Substation Design
Substation Design
SUBSTATION DESIGN
➢ SLD
➢ EQUIPMENT LAYOUT
➢ BUSBAR ARRANGEMENT
➢ FAULT LEVEL
➢ TYPE OF CONSTRUCTION
➢ CREEPAGE AND CLEARANCE
➢ GROUNDING & LIGHTNING PROTECTION
➢ SAFETY INTERLOCKS
➢ OTHERS, e.g. LIGHTING AND CIVIL
SUBSTATION DESIGN CRITERIA
2. S.C.CALCULATION :
- To permit the equipment to without damage, severe thermal
and mechanical stresses of S.C. currents.
- To provide adequate interrupting capability in CBs, strength
in post insulators
- Setting of protective relays
SUBSTATION DESIGN CRITERIA
1. System Security :
- The ideal s/s is one where each circuit is controlled by
separate CB with facility for replacement of bus bar OR CB in
the event of fault or during maintenance.
- Double Bus Bar system with Double CB arrangement is ideal.
2. Operational Flexibility :
- For efficient loading of Generators it is necessary to control
MVA and MVAR loading under all condition
5. Maintenance Facilities :
- Arrangement shall be suitable for the Planned or Emergency
Maintenance .
6. Ease of Extension ::
- To add new bays there shall be space and expansion facilities.
7. Site Considerations :
- Where the area is limited, simple arrangement with least no of
CBs.
Considerations for Choice of Busbar Arrangement
➢ Importance of Substation
➢ Reliability
➢ Redundancy
➢ Economics and availability of finance
➢ Availability of Space and Right Of Way for approaching
lines
➢ Future Expansion
Single Bus System- Primary Components,
Protection Zone
Bus
Bus- Bus-
Earthing Bus- Potential
Switch Isolator Transformer
Circuit-breaker Protection-zone,
busbar
Current
Transformer
Protection-zone,
line/trafo
Line Line
Earthing- Earthing-
Isolator Isolator
switch switch
Wave Wave
Trap Trap
Potential
Surge Transformer
arrester
x x x x
CT CT CT CT
A Transfer Bus Coupler & All feeders need one additional isolator.
Ring or Mesh System Line 1
Transformer 1 Transformer 2
Line 2
Single Bus with sectionaliser System- Primary
Components,
Over-lapping Protection Zone
Bus Section-isolator
Bus A Bus B
Circuit-breaker
CT
VT
Earthing switch
Line-
disconnect Surge arrester
Earthing switch
Bus II
Bus-
Isolators
Circuit-breaker Bus-
Earthing-I, II
CT
Earthing-
Line switch Line
Earthing-
Isolator Earthing- Isolator
switch
switch
Wave
Trap Wave
Trap
Surge
arrester Surge
arrester
Line 1 Line 2 Transformer
Double Main & Transfer Bus
Arrangement (DMT)
Transfer Bus- Bus-
Bus I Bus-coupler Bus-coupler PT -I PT -II
Bus II
Bus-
Isolators
Circuit-breaker Bus-
Earthing-I, II
CT
Earthing- Line Earthing-
switch Isolator switch
Transfer
Isolator
Wave Wave
Trap Trap
Surge Surge
arrester arrester
Line 1 Line 2
One and a Half Breaker
Arrangement
Bushing Bus A
Q0 11 Q0 41
Q0 13
Q0 12 Q0 42
Bushing
Bus B
Three Main & Transfer Bus Arrangement
2000/1/1/1A
Core Like
line 417
245kV Switchyard Layout
245 kV Outdoor switchyard (AIS) Double busbars, classical layout
1. FAULT LEVEL :
➢ Expressed as MVA or kA and duration of 1-3 Sec.
➢ Depends on source impedance
➢ All CBs are to be rated for fault level
➢ Earth Switches for making fault level
➢ - All Bus bars, bus supports to be designed to withstand forces
due to S.C
2. SAFETY CLEARANCES :
3. STRUCTURE :
Why is it required ?
➢ To support and install Buses, electrical equipment and terminate
transmission line conductors.
➢ The structures may be of steel, RCC or wood
➢ They need foundation according to soil condition at site
SUBSTATION DESIGN CONSIDERATIONS
1 11/22 1.3
2 33 1.5
3 66 2.0 to 2.2
5 220 4.5
6 400 7.0
BUS DESIGN
Present day trend is to use Rigid bus rather than strain bus due to
➢ can be constructed at lower profile.
➢ are aesthetically pleasing.
➢ corona level is lower.
1. Construction of Rigid Bus :
➢ Aluminum bus materials used for rigid bus may be of different
shapes.
➢ They may be round tubing's, channels, angles or integral web
designs.
➢ Round tubing used in all voltage levels.
➢ Square/channel tubing is used only at lower voltages.
➢ Angle bus used only at distribution voltages.
➢ Integral web bus is structurally strong and is used for high current and
long spans generally at lower voltage.
BUS DESIGN
➢ RIGID BUS :
1. BPI
2. Aluminium Tubular pipes for bus
3. Welding Sleeves of equivalent dia for Al Bus.
4. BPI clamp for fixing tubular pipe to the insulator
5. Inter connector for Al tube to strain Bus
6. Corona bells for the free ends of right bus.
➢ STRAIN BUS :
1. Insulator strings
2. ACSR conductor of right choice
3. Hardware fittings for tension points.
4. Arcing horns
5. Corona rings
ACCESSORIES REQUIRED FOR BUS CONSTRUCTION
Purpose :
so earthing is required to –
1. Soil investigation.
2. Determination of maximum ground current
3. Preliminary designing of grounding system
4. Calculation of resistance of grounding system
5. Calculation of maximum grid potential rise.
6. Calculation of step and touch voltages.
7. Correction of preliminary design.
A continuous earth conductor is placed around the
perimeter of yard to enclose as much ground as possible to
avoid current concentration.
Within the grid conductors are laid in parallel lines and at
uniform spacing along the rows of structure and equipment.
SUBSTATION EARTHING
➢ High conductivity
➢ Low underground corrosion
➢ Voltage Factors :
The value Vf in Table 8.2 is an upper limit of operating voltage,
expressed in per unit of rated voltage. This is important for correct relay
operation and operation under unbalanced fault conditions on
unearthed or impedance earthed systems,. Voltage factors, with the
permissible duration of the maximum voltage, are given in Table 8.3.
VOLTAGE TRANSFORMER
CURRENT TRANSFORMER
➢ The current transformers may be either of bushing type or wound
type.
➢ CT should be selected with a rating 25% greater than the max
current that is likely to flow during normal operation.
➢ Protective CT should have high saturation factor.
➢ The secondary circuit must not be interrupted while the primary
winding is energized. The induced secondary e.m.f. under these
circumstances will be high enough to present a danger to life and
insulation.
➢ Protection class current transformers must retain a reasonable
accuracy up to the largest relevant current. This value is known
as the accuracy limit current’
➢ The ratio of the accuracy limit current to the rated current is
known as the 'accuracy limit factor
CURRENT TRANSFORMER
➢ RATINGS :
Transformer ratings shall be such that the transformer can
deliver its rated current under steady loading conditions without
exceeding the limits of temperature-rise specified in IS : 2026 (
Part II ) - 1977* assuming that the applied voltage is equal to the
rated voltage and that the supply is at rated frequency.
➢ SERVICE CONDITIONS :
Transformers complying with IS-2026 are suitable for operation
continuously at their ratings, provided the temperature of the
cooling air or water does not exceed any of the reference
ambient temperatures specified
POWER TRANSFORMER
➢ kVA Ratings:
kVA ratings for three-phase transformers are given in below table
➢ Temp Rise:
The transformer shall confirm to the requirements of
temperature rise specified in IS : 2026 (Part II)
POWER TRANSFORMER
➢ Insulation Levels :
➢ Connection Symbol :
o The preferred connections for two winding transformers up
to 66 kV high voltage ( HV ) side rating are delta/star ( Dyn ) and
star/star ( YNyn ). For higher voltages, connections star/star
(YNyn) or star/delta ( YNd ) may be preferred.
o The selection of connection group should be made taking into
consideration the requirements of parallel operation with other
transformers
➢ Impedance :
o The transformer impedance is decided taking into Consideration
the secondary fault levels and the voltage dip.
o typical impedance values are given IS : 2026 ( Part 1 )-19777.
POWER TRANSFORMER
➢ Termination Arrangement :