Assessment of Power Swing Blocking Functions
Assessment of Power Swing Blocking Functions
Abstract—Power swings and loss of synchronism are periodically during these swings. The natural frequency is
complex events which occur during power system faults, line typically in the range of 0.5–2 Hz for stable swings and 4–10
switching, generator disconnection, and the loss or application Hz for unstable swings [3].
of large loads. As generators have different frequencies for a
duration following the event, this results in power swings which
cause voltages and currents in different parts of the network to The classical two machine system in Fig 1 can be used to
swing in amplitude and phase angle. Power swing blocking describe the performance of distance protection during power
(PSB) is a vital security feature in distance protection relays for swings. The impedance seen by the relay at R during a power
preventing unnecessary tripping during temporary power swing can be determined by (1).
system oscillatory events. A case study is taken as an example,
which following a system disturbance on the Irish transmission
system, there was a subsequent power swing event on a part of
a 110 kV network. DigSilent PowerFactory was used to perform
dynamic time-domain simulations of the event. A COMTRADE
A B
file is generated from simulations and can be “played back” to
a relay to verify how the relay responds to various stable and S R
ZS R ZL ZR
unstable power swing. The paper also outlines a utility’s
experience in analysing PSB algorithms on distance protective
relays in use on a transmission system. Finally, an overview of
the methods used in developing a systematic and practical Fig 1. Two Machine System
approach to testing and mitigating the effects of the disturbance
on the network is investigated.
Frequency, amplitude, and duration of power swings are
Keywords— Power swing, Power swing blocking, Out of step, determined by the parameters of the power system and
Distance protection testing, DigSilent PowerFactory. generators as well as by the swing trigger conditions,
especially the short-circuit duration.
I. INTRODUCTION When one of these disturbances occurs, it will cause
The primary protection used to protect transmission lines changes in the electrical power parameters [5].
is a numerical distance or impedance protection relay. Today
these relays are known as Intelligent Electronic Devices
(IEDs). The distance or impedance measuring principle −
represents the most widely applied non-unit protection as = (1)
primary (or main) protection to high voltage transmission
lines.
Line switching, generator disconnection, and the addition where:
and loss of large blocks of load can cause instability resulting ES is the voltage of machine S
in power swings in the electrical power system. The use of ER is the voltage of machine R
IED’s has allowed the protection algorithms to become more δ is the angle by which ES leads ER
and more adaptive to the conditions of power systems. The ZS is the impedance of source S
impedance seen by the relay oscillates due to swings of ZR is the impedance of source R
voltage and current during a power swing event. This must be ZL is the impedance of the transmission line (AB)
taken into consideration during the setting of the distance ZT is the total impedance between the two
relay. machines
Distance protection relays incorporate a PSB function,
which blocks the relay operation during a stable power swing. A sudden load/generation imbalance may create a power
In the event of an out-of-step (OOS) condition or an unstable swing resulting in the load impedance oscillating and entering
power swing, the relay should activate. This should result in a the relay tripping zones.
controlled separation of the system at predetermined locations The occurrence of a fault will cause a voltage drop, while
to prevent widespread power outage and damage to generators the disconnection of a line will change the total impedance ZT
[1]. seen by the two machines.
During a power swing, the apparent impedance is A power swing is considered unstable if a generator or a
fluctuating, so it will enter the relay tripping zones leading to group of generators rotors slip poles when some corrective
undesired relay operation [2]. Voltages, currents, and the action is necessary.
derived quantities (e.g., power or impedance) are oscillating
Authorized licensed use limited to: University of Gothenburg. Downloaded on November 30,2020 at 13:57:32 UTC from IEEE Xplore. Restrictions apply.
II. POWER SWING ANALYSIS the impedance seen by relays in the network to enter their
Consider a transmission line AB, which connects two respective impedance tripping zones. In most instances, the
generating stations, as shown in Fig 1. The voltage at the remaining generators can balance the system and the
relay R location is V. The current flowing through the line is impedance returns to the load area, and this is known as a
given by: stable power swing.
X
− Outer Blinder
= (2)
+ + Inner Blinder
Impedance
Zones
Stable Swing
= − (3) Load
Area
−
= = = − (4)
B ZR Power Swing
Inner Blinder
Impedance
n>1 Trajectory Impedance
Zones
δ
90o Load Point Load
Area
R
A
ZS R
n=1
S
n<1
Fig 2. Impedance trajectories as seen by a distance relay during a power
swing
Fig 4. Unstable Power Swing Condition or Out of Step
Authorized licensed use limited to: University of Gothenburg. Downloaded on November 30,2020 at 13:57:32 UTC from IEEE Xplore. Restrictions apply.
X X
Outer Blinder
ΔX1
Inner Blinder
Impedance
Zones ΔX3 ΔX2
Fault
Load
Area
ΔR3 ΔR2 ΔR1
R
Fig 5. Fault condition When the impedance enters the power swing detection
zone, a power swing is active, and the distance zones are
blocked from tripping provided that the monotony and
III. POWER SWING DETECTION METHODS continuity are satisfied.
PSB functions are utilised on distance protection relays in
order to prevent the undesired tripping on some or all zones
during power swing events. However, relays must still be IV. POWER SYSTEM EVENT INVESTIGATION
capable of detecting internal faults during power swing In 2014, following a system disturbance, there was a
events and release the impedance tripping function. During subsequent power swing event on the part of the Irish 110 kV
severe power swing conditions from which a system is transmission network. The distance protection relays in use
unlikely to recover, stability might only be regained if the had PSB enabled, but the function did not correctly block the
swinging sources are separated [5]. distance protection from operating. This resulted in the loss
of three transmission stations. After examining the relay
A. Dual Blinder Method sequence of events and fault records, it was determined that
Traditional approaches for detecting power swing the relay operated in zone 1 time (instantaneous) for a fault
conditions utilise a simplified method where the impedance clearly located in zone 4 (1.2s). In a follow-up investigation,
locus is monitored. When the impedance enters the area an issue was found in the detection algorithm of the relay
between the outer and inner blinders, as shown in Fig 3, a itself.
power swing condition is initiated provided that the
impedance remains within this area for some time. When a A. Fault Background
power swing is detected, some or all zone tripping functions On the part of the 110 kV transmission network, there was
are blocked until the condition has passed, becomes unstable a fault on a line between Stations C and D shown in Fig 7.
or an internal fault occurs during this condition. When the While the primary protection for this line picked up and
swing locus exits the outer blinder, a new timer can be set to cleared the fault correctly, an outer distance zone from the
deactivate the PSB. In reality, the impedance trajectories will protection in Station A also picked up. This zone is used for
not follow a perfect elliptical path. back-up protection and has a long-time delay of 1.2 secs [9].
The outer zone should only operate in exceptional
B. Continuous Impedance Method circumstances where a fault is not cleared in the primary
The continuous impedance detection method is an location.
advanced and more complex detection method than the dual Along with the outer zone pickup from this relay, the PSB
blinder detection method. The power swing detection element also picked up; this blocked the relevant impedance
function is based on a continuous impedance calculation [6]. zones. However, upon reset of the PSB element following the
An impedance calculation is performed in 5ms steps (50 Hz) fault clearance, a trip was issued incorrectly from Station A
and compared with the previous 5ms calculation. Continuity distance protection. This protection operation resulted in a
verifies that the trajectory is not motionless and requires that significant loss of supply to customers and disconnection of
the successive ΔR and ΔX be above a set threshold [7]. generation sources in the area. The considerable impact to
As shown in Fig 6, checking that the successive ΔR and ΔX customers was due to the network feeding arrangements at
have the same signs, confirms that the trajectory does not the time, where the line between Stations E and F was out of
change direction (Monitory). Finally, by looking at the ratios service, effectively leaving this part of the network in a tail
of the successive ΔR and ΔX and comparing them to a feeding arrangement from Station A [8].
threshold value, confirms that there are no sudden changes in After an investigation and consultation with the
the trajectory (Smoothness). manufacturer, an issue was found with the operation of the
This method avoids the need for detailed system analysis PSB function in the specific relay type. The manufacturer
when setting the distance relay and can detect slip frequencies corrected the functionality in a subsequent firmware release,
up to 7 Hz. and this solution was applied retrospectively to all distance
protection relays of this type on the system.
Authorized licensed use limited to: University of Gothenburg. Downloaded on November 30,2020 at 13:57:32 UTC from IEEE Xplore. Restrictions apply.
V. POWER SYSTEM SIMULATION
The transmission networks simulations reported in the
paper uses DigSilent Powerfactory software that includes a
dynamic model of the power system and the protection relays.
An overall protection study of dynamic simulations was made
in order to investigate the operation of the PSB function of
the various lines. The simulations allowed the identification
of various PSB and tripping locations.
The case simulated was a fault on a line between Stations
C and D shown in Fig 7. The primary protection for this line
picked up and cleared the fault correctly, an outer distance
zone 4 from the protection in Station A also picked up.
Fig 8. R-X Plane for Fault Simulation in zone 4 of protected Line AB
Fig 9. R-X Plane showing an unstable power swing zone 4 of protected Line
AB
Authorized licensed use limited to: University of Gothenburg. Downloaded on November 30,2020 at 13:57:32 UTC from IEEE Xplore. Restrictions apply.
constant current and constant voltage methods are the ones The following equation (7) can be used to superimpose the
usually applied. voltage waveforms and the current.
swing.
D ete
PSB
Fig 11. PSB tool for the Superimposition of Voltage and Current Plots
Authorized licensed use limited to: University of Gothenburg. Downloaded on November 30,2020 at 13:57:32 UTC from IEEE Xplore. Restrictions apply.
DigSilent PowerFactory was used to perform dynamic in the field as it simplifies the testing, negating the need for
time-domain simulations, as shown in Fig 12. The three-phase complex calculations and knowledge of advanced simulation
currents and voltages obtained from the time domain software techniques.
simulations from the case study were then converted to The stable and unstable power swing COMTRADE files
COMTRADE files, which are then used to test the actual relay that were generated for the tests performed in this paper can
device. The COMTRADE files can then be used with any be used in the future to test the distance protection relays. The
modern relay test equipment, which allows the various COMTRADE files can be played back to the distance
analogue signals to be played back. protection relays to determine if they operate correctly for
stable and unstable power swings.
REFERENCES
Authorized licensed use limited to: University of Gothenburg. Downloaded on November 30,2020 at 13:57:32 UTC from IEEE Xplore. Restrictions apply.