Service Manual: Controller
Service Manual: Controller
Controller
PowerCommand1301
English
Original Instructions 9-2019 A031B792 (Issue 3)
Table of Contents
SECTION PAGE
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ix
List of Acronyms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xiii
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xv
1. INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
About This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
System Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Test Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
How to Obtain Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
2. CIRCUIT BOARD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Base Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
TB1 Customer Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
DS1 LED Status Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
S1 Sleep Mode Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
3. CONTROL OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Control Panel Power on/Off Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Graphical Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Display Text / Symbolic Versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Display Menu Selection Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Previous Main Menu Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Off Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Not in Auto Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Shutdown Status Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Warning Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Remote Start Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Auto Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Manual Run Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
System Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
TERM DEFINITION
Accessory A part comes standard with the product. An accessory is optional and provides additional
Part interfaces or functionality.
Active General terms to describe the states for inputs, signals, or outputs that have only two
Inactive states (like true/false or 1/0). For example, a low coolant level switch is either on (active)
or off (inactive). The Ready to Load output is either on (active) or off (inactive).
For events/faults, this term describes the time the PCC generates the event/fault through
the time the event/fault is cleared.
Active-high Some inputs and outputs use voltage differential to distinguish between active and inac-
Active-low tive. If an input or output is active-high, a high voltage differential means the input or out-
put is active, and a low voltage differential means the input or output is inactive. If an in-
put or output is active-low, a low voltage differential means the input or output is active,
and a high voltage differential means the input or output is inactive.
Configurable analog Both terms refer to inputs that can be assigned one of several functions, depending on
input the genset and the application. For example, the same input might generate a fault in
Configurable input one application but enable Battle Short mode in another application. “Configurable input”
refers to discrete inputs (for example, open or closed). “Configurable analog input” refers
to analog inputs (for example, 0−5 VDC).
Configurable analog Both terms refer to outputs that can be controlled by one of several functions, depending
output on the genset and the application. For example, the same output might be controlled by
Configurable output event 1465 (Ready to Load) in one application and by shutdown fault 1433 (Local Emer-
gency Stop) in another application. “Configurable output” refers to discrete outputs (for
example, open or closed). “Configurable analog input” refers to analog outputs (for exam-
ple, 0−5 VDC).
Connection A connection between two devices. A connection might be as simple as one pin-to-pin
connection, or it might require several pins as well as additional components such as re-
lays, fuses, etc. This term also includes some settings that refer to the physical (for ex-
ample, normally-closed vs. normally-open) or electrical (for example, active-high vs. ac-
tive-low) characteristics of the connection.
Connector This term has no meaning if you do not have access to the PCC base board or the back
panel of the Operator Panel.
One or more pins that are in the same housing. Many times, the pins are related by func-
tion (for example, pins that are connected to the engine) or by electrical characteristics
(for example, relay outputs).
This term also refers to the end of a wire or harness that is plugged into the housing.
Event Used to notify the operator or external devices whether or not certain conditions are true.
Fault Each event or fault has two sets of conditions. When the first set of conditions becomes
true, the event or fault becomes active. This might turn on or turn off a light or LED, dis-
play a warning on the PCC, shut down the genset, or so on. When the second set of
conditions becomes true, the event or fault becomes inactive and can be cleared.
The PCC generates a fault when the conditions indicate a more serious problem; the
PCC generates an event only for information purposes.
Genset Generator set
Low-side driver When this output is active, it provides a path to ground.
Mode A term to describe certain states that affect the PCC’s behavior. The PCC is either in a
Mode of operation particular mode or not in a particular mode, and the PCC’s behavior changes accordingly.
Sometimes, the PCC is always in one mode out of a set of two or more modes. For ex-
ample, the PCC is always in one of the modes of operation: Off mode, Auto mode, or
Manual mode.
Mounting The physical placement and installation of the PCC or the Operator Panel.
After determining that a printed circuit board assem- WARNING Stand on a dry wooden platform or
bly is faulty, replace it; do not repair it. Attempts to rubber insulating mat, make sure your clothing
repair a printed circuit board can lead to costly dam- and shoes are dry, remove jewelry and use tools
age to the equipment. with insulated handles.
The following paragraphs describe the connectors The status indicator lamp is illuminated when the
(J), terminal board (TB), relays (R) and the LED sta- Base board is in the Power On mode (processor is
tus indicator. Figure 2-3 shows the pin locations for operating).
all Base board connectors.
SLEEP MODE
RS-485 SELECTION CUSTOMER
COMMUNICATIONS CONNECTIONS
S1
TB2 TB1
DS1 STATUS
INDICATOR
J11
J13
VOLTAGE/
FIELD
ENGINE
HARNESS
J12
CT’S
J2
J1
S1 SLEEP
MODE
SELECTION
SWITCH
GRAPHICAL
DISPLAY LED
INDICATORS
OFF MODE
BUTTON
Figure 3-2 shows the features of the front panel. It SYMBOL DESCRIPTION
includes six LED indicators, the graphical display,
and six buttons used to navigate through the menus Generator Warning Fault
and adjust parameters.
Generator Shutdown Fault
Graphical Display
This graphical display is used to view menus of the Coolant Temperature
menu-driven operating system. The bottom of the
graphical display indicates the functions that are
Oil Pressure
available by pressing the four selection buttons. Re-
fer to the menu trees later in this section.
Voltage Alternating Current (VAC)
System messages (communication, event, and
fault) are also shown on the graphical display. For
more information, see System Messages later this Voltage Direct Current (VDC)
section.
AC Current
Display Text / Symbolic Versions
This graphical display can be set up to show either Hz Frequency
text or symbolic versions for fault messages, some
Operator menus, and the Mode Change menu. A Battery
description of commonly used symbols used are in-
Out of Range
cluded in Table 3-1. Combinations of symbols are
used to display some fault conditions. Additional High or Pre-High
specialized symbols are also used for some faults.
Low or Pre-Low
When shipped from the factory, symbolic display is
selected. (Refer to the Setup menu to change to text
Annunciator
or symbolic display.)
NOTE: In the Screen Adjust menu, settings are not If the button is pressed during generator set op-
saved when the button is pressed. eration (manual or remote start), the engine will im-
mediately shut down. If possible, hot shutdown un-
der load should be avoided to help prolong the reli-
The button is also used to acknowledge warning ability of the generator set.
and shutdown messages after the fault has been
corrected. Pressing this button clears the fault from The button is also used to acknowledge warning
the front panel display and the previous menu is re- and shutdown messages after the fault has been
displayed. corrected. Pressing this button clears the fault from
the front panel and resets the control.
NOTE: Pressing the or button also clears the
fault from the front panel display. Not in Auto Indicator
This red lamp is lit when the control is not in the Auto
mode.
Warning Indicator
Communication Messages
Note: If either communication message remains dis- FIGURE 3-5. RE-ESTABLISHING COMMUNICATION
played (cannot view other menus), this indicates that WITH CONTROL
Fault Messages
A Fault message is an indicator of a Warning or
Shutdown condition. It includes the fault number, a
short description, and when the fault occurred (see
Figure 3-7). Symbolic fault messages include the
fault code number and symbols, indicating the type FIGURE 3-6. EVENT MESSAGE
of fault (see Figure 3-8). With the symbolic versions
of fault messages, the and symbols flash.
Section 4 provides a list of fault codes, fault types,
messages displayed, and descriptions of the faults. Fault = WARNING
or SHUTDOWN
Five of the most recent faults are placed in a fault
history file that can be viewed using the Fault Histo-
ry Menus.
Fault Acknowledgement
Shutdown faults must be acknowledged after the
faults have been corrected. If in Auto or Manual Run
FIGURE 3-7. FAULT MESSAGE
mode, the control must be set to “O” (off). Also,
faults are acknowledged when in Auto and the Re-
mote Start command is removed. Faults are cleared
from the control panel display by pressing the , EXAMPLE OF
A SYMBOLIC
, or button. WARNING
FAULT
214
Faults are re-announced if they are detected again
EXAMPLE OF
A SYMBOLIC
SHUTDOWN 1
FAULT
Switching to Auto, Manual Run, or Off mode can be NOTE:If an incorrect password is entered, the Op-
restricted to authorized personnel. If a control panel erator menu that was displayed before
is set up with the mode change access code feature Auto, Manual Run, or Off mode was se-
enabled, an access code must first be entered be- lected is redisplayed.
fore the mode can be changed.
ALTERNATING
ARROWS ARE
DISPLAYED
AUTO MODE
SELECTED
THREE PHASE
ONLY SINGLE
PHASE
ONLY
THREE PHASE
WYE ONLY
CURRENT
SENSE ONLY
THREE PHASE
ONLY SINGLE
PHASE
ONLY
THREE PHASE
WYE ONLY
CURRENT
SENSE ONLY
2ND 3RD
SERVICE SERVICE
MENU MENU
This submenu displays the number of engine starts, This submenu displays the optional control panel
hours of operation for the engine, and hours of op- software part number, software version, screen part
eration for the control. number, and screen version of the display.
OR
Fault 2
Oldest Fault
(Maximum of 5)
Pressing the VIEW button in the Setup “Password” Genset Service menus − Go to page 4-4.
menu, will display the 1st Genset Service menu Genset Setup menus − Go to page 4-23.
1ST
GENSET
SERVICE
MENU 2ND
GENSET
SERVICE
MENU
Volts AC: Displays the AC voltage (190, 200, If Fuel System is set to “Gas”
208, 220, 230, 240, 380, 400, 416, 440, 460, or
480 VAC). Fuel Burn Delay: After the genset receives a
stop signal, this feature allows for setting a fuel
Hertz: Displays the genset frequency (50 or 60 time delay from 0 to 10 seconds in which the
Hz). The control selects limits, gains, and fre- ignition remains on so that any fuel down
quency values based upon this selection. stream of the intake manifold is burned.
No. of Phases: Displays the number of phases
(1 or 3). Start/Stop Delay Menu
Phase: Displays the phase type (Delta or Wye). The time delay after receiving a valid start signal,
until the genset starts, can be adjusted. The time
Genset Menu, Part 2 delay that the genset is allowed to run at rated
speed after receiving a stop signal, until the genset
The second genset menu allows for enabling or dis- stops, can also be adjusted. These time delays do
abling charging alternators. not apply to manual start/runs.
Charging Alt. Enable: Start: The genset start time delay can be ad-
justed from 0 to 300 seconds.
A starter disconnect will occur whenever any
one of the following three possible signals Stop: The genset stop time delay can be ad-
reaches its disconnect setpoint. justed from 0 to 600 seconds.
PART 1
PART 2
CONTINUED ON
PAGE 4-8
A RETURN TO
PAGE 4-7
B
YES NO
K
OR
C E
GO TO AVR CONTINUED
SETUP MENUS ON PAGE 4-10
ON PAGE 4-12
RETURN TO
E PAGE 4-8
F
IF AVR IS NOT
ENABLED
OR
YES NO
IF AVR IS
OR ENABLED
D H
GO TO GO TO
GOVERNOR PAGE 4-12
SETUP MENUS
ON PAGE 4-14
NOMINAL
The Automatic Voltage Regulator (AVR) submenus
are available only if the AVR is enabled (see page
4-8). KNEE FREQUENCY
NOMINAL
(100%)
SLOPE VOLTAGE SET-
Two Automatic Voltage Regulator (AVR) submenus VOLTAGE POINT CURVE
(see Figure 4-8) can be used to adjust Volts/Hz Rol- FREQUENCY
loff and Regulator Gains settings.
FIGURE 4-7. KNEE FREQUENCY AND SLOPE
Volts/Hz Rolloff Menu
V/Hz Knee: The Knee Frequency can be ad-
justed from 0.0 to 10.0 Hertz in 0.1 Hz incre-
The Volts/Hz Rolloff function helps optimize the ments. When generator set speed decreases by
genset’s response to added load. If the engine more than the value of the knee frequency, the
speed drops below nominal frequency, the control generator set voltage decreases by the %/Hz
automatically drops the voltage until the engine value.
speed starts to recover.
V/Hz Rolloff: The Rolloff setting can be adjusted
from 0.0 to 5.0 percent of rated voltage, in 0.1%
This menu allows for adjusting the knee frequency increments.
and voltage setpoint slope parameters. The knee
frequency is the value below nominal frequency at Regulator Gains Menu
which the rolloff function begins. For example, if the
knee frequency is set to 5 Hz on a 60 Hz genset, this The Regulator menu allows for setting proportional
function begins when the frequency drops below 55 Gain, Integral Gain, and Damping values.
Hz.
Gain: The proportional Gain (K1) multiplier can
be set from 5 to 1000%. This allows for a scale
Slope refers to how fast the voltage is rolled off be- factor of 0.05 to 10.0.
low the knee frequency. The voltage is rolled off the
slope percent setting for every 1 Hz below the knee. Int: The Integral Gain (K2) multiplier can be set
For example, on a 60 Hz genset, if the slope is set to from 5 to 1000%.
5% and the knee frequency is set to 5 Hz, then if the D: The Damping adjustment can be set from 95
frequency drops to 54 Hz, the voltage set point is re- to 105%.
RETURN TO
PAGE 4-8
Governor Crank Fuel Menu The Electronic Governor menu allows for setting
Crank Exit Fuel DC, Dither Factor, and Damping
The Governor Crank Fuel menu allows for setting values. This menu is displayed only if the governor
the Initial Crank Fuel Duty Cycle, the Initial Crank has been enabled with the Engine Electronic Gover-
Fueling Period, the Crank Fuel Ramp Rate, and the nor Enable menu.
Maximum Crank Fuel Duty Cycle.
Crank Exit Fuel DC: The Crank Exit Fuel Duty
Initial DC: The Initial Crank Fuel Duty Cycle is Cycle is the value at which the governor duty
the initial value assigned to the Governor Duty cycle is held after disengaging the starter until
Cycle parameter when cranking begins. This the governor is enabled. This value can be set
value can be set from 0 to 50 percent. from 0 to 100%.
Initial Time: The Initial Crank Fueling Period is Dither Factor: Dither is a signal that is superim-
the amount of time for which the value of Initial posed on the PWM (pulse width modulation)
Crank Fuel Duty Cycle is assigned to the gover- duty cycle to prevent the actuator valve from
nor duty cycle after cranking begins. This value sticking. The Dither Factor is the dither percent
can be set from 0 to 10 seconds. added to the current duty cycle. The Dither Fac-
Ramp Rate: The Crank Fuel Ramp Rate is the tor can be set from 0 to 30%. The dither function
rate at which the value of the Governor Duty is disabled when the dither factor is set to 0%.
Cycle is ramped up by during the Crank State,
Ramp Time: This feature is used to set the mini-
after expiration of the Initial Crank Fueling Peri-
mum governor speed reference ramp rate. The
od. This value can be set from 5 to 100.
governor Ramp Time can be set from 0.00 to
Max DC: The Maximum Crank Fuel Duty Cycle 30.0 seconds, in 0.01 second increments.
is the maximum level to which the Governor
Duty Cycle should be limited to during a crank Electronic Governor Enable Speed Menu
state. This value can be set from 50 to 100%.
The Electronic Governor Enable Speed menu al-
Electronic Governor Regulator Menu lows for setting the minimum and maximum gover-
nor duty cycle.
The Electronic Governor Regulator menu allows for
setting proportional Gain, Integral Gain, and Damp- Min. Gov DC: The Minimum Governor Duty
ing values. Cycle can be set from 0 to 100%.
Gain: The proportional governor gain (K1) mul- Max. Gov DC: The Maximum Governor Duty
tiplier can be set from 5 to 1000%. This allows Cycle (with dithered value) can be set from 0 to
for a scale factor of 0.05 to 10.0. 100%).
RETURN TO
PAGE 4-10
The Meter Calib menu allows for adjusting the actu- Metering Current Adjust Menu
al output voltage of the genset. The percentage can
The Metering Current Adjust menu allows for ad-
be set from 90 to 110%. The alternator voltage is
justing metered amps.
also shown on this menu.
1. With the genset OFF, attach a calibrated am-
Freq. Adjust Menu meter to L1.
2. Start the genset and allow it to reach normal op-
The Frequency Adjust menu allows for adjusting the
erating speed.
genset frequency. The frequency can be adjust from
−6.0 to +6.0 Hz. The actual frequency is also shown 3. Display the Metering Current Adjust menu.
on this menu. 4. Load the genset to maximum rated kVA at rated
voltage.
Metering Voltage Adjust Menu
5. Calibrate the reading for L1 current so that the
The Metering Voltage Adjust menu allows for ad- reading on the display agrees with calibrated
justing metered genset line voltage. ammeter.
1. With the genset OFF, attach a calibrated volt- 6. After adjusting, press the SAVE button to save
meter to the AC output from L1 to L2. (L1 to the setting.
Neutral for single phase alternators.) 7. Shut the generator set OFF.
2. Start the genset and allow it to reach normal op- 8. Repeat steps 1 through 7 for L2 and L3. (In step
erating speed. 1, attach meter to L2 to calibrate L2 current, and
3. Display the Metering Voltage Adjust menu. L3 to calibrate L3 current.)
CONTINUED ON
PAGE 4-21
MODBUS SUBMENUS
3. Enter the password into the Genset Setup FIGURE 4-15. SETUP PASSWORD MENUS
The second Genset Setup Menu provides access to After the correct password is entered, it will be re-
the following menu: membered until five minutes of button inactivity has
elapsed. If five minutes of button inactivity has
Engine Protection elapsed, you will have to re-enter the password to
access and change Genset Setup menus.
Genset Setup Password Menu
Adjusting Values/Parameters
Adjusting the Genset Setup menus is restricted to
service personnel and a password must be entered Once the correct password has been entered on the
to modify these menus. Genset Setup Password menu, the first Genset Set-
up submenu is displayed.
Once the Genset Setup button (2) is selected on the
Setup Menus menu (see Figure 4-15), the Genset 1. Press the buttons above the and symbols
Setup Password menu is displayed. in the digital display to navigate between sub-
menus.
When the Genset Setup Password menu is dis-
played, the first numeric character (0) is highlighted 2. Press the ADJUST selection button to select
(see Figure 4-16). the first parameter or value to be changed.
NOTE: When selected (highlighted), each charac- 3. Press the + or − selection buttons to adjust val-
ter initially turns to “0” and the remaining ues or select parameters.
characters turn to “X”.
4. Press the arrow selection button to navi-
NOTE: Make sure that each numeric character is gate to the next or previous adjustable value or
correct before you move to the next charac- parameter.
ter. If a wrong character is entered, you will
not be able to go back and correct it. If the 5. After adjusting values/selecting parameters,
wrong password is entered, you will be able press the SAVE button to save your settings.
to view the Genset Setup menus but you
won’t be able to change them. NOTE: If the button is pressed before
pressing the SAVE button, the changes
To enter the Genset Setup password 1209: are not saved.
1. With the first character highlighted, press the 6. Press the button to return to the genset Set-
button below to the + or − symbols until the val- up Menus menu.
ue reads “1.”
2. Press the arrow selection button to move 7. To return to the Service Menu from the genset
to the next numeric character. Setup Menus menu, press the button.
1ST
GENSET
SETUP
MENU
2ND
GENSET
SETUP
MENU
The Genset submenus are available by pressing The kVA Rating menu displays the kVA rating of
the (1) button on the first Genset Setup menu (see single-phase or three-phase, 50 or 60 hertz standby
Figure 4-16). genset systems. These value are used by the con-
trol to determine what is 100% load. The values
Note: Appendix A provides a block diagram that illus- must match the kVA rating of the genset application
trates the sequence of how the Genset Setup Subme- and cannot be more than 2000 kVA.
nus are displayed.
3Ph/50Hz: The three phase, 50 Hertz rating
can be set from 0 to 2000 kVA.
Figure 4-17 through Figure 4-19 is a block represen-
tation of the Genset Submenus. 3Ph/60Hz: The three phase, 60 Hertz rating
can be set from 0 to 2000 kVA.
Genset Menu 1Ph/50Hz: The single phase, 50 Hertz rating
can be set from 0 to 2000 kVA.
The Genset menu is used to set the CT Ratio, en-
able the Magnetic Pickup Unit (MPU), set the num- 1Ph/60Hz: The single phase, 60 Hertz rating
ber of teeth pulses per revolution on the Flywheel, can be set from 0 to 2000 kVA.
and set the Speed/Frequency Ratio.
Prime kVA Rating Menu
CT Ratio: The CT Ratio value must be set to
match the CT Ratio of the current transformers The kVA Rating menu displays the kVA rating of
on the genset. single-phase or three-phase, 50 or 60 hertz prime
genset systems. These value are used by the con-
MPU Enable: Displays whether or not the Mag- trol to determine what is 100% load. The values
netic Pickup Unit is installed (Yes or No). must match the kVA rating of the genset application
Fly. Teeth: The total number of teeth pulses per and cannot be more than 2000 kVA.
revolution on the flywheel (used for electronic 3Ph/50Hz: The three phase, 50 Hertz rating
governed systems) can be set from 0 to 256. can be set from 0 to 2000 kVA.
RPM/Hz Ratio: Allows for setting the Speed/ 3Ph/60Hz: The three phase, 60 Hertz rating
Frequency Ratio to 20, 30, or 60 RPM/Hz. can be set from 0 to 2000 kVA.
Application Rating Select Menu 1Ph/50Hz: The single phase, 50 Hertz rating
can be set from 0 to 2000 kVA.
The genset application rating can be set to either 1Ph/60Hz: The single phase, 60 Hertz rating
Standby or Prime. can be set from 0 to 2000 kVA.
CONTINUED ON
PAGE 4-29
Low Batt: The low battery voltage threshold can H. Batt TD: A time delay from 2 to 60 seconds
be set from 11.0 to 13.0 VDC for 12 volt batter- can be set before the High Battery warning
ies and from 22.0 to 27.0 VDC for 24 volt batter- message (fault code 214) is announced.
ies, in 0.1 VDC increments. Wk Batt TD: A time delay from 1 to 5 seconds
High Batt: The high battery voltage threshold can be set before the Weak Battery warning
can be set from 14.0 to 17.0 VDC for 12 volt bat- message (fault code 221) is announced.
12V 24V
OR
OR
C
CONTINUED ON
PAGE 4-31
SWITCH SENDER
OR
CONTINUED ON
PAGE 4-39
CONTINUED ON
PAGE 4-41
The Base board (Figure 4-25) provides connection Note: The InPower service tool or access to the Gen-
set Service Menus is required to modify the customer
points (TB1) for remote control and monitor options.
fault inputs.
TB1 Customer Inputs
TB1 Customer Outputs
Note: Available options will vary between control
models (control with or without display). Note: Available options will vary between control
models (control with or without display).
Remote Start: When the control is in Auto/Remote
mode, grounding this input initiates the engine
Customer Outputs 1 and 2: One set of normally
cranking and start sequence. This circuit must be
open (NO) contacts, rated for 2 amps at 30 VDC for
opened to permit resetting a shutdown condition
each of the two output signals. The relays can be
with the Reset input. (The remote stop is actually the
used to control small devices and indicator lamps.
removal of the remote start signal to the control.)
Local/Remote Emergency Stop: Grounding this The nature of the customer output signal (contacts
input causes an immediate shutdown. Emergency closed) is an optional customer selection. Example
stop must be reset at the front panel. outputs: Genset running (event), common warning,
common shutdown, etc. (Refer to Table 5-3 for the
Customer Fault Inputs 1 and 2: Grounding any warning and shutdown code listing and Table 4-1 for
one of these inputs activates the corresponding the event code listing.)
warning or shutdown sequence.
Each relay can be independently programmed to
External sensing equipment must be connected to energize by entering the a code number (0 through
the designated digital input. 255, default = 0) for the desired event.
The nature of the fault is an optional customer selec-
Note: The InPower service tool or access to the Gen-
tion. Example inputs: Low Coolant Level, Low Fuel set Service Menus is required to modify the customer
Pressure, Ground Fault, etc. outputs.
COOLANT
TEMPERATURE
SENDER E2
OIL
PRESSURE
SENDER E1
2. If the key switch fails to open, refer to the generator set service
manual for other possible causes and solutions.
If there is no actual fault, the problem may be Disconnect the signal lead from TB1 and reset the control.
an external wiring problem.
CUST_IN1 − TB1-14
CUST_IN2 − TB1-12
If the message drops out, the external wiring has a short circuit.
Grounding of either input activates fault.
DRAWING PAGE
0630−2926_G_200609
SETUP AND
SERVICE
GENSET
MENUS
GO TO
A030K737
SEE
OR
VIEWING AND
ADJUSTING
IF AVR IS
NOTIF AVR IS
ENABLEDENABLED
OR
NO
VIEWING ONLY
OR
YES
GENSET SERVICE MENUS
NO
OR
YES
OR
GO TO GENSET
SERVICE MENUS
VIEWING AND
VIEWING ONLY ADJUSTING
OR
24V
12V
OR
OR
SWITCH
SENDER
OR
A-6
power.cummins.com
Copyright E 2019 Cummins Inc. All rights reserved.
Cummins, the “C” logo, PowerCommand, AmpSentry, and InPower are trademarks of Cummins Inc.
Other company, product, or service names may be trademarks or service marks of others.
Specifications are subject to change without notice.