DEC40 USERv4
DEC40 USERv4
INTRODUCTION FEATURES
Pressure driven automatic start and stop
DEC-40 is a state of the art unit for the
control of both screw and piston type Voltage Protection Relay function
compressors. Phase Order Protection Relay function
Mains phase voltages display
The unit integrates all functions needed in a
compressor system. Thus no extra units are No need for external transformer
required in a compressor panel providing Star / Delta startup
cost reduction and simplicity. Load solenoid control
The unit is directly powered from 230/400 volt 1 programmable relay output
mains. It provides power supply for fault Optically isolated configurable digital inputs
switches and sensors. Thus external 2 pressure sensor inputs
transformer is not required in the panel. 2 temperature sensor inputs
The unit monitors mains phase voltages and Additional motor PTC input
frequency. It features high/low voltage and Logic level serial port
phase order protections. MODBUS-RTU communication
The standard logic level serial port features Password protected front panel programming
MODBUS communication. The unit allows Low panel depth, easy installation
monitoring and programming through Wide operating temperature range
computer. Sealed front panel (IP54)
2 part connector system for easy installation
-1-
DEC-40 USER MANUAL V4
SAFETY NOTICE
Failure to follow below instructions will
result in death or serious injury
-2-
DEC-40 USER MANUAL V4
TABLE OF CONTENTS
Section
1. INSTALLATION
1.1. FRONT / REAR PANELS
1.2. MECHANICAL INSTALLATION
1.3. ELECTRICAL INSTALLATION
1.4. CONNECTION DIAGRAM
2. PUSHBUTTON FUNCTIONS
3. DISPLAY NAVIGATION
4. MODES OF OPERATION
5. ALARMS AND WARNINGS
6. OTHER FEATURES
6.1. RESETTING SERVICE COUNTERS
6.2. MODIFYING HOUR COUNTERS
6.3. CONNECTION TOPOLOGIES
6.4. PREVENTING PRESSURE LOSS
6.5. ALARM HISTORY
7. INPUTS
8. RELAY OUTPUTS
9. PROGRAMMING
9.1. INTRODUCTION TO PROGRAMMING
9.2. PARAMETER LIST
10. MODBUS COMMUNICATIONS
10.1. DESCRIPTION
10.2. MODBUS REGISTER LIST
11. MULTIPLE CONTROLLER OPERATION
12. DECLARATION OF CONFORMITY
13. TECHNICAL SPECIFICATIONS
-3-
DEC-40 USER MANUAL V4
1. INSTALLATION
Before installation:
Read the user manual carefully, determine the correct connection diagram.
Remove all connectors and mounting brackets from the unit, then pass the unit through
the mounting opening.
Put mounting brackets and tighten. Do not tighten too much, this can brake the enclosure.
Make electrical connections with plugs removed from sockets, then place plugs to their
sockets.
Note that the power supply terminal is separated from measurement terminals.
-4-
DEC-40 USER MANUAL V4
-5-
DEC-40 USER MANUAL V4
-6-
DEC-40 USER MANUAL V4
-7-
DEC-40 USER MANUAL V4
2. PUSHBUTTON FUNCTIONS
Programming and measurement displays are visualized using below buttons:
-8-
DEC-40 USER MANUAL V4
3. DISPLAY NAVIGATION
Usually the upper display shows the pressure-1 value or the pressure switch-1 position.
The lower display shows the temperature-1.
Other values are scrolled by pressing the MENU button. For better clarity, the upper
display will show the parameter name and the lower display will show the parameter value.
Some parameters are longer than 1 display. For these parameters, when MENU button
is presssed the parameter name apeears on the upper display. When MENU button is
released, the parameter value is shown on both displays.
In the occurrence of a fault condition, the fault code will appear on the
upper display.
-9-
DEC-40 USER MANUAL V4
- 10 -
DEC-40 USER MANUAL V4
4. MODES OF OPERATION
Selecting the Operating Mode:
At power-up, the unit will turn all lights on for 3 seconds in order to allow lamp check. Then
it goes in the STOP mode and the stop led turns on.
The compressor may be run through Remote Start signal (upper display shows for 5
seconds) or by pressing the RUN button.
If P28 Safety Timer has not elapsed, the run led will flash until expiration of the timer. Then
if the pressure is below the limit set by P05 Start Pressure, then the compressor will run.
The compressor may be stopped with Remote Stop signal (upper display shows for
5 seconds) or the STOP button.
Stop Procedure:
STOP led starts flashing.
If the compressor is loaded, then the LOAD relay will release and the compressor
continues to run during P28 Safety Timer or P26 Unload Timer (whichever is longer).
At this step, operation may be resumed by pressing the RUN button. If STOP
button is pressed during unloaded operation, then the compressor stops immediately.
The stop led flashes until the compressor comes to complete stop.
- 11 -
DEC-40 USER MANUAL V4
Start Procedure:
If mains phase voltages and frequency are between preset limits and the phase order is
correct, then the POWER led will turn on. The compressor may run only when the power
led is on. Otherwise it cannot run.
The Run mode of operation is selected by pressing the RUN button or by sending
REMOTE START/STOP signal (if enabled). At this position, when the pressure falls below
P05 Start Pressure (or pressure switch closes) the unit decides to run the compressor.
Befor running the compressor the STAR relay output becomes active. After P15 Delay
between Relays Timer LINE relay will be activated. Thus the motor starts in star mode.
After P23 Star Timer the STAR relay opens and after P24 Star/Delta Transition Timer the
DELTA relay operates.
After P25 Timer before Loading the LOAD relay operates and the compressor starts
producing compressed air.
- 12 -
DEC-40 USER MANUAL V4
Alarms and warnings may be reset by pressing the MENU button. The EMERGENCY
STOP alarm cannot be reset by pressing buttons, the alarm signal must be removed.
TIME REMAINING TO
REACTION (If parameter P88 is set to “1” only)
SERVICE
> 100 hours No warning given.
- 13 -
DEC-40 USER MANUAL V4
- 14 -
DEC-40 USER MANUAL V4
6. OTHER FEATURES
- Hold MENU and RUN buttons pressed for 3 seconds. If the high level
password is not entered in the last 90 minutes, the unit will ask the password.
- Enter the password.
- The upper display will show hours remaining for SERVICE A message.
- Press again the MENU button. The hours remaining for SERVICE A will appear
flashing on the display.
- In order to reset the hours remaining for SERVICE A, hold pressed MENU button
for 3 seconds.
- The upper display will show the next service counter which is hours remaining
for SERVICE B message.
- Press again the MENU button. The hours remaining for SERVICE B will appear
flashing on the display.
- In order to reset the hours remaining for SERVICE B, hold pressed MENU button
for 3 seconds.
- By pressing the MENU button again, below counters can be scrolled and reset:
- 15 -
DEC-40 USER MANUAL V4
MESSAGE DESCRIPTION
Total motor run hours
(ON_LOAD+OFF_LOAD)
This counter increments while the motor runs.
Total load time (load contactor active)
This counter increments while LOAD led is on.
- Hold pressed together MENU , RUN and STOP buttons for 3 seconds. If
the high level password is not entered in the last 90 minutes, the unit will ask password
().
- Enter password.
- Press MENU button for 3 seconds, the display wil show SEt message and the
counter will be adjusted to the new value. If MENU button is pressed for short
duration, then the value will not be modified and the next hour counter will be displayed.
Same steps are repeated for further modification.
- 16 -
DEC-40 USER MANUAL V4
The unit supports various connection topologies. The topology is selected through
parameter P48.
Different topologies and terminal connections are as below:
P48 = 1
P48 = 3
P48 = 3
P48 = 2
The power supply and measuring terminals
of the unit are isolated. In order to enable
above topology, the unit must be specially
manufactured.
- 17 -
DEC-40 USER MANUAL V4
If the pressure stays above the P05 Start Pressure, during P26 Unload Timer then
the unit will stop the motor. If the pressure falls below P05 Start Pressure then the motor
will run again.
Before the compressor is loaded, a timer equal to P23+P24+P25+P15x3 will be
elapsed.
During this period, depending on the air consumption, the pressure may fall below
P05 Start Pressure.
In most applications, it is required that the pressure never falls below the P05 Start
Pressure limit.
In order to prevent this unwanted situation, the unit offers 3 different operating
modes selected through program parameter P45. The unit calculates dynamically the
restart pressure (Pi)
- 18 -
DEC-40 USER MANUAL V4
In order to visualize the latest alarm in the history press MENU button until
- 19 -
DEC-40 USER MANUAL V4
7. DİGİTAL INPUTS
The unit offers 4 user configurable digital inputs.
The characteristics of these inputs are configured through parameters P73 to P76.
The configuration record consists on 3 parts. The programmed value is the sum of these
3 parts.
- 20 -
DEC-40 USER MANUAL V4
8. RELAY OUTPUTS
The unit provides 5 relay outputs. All of them have selectable functions.
Relays default functions are as following (Related function parameter is set to “0”):
RL1 = MAIN CONTACTOR relay (P84=0)
RL2 = DELTA CONTACTOR relay (P85=0)
RL3 = STAR CONTACTOR relay (P86=0)
RL4 = LOAD relay (P87=0)
RL5 =ALARM Relay (P40=0)
- 21 -
DEC-40 USER MANUAL V4
9. PROGRAMMING
- The upper display will show . Enter the password using RUN and STOP
buttons and press MENU button. For fast increment/decrement, hold pressed
RUN and STOP buttons.
To Exit Programming Menu:
- Display parameter value by pressing the MENU button. Adjust the parameter with
RUN and STOP buttons and return to parameter number selection by pressing the
MENU button.
- 22 -
DEC-40 USER MANUAL V4
- 23 -
DEC-40 USER MANUAL V4
No Description Adjustment Range Factory set
0 ... (P09)
While the air end temperature is
below this limit, instead of P04
Temperature (T1) for
P14 Stop Pressure, P05+(P04-P05)/4 0 °C
Pressure Compensation
value is used.
Thus the compressor stops
before reaching Stop Pressure .
P15 Delay Between Relays 20 ... 250 200ms
P16 Voltage Unbalance Ratio 0 ...20 5%
0:Disable
1:Absolute temperature
Temp. T2 Sensor operation 2:Differential temperature
P17 0
mode If this parameter is set to 0, the
P18, P19, P20 and P22
parameters will not be displayed.
P18 Top range Temp. T2 Sensor (P19+2) ... 200 130 °C
(P20+2) ... (P18-2)
Temp. T2 Sensor High Limit
P19 (Temperature differential alarm 110 °C
(Delta Alarm Limit)
Limit)
-40 ... (P19-2)
Low Alarm/Delta Warning
P20 (Temperature differential warning -10 °C
Temp. T2
Limit)
Alarm/Warning Duration
P21 1 ... 600 10 sec
time
Offset value Temp. 2
P22 -10:+10 0 °C
Sensor
P23 Star Timer 2 ... 20 7 sec
P24 Star /Delta transition Timer 10 ... 50 35 ms
P25 Timer before loading 1 ... 120 1 sec
P26 unload timer 0 ... 10 2 min
0: Fixed
1: Variable
If set to 1:
Unload timer fixed or If the stop duration is more than
P27 0
variable the unload run duration, the
unload timer is reduced by 1
minute at each run, until an
absolute minimum of 2 minutes.
1 ... 240
P28 Safety Timer Refer to chapter 4 for this 30 sec
parameter.
- 24 -
DEC-40 USER MANUAL V4
No Description Adjustment Range Factory set
0 ... 32767
P29 Service A Period If this parameter is set to 0, then 2000 hours
no service A warning is given.
0 ... 32767
P30 Service B Period If this parameter is set to 0, then 4000 hours
no service B warning is given.
0 ... 32767
P31 Service C Period If this parameter is set to 0, then 6000 hours
no service C warning is given.
0 ... 32767
P32 Service D Period If this parameter is set to 0, then 14000 hours
no service D warning is given.
0 ... 32767
P33 Service E Period If this parameter is set to 0, then 20000 hours
no service E warning is given.
0: Disable
P34 Display Extra sensors 1
1: Enable
P35 Low level password 0 ... 999 1
P36 High level password 0 ... 999 2
P37 Maximum Starts per Hour 6 ... 240 120
0:Disable
1:Enable
P38 Low Voltage Alarm Enable If this parameter is set to 0, the 1
P39 parameter will not be
displayed.
P39 Low Voltage Alarm Value 200 ... 600 360 V-AC
P40 RL5 function selection Refer chapter 8 for details. 2
30 ... (P09-2)
P41 Fan On Temperature 85 °C
Refer chapter 8 for more details.
Delta T Fan Off 5 ... 15
P42 5 °C
Temperature Refer chapter 8 for more details.
P43 Flasher OFF period 0-999s 2
P44 Flasher ON period 0-11999 min 2
0: standard operation
Pressure loss preventing
P45 1: step increase/decrease 0
method
2: dynamic calculation
P46 Temperature Unit 0=C (Celcius) / 1=F (Fahrenheit) 0
- 25 -
DEC-40 USER MANUAL V4
No Description Adjustment Range Factory set
Slave Comp. Max.
P47 Continuous Running (Multi 0:65535 min 0
Mod)
1: 1 phase
P48 Connection topology 2: 2 phases 3
3: 3 phases
P49 Phase L1 calibration 1 ...32767 1186
P50 Phase L2 calibration 1 ... 32767 1186
P51 Phase L3 calibration 1 ... 32767 1186
0: Disable
1: Enable
Low Frequency Alarm
P52 If this parameter is set to 0, the 1
Enable
P53 parameter will not be
displayed.
P53 Low Frequency Alarm Limit 10.0 ... 60.0 Hz 48.0 Hz
0: Disable
1: Enable
High Frequency Alarm
P54 If this parameter is set to 0, the 1
Enable
P55 parameter will not be
displayed.
High Frequency Alarm
P55 60.0 ... 990.0 Hz 62.0 Hz
Value
0: Disable
P56 Frequency display 1
1: Enable
0:Disable
P57 Phase L1 voltage display 0
1:Enable
0:Disable
P58 Phase L2 voltage display 0
1:Enable
0:Disable
P59 Phase L3 voltage display 0
1:Enable
0:Disable
P60 Phase L1-L2 voltage display 1
1:Enable
0:Disable
P61 Phase L2-L3 voltage display 1
1:Enable
0:Disable
P62 Phase L3-L1 voltage display 1
1:Enable
0: Disable
P63 MODBUS enable 1
1: Enable
- 26 -
DEC-40 USER MANUAL V4
No Description Adjustment Range Factory set
0: Slave
P64 Master/Slave MODBUS 0
1: Master
1: Starts multiple controller opr.
P65 MODBUS node address 240
2 ... 254: Modbus address
Slave Start Timer (Multiple
P66 1..999 sec. 180 sec
controller operation)
Master Change Period
P67 1..999 hours 100 hours
(Multiple operation)
P68 Serial Number Low Word 0 ... 65535 10
P69 Serial Number High Word 0 ... 65535 10
0: Disable
1: Enable
P70 High Voltage Alarm Enable If this parameter is set to 0, the 1
P71 parameter will not be
displayed.
P71 High Voltage Alarm Limit 200 ... 650 V 445
0: Disable
P72 Phase Order Check Enable 1
1: Enable
0 ... 2047
P73 Input1 configuration register 18
Refer chapter 7 for more details.
0 ... 2047
P74 Input 2 configuration register 28+512=540
Refer chapter 7 for more details.
0 ... 2047
P75 Input 3configuration register 8+512=520
Refer chapter 7 for more details.
0 ... 2047
P76 Input 4configuration register 16+256+=1808
Refer chapter 7 for more details.
0: Disabled
1: Pressure switch
Pressure 2 Input 2: Analog transducer
P77 0
Configuration If this parameter is set to 0 or 1,
parameters P78 ... P82 will not be
displayed.
Top range pressure P2
P78 1,7... 99.9 Bar 15.0 bar
transducer
High Pressure Sensor P2
P79 1,2... (P78-0.5) 8.8 bar
Alarm Limit
Differential pressure alarm
P80 -10.0 ... +10.0 0.5 bar
limit (P1 – P2)
Differential pressure alarm
P81 1 ... 600 10 sec
delay
- 27 -
DEC-40 USER MANUAL V4
No Description Adjustment Range Factory set
P82 Offset pressure transducer 2 -2:+2 0 bar
P83 Low Pressure alarm limit P2 0:(P79-0.5) 0
P84 RL1 function selection Refer chapter 8 for details. 0
P85 RL2 function selection Refer chapter 8 for details. 0
P86 RL3 function selection Refer chapter 8 for details. 0
P87 RL4 function selection Refer chapter 8 for details. 0
0: Disable
P88 Service Security 0
1: Enable
Variable Hour counting 0: Fixed hour counting coefficient
P89 0
method 1: Variable hour counting method
0: Bar(g)
P90 Pressure Unit 0
1: PSI
P91 Restore Point Function 0:Nothing 1:Return 2:Save 0
Motor control PWM Signal 0:Disable / 1:Enable 0
P92
(0-10V)
Motor control PWM Signal (P03-0.2):3 7.0 Bar
P93
set Value
P94 PID control P value %0.0 : 99.9 % 3.0
P95 PID control I value %0.0 : 99.9 % 0.4
P96 PID control D value %0.0 : 99.9 % 5.0
P97 PID control I inverse value %0.0 : 99.9 % 0.4
P98 PID control enable delay 1 sec - 999 sec 10 sec
P99 PID enable temperature limit (P08-2):0 0
Max.Running Multi-comp 0:8 0
P100
Number Limit
- 28 -
DEC-40 USER MANUAL V4
10.1. DESCRIPTION
The unit offers serial data communication port allowing it to be integrated in automation
systems.
The serial port works with logic levels. With special adapters, it can be converted to RS-232
or RS-485 standards.
The MODBUS properties of the unit are:
-Data transfer mode: RTU
-Serial data: 9600 bps, 8 bit data, no parity, 1 bit stop
-Supported functions:
-Function 3 (Read multiple registers, max 120 registers)
-Function 6 (Write single register)
-Function 10 (Write multiple registers, max 32 registers)
-The answer to an incoming message is sent with a minimum of 4.3ms delay after
message reception.
Each register consists of 2 bytes (16 bits). Larger data structure contain multiple registers.
Detailed description about the MODBUS protocol is found in the document “Modicon
Modbus Protocol Reference Guide”. ( http://www.modbus.org/specs.php)
Data Reading
The function 03 (read multiple registers) will be used for data reading. The MODBUS
master will send a query. The answer will be one of the below:
-A response containing the requested data
-An exceptional response indicating a read error.
The maximum number of registers read in one message is 120. If more registers are
requested, the unit will send only the first 120 registers.
The query message specifies the starting register and quantity of registers to be read. The
message structure is below:
Byte Description Value
0 Controller address 1 to 254
1 Function code 3
2 Starting address high See below the description of available
3 Starting address low registers
4 Number of registers high always 0
5 Number of registers low max 78h (120 decimal)
6 CRC low byte See below for the checksum calculation
7 CRC high byte
Here is the sequence to read 16 registers starting from address 20h (32 decimal):
01 03 00 20 00 10 45 CC (each byte is expressed as 2 hexadecimal characters)
The checksum value in the above message may be used for the verification of checksum
calculation algorithm.
- 29 -
DEC-40 USER MANUAL V4
Data Writing
The function 06 (write single register) or function 10 (write multiple registers) is used for
data writing. A maximum of 32 registers can be written at a time.
The MODBUS master will send a query containing data to be written. The answer will be
one of the below:
-A normal response confirming successful write,
-An exceptional response indicating a write error.
Only some of the available registers are authorized to be written. An attempt to write a write
protected register will result to the exceptional response.
The query message specifies the register address and data. The message structure is
below:
Byte Description Value
0 Controller address 1 to 254
1 Function code 6
2 Register address high See below the description of available registers
3 Register address low
4 Data high byte
5 Data low byte
6 CRC low byte See below for the checksum calculation
7 CRC high byte
- 30 -
DEC-40 USER MANUAL V4
Here is the sequence to write the value 0010h to the register 40h (64 decimal):
01 06 00 40 00 10 89 D2 (each byte is expressed as 2 hexadecimal characters)
The checksum value in the above message may be used for the verification of checksum
calculation algorithm
The normal response will be the same as the query:
Byte Description Value
0 Controller address 1 to 254
1 Function code 6
2 Register address high See below the description of available registers
3 Register address low
4 Data high byte
5 Data low byte
6 CRC low byte See below for the checksum calculation
7 CRC high byte
CRC calculation
Here is a procedure for generating a CRC:
1) Load a 16–bit register with FFFF hex (all 1’s). Call this the CRC register.
2) Exclusive OR the first 8–bit byte of the message (the function code byte) with the low–
order byte of the 16–bit CRC register, putting the result in the CRC register.
3) Shift the CRC register one bit to the right (toward the LSB), zero–filling the MSB. Extract
and examine the LSB. The LSB is the least significant bit of the CRC before the shift
operation.
4) If the LSB is 1: Exclusive OR the CRC register with the polynomial value A001 hex.
5) Repeat Steps 3 and 4 until 8 shifts have been performed. Thus, a complete 8–bit byte
will be processed.
6) Repeat Steps 2 through 5 for the next 8–bit byte of the message. Continue doing this
until all bytes have been processed.
7) The final contents of the CRC register is the CRC value.
8) Place the CRC into the message such that the low byte is transmitted first. The algorithm
should give the correct CRC for below messages:
01 03 00 20 00 10 45 CC
01 06 00 40 00 10 89 D2
- 31 -
DEC-40 USER MANUAL V4
Error codes
Only 3 error codes are used:
01: illegal function code
02: illegal address
10: write protection (attempt to write a read_only register)
Data types
Each register consists of 16 bits (2 bytes)
If the data type is a byte, only the low byte will contain valid data. High byte is don’t care.
For data type longer than 16 bits, consecutive registers are used. The least significant
register comes first.
- 32 -
DEC-40 USER MANUAL V4
CONTROLLER REGISTERS
ADDR. NAME DESCRIPTION LENG. R/W TYPE MUL.
- 33 -
DEC-40 USER MANUAL V4
CONTROLLER REGISTERS
ADDR. NAME DESCRIPTION LENG. R/W TYPE MUL.
PROGRAM PARAMETERS
ADDR. NAME DESCRIPTION LENG. R/W TYPE MUL.
- 34 -
DEC-40 USER MANUAL V4
PROGRAM PARAMETERS
ADDR. NAME DESCRIPTION LENG. R/W TYPE MUL.
- 35 -
DEC-40 USER MANUAL V4
PROGRAM PARAMETERS
ADDR. NAME DESCRIPTION LENG. R/W TYPE MUL.
- 36 -
DEC-40 USER MANUAL V4
40222 P94 See chapter 9.2 16 BIT R/W unsigned word 0.1
40223 P95 See chapter 9.2 16 BIT R/W unsigned word 0.1
40224 P96 See chapter 9.2 16 BIT R/W unsigned word 0.1
40225 P97 See chapter 9.2 16 BIT R/W unsigned word 0.1
40226 P98 See chapter 9.2 16 BIT R/W unsigned word 1
40227 P99 See chapter 9.2 16 BIT R/W unsigned word 1
40228 P100 See chapter 9.2 16 BIT R/W unsigned word 1
40229
- reserved reserved registers 16 BIT R/W unsigned word 1
40256
SENSOR GRAPHS
40385
PRESS_SENSOR Pressure Sensor 1 (mA - 32*16
- R-O unsigned word 1
GRAPH [32] Bar) BIT
40416
40417 TEMPERATURE
Temperature Sensor 1(Ohm 32*16
- SENSOR GRAPH R-O signed word 1
- °C) BIT
40448 [32]
40449 MOTOR PTC
Motor PTC Temperature 32*16
- SENSOR GRAPH R-O signed word 1
Sensor(Ohm - °C) BIT
40480 [32]
40481 TEMPERATURE 2
Temperature Sensor 2 32*16
- SENSOR GRAPH R-O signed word 1
(Ohm - °C) BIT
40512 [32]
40513 PRESSURE 2
Pressure Sensor 2 Graph 32*16
- SENSOR GRAPH R-O unsigned word 1
(mA - Bar) BIT
40544 [32]
- 37 -
DEC-40 USER MANUAL V4
COMMANDS
40769 C01 Reserved register 16 BIT W-O unsigned word 1
Return to Factory (value =
40770 C02 16 BIT W-O unsigned word 1
0xAA55)
Reset Counter
40771 C03 16 BIT W-O unsigned word 1
(value = Counter(1-8)
LOCK KEY
40772 C04 16 BIT W-O unsigned word 1
(Value = KEY CODE)
40773
- Reserved - 16 BIT W-O unsigned word 1
40800
Time to service A
40801 Set service 1 16 BIT W-O unsigned word 1
(low 2 bytes)
Time to service A
40802 Set service 2 16 BIT W-O unsigned word 1
(high 2 bytes)
Time to service B
40803 Set service 3 16 BIT W-O unsigned word 1
(low 2 bytes)
Time to service B
40804 Set service 4 16 BIT W-O unsigned word 1
(high 2 bytes)
Time to service C
40805 Set service 5 16 BIT W-O unsigned word 1
(low 2 bytes)
Time to service C
40806 Set service 6 16 BIT W-O unsigned word 1
(high 2 bytes)
Time to service D
40807 Set service 7 16 BIT W-O unsigned word 1
(low 2 bytes)
Time to service D
40808 Set service 8 16 BIT W-O unsigned word 1
(high 2 bytes)
Time to service E
40809 Set service 9 16 BIT W-O unsigned word 1
(low 2 bytes)
Time to service E
40810 Set service 10 16 BIT W-O unsigned word 1
(high 2 bytes)
LOADED+UNLOADED+STOP
40811 Set service 11 16 BIT W-O unsigned word 1
time (low 2 bytes)
LOADED+UNLOADED+STOP
40812 Set service 12 16 BIT W-O unsigned word 1
time (high 2 bytes)
Engine run hours
40813 Set Service 13 16 BIT W-O unsigned word 1
(low 2 bytes)
Engine run hours
40814 Set Service 14 16 BIT W-O unsigned word 1
(high 2 bytes)
Load run hours
40815 Set Service 15 16 BIT W-O unsigned word 1
(low 2 bytes)
Load run hours
40816 Set Service 16 16 BIT W-O unsigned word 1
(high 2 bytes)
Alarm history reset
40817 C05 16 BIT W-O unsigned word 1
(Value = 0xAA55 hex)
- 38 -
DEC-40 USER MANUAL V4
The WARNING register is 16 bits. Each bit indicates the existence of a warning.
BIT DESCRIPTION
0 Remote Stop
1 Remote Start
2 Parameter out of limits
3 High Temperature warning (T1)
4 No Stop since 1 Hour
5 Start waits separator pressure drop
6 Differential temperature (T1-T2)
7 Air Filter Clogged
8 Bus Fail (Multi Control)
9 Input Waiting
10-15 -
- 39 -
DEC-40 USER MANUAL V4
The SERVICE request register is 16 bits. Each bit indicates the existence of a service
request.
BIT DESCRIPTION
0 Service A requested
1 Service B requested
2 Service C requested
3 Service D requested
4 Service E requested
5-15
Operation:
1. If the communication between units is lost, then controllers will operate
independently.
2. The controller with the least engine hours will become the master and operate
following P04-P05 parameters. Other compressors will run and stop following their
engine hours.
3. If any of the compressors has P67 Master Change Period less engine hours than
the master controller, then this one becomes the new master.
4. If an alarm occurs at the master controller, then another controller will become
master.
5. If the pressure falls below P05, the master will run immediately. Other compressors
will run with delays of P66/8.
6. If at the expiration of P66 timer, the pressure is above P05 but below (P04+P05)/2,
then compressors will run with P66/4 delays.
7. When the pressure approaches P04, compressors will stop in their respective order
of run hours.
- 40 -
DEC-40 USER MANUAL V4
The CE mark indicates that this product complies with the European requirements
for safety, health environmental and customer protection.
- 41 -