Building Services - Lecture 4
Building Services - Lecture 4
BUILDING SERVICES
CIVE 3218(5)
LECTURE NOTES 4
VENTILATION SYSTEMS
Naresh Sewdin
24 August 2013
Lecture Notes 4 Building Services
1. Scope
The scope of this section is to provide you with the basic principles for designing
mechanical ventilation systems. It is applicable for ventilation services inside dwellings,
commercial, institutional and industrial buildings.
2. Introduction
Ventilation provides fresh air for breathing, to dilute and exhaust pollutants and odours
and often to exhaust heat gains. The design of ventilation services is governed by
reference to the Building Regulations-Approved Document F, British Standards BS 5925
and CIBSE Guides B. It is also essential to comply with Local Authorities requirements
(e.g. Health and Safety Act, etc).
3. Definitions
Habitable room: Any room used for dwelling purposes and not solely a kitchen,
utility room, bathroom or sanitary accommodation.
Ventilation opening: A means of ventilation permanent or variable (open or closed)
providing access to external air e.g. door, window, louvre or PSV.
PSV: Passive stack ventilation in a system of vertical ducting from room ceilings to
roof outlets providing ventilation by stack effect.
4. Ventilation systems
1
Lecture Notes 4 Building Services
i) Natural ventilation
Natural ventilation may be defined as ventilation that relies on moving air through
a building under the natural forces of wind and buoyancy. As these motivating
influences are variable, it is almost impossible to maintain consistent flow rates
and thereby ensure that optimum ventilation is achieved at all times.
Figure 4.1
2
Lecture Notes 4 Building Services
Natural ventilation is generally inadequate if the internal heat gains rise above
40W/m2. Mechanical ventilation will then be required.
Figure 4.2
3
Lecture Notes 4 Building Services
b) Supply system
A supply system is the direct opposite of the extraction method. In a
supply system, the air is delivered by a fan to the occupied space and
allowed to exhaust through purpose made openings (outlets). With suitable
ducting systems, the supply air can be distributed throughout the building
to give uniform ventilation or to match individual air flow rates to those
areas requiring different ventilation levels.
Figure 4.3
4
Lecture Notes 4 Building Services
The basic factors that affect the choice between natural and mechanical ventilation are:
1. Quantity of air required (Ventilation flow rates)
2. Quality of air required (Heated, cooled or filtered air)
3. Consistency of control required (Constant or variable flow control)
4. Isolation required from external environment (Noise, contaminants, etc)
The purpose of duct systems is to convey air to and from spaces within buildings and
provide occupants with :
1. Ventilation air
2. Thermal comfort
3. Humidity control
4. Air filtration
5. Removal of contaminants
Ductwork systems for ventilation and air conditioning can be classified into low,
medium and high pressure systems as illustrated in the table below.
Table 4.1
Ducting is generally available in rectangular, circular or flat oval sections. Ductwork less
than 0.0225 m2 cross sectional area will be more economical if made in circular section
(around 160 mm diameter).
Rectangular ducts
1. Most common for low pressure system.
2. Can be easily adapted to fit into available space
3. Branch connections are made easily.
4. Should not be the first choice for high pressure systems.
5
Lecture Notes 4 Building Services
Circular ducts
1. Easier to install for main runs of ductworks.
2. Preferable for high pressure systems due to its high inherent stiffness.
The duct materials used for ducted ventilation systems are provided in the table below.
Table 4.2
Flexible ducts are generally used for final connections to terminal units, grilles and
diffusers. Flexible duct should be kept as short as possible because it produces about 8
times the pressure drop for an equivalent smooth galvanised steel ductwork.
6
Lecture Notes 4 Building Services
6 Principles of design
Duct sizing and pressure loss calculations are normally carried out to quantify ductwork
dimensions and to provide data for specifying the fan desired. The simple design
methods for duct sizing are as follows:
1) Velocity method
2) Constant pressure drop (or equal friction loss) method
3) Static regain method
i) Velocity method
This method is based on selection of duct velocities by the designer using limiting
noise reduction and/or pressure drop. In a typical system, the velocity at the fan
connection is chosen and this is progressive reduced in the duct run from the fan
to the terminals. This is used on simple layouts or sections of the system.
For low pressure systems, typical values used for constant pressure drop rate are
0.8 – 1.2 Pa/m with duct velocities less than 10 m/s.
7
Lecture Notes 4 Building Services
Leakage from ducted air, distribution systems is an important consideration in the design
and operation of ventilation and air conditioning systems.
Leakage from sheet metal ducts occurs at the seams and joints and is therefore
proportional to the surface area of the ductwork in the system.
The designer should make allowance in the fan selection for some air leakage so that the
completed installation can meet its intended purpose. The table below provides the
recommendation margins to be considered for design purposes.
Table 4.3
Extraction rates in general toilets > 5 ach (air changes per hour)
Selected extraction rate in the toilets = 6 ach
8
Lecture Notes 4 Building Services
The extract diffuser is selected based on the required volume extraction rate and its
corresponding lowest pressure drop. The type of the extract diffuser together with its
volume extraction rate and pressure drop are specified and annexed in the detailed
calculations.
7.4 Calculation of duct sizes and friction losses along the index path
9
Lecture Notes 4 Building Services
c) Calculation of duct size for one path along the index path
From HVAC Engineers Handbook,
Q = AV
Considering one path along the index path, the area of the duct is calculated with
known values of volume flow rate (refer to section 7.3) and known values of velocity
of the air (refer to Table 4.4).
Hence, the circular diameter (d) of the duct is calculated using the following
equation:
Circular diameter, d = √4A/π
d) Calculation of friction loss for one path along the index path
From HVAC Engineers Handbook, the rectangular duct equivalent to the nearest
circular duct is selected bearing in mind the dimension of the maximum duct
dimensions available.
The friction loss per m of duct run is determined by considering both the nearest
circular equivalent duct diameter and the velocity of air in the duct.
For flexible ducts, the pressure drop is chosen to be 8 times the pressure drop for a
rigid duct.
10
Lecture Notes 4 Building Services
11
Lecture Notes 4 Building Services
From technical specification of exhaust valve, the pressure drop of the selected extract
diffuser(s) along the index path is determined.
Pressure loss due to exhaust valve = Sum of pressure drop of selected diffuser(s) along
the index path.
From technical specifications of fans, the extractor fan is selected based on the required
volume extraction rate and its corresponding lowest pressure drop. The type of the
extract fan together with its volume extraction rate and pressure drop are specified and
annexed in the detailed calculations.
8. Sample Question
One toilet 6m wide by 5m deep and one kitchen 4m wide by 5m deep are located on each
floor of a 2 storey building. Assume the height of each room to be 3m. Determine the
duct size of the main duct and branch ducts together with the rating of the fan required to
make the ventilation system operational.
12
Lecture Notes 4 Building Services
ANNEX – 1
Figure 4.4
13
Lecture Notes 4 Building Services
ANNEX – 2
Figure 4.5
14