Detection and Location of Open Conductor Faults For Power Distribution Networks Using A Contingency Analysis Approach
Detection and Location of Open Conductor Faults For Power Distribution Networks Using A Contingency Analysis Approach
Received 9 July 2024, accepted 11 August 2024, date of publication 15 August 2024, date of current version 27 August 2024.
Digital Object Identifier 10.1109/ACCESS.2024.3443917
ABSTRACT This paper presents a method for the detection and location of open conductor faults (OCFs)
in power distribution networks using contingency analysis (CA) based on unsymmetrical power flow
calculations. The proposed method is designed for use in distribution management systems and broadly
comprises two stages. The first stage is CA in study mode. This study presents a CA technique for detecting
events different from those of the transmission network to evaluate network security. Accordingly, OCFs
that can occur in the target network are analyzed using the unsymmetrical power flow method regarding
the sections of the feeder remote terminal units (FRTUs), and the results are organized as a dataset for
OCF CA (DOCA). The DOCA for the distribution lines (D/L) where topology changes have occurred
is partially changed, and a detailed fault analysis is performed. The second stage is OCF detection and
location in a real-time operating mode. This study proposes a method that compares the mean square error
between real-time FRTU measurements and DOCA. The reliability of the proposed method is verified using
MATLAB/Simulink to conduct various case studies on the IEEE 33 bus and 118 bus standard test models. The
advantages of the proposed method can be summarized as follows: First, by comparing the distance between
the entire set of measurements and DOCA, the proposed method achieves a considerably higher detection rate
than those achieved by existing methods that use a single measurement element. Second, when calculating
the distance between the two sets, the proposed method uses weights based on the magnitude variation of
the comparison elements, which results in almost no false positives, making it robust to realistic conditions
such as measurement sensor errors and communication delays. Third, fast responses during operations are
also possible because detection and location are performed simultaneously.
INDEX TERMS Open conductor fault, contingency analysis, unsymmetrical power flow method, fault
detection and location method, power distribution network.
2024 The Authors. This work is licensed under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 License.
114304 For more information, see https://creativecommons.org/licenses/by-nc-nd/4.0/ VOLUME 12, 2024
G.-D. Sim et al.: Detection and Location of OCFs for Power Distribution Networks
In power distribution networks, faults have traditionally methods because they use certain detection elements of field
been detected on the basis of momentary fluctuations in the devices, and they are unable to consider the effects of false
measurement values of field terminal units and protective positives (FPs) and false negatives (FNs) in field devices
equipment. However, OCFs are accompanied by dynamic when the DMS determines the final location.
changes after the instantaneous disconnection of conductors Third, OCF detection research was also conducted using
or connections. In addition, various fault behaviors (high- artificial intelligence [11], [12], [13], [14]. One proposed
impedance faults, overcurrent faults, arcing, etc.) can occur method used an artificial neural network-based algorithm to
depending on whether there is contact with a medium after learn actual faults and the voltage and current of an EMTP
the fault, which can lead to secondary damage such as fires model and made comparisons with relay measurement val-
and electric shock injuries. Therefore, there is a need for a ues [11]. Another method performed detection by removing
detection and location technology that is specific to OCFs and voltage and current noise and learning features by the discrete
different from existing methods. wavelet transform [12]. Further, a technique that extracted
Various studies have been conducted on OCF detection fault features using the variational mode decomposition tech-
and location. First, attempts were made to detect OCFs using nique and ultimately determined faults via a support vector
feeder remote terminal units (FRTUs) and their measurement machine was also presented [13]. Another study performed
values [2], [3], [4], [5], [6]. A voltage-based OCF detection detection by using deep learning to extract voltage and cur-
method using voltage outage [2] and OCF detection methods rent features from the frequency band directly after OCFs
using the current unbalance of negative-sequence current and applied them to a field phasor measurement unit [14].
compared to positive-sequence current were proposed [3], In addition, a method that extracted features from sensor
[4]. These deterministic detection methods have the advan- signals and detected faults using a graph-embedded low-rank
tage of easy applicability to actual networks because the tensor learning machine was proposed [15]. In another study,
fluctuations of a certain element are set as the detection the characteristics of three-phase current waveform data were
criteria; however, they are unavoidably influenced by the analyzed using convolutional neural networks to estimate the
network environment and fault location. To resolve these type, phase, and location of faults, including high-impedance
problems, detection methods utilizing multiple detection ele- faults [16]. The abovementioned methods perform learning
ments as open fault condition (OFC) were proposed [5]. using instantaneous value-based data; however, they are not
However, this approach has the limitation of being vulnerable realistic because the historical stored data of the actually
to any increase in the DER connection and end-of-line faults operating DMS is based on root-mean-square values. In addi-
that produce little fluctuation. A method was proposed to tion, there is a problem in that the detection criteria can vary
calculate the impedance during low-impedance ground fault according to the environment of the target network.
(LIGF) and high-impedance ground fault (HIGF) conditions Fourth, studies were conducted on the detection and loca-
after OCF. This impedance was then reflected in the operating tion of OCFs by contingency analysis (CA) [17], [18].
range of distance relays for detection [6]. This method has One proposed method calculated the Thevenin equivalent
limitations in that because of the range of fault impedance impedance for each symmetrical component assuming a
considered, it cannot consider dynamic changes in the OCF single-phase OCF in a line section and used the load-side
aspect. zero-sequence component current fluctuation rate for the
Second, studies were conducted on primary detection using assumed substation secondary-side zero-sequence compo-
field-installed devices and determining final location either nent voltage as the detection criterion [17]. This method is
by collecting data from these devices in the distribution limited by the problem of setting the voltage fluctuation cri-
management system (DMS) or via communication between terion and the fact that it requires a measurement environment
them [7], [8], [9], [10]. Research was conducted on meth- that guarantees simultaneity. Further, a method that estimated
ods that detect OCFs using voltage outage information from the voltage of fault candidate points and ultimately performed
feeder-end voltage sensors and identify fault sections by power flow calculations to select the final fault locations as
topology analysis [7]. A method was proposed to detect OCFs the locations with the smallest deviation between the mea-
by measuring voltage unbalance with smart meters at the end sured voltage and the calculated voltage at the substation
of a line and identifies the fault section by a common path secondary side was also studied [18]. This method can be
search between detection devices [8]. Furthermore, a method applied to common network topologies but has problems
was proposed to detect faults from the voltage unbalance in in that it does not consider DER and takes a long time to
the secondary side of the distribution transformer and iden- determine the location because of its repeated power-flow
tify OCF locations via device-to-device communication [9]. calculations.
In addition, a method was proposed to detect OCFs by calcu- To summarize the above literature review, methods that
lating transient zero-sequence admittance at the FRTU and are based on field devices and methods that make a final
fault location from the difference in zero-sequence admit- OCF decision and perform location via cooperation between
tance at the source- and load-side of the fault point [10]. These field devices and DMS have problems in that their detection
methods have the same limitations as the abovementioned criteria are set according to the target network and they are
vulnerable to operational noise (FPs, FNs, communications II. OCF CHARACTERISTIC ANALYSIS AND REVIEW OF
delays and failures, etc. in field devices). Methods that use CA PREVIOUS STUDIES
have problems in that they do not consider the various OCF OCFs occur because of factors such as mechanical impacts
behaviors, can only be applied to certain network topologies, from the external environment, mechanical defects in con-
and do not have a clear basis for setting the detection criteria. nections, and corrosion due to deterioration; they are defined
In addition, only methods that apply to real-time operational as unintentional single-phase or double-phase openings in
situations are mentioned, and insufficient consideration is energized conductors. In OCFs, the measurement values of
given to the time spent and computations performed by FRTUs fluctuate during faults because of two reasons:
DMSs that manage hundreds or thousands of distribution 1) Changes in the fault itself: In an OCF, the conductor
lines (D/Ls). itself is mechanically separated. Therefore, the aspects of the
To resolve these problems, this paper proposes a real-time OCF can dynamically change, commencing directly after the
OCF detection and location method that performs offline CA, fault. As such, OCFs cannot simply be defined as openings
which considers various behaviors of OCF and compares the in an electrical circuit but can be broadly classified according
results with real-time FRTU measurement values. CA, which to three aspects: (1) a high-resistance state is maintained,
is a detailed fault-analysis method that requires consider- in which the power line does not contact a low-resistance
able computation and time, is performed separately offline. medium after the fault; (2) a separated power line contacts
During real-time operations, OCF detection and location are a low-resistance medium such as the earth or a pole, and
performed by comparing the mean squared error (MSE), the fault changes into a ground fault (GF); (3) the situation
considering the FRTU measurement error. The contributions changes into an OCF after the GF occurs.
of this paper can be summarized as follows: 2) Fluctuations in measurement values due to the network
1) A CA method based on an unsymmetrical power flow structure: If an OCF occurs in a power distribution network
method is proposed, considering OCF characteristics and that comprises simple loads, the voltage fluctuations on the
DERs. To overcome the limitations of certain detection ele- source side of the fault point are minimal, and the current is
ments, CA is employed to detect fluctuations in voltage, affected by the load drop caused by the fault [2], [4]. How-
current, and power factor (PF) angle, which are organized ever, various voltage and current fluctuations can occur on
into a dataset for OCF CA (DOCA). By comparing DOCA the load side of the fault point depending on the transformer
with the overall measurement set, the detection rate of the connection [5]. When a 1 load is connected to the primary-
proposed method is significantly higher than those of existing side 1 connection transformer and the Yg-Yg connection,
methods using a single measurement element. it acts as the current source after the OCF occurs, and a
2) When comparing the distance between the FRTU voltage close to a maximum of 0.5 pu can be maintained.
measurement set and DOCA, the proposed method applies However, the maintained voltage can fluctuate because of the
weights based on the magnitude variation of comparison internal voltage drop caused by the load current. In the case
elements (calculated in advance), thus resulting in almost no of a Yg-1 connection to supply an industrial high-voltage
FPs. The measurement error of sensors and the sensitivity customer (using a motor) or a transformer to connect a DER,
are also analyzed in advance, thereby affording OCF decision a maximum voltage of 1.0 pu can be maintained. The voltage
and location criteria suitable for the network. Therefore, the and current fluctuation patterns vary because of the distri-
method is robust to realistic conditions, such as measurement bution of the load and the amount of distributed generation
errors and communication delays that may occur in the oper- below the fault point due to the transformer connection.
ation of the distribution system. To determine whether an OCF has occurred, it is necessary
3) The dataset of DOCA is composed of the values of mea- to detect instantaneous changes. Therefore, OCF detection
surement elements when OCF occurs in a specific section. methods that use fluctuations in the measurement values
Detection and location are performed simultaneously when of field terminal devices have traditionally been employed.
determining the event by a comparison with the measure- Typical examples of these include a method that uses current
ment values of FRTU, which enables quick response during unbalance (the ratio of the positive phase sequence compo-
operation. nent to the negative phase sequence component) changes [3],
4) The proposed method of performing CA along with a method that detects OCFs by combining multivariate detec-
detection and location of OCFs uses only data and measure- tion elements into a decision tree [5], and methods that
ment infrastructure that are commonly possessed by most detect OCFs using voltage drop and voltage unbalance and
power companies today. Therefore, this study is highly appli- determine the locations of the OCFs by a path search [7],
cable to actual network operations. [8]. To examine the limitations of existing OCF detection
The remainder of this paper is organized as fol- methods, the test power distribution network shown in Fig. 1
lows. Section II analyzes the characteristics of OCFs. was used. In Fig. 1, the impedance of M.Tr. is 30% based
Section III describes the CA-based OCF detection and loca- on 100 MVA, and each load is assumed to be 0.5 MVA
tion algorithm. Section IV verifies the algorithm by case (lagging PF of 0.95). The distribution transformer for the load
studies. Finally, Section V concludes this paper. is 6% of 1-MVA capacity, and Yg-Yg and 1-Yg connections
1V k1
k+1
V1 Vs,1
V k+1 Vs,2 1V k
2 2
. = .. + .. (5)
.. . .
Vnk+1 Vs,n 1V kn
TABLE 4. Average of difference in measurement values of the FRTU load. Moreover, to consider characteristics similar to those of
according to fault point resistances (HIGF after OCF).
actual power distribution operations, a voltage ride-through
function is incorporated from among DER grid codes [33].
6) Protective equipment: For the line protective equip-
ment, it is assumed that an overcurrent relay-based breaker is
installed at the feeder start point, and reclosers are placed in
the middle of feeders. The protective equipment standards of
Korea Electric Power Corporation are used for the minimum
pick-up current, time dial setting, and protection coordina-
tion [31].
TABLE 5. Average of difference in measurement values of FRTU according
to fault point resistances (LIGF after OCF). 7) Load and lines: The load is connected to all buses, and
total active and reactive powers of 3.715 MW and 2.3 MVAr,
respectively, are set up for the 33-bus network, while total
active and reactive powers of 22.709 MW and 172.041 MVAr
are set up for the 118-bus network, respectively. D/L #1, D/L
#2, and D/L #3 are set at 10.28 MW and 7.97 Mvar, 7.38 MW
and 5.11 Mvar, and 5.05 MW and 3.96 Mvar, respectively. For
the line impedance data, the data that are presented in the test
network are used.
8) Transformer: The existence of a Yg-1 connection,
and the measurement data of the FRTU connection point are which is generally used for DER network connections to
used. In Table 4, the voltage, current, and PF angle that occur prevent the spread of low-voltage-side GFs and suppress
according to fault resistance when there is an HIGF after harmonics, is assumed, and the transformer for low-voltage
an OCF are compared with the case where the maximum loads is set up with a Yg-Yg connection.
resistance of 5000 occurs. The test results revealed that 9) Measurement error consideration: To reflect the mea-
in the case of voltage, a maximum difference of 0.191% surement error of the FRTU during faults, an error is assumed
occurred, and in the case of current and PF angle, differences according to IEEE C57.13 [24] and IEC 61869 [25]; it is
of 5.13% and 5.95% occurred, respectively. Table 5 presents distributed randomly (Gaussian distribution) and used.
an analysis of the differences in voltage, current, and PF
when comparing a certain fault point resistance and other A. TESTS USING THE 33-BUS NETWORK
fault point resistances when an LIGF occurs after an OCF. Table 6 presents a comparison of the proposed OCF detection
In the case of 15 , the difference in current with 30 and location method and methods used in previous studies.
was not large at 3.77%; however, when compared to 50 , The proposed method is compared with a current unbal-
there was a relatively large error of 8.07%. In the case of ance method [3], multivariate method [5], voltage outage
30 , there was a maximum difference of 6.85% in phase method [7], and voltage unbalance method [8]. The methods
compared to 50 , and the error was smaller than in the case used in previous studies are expressed in (13)–(15).
of 15 . In Tables 4 and 5, the error in voltage according
to the fault resistance is relatively small, and ultimately it
TABLE 6. Results of OCF detection and location for the IEEE 33 test
does not exceed the detection criterion when calculating MSE system.
including voltage. Accordingly, it was assumed in this work
that the high resistance during the CA was the medium value
of 2000 , and the low resistance was 30 , which had the
smallest error.
4) FRTU: FRTUs are installed in each piece of protective
equipment and SW, and the sampling period of FRTUs is set
by setting the simulation time step to 130 µs. In addition, it is
assumed that it takes a maximum of 2 s to transmit data to
the front-end processor (FEP) after the polling command is
received.
5) DER: As for the capacity of the 33-bus DER, 0.8 MW,
which is the maximum value among the values suggested
by the reference literature [27], is used as the capacity of
each DER. In the case of the 118-bus network, the con-
nection varies according to the D/L. For D/L#1 and D/L#2,
9 and 3 MW are connected, assuming 1.5 and 1 MW per 1) The current unbalance method [3] detects the ratio of
PV, respectively. D/L#3 comprises a network with only a the positive phase sequence component to the negative phase
sequence component as follows: that the proposed method is effective at detecting faults in
I2 networks connected to multiple DERs and at the ends of lines.
Iub = , (13) The FP rate given in Table 6 is the rate at which fault type 11
I1
(GF) was incorrectly judged as an OCF. The proposed method
where Iub is the ratio of the positive phase sequence compo- produced only one FP in the single-line GF scenario. As for
nent to negative phase sequence component, I1 is the positive the other methods, the single-element methods had FP rates of
sequence of current, and I2 is negative sequence of current. 30% or more when there was a GF fault, and the multivariate
An OCF is detected if this ratio is greater than 15%. method had an FP rate of more than 15%. From these results,
2) The multivariate detection element method [5] detects it was found that the proposed method had a high detec-
OCFs by combining various OFCs such as overvoltage, volt- tion rate improvement of 27.3%–50.8% and dramatically
age outage, and current unbalance fluctuations into a decision improved the FN rate (30.2%–65.3%) for faults at the ends
tree. of lines and in lines with a high DER connection capacity,
3) The voltage outage method [7] uses the voltage drop rate which is a weakness of the existing methods. In particular,
for OCF detection as follows: it was verified that there was a 9.2%–31.6% improvement in
Vpost − Vpre FPs for GFs with more than a certain fault resistance that pro-
1V = , (14)
Vpre duces fault point load-side measurement value fluctuations
similar to those of OCFs. In addition, location rates were
where Vpost is the voltage after the event and Vpre is the
compared. Previous studies [3], [5] only proposed detection
voltage before the event. An OCF is detected if 1V is 30%
methods, while some studies [7], [8] estimated locations by
or more.
common topology searches in the source-side direction of
4) The voltage unbalance method [8] uses the voltage
OCF detection equipment. The location rates were calculated
unbalance ratio for detecting an OCF.
as the ratio of successful locations out of all OCF cases. The
s √ 4 + V4 + V4
1 − 3 − 6β VAB proposed method showed good results with a location rate of
K= √ , β= BC AC
(15) 92.9%. The previous studies [7], [8] showed poor location
1 − 3 − 6β 2 + V2 + V2 2
VAB BC AC rates of 8.6% and 10.3% because many topology searches
where K is voltage unbalance rate, VAB , VBC , Vcb is the mag- failed because of the DERs and the FNs of FRTUs.
nitude of line voltages. An OCF is detected if K is 30% or To determine whether fault locations can be classified as
more. per MSE, Fig. 9 presents the measurement values during
In the proposed method, the individual event alarm of the OCFs in the source- and load-side sections of the SW (#1,
FRTU criterion for detecting OCFs is set at 6% for voltage by #2, #4, #6) installation point nearest to each fault location.
adding the measurement error and the voltage fluctuation rate Fig. 9 shows the voltage (■), current (◆), and PF (●) when
as mentioned previously. In the case of current, it is set at 15% a fault occurs in the source-side section of the SW as well
as per a previous study [3]. Finally, OCF detection based on as the voltage (■), current (◆), and PF (●) when a fault
minimum MSE is set at 7%, considering measurement error occurs in the load-side section. When high-resistance faults
and the margin. occurred after OCFs in the source- and load-side sections
Table 6 lists the detection rate, FP rate, and location rate in of SW#1, the voltage, current, and PF patterns were similar
the previous methods and the proposed method. The detection at other SWs, but current value differences occurred in the
rate refers to the ratio at which OCFs are classified and FRTUs of CB, RC#2, and SW#6. Furthermore, in the case
detected for all faults. Table 6 reveals that the proposed of GFs after OCFs, there was a difference in the current
method improves the detection rate compared to the previous measurements at CB, SW#1, RC#2, and SW#6 as well as a
methods regardless of the fault location. In the case of the difference in the PF measurement values at RC#2 and SW#6.
voltage-based method, when a fault occurred at the end of In the other graphs as well, if the fault section changes, there
the line, the detection rate decreased because the voltage was is certainly at least one FRTU that shows a difference in at
maintained owing to the DERs. In the case of the current least one of the three measurement elements. Therefore, it is
unbalance-based method, when the difference between the possible to perform location because a difference occurs in
PV output and the load below the fault point was small, the MSE values at both ends of the FRTU section when a fault
as in the case of fault locations ‘‘F3’’ and ‘‘F4’’ in Fig. 7, occurs.
the detection rate decreased because the unbalance was low To verify the possibility of distinguishing OCFs from other
owing to the current supplied by the DERs. The multivariate events, the FRTU measurement values during GFs and OCFs
detection-based method was also found to have a sharply at designated fault locations in the IEEE 33 bus are compared
reduced detection rate when the fault occurred at the end of as shown in Fig. 10. In the graph, the light-colored marks
the line because most OFCs had little fluctuation. Particularly show the voltage, current, and PF during an OCF, and the
in the case of location ‘‘F3’’, which is on the shortest branch regular marks show the measurement values during a GF.
line, all the previous methods showed low detection rates, but In the case of fault location ‘‘F1’’ in Fig. 7, the voltage
the proposed method achieved a high detection rate with little measurement values of the FRTU connected to the load side
difference from those for other locations. This result indicates of the fault point showed similar patterns during the OCF
FIGURE 9. Comparison of measured values of faults at both sides of the SW (From the left: SW#1, RC#1, SW#2, SW#3, SW#4, SW#5, RC#2, and SW#6).
FIGURE 10. Comparison of measured values of each FRTU when OCF or GF occurs.
and the GF. However, there were differences in current and small. Most of the location attempts were successful when
PF measurement values at the FRTU connected to the source an OCF was detected. The FP rate for GFs was also low, and
side of the fault point. In the case of fault location ‘‘F4,’’ FPs only occurred in 2 out of 36 scenarios.
there was no considerable difference in PF, but there were To verify reliability in an actual network, tests were per-
large differences in the current measurement values at CB and formed by changing the polling time of the FRTUs as given in
RC#2. In addition, at all fault locations, there was at least one Table 9. Maximum delay times were assumed, and an FRTU
FRTU where differences in the OCF and GF measurement that transmitted polling commands randomly was selected.
values occurred. Maximum delay times of 1.5, 2, 3, and 4 s were assumed,
given the processing times from the FRTU to the central office
B. PERFORMING TESTS USING THE 118-BUS NETWORK terminal (COT), from the COT to the FEP, and from the FEP
This study analyzes the detection rate and FP rate according to the DMS. The results are presented in Table 9. When the
to adjustments in detection criterion (ε) of in. (11) for the communication delay was 2 s, the detection rate was high and
network as given in Table 7. In the test results, at 6% or less, showed no difference compared to the existing results. When
there were no FPs, but the detection rate was relatively low. the communication delay was 3 s or more, the detection rate
The FP rate was the same at 7% and 8%, but the detection decreased slightly because of the difference in measurement
rate increased at 8%. At 9% and above, the detection rate times, data transmissions in an outage due to the operation of
increased, but the FP rate increased sharply. On the basis of the protective equipment, etc. However, a high detection rate
these results, the detection criterion was set at 8%; Table 8 was maintained.
presents the results of the analysis of each feeder. As the To verify the effects of communication failures, the detec-
DER connections became more numerous, the detection rate tion rate according to the wired/wireless ratio of FRTUs is
decreased, but the overall detection rate for each D/L was examined; the corresponding results are given in Table 10.
high, and the difference due to the DER connections was In FRTU wired communications, fiber-optic cables were
TABLE 7. Detection and FP rate according to detection criteria. the proposed algorithm was installed. All simulations were
performed on a PC with an Intel core i7 3.4-GHz CPU and
32-GB RAM. When CA was performed with the algorithm,
it took 0.77 and 9.04 s in the case of the IEEE 33 bus and
118 bus, respectively. As mentioned previously, the CA is
performed in the non-real-time study mode, and other than
the initial startup, it is only performed for D/Ls that have
TABLE 8. Results of OCF detection and location for the 118-bus test undergone topology changes. Therefore, this level of time
system. consumption will not be a significant issue when applying
the proposed method.
V. CONCLUSION
This study proposes a contingency analysis-based OCF detec-
tion and location method for power distribution networks.
Following are the main conclusions of this study:
1) By comparing the distance between the entire mea-
surement set and DOCA, the proposed method significantly
TABLE 9. Test results considering communication delay. improves the OCF detection rate by 27.3%–50.8% compared
to existing methods that use a specific detection element.
In addition, the proposed method improves FNs for faults
in lines with a high DER connection capacity and line ends,
which is a weakness of existing methods.
2) Using the weights based on the magnitude variation
of the comparison elements when calculating the distance
between the DOCA and FRTU sets, the proposed method
significantly reduces the occurrence of FPs in other events
such as GFs by 9.2%–31.6%. Improving upon FPs, which
are a type of false alarm, is very important for operations.
used, and it was assumed that almost no communica- Repeated false alarms are significant in that they can lead
tion failures occurred. In FRTU wireless communications, to a ‘‘Cry Wolf Effect’’ in which alarms for actual events
frequency-based methods and wireless local area network are ignored because operators and field crews are repeatedly
were used, and a communication failure rate of ∼10% was overworked and ignore repeated alarms. In addition, tests that
assumed. In Korea, most communications are performed via reflect realistic conditions such as FRTU measurement errors,
wires, but in countries with inadequate infrastructure invest- time delays due to polling commands, and communications
ment, the ratio of wireless communications is higher, and the failures due to the wired/wireless communication ratio are
effect of communication failures is greater. To examine this, performed. Accordingly, the proposed method is confirmed
Korea’s wired/wireless communication ratio of 85:15 was to be robust under a variety of realistic conditions, proving
compared with ratios of 50:50 and 15:85. Although commu- its adaptability to actual power-distribution networks.
nication failures occurred as the wireless ratio increased, the 3) In the location of OCFs, the proposed approach shows
detection rate did not change significantly, and a single com- better results compared by 82.6%–84.3% to previous meth-
munication failure had almost no effect. This result implies ods. OCFs are permanent faults, and they must be dealt
that the proposed method is robust against communications with by dispatching field crews, which makes it crucial to
failures. locate them in comparison with other events. Therefore, the
Finally, the time taken to create contingency cases from an proposed algorithm, which performs detection and location
actual DMS was measured to determine the time taken when simultaneously, will be able to increase reliability by enabling
rapid responses during actual operations.
TABLE 10. Test results considering communication failures.
4) The proposed algorithm uses data that are com-
monly possessed by power companies and the typical FRTU
measurement values. Therefore, it is practical in that there
is no need for special investments in facilities, and it can be
universally applied to power distribution network operation
systems that are equipped with basic infrastructure. This
paper proposes an aperiodic screening method. However,
additional research is required on the criteria for selecting
the target D/Ls that need CA. It is possible to determine the
risk of forest fires from weather data and predict situations in
which damages increase when OCFs occur. In addition, the [15] H. Xu, X. Wang, J. Huang, F. Zhang, and F. Chu, ‘‘Semi-supervised
accident rates in a distributed power network increase when multi-sensor information fusion tailored graph embedded low-rank tensor
learning machine under extremely low labeled rate,’’ Inf. Fusion, vol. 105,
the network is newly installed or when its lifespan is expiring May 2024, Art. no. 102222.
and the time for replacement is approaching [34]. These facts [16] J. B. Thomas, S. G. Chaudhari, K. V. Shihabudheen, and N. K. Verma,
could be used to adjust the period and scope of the analysis ‘‘CNN-based transformer model for fault detection in power system net-
works,’’ IEEE Trans. Instrum. Meas., vol. 72, pp. 1–10, 2023.
and reduce the overall time taken by contingency analysis. [17] X. Wang, T. Ding, and W. Xu, ‘‘An open conductor condition monitoring
As DER connections rapidly increase, fault detection and scheme using natural voltage and current disturbances,’’ IEEE Trans.
location are becoming increasingly complex. However, the Power Del., vol. 34, no. 3, pp. 1193–1202, Jun. 2019.
[18] S. H. Mortazavi, Z. Moravej, and S. M. Shahrtash, ‘‘A searching based
lack of timely and commensurate investments in facilities is method for locating high impedance arcing fault in distribution networks,’’
a common problem that must be resolved to protect power IEEE Trans. Power Del., vol. 34, no. 2, pp. 438–447, Apr. 2019.
distribution networks. Therefore, it is important to devise [19] Z. Lin, Z. Hu, and Y. Song, ‘‘Distribution network expansion planning
considering N − 1 criterion,’’ IEEE Trans. Power Syst., vol. 34, no. 3,
methods that can handle power distribution networks that pp. 2476–2478, May 2019.
create changes within the current infrastructure and systems, [20] Q. Zou, F. Luo, and T. Zhang, ‘‘An incidence matrix based analytical
and the use of the proposed method will be effective in reduc- method of N-1 contingency parallel analysis of main transformers in distri-
bution networks,’’ CSEE J. Power Energy Syst., early access, May 6, 2022,
ing damages caused by OCFs in current power-distribution doi: 10.17775/CSEEJPES.2021.01490.
networks. [21] S. J. Simmons, ‘‘Breadth-first trellis decoding with adaptive effort,’’ IEEE
Trans. Commun., vol. 38, no. 1, pp. 3–12, Jan. 1990.
[22] J. J. Grainger, W. D. Stevenson, and G. W. Chang, Power System Analysis,
REFERENCES 2nd ed., New York, NY, USA: McGraw-Hill, 2016, pp. 422–430.
[1] G. Bade. (Nov. 2018). PG&E Reports Second Line Fault in Camp Fire [23] J.-S. Hong, G.-D. Sim, J.-H. Choi, S.-J. Ahn, and S.-Y. Yun, ‘‘Fault location
Area. [Online]. Available: https://www.utilitydive.com/news/ method using phasor measurement units and short circuit analysis for
[2] Y.-S. Ko, ‘‘A self-isolation method for the HIF zone under the network- power distribution networks,’’ Energies, vol. 13, no. 5, p. 1294, Mar. 2020.
based distribution system,’’ IEEE Trans. Power Del., vol. 24, no. 2, [24] IEEE Standard Requirements for Instrument Transformers, Standard
pp. 884–891, Apr. 2009. C57.13, 2016.
[3] D. K. J. S. Jayamaha, I. H. N. Madhushani, R. S. S. J. Gamage, [25] IEC Instrument Transformers—Part 2: Additional Requirements for Cur-
P. P. B. Tennakoon, J. R. Lucas, and U. Jayatunga, ‘‘Open conductor fault rent Transformers, Standard 61869, IEC, 2012.
detection,’’ in Proc. Moratuwa Eng. Res. Conf. (MERCon), Moratuwa, Sri [26] IEEE Standard for Interconnection and Interoperability of Distributed
Lanka, May 2017, pp. 363–367. Energy Resources With Associated Electric Power Systems Interfaces,
[4] A. Wontroba, A. P. Morais, G. J. Cardoso, J. P. A. Vieira, P. E. Farias, IEEE Standard IEEE 1547, 2018.
M. Gallas, and J. P. Rossini, ‘‘High-impedance fault detection on downed [27] S. H. Dolatabadi, M. Ghorbanian, P. Siano, and N. D. Hatziargyriou,
conductor in overhead distribution networks,’’ Electr. Power Syst. Res., ‘‘An enhanced IEEE 33 bus benchmark test system for distribution sys-
vol. 211, Oct. 2022, Art. no. 108216. tem studies,’’ IEEE Trans. Power Syst., vol. 36, no. 3, pp. 2565–2572,
[5] J.-S. Hong, S.-Y. Hyun, Y.-W. Lee, J.-H. Choi, S.-J. Ahn, and S.-Y. Yun, May 2021.
‘‘Detection of open conductor fault using multiple measurement factors [28] D. Zhang, Z. Fu, and L. Zhang, ‘‘An improved TS algorithm for loss-
of feeder RTUs in power distribution networks with DGs,’’ IEEE Access, minimum reconfiguration in large-scale distribution systems,’’ Electr.
vol. 9, pp. 143564–143579, 2021. Power Syst. Res., vol. 77, nos. 5–6, pp. 685–694, Apr. 2007.
[6] V. H. Makwana and B. R. Bhalja, ‘‘A new digital distance relaying [29] S.-Y. Hyun, J.-S. Hong, S.-Y. Yun, C.-H. Kim, and Y. Lee, ‘‘Arc modeling
scheme for series-compensated double-circuit line during open conductor and kurtosis detection of fault with arc in power distribution networks,’’
and ground fault,’’ IEEE Trans. Power Del., vol. 27, no. 2, pp. 910–917, Appl. Sci., vol. 12, no. 6, pp. 2777–2793, Mar. 2022.
Apr. 2012. [30] Y.-B. Jung, W.-S. Choi, Y.-S. Jeon, and B.-S. Lee, ‘‘Development of
[7] L. Garcia-Santander, P. Bastard, M. Petit, I. Gal, E. Lopez, and H. Opazo, method for detecting high impedance fault,’’ KEPCO, Naju, South Korea,
‘‘Down-conductor fault detection and location via a voltage based method Tech. Rep. R11DA01, Sep. 2013, pp. 90–93.
for radial distribution networks,’’ IEE Proc., Gener., Transmiss. Distrib., [31] Guidelines for Distribution Network Protection, KEPCO, Naju,
vol. 152, no. 2, p. 180, 2005. South Korea, Oct. 2008.
[8] F. L. Vieira, P. H. M. Santos, J. M. C. Filho, R. C. Leborgne, and [32] V. D. Andrade and E. Sorrentino, ‘‘Typical expected values of the fault
M. P. Leite, ‘‘A voltage-based approach for series high impedance fault resistance in power systems,’’ in Proc. IEEE/PES Transmiss. Distrib. Conf.
detection and location in distribution systems using smart meters,’’ Ener- Expo., Latin Amer. (TD-LA), Sao Paulo, Brazil, Nov. 2010, pp. 602–609.
gies, vol. 12, no. 15, p. 3022, Aug. 2019. [33] Technical Standards of the Distributed Energy Resource Connection in
[9] E. M. Esmail, M. M. Elgamasy, T. A. Kawady, A.-M.-I. Taalab, Power Distribution System, KEPCO, Naju, South Korea, 2021.
N. I. Elkalashy, and M. A. Elsadd, ‘‘Detection and experimental investiga- [34] G. Klutke, P. C. Kiessler, and M. A. Wortman, ‘‘A critical look at the
tion of open conductor and single-phase Earth return faults in distribution bathtub curve,’’ IEEE Trans. Rel., vol. 52, no. 1, pp. 125–129, Mar. 2003.
systems,’’ Int. J. Electr. Power Energy Syst., vol. 140, Sep. 2022,
Art. no. 108089.
[10] J. Li, Y. Liu, C. Li, D. Zeng, H. Li, and G. Wang, ‘‘An FTU-based
method for locating single-phase high-impedance faults using transient
zero-sequence admittance in resonant grounding systems,’’ IEEE Trans.
Power Del., vol. 37, no. 2, pp. 913–922, Apr. 2022.
[11] M. Michalik, M. Lukowicz, W. Rebizant, S.-J. Lee, and S.-H. Kang,
‘‘New ANN-based algorithms for detecting HIFs in multigrounded MV GI-DO SIM (Student Member, IEEE) received
networks,’’ IEEE Trans. Power Del., vol. 23, no. 1, pp. 58–66, Jan. 2008.
the B.S. and M.S. degrees in electrical engineer-
[12] H.-G. Yeh, S. Sim, and R. J. Bravo, ‘‘Wavelet and denoising techniques
ing from Chonnam National University, Gwangju,
for real-time HIF detection in 12-kV distribution circuits,’’ IEEE Syst. J.,
vol. 13, no. 4, pp. 4365–4373, Dec. 2019.
South Korea, in 2018 and 2020, respectively,
[13] B. K. Chaitanya, A. Yadav, and M. Pazoki, ‘‘An intelligent detection of where he is currently pursuing the Ph.D. degree
high-impedance faults for distribution lines integrated with distributed with the Department of Electrical Engineering.
generators,’’ IEEE Syst. J., vol. 14, no. 1, pp. 870–879, Mar. 2020. His research interests include distribution net-
[14] J. Che, T. Kim, S. Pyo, J. Park, B. An, and T. Park, ‘‘Prevention of wildfires work protection technologies, fault analysis, fault
using an AI-based open conductor fault detection method on overhead detection and location, and protection coordina-
line,’’ Energies, vol. 16, no. 5, p. 2366, Mar. 2023. tion optimization.
HYO-SEOP IM (Student Member, IEEE) SEON-JU AHN (Member, IEEE) received the
received the B.S. degree in electrical engineering B.S., M.S., and Ph.D. degrees in electrical engi-
from Chonnam National University, Gwangju, neering from Seoul National University, Seoul,
South Korea, in 2022, where he is currently pur- South Korea, in 2002, 2004, and 2009, respec-
suing the integrated Ph.D. degree with the Depart- tively. He is currently a Professor with Chonnam
ment of Electrical Engineering. His research National University, Gwangju, South Korea. His
interests include distributed generation and oper- current research interests include power quality,
ating distribution systems. distributed energy resources, microgrids, smart
grids, and real-time simulation.