Transformer - Wikipedia
Transformer - Wikipedia
Transformers are used to change AC voltage levels, such transformers being termed step-up or
step-down type to increase or decrease voltage level, respectively. Transformers can also be
used to provide galvanic isolation between circuits as well as to couple stages of signal-
processing circuits. Since the invention of the first constant-potential transformer in 1885,
transformers have become essential for the transmission, distribution, and utilization of
alternating current electric power.[1] A wide range of transformer designs is encountered in
electronic and electric power applications. Transformers range in size from RF transformers less
than a cubic centimeter in volume, to units weighing hundreds of tons used to interconnect the
power grid.
Principles
Ideal transformer
Ideal transformer equations
An ideal transformer is linear, lossless and
By Faraday's law of induction:
perfectly coupled. Perfect coupling
implies infinitely high core magnetic (Eq. 1[a][2])
permeability and winding inductance and
zero net magnetomotive force (i.e. (Eq. 2)
ipnp − isns = 0).[3][c]
where is the instantaneous voltage, is the
number of turns in a winding, dΦ/dt is the
derivative of the magnetic flux Φ through one
turn of the winding over time (t), and
subscripts P and S denotes primary and
secondary.
(Eq. 5)
(Eq. 7)
A varying current in the transformer's primary winding creates a varying magnetic flux in the
transformer core, which is also encircled by the secondary winding. This varying flux at the
secondary winding induces a varying electromotive force or voltage in the secondary winding.
This electromagnetic induction phenomenon is the basis of transformer action and, in
accordance with Lenz's law, the secondary current so produced creates a flux equal and
opposite to that produced by the primary winding.
The windings are wound around a core of infinitely high magnetic permeability so that all of the
magnetic flux passes through both the primary and secondary windings. With a voltage source
connected to the primary winding and a load connected to the secondary winding, the
transformer currents flow in the indicated directions and the core magnetomotive force cancels
to zero.
According to Faraday's law, since the same magnetic flux passes through both the primary and
secondary windings in an ideal transformer, a voltage is induced in each winding proportional to
its number of turns. The transformer winding voltage ratio is equal to the winding turns ratio.[6]
The load impedance referred to the primary circuit is equal to the turns ratio squared times the
secondary circuit load impedance.[7]
Real transformer
The ideal transformer model neglects many basic linear aspects of real transformers, including
unavoidable losses and inefficiencies.[8]
(a) Core losses, collectively called magnetizing current losses, consisting of[9]
Hysteresis losses due to nonlinear magnetic effects in the transformer core, and
Eddy current losses due to joule heating in the core that are proportional to the square of the
transformer's applied voltage.
(b) Unlike the ideal model, the windings in a real transformer have non-zero resistances and
inductances associated with:
Joule losses due to resistance in the primary and secondary windings[9]
Leakage flux that escapes from the core and passes through one winding only resulting in
primary and secondary reactive impedance.
(c) similar to an inductor, parasitic capacitance and self-resonance phenomenon due to the
electric field distribution. Three kinds of parasitic capacitance are usually considered and the
closed-loop equations are provided[10]
Capacitance between adjacent turns in any one layer;
Capacitance between adjacent layers;
Capacitance between the core and the layer(s) adjacent to the core;
Inclusion of capacitance into the transformer model is complicated, and is rarely attempted; the
'real' transformer model's equivalent circuit shown below does not include parasitic capacitance.
However, the capacitance effect can be measured by comparing open-circuit inductance, i.e.
the inductance of a primary winding when the secondary circuit is open, to a short-circuit
inductance when the secondary winding is shorted.
Leakage flux
The ideal transformer model assumes that all flux generated by the primary winding links all the
turns of every winding, including itself. In practice, some flux traverses paths that take it outside
the windings.[11] Such flux is termed leakage flux, and results in leakage inductance in series
with the mutually coupled transformer windings.[12] Leakage flux results in energy being
alternately stored in and discharged from the magnetic fields with each cycle of the power
supply. It is not directly a power loss, but results in inferior voltage regulation, causing the
secondary voltage not to be directly proportional to the primary voltage, particularly under
heavy load.[11] Transformers are therefore normally designed to have very low leakage
inductance.
In some applications increased leakage is desired, and long magnetic paths, air gaps, or
magnetic bypass shunts may deliberately be introduced in a transformer design to limit the
short-circuit current it will supply.[12] Leaky transformers may be used to supply loads that
exhibit negative resistance, such as electric arcs, mercury- and sodium- vapor lamps and neon
signs or for safely handling loads that become periodically short-circuited such as electric arc
welders.[9]: 485
Air gaps are also used to keep a transformer from saturating, especially audio-frequency
transformers in circuits that have a DC component flowing in the windings.[13] A saturable
reactor exploits saturation of the core to control alternating current.
Knowledge of leakage inductance is also useful when transformers are operated in parallel. It
can be shown that if the percent impedance[e] and associated winding leakage reactance-to-
resistance (X/R) ratio of two transformers were the same, the transformers would share the load
power in proportion to their respective ratings. However, the impedance tolerances of
commercial transformers are significant. Also, the impedance and X/R ratio of different capacity
transformers tends to vary.[15]
Equivalent circuit
Core loss and reactance is represented by the following shunt leg impedances of the model:
Core or iron losses: RC
Magnetizing reactance: XM.
RC and XM are collectively termed the magnetizing branch of the model.
Core losses are caused mostly by hysteresis and eddy current effects in the core and are
proportional to the square of the core flux for operation at a given frequency.[9]: 142–143 The finite
permeability core requires a magnetizing current IM to maintain mutual flux in the core.
Magnetizing current is in phase with the flux, the relationship between the two being non-linear
due to saturation effects. However, all impedances of the equivalent circuit shown are by
definition linear and such non-linearity effects are not typically reflected in transformer
equivalent circuits.[9]: 142 With sinusoidal supply, core flux lags the induced EMF by 90°. With
open-circuited secondary winding, magnetizing branch current I0 equals transformer no-load
current.[16]
Instrument transformer, with polarity
dot and X1 markings on low-voltage
("LV") side terminal
The resulting model, though sometimes termed 'exact' equivalent circuit based on linearity
assumptions, retains a number of approximations.[16] Analysis may be simplified by assuming
that magnetizing branch impedance is relatively high and relocating the branch to the left of
the primary impedances. This introduces error but allows combination of primary and referred
secondary resistances and reactance by simple summation as two series impedances.
Transformer equivalent circuit impedance and transformer ratio parameters can be derived from
the following tests: open-circuit test, short-circuit test, winding resistance test, and transformer
ratio test.
Polarity
A dot convention is often used in transformer circuit diagrams, nameplates or terminal markings
to define the relative polarity of transformer windings. Positively increasing instantaneous
current entering the primary winding's 'dot' end induces positive polarity voltage exiting the
secondary winding's 'dot' end. Three-phase transformers used in electric power systems will
have a nameplate that indicate the phase relationships between their terminals. This may be in
the form of a phasor diagram, or using an alpha-numeric code to show the type of internal
connection (wye or delta) for each winding.
Effect of frequency
The EMF of a transformer at a given flux increases with frequency.[9] By operating at higher
frequencies, transformers can be physically more compact because a given core is able to
transfer more power without reaching saturation and fewer turns are needed to achieve the
same impedance. However, properties such as core loss and conductor skin effect also increase
with frequency. Aircraft and military equipment employ 400 Hz power supplies which reduce
core and winding weight.[17] Conversely, frequencies used for some railway electrification
systems were much lower (e.g. 16.7 Hz and 25 Hz) than normal utility frequencies (50–60 Hz)
for historical reasons concerned mainly with the limitations of early electric traction motors.
Consequently, the transformers used to step-down the high overhead line voltages were much
larger and heavier for the same power rating than those required for the higher frequencies.
Operation of a transformer at its designed voltage but at a higher frequency than intended will
lead to reduced magnetizing current. At a lower frequency, the magnetizing current will
increase. Operation of a large transformer at other than its design frequency may require
assessment of voltages, losses, and cooling to establish if safe operation is practical.
Transformers may require protective relays to protect the transformer from overvoltage at
higher than rated frequency.
One example is in traction transformers used for electric multiple unit and high-speed train
service operating across regions with different electrical standards. The converter equipment
and traction transformers have to accommodate different input frequencies and voltage
(ranging from as high as 50 Hz down to 16.7 Hz and rated up to 25 kV).
At much higher frequencies the transformer core size required drops dramatically: a physically
small transformer can handle power levels that would require a massive iron core at mains
frequency. The development of switching power semiconductor devices made switch-mode
power supplies viable, to generate a high frequency, then change the voltage level with a small
transformer.
Transformers for higher frequency applications such as SMPS typically use core materials with
much lower hysteresis and eddy-current losses than those for 50/60 Hz. Primary examples are
iron-powder and ferrite cores. The lower frequency-dependant losses of these cores often is at
the expense of flux density at saturation. For instance, ferrite saturation occurs at a substantially
lower flux density than laminated iron.
Large power transformers are vulnerable to insulation failure due to transient voltages with
high-frequency components, such as caused in switching or by lightning.
Energy losses
Transformer energy losses are dominated by winding and core losses. Transformers' efficiency
tends to improve with increasing transformer capacity.[18] The efficiency of typical distribution
transformers is between about 98 and 99 percent.[18][19]
As transformer losses vary with load, it is often useful to tabulate no-load loss, full-load loss,
half-load loss, and so on. Hysteresis and eddy current losses are constant at all load levels and
dominate at no load, while winding loss increases as load increases. The no-load loss can be
significant, so that even an idle transformer constitutes a drain on the electrical supply.
Designing energy efficient transformers for lower loss requires a larger core, good-quality
silicon steel, or even amorphous steel for the core and thicker wire, increasing initial cost. The
choice of construction represents a trade-off between initial cost and operating cost.[20]
where, f is the frequency, η is the hysteresis coefficient and βmax is the maximum flux
density, the empirical exponent of which varies from about 1.4 to 1.8 but is often given as
1.6 for iron.[20] For more detailed analysis, see Magnetic core and Steinmetz's equation.
Eddy current losses
Eddy currents are induced in the conductive metal transformer core by the changing
magnetic field, and this current flowing through the resistance of the iron dissipates energy
as heat in the core. The eddy current loss is a complex function of the square of supply
frequency and inverse square of the material thickness.[20] Eddy current losses can be
reduced by making the core of a stack of laminations (thin plates) electrically insulated
from each other, rather than a solid block; all transformers operating at low frequencies use
laminated or similar cores.
Magnetostriction related transformer hum
Magnetic flux in a ferromagnetic material, such as the core, causes it to physically expand
and contract slightly with each cycle of the magnetic field, an effect known as
magnetostriction, the frictional energy of which produces an audible noise known as mains
hum or "transformer hum".[21] This transformer hum is especially objectionable in transformers
supplied at power frequencies and in high-frequency flyback transformers associated with
television CRTs.
Stray losses
Leakage inductance is by itself largely lossless, since energy supplied to its magnetic fields is
returned to the supply with the next half-cycle. However, any leakage flux that intercepts
nearby conductive materials such as the transformer's support structure will give rise to eddy
currents and be converted to heat.[22]
Radiative
There are also radiative losses due to the oscillating magnetic field but these are usually
small.
Mechanical vibration and audible noise transmission
In addition to magnetostriction, the alternating magnetic field causes fluctuating forces
between the primary and secondary windings. This energy incites vibration transmission in
interconnected metalwork, thus amplifying audible transformer hum.[23]
Construction
Cores
Closed-core transformers are constructed in 'core form' or 'shell form'. When windings surround
the core, the transformer is core form; when windings are surrounded by the core, the
transformer is shell form.[24] Shell form design may be more prevalent than core form design for
distribution transformer applications due to the relative ease in stacking the core around
winding coils.[24] Core form design tends to, as a general rule, be more economical, and
therefore more prevalent, than shell form design for high voltage power transformer
applications at the lower end of their voltage and power rating ranges (less than or equal to,
nominally, 230 kV or 75 MVA). At higher voltage and power ratings, shell form transformers tend
to be more prevalent.[24][25][26] Shell form design tends to be preferred for extra-high voltage
and higher MVA applications because, though more labor-intensive to manufacture, shell form
transformers are characterized as having inherently better kVA-to-weight ratio, better short-
circuit strength characteristics and higher immunity to transit damage.[26]
Laminated steel cores
Transformers for use at power or audio frequencies typically have cores made of high
permeability silicon steel.[27] The steel has a permeability many times that of free space and the
core thus serves to greatly reduce the magnetizing current and confine the flux to a path which
closely couples the windings.[28] Early transformer developers soon realized that cores
constructed from solid iron resulted in prohibitive eddy current losses, and their designs
mitigated this effect with cores consisting of bundles of insulated iron wires.[29] Later designs
constructed the core by stacking layers of thin steel laminations, a principle that has remained
in use. Each lamination is insulated from its neighbors by a thin non-conducting layer of
insulation.[30] The transformer universal EMF equation can be used to calculate the core cross-
sectional area for a preferred level of magnetic flux.[9]
The effect of laminations is to confine eddy currents to highly elliptical paths that enclose little
flux, and so reduce their magnitude. Thinner laminations reduce losses,[27] but are more
laborious and expensive to construct.[31] Thin laminations are generally used on high-frequency
transformers, with some of very thin steel laminations able to operate up to 10 kHz.
Laminating the core greatly
reduces eddy-current
losses
One common design of laminated core is made from interleaved stacks of E-shaped steel
sheets capped with I-shaped pieces, leading to its name of E-I transformer.[31] Such a design
tends to exhibit more losses, but is very economical to manufacture. The cut-core or C-core
type is made by winding a steel strip around a rectangular form and then bonding the layers
together. It is then cut in two, forming two C shapes, and the core assembled by binding the
two C halves together with a steel strap.[31] They have the advantage that the flux is always
oriented parallel to the metal grains, reducing reluctance.
A steel core's remanence means that it retains a static magnetic field when power is removed.
When power is then reapplied, the residual field will cause a high inrush current until the effect
of the remaining magnetism is reduced, usually after a few cycles of the applied AC
waveform.[32] Overcurrent protection devices such as fuses must be selected to allow this
harmless inrush to pass.
On transformers connected to long, overhead power transmission lines, induced currents due to
geomagnetic disturbances during solar storms can cause saturation of the core and operation
of transformer protection devices.[33]
Distribution transformers can achieve low no-load losses by using cores made with low-loss
high-permeability silicon steel or amorphous (non-crystalline) metal alloy. The higher initial cost
of the core material is offset over the life of the transformer by its lower losses at light load.[34]
Solid cores
Powdered iron cores are used in circuits such as switch-mode power supplies that operate
above mains frequencies and up to a few tens of kilohertz. These materials combine high
magnetic permeability with high bulk electrical resistivity. For frequencies extending beyond the
VHF band, cores made from non-conductive magnetic ceramic materials called ferrites are
common.[31] Some radio-frequency transformers also have movable cores (sometimes called
'slugs') which allow adjustment of the coupling coefficient (and bandwidth) of tuned radio-
frequency circuits.
Toroidal cores
Toroidal transformers are built around a ring-shaped core, which, depending on operating
frequency, is made from a long strip of silicon steel or permalloy wound into a coil, powdered
iron, or ferrite.[35] A strip construction ensures that the grain boundaries are optimally aligned,
improving the transformer's efficiency by reducing the core's reluctance. The closed ring shape
eliminates air gaps inherent in the construction of an E-I core.[9] : 485 The cross-section of the
ring is usually square or rectangular, but more expensive cores with circular cross-sections are
also available. The primary and secondary coils are often wound concentrically to cover the
entire surface of the core. This minimizes the length of wire needed and provides screening to
minimize the core's magnetic field from generating electromagnetic interference.
Toroidal transformers are more efficient than the cheaper laminated E-I types for a similar
power level. Other advantages compared to E-I types, include smaller size (about half), lower
weight (about half), less mechanical hum (making them superior in audio amplifiers), lower
exterior magnetic field (about one tenth), low off-load losses (making them more efficient in
standby circuits), single-bolt mounting, and greater choice of shapes. The main disadvantages
are higher cost and limited power capacity (see Classification parameters below). Because of
the lack of a residual gap in the magnetic path, toroidal transformers also tend to exhibit higher
inrush current, compared to laminated E-I types.
Ferrite toroidal cores are used at higher frequencies, typically between a few tens of kilohertz to
hundreds of megahertz, to reduce losses, physical size, and weight of inductive components. A
drawback of toroidal transformer construction is the higher labor cost of winding. This is
because it is necessary to pass the entire length of a coil winding through the core aperture
each time a single turn is added to the coil. As a consequence, toroidal transformers rated more
than a few kVA are uncommon. Relatively few toroids are offered with power ratings above
10 kVA, and practically none above 25 kVA. Small distribution transformers may achieve some of
the benefits of a toroidal core by splitting it and forcing it open, then inserting a bobbin
containing primary and secondary windings.[36]
Air cores
A transformer can be produced by placing the windings near each other, an arrangement
termed an "air-core" transformer. An air-core transformer eliminates loss due to hysteresis in
the core material.[12] The magnetizing inductance is drastically reduced by the lack of a
magnetic core, resulting in large magnetizing currents and losses if used at low frequencies.
Air-core transformers are unsuitable for use in power distribution,[12] but are frequently
employed in radio-frequency applications.[37] Air cores are also used for resonant transformers
such as Tesla coils, where they can achieve reasonably low loss despite the low magnetizing
inductance.
Windings
The electrical conductor used for the windings depends upon the application, but in all cases
the individual turns must be electrically insulated from each other to ensure that the current
travels throughout every turn. For small transformers, in which currents are low and the
potential difference between adjacent turns is small, the coils are often wound from enamelled
magnet wire. Larger power transformers may be wound with copper rectangular strip
conductors insulated by oil-impregnated paper and blocks of pressboard.[38]
High-frequency transformers operating in the tens to hundreds of kilohertz often have windings
made of braided Litz wire to minimize the skin-effect and proximity effect losses.[39] Large
power transformers use multiple-stranded conductors as well, since even at low power
frequencies non-uniform distribution of current would otherwise exist in high-current
windings.[38] Each strand is individually insulated, and the strands are arranged so that at
certain points in the winding, or throughout the whole winding, each portion occupies different
relative positions in the complete conductor. The transposition equalizes the current flowing in
each strand of the conductor, and reduces eddy current losses in the winding itself. The
stranded conductor is also more flexible than a solid conductor of similar size, aiding
manufacture.[38]
The windings of signal transformers minimize leakage inductance and stray capacitance to
improve high-frequency response. Coils are split into sections, and those sections interleaved
between the sections of the other winding.
Power-frequency transformers may have taps at intermediate points on the winding, usually on
the higher voltage winding side, for voltage adjustment. Taps may be manually reconnected, or
a manual or automatic switch may be provided for changing taps. Automatic on-load tap
changers are used in electric power transmission or distribution, on equipment such as arc
furnace transformers, or for automatic voltage regulators for sensitive loads. Audio-frequency
transformers, used for the distribution of audio to public address loudspeakers, have taps to
allow adjustment of impedance to each speaker. A center-tapped transformer is often used in
the output stage of an audio power amplifier in a push-pull circuit. Modulation transformers in
AM transmitters are very similar.
Cooling
It is a rule of thumb that the life expectancy of electrical insulation is halved for about every
7 °C to 10 °C increase in operating temperature (an instance of the application of the Arrhenius
equation).[40]
Small dry-type and liquid-immersed transformers are often self-cooled by natural convection
and radiation heat dissipation. As power ratings increase, transformers are often cooled by
forced-air cooling, forced-oil cooling, water-cooling, or combinations of these.[41] Large
transformers are filled with transformer oil that both cools and insulates the windings.[42]
Transformer oil is often a highly refined mineral oil that cools the windings and insulation by
circulating within the transformer tank. The mineral oil and paper insulation system has been
extensively studied and used for more than 100 years. It is estimated that 50% of power
transformers will survive 50 years of use, that the average age of failure of power transformers
is about 10 to 15 years, and that about 30% of power transformer failures are due to insulation
and overloading failures.[43][44] Prolonged operation at elevated temperature degrades
insulating properties of winding insulation and dielectric coolant, which not only shortens
transformer life but can ultimately lead to catastrophic transformer failure.[40] With a great body
of empirical study as a guide, transformer oil testing including dissolved gas analysis provides
valuable maintenance information.
Building regulations in many jurisdictions require indoor liquid-filled transformers to either use
dielectric fluids that are less flammable than oil, or be installed in fire-resistant rooms.[18] Air-
cooled dry transformers can be more economical where they eliminate the cost of a fire-
resistant transformer room.
The tank of liquid-filled transformers often has radiators through which the liquid coolant
circulates by natural convection or fins. Some large transformers employ electric fans for
forced-air cooling, pumps for forced-liquid cooling, or have heat exchangers for water-
cooling.[42] An oil-immersed transformer may be equipped with a Buchholz relay, which,
depending on severity of gas accumulation due to internal arcing, is used to either trigger an
alarm or de-energize the transformer.[32] Oil-immersed transformer installations usually include
fire protection measures such as walls, oil containment, and fire-suppression sprinkler systems.
Polychlorinated biphenyls (PCBs) have properties that once favored their use as a dielectric
coolant, though concerns over their environmental persistence led to a widespread ban on their
use.[45] Today, non-toxic, stable silicone-based oils, or fluorinated hydrocarbons may be used
where the expense of a fire-resistant liquid offsets additional building cost for a transformer
vault.[18][46] However, the long life span of transformers can mean that the potential for
exposure can be high long after banning.[47]
Some transformers are gas-insulated. Their windings are enclosed in sealed, pressurized tanks
and often cooled by nitrogen or sulfur hexafluoride gas.[46]
Experimental power transformers in the 500–1,000 kVA range have been built with liquid
nitrogen or helium cooled superconducting windings, which eliminates winding losses without
affecting core losses.[48][49]
Insulation
Insulation must be provided between the individual turns of the windings, between the
windings, between windings and core, and at the terminals of the winding.
Inter-turn insulation of small transformers may be a layer of insulating varnish on the wire.
Layer of paper or polymer films may be inserted between layers of windings, and between
primary and secondary windings. A transformer may be coated or dipped in a polymer resin to
improve the strength of windings and protect them from moisture or corrosion. The resin may
be impregnated into the winding insulation using combinations of vacuum and pressure during
the coating process, eliminating all air voids in the winding. In the limit, the entire coil may be
placed in a mold, and resin cast around it as a solid block, encapsulating the windings.[50]
Large oil-filled power transformers use windings wrapped with insulating paper, which is
impregnated with oil during assembly of the transformer. Oil-filled transformers use highly
refined mineral oil to insulate and cool the windings and core. Construction of oil-filled
transformers requires that the insulation covering the windings be thoroughly dried of residual
moisture before the oil is introduced. Drying may be done by circulating hot air around the core,
by circulating externally heated transformer oil, or by vapor-phase drying (VPD) where an
evaporated solvent transfers heat by condensation on the coil and core. For small transformers,
resistance heating by injection of current into the windings is used.
Bushings
Larger transformers are provided with high-voltage insulated bushings made of polymers or
porcelain. A large bushing can be a complex structure since it must provide careful control of
the electric field gradient without letting the transformer leak oil.[51]
Classification parameters
An electrical substation in
Melbourne, Australia showing three
of five 220 kV – 66 kV transformers,
each with a capacity of 150 MVA
Applications
Various specific electrical application designs require a variety of transformer types. Although
they all share the basic characteristic transformer principles, they are customized in
construction or electrical properties for certain installation requirements or circuit conditions.
In many electronic devices, a transformer is used to convert voltage from the distribution wiring
to convenient values for the circuit requirements, either directly at the power line frequency or
through a switch mode power supply.
Signal and audio transformers are used to couple stages of amplifiers and to match devices
such as microphones and record players to the input of amplifiers. Audio transformers allowed
telephone circuits to carry on a two-way conversation over a single pair of wires. A balun
transformer converts a signal that is referenced to ground to a signal that has balanced voltages
to ground, such as between external cables and internal circuits. Isolation transformers prevent
leakage of current into the secondary circuit and are used in medical equipment and at
construction sites. Resonant transformers are used for coupling between stages of radio
receivers, or in high-voltage Tesla coils.
Discovery of induction
Electromagnetic induction, the principle of the operation of the transformer, was discovered
independently by Michael Faraday in 1831 and Joseph Henry in 1832.[54][55][56][57] Only Faraday
furthered his experiments to the point of working out the equation describing the relationship
between EMF and magnetic flux now known as Faraday's law of induction:
where is the magnitude of the EMF in volts and ΦB is the magnetic flux through the circuit
in webers.[58]
Faraday performed early experiments on induction between coils of wire, including winding a
pair of coils around an iron ring, thus creating the first toroidal closed-core transformer.[57][59]
However he only applied individual pulses of current to his transformer, and never discovered
the relation between the turns ratio and EMF in the windings.
The first type of transformer to see wide use was the induction coil, invented by Irish-Catholic
Rev. Nicholas Callan of Maynooth College, Ireland in 1836.[57] He was one of the first
researchers to realize the more turns the secondary winding has in relation to the primary
winding, the larger the induced secondary EMF will be. Induction coils evolved from scientists'
and inventors' efforts to get higher voltages from batteries. Since batteries produce direct
current (DC) rather than AC, induction coils relied upon vibrating electrical contacts that
regularly interrupted the current in the primary to create the flux changes necessary for
induction. Between the 1830s and the 1870s, efforts to build better induction coils, mostly by
trial and error, slowly revealed the basic principles of transformers.
In 1876, Russian engineer Pavel Yablochkov invented a lighting system based on a set of
induction coils where the primary windings were connected to a source of AC. The secondary
windings could be connected to several 'electric candles' (arc lamps) of his own design. The
coils Yablochkov employed functioned essentially as transformers.[60]
In 1878, the Ganz factory, Budapest, Hungary, began producing equipment for electric lighting
and, by 1883, had installed over fifty systems in Austria-Hungary. Their AC systems used arc
and incandescent lamps, generators, and other equipment.[57][61]
In 1882, Lucien Gaulard and John Dixon Gibbs first exhibited a device with an initially widely
criticized laminated plate open iron core called a 'secondary generator' in London, then sold the
idea to the Westinghouse company in the United States in 1886.[29] They also exhibited the
invention in Turin, Italy in 1884, where it was highly successful and adopted for an electric
lighting system.[62] Their device used a fixed 1:1 ratio to supply a series circuit for the utilization
load (lamps). The voltage of their system was controlled by pushing in and pulling out its open
iron core.[63]
Induction coils with open magnetic circuits are inefficient at transferring power to loads. Until
about 1880, the paradigm for AC power transmission from a high voltage supply to a low
voltage load was a series circuit. Open-core transformers with a ratio near 1:1 were connected
with their primaries in series to allow use of a high voltage for transmission while presenting a
low voltage to the lamps. The inherent flaw in this method was that turning off a single lamp (or
other electric device) affected the voltage supplied to all others on the same circuit. Many
adjustable transformer designs were introduced to compensate for this problematic
characteristic of the series circuit, including those employing methods of adjusting the core or
bypassing the magnetic flux around part of a coil.[62] Efficient, practical transformer designs did
not appear until the 1880s, but within a decade, the transformer would be instrumental in the
war of the currents, and in seeing AC distribution systems triumph over their DC counterparts, a
position in which they have remained dominant ever since.[64]
In both designs, the magnetic flux linking the primary and secondary windings traveled almost
entirely within the confines of the iron core, with no intentional path through air (see Toroidal
cores below). The new transformers were 3.4 times more efficient than the open-core bipolar
devices of Gaulard and Gibbs.[67] The ZBD patents included two other major interrelated
innovations: one concerning the use of parallel connected, instead of series connected,
utilization loads, the other concerning the ability to have high turns ratio transformers such that
the supply network voltage could be much higher (initially 1,400 to 2,000 V) than the voltage of
utilization loads (100 V initially preferred).[68][69] When employed in parallel connected electric
distribution systems, closed-core transformers finally made it technically and economically
feasible to provide electric power for lighting in homes, businesses and public spaces. Bláthy
had suggested the use of closed cores, Zipernowsky had suggested the use of parallel shunt
connections, and Déri had performed the experiments;[70] In early 1885, the three engineers
also eliminated the problem of eddy current losses with the invention of the lamination of
electromagnetic cores.[71]
Transformers today are designed on the principles discovered by the three engineers. They also
popularized the word 'transformer' to describe a device for altering the EMF of an electric
current[72] although the term had already been in use by 1882.[73][74] In 1886, the ZBD engineers
designed, and the Ganz factory supplied electrical equipment for, the world's first power station
that used AC generators to power a parallel connected common electrical network, the steam-
powered Rome-Cerchi power plant.[75]
Westinghouse improvements
Westinghouse, Stanley and associates soon developed a core that was easier to manufacture,
consisting of a stack of thin 'E‑shaped' iron plates insulated by thin sheets of paper or other
insulating material. Pre-wound copper coils could then be slid into place, and straight iron
plates laid in to create a closed magnetic circuit. Westinghouse obtained a patent for the new
low-cost design in 1887.[70]
In 1891, Nikola Tesla invented the Tesla coil, an air-cored, dual-tuned resonant transformer for
producing very high voltages at high frequency.[83]
Audio frequency transformers ("repeating coils") were used by early experimenters in the
development of the telephone.[84]
See also
Notes
a. With turns of the winding oriented perpendicularly to the magnetic field lines, the flux is
the product of the magnetic flux density and the core area, the magnetic field varying with
time according to the excitation of the primary. The expression , defined as the
derivative of magnetic flux with time , provides a measure of rate of magnetic flux in
the core and hence of EMF induced in the respective winding. The negative sign in eq. 1 &
eq. 2 is consistent with Lenz's law and Faraday's law in that by convention EMF "induced by
an increase of magnetic flux linkages is opposite to the direction that would be given by
the right-hand rule."
b. Although ideal transformer's winding inductances are each infinitely high, the square root
of winding inductances' ratio is equal to the turns ratio.
c. This also implies the following: The net core flux is zero, the input impedance is infinite
when secondary is open and zero when secondary is shorted; there is zero phase-shift
through an ideal transformer; input and output power and reactive volt-ampere are each
conserved; these three statements apply for any frequency above zero and periodic
waveforms are conserved.[5]
d. Direction of transformer currents is according to the Right-Hand Rule.
e. Percent impedance is the ratio of the voltage drop in the secondary from no load to full
load.[14]
References
1. Bedell, Frederick (1942). "History of A-C Wave Form, Its Determination and
Standardization". Transactions of the American Institute of Electrical Engineers. 61 (12):
864. doi:10.1109/T-AIEE.1942.5058456 (https://doi.org/10.1109%2FT-AIEE.1942.5058456) .
S2CID 51658522 (https://api.semanticscholar.org/CorpusID:51658522) .
2. Skilling, Hugh Hildreth (1962). Electromechanics. John Wiley & Sons, Inc. p. 39
3. Brenner & Javid 1959, §18-6 The Ideal Transformer, pp. 598–600
4. Brenner & Javid 1959, §18-1 Symbols and Polarity of Mutual Inductance, pp.=589–590
5. Crosby 1958, p. 145
6. Paul A. Tipler, Physics, Worth Publishers, Inc., 1976 ISBN 0-87901-041-X, pp. 937-940
7. Flanagan, William M. (1993). Handbook of Transformer Design & Applications (https://archi
ve.org/details/FlagananHandbookOfTransformerDesignApplications) (2nd ed.). McGraw-
Hill. ISBN 978-0-07-021291-6. pp. 2-1, 2-2
8. Electrical Engineering: An Introduction. Saunders College Publishing. 1984. p. 610. ISBN 0-
03-061758-8.
9. Say, M. G. (1983). Alternating Current Machines (5th ed.). London: Pitman. ISBN 978-0-
273-01969-5.
10. L. Dalessandro, F. d. S. Cavalcante, and J. W. Kolar, "Self-Capacitance of High-Voltage
Transformers," IEEE Transactions on Power Electronics, vol. 22, no. 5, pp. 2081–2092, 2007.
11. McLaren 1984, pp. 68–74
12. Calvert, James (2001). "Inside Transformers" (https://web.archive.org/web/2007050911140
7/http://www.du.edu/~jcalvert/tech/transfor.htm) . University of Denver. Archived from the
original (http://www.du.edu/~jcalvert/tech/transfor.htm) on May 9, 2007. Retrieved
May 19, 2007.
13. Terman, Frederick E. (1955). Electronic and Radio Engineering (https://archive.org/details/e
lectronicradioe00term) (4th ed.). New York: McGraw-Hill. pp. 15 (https://archive.org/detai
ls/electronicradioe00term/page/15) .
14. Heathcote 1998, p. 4
15. Knowlton, A.E., ed. (1949). Standard Handbook for Electrical Engineers (8th ed.). McGraw-
Hill. p. see esp. Section 6 Transformers, etc, pp. 547–644. Nomenclature for Parallel
Operation, pp. 585–586
16. Daniels 1985, pp. 47–49
17. "400 Hz Electrical Systems" (http://www.aerospaceweb.org/question/electronics/q0219.sht
ml) . Aerospaceweb.org. Retrieved May 21, 2007.
18. De Keulenaer et al. 2001
19. Kubo, T.; Sachs, H.; Nadel, S. (2001). Opportunities for New Appliance and Equipment
Efficiency Standards (http://www.aceee.org/research-report/a016) . American Council for
an Energy-Efficient Economy. p. 39, fig. 1. Retrieved June 21, 2009.
20. Heathcote 1998, pp. 41–42
21. "Understanding Transformer Noise" (https://web.archive.org/web/20060510231426/http://
www.federalpacific.com/literature/drytrans/10transformernoise.pdf) (PDF). FP. Archived
from the original (http://www.federalpacific.com/literature/drytrans/10transformernoise.pd
f) (PDF) on 10 May 2006. Retrieved 30 January 2013.
22. Nailen, Richard (May 2005). "Why We Must Be Concerned With Transformers" (https://web.
archive.org/web/20090429031651/http://www.blnz.com/news/2008/04/23/must_concern
ed_with_transformers_9639.html) . Electrical Apparatus. Archived from the original (http://
www.blnz.com/news/2008/04/23/must_concerned_with_transformers_9639.html) on
2009-04-29.
23. Pansini 1999, p. 23
24. Del Vecchio et al. 2002, pp. 10–11, Fig. 1.8
25. Hydroelectric Research and Technical Services Group. "Transformers: Basics, Maintenance,
and Diagnostics" (http://permanent.access.gpo.gov/lps113746/Trnsfrmr.pdf) (PDF). U.S.
Dept. of the Interior, Bureau of Reclamation. p. 12. Retrieved Mar 27, 2012.
26. US Army Corps of Engineers (1994). "EM 1110-2-3006 Engineering and Design –
Hydroelectric Power Plants Electrical Design" (https://archive.org/details/U.S._Army_Corps_
of_Engineers_Engineering_and_Design_Hydroelectric_Power_Plants_E) . Chapter 4 Power
Transformers. p. 4-1.
27. Hindmarsh 1977, pp. 29–31
28. Gottlieb 1998, p. 4
29. Allan, D.J. (Jan 1991). "Power Transformers – The Second Century". Power Engineering
Journal. 5 (1): 5–14. doi:10.1049/pe:19910004 (https://doi.org/10.1049%2Fpe%3A1991000
4) .
30. Kulkarni & Khaparde 2004, pp. 36–37
31. McLyman 2004, pp. 3-9 to 3-14
32. Harlow 2004, §2.1.7 & §2.1.6.2.1 in Section §2.1 Power Transformers by H. Jin Sim and Scott
H. Digby in Chapter 2 Equipment Types
33. Boteler, D. H.; Pirjola, R. J.; Nevanlinna, H. (1998). "The Effects of Geomagnetic
Disturbances On Electrical Systems at the Earth's Surface". Advances in Space Research.
22 (1): 17–27. Bibcode:1998AdSpR..22...17B (https://ui.adsabs.harvard.edu/abs/1998AdSpR..
22...17B) . doi:10.1016/S0273-1177(97)01096-X (https://doi.org/10.1016%2FS0273-1177%289
7%2901096-X) .
34. Hasegawa, Ryusuke (June 2, 2000). "Present Status of Amorphous Soft Magnetic Alloys".
Journal of Magnetism and Magnetic Materials. 215–216 (1): 240–245.
Bibcode:2000JMMM..215..240H (https://ui.adsabs.harvard.edu/abs/2000JMMM..215..240
H) . doi:10.1016/S0304-8853(00)00126-8 (https://doi.org/10.1016%2FS0304-8853%280
0%2900126-8) .
35. McLyman 2004, p. 3-1
36. "Toroidal Line Power Transformers. Power Ratings Tripled. | Magnetics Magazine" (https://w
eb.archive.org/web/20160924114636/http://www.magneticsmagazine.com/main/articles/t
oroidal-line-power-transformers-power-ratings-tripled/) . www.magneticsmagazine.com.
Archived from the original (http://www.magneticsmagazine.com/main/articles/toroidal-line
-power-transformers-power-ratings-tripled/) on 2016-09-24. Retrieved 2016-09-23.
37. Lee, Reuben. "Air-Core Transformers" (http://www.vias.org/eltransformers/lee_electronic_tr
ansformers_07b_22.html) . Electronic Transformers and Circuits. Retrieved May 22, 2007.
38. CEGB 1982
39. Dixon, Lloyd (2001). "Power Transformer Design" (http://focus.ti.com/lit/ml/slup126/slup126.
pdf) (PDF). Magnetics Design Handbook. Texas Instruments.
40. Harlow 2004, §3.4.8 in Section 3.4 Load and Thermal Performance by Robert F. Tillman in
Chapter 3 Ancillary Topics
41. Pansini 1999, p. 32
42. H. Lee Willis, Power Distribution Planning Reference Book, 2004 CRC Press. ISBN 978-0-
8247-4875-3, pg. 403
43. Hartley, William H. (2003). Analysis of Transformer Failures (https://web.archive.org/web/2
0131020185815/http://www.bplglobal.net/eng/knowledge-center/download.aspx?id=191) .
36th Annual Conference of the International Association of Engineering Insurers. p. 7 (fig.
6). Archived from the original (http://www.bplglobal.net/eng/knowledge-center/download.
aspx?id=191) on 20 October 2013. Retrieved 30 January 2013.
44. Hartley, William H. (~2011). "An Analysis of Transformer Failures, Part 1 – 1988 through 1997"
(https://web.archive.org/web/20180618175745/http://www.hsb.com/TheLocomotive/AnAn
alysisOfTransformerFailuresPart1.aspx) . The Locomotive. Archived from the original (htt
p://www.hsb.com/TheLocomotive/AnAnalysisOfTransformerFailuresPart1.aspx) on 18
June 2018. Retrieved 30 January 2013.
45. "ASTDR ToxFAQs for Polychlorinated Biphenyls" (https://wwwn.cdc.gov/TSP/ToxFAQs/ToxF
AQsLanding.aspx?id=140&tid=26) . 2001. Retrieved June 10, 2007.
46. Kulkarni & Khaparde 2004, pp. 2–3
47. "What silicone wristbands say about chemical exposure in Uruguayan children" (http://ww
w.buffalo.edu/news/releases/2020/07/015.html) . www.buffalo.edu. Retrieved
2022-01-28.
48. Mehta, S.P.; Aversa, N.; Walker, M.S. (Jul 1997). "Transforming Transformers
[Superconducting windings]" (http://www.superpower-inc.com/files/T141+IEEE+Spectrum+
XFR.pdf) (PDF). IEEE Spectrum. 34 (7): 43–49. doi:10.1109/6.609815 (https://doi.org/10.110
9%2F6.609815) . Retrieved 14 November 2012.
49. Pansini 1999, pp. 66–67
50. Lane, Keith (2007) (June 2007). "The Basics of Large Dry-Type Transformers" (http://ecmw
eb.com/content/basics-large-dry-type-transformers) . EC&M. Retrieved 29 January 2013.
51. Ryan 2004, pp. 416–417
52. Heathcote 1998, p. 1
53. Poyser, Arthur William (1892). Magnetism and Electricity: A Manual for Students in
Advanced Classes (https://archive.org/details/bub_gb_JzBAAAAAYAAJ) . London and New
York: Longmans, Green, & Co. p. 285 (https://archive.org/details/bub_gb_JzBAAAAAYAAJ/p
age/n298) , fig. 248.
54. "A Brief History of Electromagnetism" (http://web.hep.uiuc.edu/home/serrede/P435/Lectur
e_Notes/A_Brief_History_of_Electromagnetism.pdf) (PDF).
55. "Electromagnetism" (http://siarchives.si.edu/history/exhibits/henry/electromagnetism) .
Smithsonian Institution Archives.
56. MacPherson, Ph.D., Ryan C. Joseph Henry: The Rise of an American scientist (https://web.a
rchive.org/web/20151208121757/http://www.ryancmacpherson.com/publications/3-book-re
views/49-joseph-henry-the-rise-of-an-american-scientist.html) . Archived from the
original (http://www.ryancmacpherson.com/publications/3-book-reviews/49-joseph-henry
-the-rise-of-an-american-scientist.html) on 2015-12-08. Retrieved 2015-10-28.
57. Guarnieri 2013, pp. 56–59
58. Chow, Tai L. (2006). Introduction to Electromagnetic Theory: A Modern Perspective (http
s://books.google.com/books?id=dpnpMhw1zo8C&pg=PA171) . Sudbury, Mass.: Jones and
Bartlett Publishers. p. 171. ISBN 978-0-7637-3827-3.
59. Faraday, Michael (1834). "Experimental Researches on Electricity, 7th Series" (https://archiv
e.org/details/philtrans08694360) . Philosophical Transactions of the Royal Society. 124:
77–122. doi:10.1098/rstl.1834.0008 (https://doi.org/10.1098%2Frstl.1834.0008) .
S2CID 116224057 (https://api.semanticscholar.org/CorpusID:116224057) .
60. "Stanley Transformer – 1886 - MagLab" (https://web.archive.org/web/20171011232657/http
s://nationalmaglab.org/education/magnet-academy/history-of-electricity-magnetism/mus
eum/stanley-transformer) . Archived from the original (https://nationalmaglab.org/educati
on/magnet-academy/history-of-electricity-magnetism/museum/stanley-transformer) on
2017-10-11. Retrieved 2021-07-27.
61. Hughes 1993, pp. 95–96
62. Uppenborn, F. J. (1889). History of the Transformer (https://archive.org/details/historyoftra
nsfo00upperich) . London: E. & F. N. Spon. pp. 35 (https://archive.org/details/historyoftra
nsfo00upperich/page/35) –41.
63. Halacsy, Andrew; Fuchs, George (April 1961). "Transformer Invented 75 Years Ago" (https://
web.archive.org/web/20231128081004/https://ieeexplore.ieee.org/document/4500994) .
Transactions of the American Institute of Electrical Engineers. Part III: Power Apparatus and
Systems. 80 (3): 121–125. doi:10.1109/AIEEPAS.1961.4500994 (https://doi.org/10.1109%2FAIE
EPAS.1961.4500994) . S2CID 51632693 (https://api.semanticscholar.org/CorpusID:5163269
3) . Archived from the original on November 28, 2023. Retrieved November 28, 2023.
64. Coltman 1988, pp. 86–95
65. Halacsy & Von Fuchs 1961, pp. 121–125
66. Lucas, J.R. "Historical Development of the Transformer" (http://www.elect.mrt.ac.lk/Transfo
rmer_history_2000.pdf) (PDF). IEE Sri Lanka Centre. Retrieved Mar 1, 2012.
67. Jeszenszky, Sándor. "Electrostatics and Electrodynamics at Pest University in the Mid-19th
Century" (https://web.archive.org/web/20220627060208/http://ppp.unipv.it/Collana/Page
s/Libri/Saggi/Volta%20and%20the%20History%20of%20Electricity/V%26H%20Sect2/V%26
H%20175-182.pdf) (PDF). University of Pavia. Archived from the original on June 27, 2022.
Retrieved Mar 3, 2012.
68. "Hungarian Inventors and Their Inventions" (https://web.archive.org/web/20120322223457/
http://www.institutoideal.org/conteudo_eng.php?&sys=biblioteca_eng&arquivo=1&artigo=9
4&ano=2008) . Institute for Developing Alternative Energy in Latin America. Archived
from the original (http://www.institutoideal.org/conteudo_eng.php?&sys=biblioteca_eng&a
rquivo=1&artigo=94&ano=2008) on 2012-03-22. Retrieved Mar 3, 2012.
69. "Bláthy, Ottó Titusz" (http://www.omikk.bme.hu/archivum/angol/htm/blathy_o.htm) .
Budapest University of Technology and Economics, National Technical Information Centre
and Library. Retrieved Feb 29, 2012.
70. Smil, Vaclav (2005). Creating the Twentieth Century: Technical Innovations of 1867–1914
and Their Lasting Impact (https://archive.org/details/creatingtwentiet0000smil) . Oxford:
Oxford University Press. p. 71 (https://archive.org/details/creatingtwentiet0000smil/page/7
1) . ISBN 978-0-19-803774-3. "ZBD transformer."
71. Electrical Society of Cornell University (1896). Proceedings of the Electrical Society of
Cornell University. Andrus & Church. p. 39.
72. Nagy, Árpád Zoltán (Oct 11, 1996). "Lecture to Mark the 100th Anniversary of the Discovery
of the Electron in 1897 (preliminary text)" (https://web.archive.org/web/20121125115109/htt
p://www.kfki.hu/~aznagy/lecture/lecture.htm) . Budapest. Archived from the original (htt
p://www.kfki.hu/~aznagy/lecture/lecture.htm) on November 25, 2012. Retrieved July 9,
2009.
73. Oxford English Dictionary (https://archive.org/details/oxfordenglishdic0015unse)
(2nd ed.). Oxford University Press. 1989.
74. Hospitalier, Édouard (1882). The Modern Applications of Electricity (https://archive.org/det
ails/modernapplicati00hospgoog) . Translated by Julius Maier. New York: D. Appleton &
Co. p. 103 (https://archive.org/details/modernapplicati00hospgoog/page/n121) .
75. "Ottó Bláthy, Miksa Déri, Károly Zipernowsky" (https://web.archive.org/web/201012060428
32/http://www.iec.ch/cgi-bin/tl_to_htm.pl?section=technology&item=144) . IEC Techline.
Archived from the original (http://www.iec.ch/cgi-bin/tl_to_htm.pl?section=technology&ite
m=144) on 2010-12-06. Retrieved Apr 16, 2010.
76. Brusso, Barry; Allerhand, Adam (January 2021). "A Contrarian History of Early Electric
Power Distribution" (https://web.archive.org/web/20201212083429/https://ieeexplore.ieee.
org/stamp/stamp.jsp?arnumber=9292399) . IEEE Industry Applications Magazine.
IEEE.org: 12. doi:10.1109/MIAS.2020.3028630 (https://doi.org/10.1109%2FMIAS.2020.30286
30) . S2CID 230605234 (https://api.semanticscholar.org/CorpusID:230605234) .
Archived from the original (https://ieeexplore.ieee.org/document/9292399) on December
12, 2020. Retrieved January 1, 2023.
77. History of Tinicum Township (PA) 1643–1993 (http://tthsdelco.org/wp-content/uploads/201
4/02/History%20of%20Tinicum%20Twp.pdf) (PDF). Tinicum Township Historical Society.
1993. Archived (https://web.archive.org/web/20150423202458/http://tthsdelco.org/wp-co
ntent/uploads/2014/02/History%20of%20Tinicum%20Twp.pdf) (PDF) from the original on
April 23, 2015.
78. William R. Huber (2022). George Westinghouse Powering the World (https://books.google.c
om/books?id=UdBcEAAAQBAJ&dq=Westinghouse+purchased+the+patent+rights+to+the+
Gaulard%E2%80%93Gibbs+system+in+February+of+that+year&pg=PA84) . McFarland &
Company. p. 84. ISBN 9781476686929.
79. Skrabec, Quentin R. (2007). George Westinghouse: Gentle Genius (https://books.google.co
m/books?id=C3GYdiFM41oC&pg=PA102) . Algora Publishing. p. 102. ISBN 978-0-87586-
508-9.
80. Coltman 2002
81. International Electrotechnical Commission. Otto Blathy, Miksa Déri, Károly Zipernowsky (htt
ps://web.archive.org/web/20101206042832/http://www.iec.ch/cgi-bin/tl_to_htm.pl?section
=technology&item=144) . Archived from the original (http://www.iec.ch/cgi-bin/tl_to_htm.
pl?section=technology&item=144) on December 6, 2010. Retrieved May 17, 2007. {{cite
book}}: |work= ignored (help)
82. Neidhöfer, Gerhard (2008). Michael von Dolivo-Dobrowolsky and Three-Phase: The
Beginnings of Modern e Technology and Power Supply (http://d-nb.info/990964361) (in
German). In collaboration with VDE "History of Electrical Engineering" Committee (2nd ed.).
Berlin: VDE-Verl. ISBN 978-3-8007-3115-2.
83. Uth, Robert (Dec 12, 2000). "Tesla Coil" (https://www.pbs.org/tesla/ins/lab_tescoil.html) .
Tesla: Master of Lightning. PBS.org. Retrieved May 20, 2008.
84. "telephone | History, Definition, Invention, Uses, & Facts | Britannica" (https://www.britannic
a.com/technology/telephone) . www.britannica.com. Retrieved 2022-07-17.
Bibliography
External links
General links: