑛𝑐𝑒 𝑎𝑡 𝑓𝑢𝑙𝑙 𝑙𝑜𝑎𝑑 𝑖. 𝑒 𝑡20 𝐶
𝑡20 𝐶 = 𝑡𝑒𝑚𝑝𝑒𝑟𝑎𝑡𝑢𝑟𝑒 𝑎𝑡 𝐹𝑙 𝑐𝑜𝑛𝑑𝑖𝑡𝑖𝑜𝑛 𝑤ℎ𝑖𝑐ℎ 𝑖𝑠 𝑟𝑒𝑞𝑢𝑖𝑟𝑒𝑑.
234.5 + 𝑡20 𝐶
𝑅𝑡2 = 𝑅𝑡1
234.5 + 𝑡10 𝐶
For carrying out impulse test, impulse generator is used which will develop
unidirectional wave shape. As per IS 2026–1962 a 1/50 wave is used for impulse
testing
We will first see the meaning of a 1/50 wave, its shape and how the shape of the
wave is obtained with the impulse generator.
The simplest basic circuit for developing a 1/50 wave and its application to the
electrical equipment under test is shown in fig:-a, the 1/50 wave is represented in
fig:-b.
The low voltage from this can be applied to the CRO. tube which will record the
wave shape applied to the equipment and also if there is any damage to the
insulation or weakening of insulation during this test can be determined from the
photographs of wave shapes obtained from CRO tubes
Types of faults :-
1.) Mechanical fault:-
A fault which occurs due to mechanical failure in the electrical machines are
called as mechanical fault.
Following are the reasons of mechanical faults:-
1.) Warn out bearings 2.) Misalignment 3.) Rotor unbalance
4.) Bent shaft 5.) Excessive belt pull.
6.) Failure of lubricating system 7.) Loose foundation
8.) Overloaded bearings 9.) Out of roundness in a Commutator
3. Electrical faults:-
a.) Internal Short circuit fault (turn to turn fault)
b.) Open circuit fault
c.) Ground fault
d.) Poor contact in armature winding.
e) Wrong setting of brushes.
f.) Overheating of Commutator due to sparking
g.) Overvoltage, Over frequency and Under frequency.
h.) Single phasing