Diesel Generator Calculation
Diesel Generator Calculation
future expansion ratio is 10% Average use of Equipment is 0.8 (1 is full time
use)
4 No’s of 1Ph 230V,80Watt CFL bulb, Diversity factor is 0.8, Starting and Running P.F is 0.8
2 No’s of 1Ph 230V,3000Watt Air conditioner, Diversity factor is 1, Starting and Running P.F is
0.8
2 No’s of 1Ph 230V,500watt Halogen Light , Diversity factor is 0.8, Starting and Running P.F is 0.8
1 No’s of 1Ph 230V,10KW Motor with Y-D, Diversity factor is 0.8, Starting is 0.7 and Running P.F
is 0.8
1 No’s of 3Ph 430V,130KW Motor with Soft starter, Diversity factor is 0.8, Starting is 0.7 and
Running P.F is 0.8
Calculation:-
Type Of Load Equipment Starting Current
Linear Load: - The relationship between the voltage and current waveforms are sinusoidal
and the current at any time is proportional to the voltage (follows OHM’s law)
Non Linear Load: - A non-linear load the current isn’t proportional to the voltage and it
fluctuates based on the alternating load impedance. (eg- variable-speed drives and electronic
devices such as computers, printers,)
Diversity Factor:- : Diversity factor is defined as the ratio of the sum of the maximum
demands of the various part of a system to the coincident maximum demand of the whole
system
Formulae:-
Full Load(Kw) = (No of component x wattage x Diversity Factor)/1000
Full Load(KVA) = Kw/P.F
Full load current = (No of component x wattage x Diversity Factor)/volt x P.F
Starting KVA = type of Starter value x (KW/P.F)
Starting Current = % of Starting current x Full Load Current.
Summary:-
• Total Starting KVA = 468.KVA
• Total Starting Current = 725Amp
• Total Running KVA = 137KVA
• Total Running Current = 242Amp
• Size of Diesel Generator = 412KVA