Chapter 23 Excitation System
Chapter 23 Excitation System
CHAPTER 23
EXCITATION SYSTEM
23.1.1 DC EXCITATION
This is the traditional method. A DC generator is mounted on the main shaft &
separately or shunt excited, the output being fed to the rotor of the main generators
through slip rings or brushgear. Commutation difficulties at high speeds have
sometimes led to geared or separately driven exciters.
ET – ‘08 227
POWER GENERATION AND EVACUATION EXCITATION SYSTEM
Self-excitation system initiated by station batteries is used for exciting the rotor
windings of Steam turbine generator (STG).
A common shaft carries the rectifier wheels, the rotor of the main exciter and the
permanent magnet rotor of the pilot exciter. The shaft is rigidly coupled to the generator
ET – ‘08 228
POWER GENERATION AND EVACUATION EXCITATION SYSTEM
rotor & supported on end bearing shield. The generator & the exciter bearings are thus
supported on a total of three bearings. Mechanical coupling of the two shaft assemblies
results in the central shaft bore through the Multikontakt electrical system consisting of
plug in bolts and sockets.
One diode is mounted each in the light metal heat sink and then connected in parallel.
Associated with each diode is a fuse that serves to switch off the diode from the circuit
if it fails.
The 3-phase connection between armature and diodes is obtained via copper conductors
arranged on the shaft circumference between the rectifier wheels and the main exciter.
The conductors are attached by means of the binding clips and equipped with the
internal diode connections. One conductor is provided for each arm of Diode Bridge.
The conductors originate at a bus ring system of the main exciter.
ET – ‘08 229
POWER GENERATION AND EVACUATION EXCITATION SYSTEM
to form damper winding. Between the two poles a Quadrature-axis coil is fitted for
inductive measurement of the field current.
The rotor consists of stacked laminations that are compressed by through bolts over
compression rings. The 3- phase winding is inserted in the laminated rotor .The
winding conductors are transposed within the core length and turns of the winding are
secured with steel bands. The connections are made on the side facing the rectifier
wheels; the winding ends are run to a bus ring system to which 3- phase leads leading
to the rectifier wheels are also connected. After full impregnation with epoxy resin and
curing , the complete rotor is shrunk onto the shaft.
Manual control of an exciter field rheostat suffices for very small machines, but
otherwise the use of automatic voltage regulators (AVR) is universal.
ET – ‘08 230
POWER GENERATION AND EVACUATION EXCITATION SYSTEM
Torque-motor Regulator –
Is a sensitive quick acting device comprising multi tapped resistors connected into the
exciter field circuit & brought out to closely spaced rows of silver contacts. Short
circuiting sectors roll over the contacts in accordance with the torque of a small split
phase disc motor against spring loading & eddy current damping. Voltage setting is
simple, & droop & compounding effects can be adjusted independently.
Vibrator Regulator –
Is the type of AVR in which the exciter field rheostat is rapidly switched in & out of
circuit to correct deviations from nominal voltage setting. A control magnet is
energized from the voltage to be regulated & its main contacts are closed by a spring. If
the voltage rises, the pull of the spring is overcome & the contacts open, inserting the
field rheostat into circuit. The resulting fall in voltage causes the contacts to re-close.
The cyclic process takes place rapidly & repeatedly, holding the voltage within the
limits prescribed.
The main parts of the regulator equipment are two closed loop control systems
including a separate gate control set and thyristor set each, field discharge circuit, an
open loop control system for exchanging signal between the regulator equipment and
the control room, and the power supply circuits.
ET – ‘08 231
POWER GENERATION AND EVACUATION EXCITATION SYSTEM
For optimum utilization of inductive & capacitive load capabilities of the generator, the
A.V.R is provided with Rotor current limiter and Rotor angle limiter. The MANUAL
control system controls the excitation current in the main exciter field winding.
Normally, the automatic voltage regulation system (AUTO) is operative, including the
start-up & shutdown of the machine. The set point adjuster of the excitation current
control (MANUAL) is possible at any time. Under certain emergency & fault
conditions, the changeover from AUTO to MANUAL mode is initiated automatically.
Correct operation of the follow-up control is monitored & can also be observed on a
matching instrument (null voltmeter) in the control room. This instrument also permits
manual matching.
23.5 LIMITERS
Under Excitation Limiter –
It ensures that, in the under-excited range the minimum excitation required for stable
parallel operation of the generator with the system is available & the under-excited
reactive power is limited accordingly. The response characteristic is formed on the
basis of the generator reactive current, active current & terminal voltage & can be
matched to generator and system data.
ET – ‘08 232
POWER GENERATION AND EVACUATION EXCITATION SYSTEM
V / Hz Limiter –
Prevents excessive magnetic flux increase and thermal stressing of the unit transformer
& of the generator. The function of the V / Hz limiter is to issue a signal to the voltage
regulator, to reduce the excitation current when a pre-set V / Hz limit value is
increased.
ET – ‘08 233
POWER GENERATION AND EVACUATION EXCITATION SYSTEM
ET – ‘08 234