Exp 1
Exp 1
Faculty of Engineering
Department of Chemical Engineering
• Objectives
1. Study the dynamic behavior of a level control system subject to a step
change in inflow.
2. Analyze the system’s response without feedback control (open-loop
behavior).
3. Identify the characteristics of a pure capacitive system, particularly how
the liquid level changes over time.
4. Evaluate the impact of inlet flow rate adjustments on the system’s
stability.
5. Calculate the results of the experiment such as gain constant (Kp) and
tank cross-sectional area (A).
• Introduction
The study of process control plays a crucial role in industrial automation and
fluid dynamics. One fundamental experiment in this domain is level control in
an open-loop system, which focuses on understanding the dynamics of liquid
level variations in a tank without the influence of a feedback control system.
Open-loop systems operate without automatic corrections, meaning that any
change in input directly affects the system’s behaviour.
In this experiment, a capacitive process is examined, where the tank behaves as
a pure integrator due to its inability to self-regulate. The dynamic response of
the system is analysed under different conditions, including sudden variations in
inflow rate. Since the response does not exhibit a first-order behaviour but
rather a pure integration, traditional tuning methods like Cohen-Coon cannot be
applied. Instead, manual adjustments are required to maintain the desired water
level.
This experiment provides valuable insights into process dynamics, system
response characteristics, and manual tuning approaches for non-self-regulating
processes.
• Theory
A level control system is a dynamic mechanism used to regulate the liquid level
in a tank to a predetermined setpoint. In an open-loop system, the liquid level is
managed by manually adjusting the inflow rate without real-time monitoring of
the actual level. Conversely, a closed-loop system utilizes sensors to
continuously measure the liquid level and provide feedback to an automatic
controller, which adjusts the inflow or outflow as needed to maintain the desired
level.
Controller Selection
- First-Order Lag Systems:
These systems typically respond well to Proportional-Integral-
Derivative (PID) controllers, as they are self-regulating and naturally
settle to a steady-state.
- Pure Capacitive Systems:
Due to their integrating nature, these systems require PI or PID
controllers specifically tuned to prevent drift and ensure system
stability.
• Study example: Water Tanks
The following two examples demonstrate the difference between both types of
control systems.
−t
h(t) = Kp (1 − e τ )
- Example 2: Liquid level with constant flow outlet
- To Find the T.F. that relates the head to the input flowrate q(t).
dh
qi − qo = A
dt
dhs
qis − qos = A =0
dt
d(h − hs )
(qi − qis ) − (qo − qos ) = A
dt
dh
Qi − Qo = A
dt
Q i (s) − Q o (s) = AsH(s)
Q i (s) Q o (s)
H(s) = −
As As
h(t) = Kp × t
• Apparatus
1. Storage Tank (C1): A borosilicate glass tank with a capacity of 10L, which
serves as the primary system for observing liquid level variations.
2. Feeding tank (D1): Provides a continuous and stable flow of fluid to the
pump and then to the rest of the system and helps control the fluid level
within the system, contributing to stable operations.
3. Centrifugal Pumps (G1 & G2) with case and rotor of AISI 304 stainless
steel, Qmax = 4m3/h, Hmax = 30 m:
• G1: Transfers water from the feeding tank into the control tank.
• G2: Recirculates water back to the feeding tank.
4. Rotameter (FI1): Stainless steel and glass instrument with a range of 100 to
1000 L/h, used to monitor inflow rates.
5. Differential-Pressure Transmitter: Measures level variations and provides
data for system analysis, AISI 316 stainless steel with 4 to 20 mA output
signal.
6. Pneumatic Control Valve (LV1): Adjusts water flow rates based on manual
control settings.
7. Control Panel: Used to switch between manual and automatic modes for
flow regulation.
8. Compressed Air Supply Unit: Required at 0.3 Nm³/h, 6 bar max for
pneumatic valve operation.
11.After that make a step change in the flowrate of the inlet water using the
manual valve by increasing the flowrate from 250 to 350 L/h.
12. Observe the change in height of the water with time by follow up the
shown figure on the PC.
13.After that return to Automatic mood, choice the set point to be 30% as it
was, and wait until the operation reaches the steady state.
14.After that change the mood from Aut. To Manual mood.
15.Now, make a step change in the inlet flow rate by decreasing it to 150
L/h.
16.Observe the behaviour of the process and record the obtained data (Time
vs height).
• Data
- Storage tank volume:
1 m3
VT = 10 L × = 0.01 m3
1000 L
π(Do )²
Ac =
4
π ( 0.168)²
Ac = = 0.022 m2
4
slope
Kp =
step change
1
Ac =
Kp
- The fluid height is given as a percent of the total height of the tank then it
is required to convert the fluid height into meters.
Calculation sample:
Emptying Data
Sheet.xlsx
• Calculations
0.3
0.25
0.2
0.15
0.1
0.05
0
0 100 200 300 400 500 600 700 800 900
TIME (SEC)
L 1 m3 1h
100 × × = 2.77 × 10−5 m3 ⁄s
h 1000 L 3600 s
- Filling slope:
0.0004 m⁄s
- Static gain:
slope
Kp =
step change
m 1 m3
Kp = 0.0004 × = 14.44 m−2
s 2.77 × 10−5 s
1 1
Ac = = = 0.069 m2
Kp 14.44 m−2
- Part B: Emptying the storage tank
0.08
0.06
0.04
0.02
0
0 100 200 300 400 500
-0.02
TIME (SEC)
L 1 m3 1h
−100 × × = −2.77 × 10−5 m3 ⁄s
h 1000 L 3600 s
- Filling slope:
− 0.0003 m⁄s
- Static gain:
slope
Kp =
step change
m 1 m3
Kp = − 0.0003 × = 10.83 m−2
s − 2.77 × 10−5 s
1 1
Ac = = = 0.092 m2
Kp 10.83 m−2
• Results
In Part A of the experiment, where the flow rate increased, the cross-
sectional area was found to be 0.069, resulting in a deviation of 0.047
from the theoretical value.
In Part B, where the flow rate decreased, the cross-sectional area was
measured as 0.092, leading to a deviation of 0.070 from the theoretical
value.
Part A:
0.069 m2 − 0.022 m2
ϵ%= | | × 100% = 213.63 %
0.022 m2
Part B:
0.092 m2 − 0.022 m2
ϵ%= | | × 100% = 318.18 %
0.022 m2
The results showed that altering the flow rate significantly influenced the
measured cross-sectional area, deviating from theoretical predictions. When
the flow rate increased, the cross-sectional area was larger than expected,
and a further increase was observed when the flow rate was reduced. These
discrepancies suggest that factors such as pressure fluctuations, flow
resistance, and unaccounted energy losses played a role in modifying the
system’s behaviour.
• References
- Laboratory Manual
- Ogata, K. (2010). Modern Control Engineering (5th Edition).
- Dorf, R. C., & Bishop, R. H. (2017). Modern Control Systems (13th
Edition)
- Stephanopoulos, G. (1984). Chemical Process Control: An Introduction to
Theory and Practice. Prentice Hall.
- Roffel, B., & Betlem, B. (2007). Process Dynamics and Control:
Modeling for Control and Prediction. John Wiley & Sons.