Lect. 5 Protection 2022
Lect. 5 Protection 2022
Lecture 5
4
Directional Elements ?
6
This is done by setting the directional relays R1’ and R2’ in
with their directional elements looking into the protected line,
and giving them lower time and current settings than relays R1
and R2.
The usual practice is to set relays R1’ and R2’ to 50% of the
normal full load of the protected circuit and 0.1TMS
7
Directional OC Relays- RING MAINS
A particularly common arrangement
within distribution networks is the Ring
In a typical ring main with associated
overcurrent protection, current may flow in
either direction through the various relay
locations, and therefore directional
overcurrent relays are applied.
With modern numerical relays, a
directional facility is often available
for little or no extra cost, so that it
may be simpler in practice to apply
directional relays at all locations 8
The usual grading procedure for relays in a ring main circuit is to
open the ring at the supply point and to grade the relays first
clockwise and then anti-clockwise.
The relays looking in a clockwise direction around the ring are
arranged to operate in the sequence 1-2-3-4-5-6
9
The arrows associated with the relaying points indicate the
direction of current flow that will cause the relay to operate.
A double-headed arrow is used to indicate a non-directional
relay, such as those at the supply point where the power can
flow only in one direction.
A single-headed arrow is used to indicate a directional relay,
such as those at intermediate substations around the ring
where the power can flow in either direction.
The directional relays are set in accordance with the invariable
rule, applicable to all forms of directional protection, that the
current in the system must flow from the substation busbars
into the protected line in order that the relays may operate.
10
The polarizing quantity of a directional relay
1. It is the reference against which the phase angle of
the other quantity is compared. Consequently the
phase angle of the polarizing quantity must remain
fixed when other quantity suffers wide change in
phase angle.
Phase A IA VBC
Phase B IB VCA
Phase C IC VAB
12
For earth fault the reference, or polarizing signal is Vres, it obtained from broken
delta.
The directional earth fault protection is activated when the following two
conditions happened:
– the residual current is higher than the setting threshold;
– the residual current phase in relation to the residual voltage in a tripping zone.
Protected Phase Operating Signal Polarizing Signal
Ground Ires=3Io Vres=3V0
13
14
15
1. Residually connected Earth-fault Relay
More sensitive protection against earth faults can be obtained by
using a relay that responds only to the residual current, since a
residual component exists only when fault current flows to earth.
In absence of earth-fault the vector sum of three line
currents is zero. Hence the vector sum of
three secondary currents is also zero.
The earth-fault relay is connected
such that the residual current flows
through it.
In the absence of earth-fault,
therefore, the residually connected earth-
fault relay does not operate
16
Proactive frequency control for high renewables penetrated power systems 17
Proactive frequency control for high renewables penetrated power systems 18
Proactive frequency control for high renewables penetrated power systems 19
Restricted Earth-Fault Protection for Star Winding