0% found this document useful (0 votes)
43 views40 pages

MSR42 Safety Module: User Manual

The MSR42 Safety Module User Manual provides essential information on the installation, configuration, and operation of the equipment, emphasizing the importance of following safety instructions and applicable codes. It includes warnings about potential hazards and outlines the responsibilities of trained personnel in handling the module. Additionally, the manual contains a summary of changes, additional resources, and detailed chapters covering various aspects of the module's functionality and maintenance.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
43 views40 pages

MSR42 Safety Module: User Manual

The MSR42 Safety Module User Manual provides essential information on the installation, configuration, and operation of the equipment, emphasizing the importance of following safety instructions and applicable codes. It includes warnings about potential hazards and outlines the responsibilities of trained personnel in handling the module. Additionally, the manual contains a summary of changes, additional resources, and detailed chapters covering various aspects of the module's functionality and maintenance.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 40

MSR42 Safety Module

Bulletin Number 440R

User Manual Original Instructions


MSR42 Safety Module User Manual

Important User Information


Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize
themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.

Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to
be carried out by suitably trained personnel in accordance with applicable code of practice.

If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use
or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for
actual use based on the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software
described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is
prohibited.

Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.

ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.

IMPORTANT Identifies information that is critical for successful application and understanding of the product.

These labels may also be on or inside the equipment to provide specific precautions.

SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.

BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.

ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).

The following icon may appear in the text of this document.

Identifies information that is useful and can help to make a process easier to do or easier to understand.

2 Rockwell Automation Publication 440R-UM008B-EN-P - July 2022


Table of Contents
About This Publication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Summary of Changes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Chapter 1
Introduction General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Special Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Customer Configurations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Typical Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Application Restrictions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Chapter 2
System Configuration Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Basic Configurations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Customer Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Status Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Status Indicator Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Response Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Micro400 Safety Light Curtain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Other Safety Components Connected to GPIO Terminals. . . . . . . . 15
MSR45E Extension Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Basic Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Chapter 3
Installation Mounting Location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Cable and Wires . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Supply Voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Earth Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Micro400 Safety Light Curtain Connection . . . . . . . . . . . . . . . . . . . . . . . . 17
Start Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Manual Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Automatic Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Minimum Off Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
EDM or Start Release. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Safety Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Safety Override . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
OSSD Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Muting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Blanking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Blanking Teach-In . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Single Scan Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Test the MSR42 Safety Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Chapter 4
Maintenance Diagnostic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Rockwell Automation Publication 440R-UM008B-EN-P - July 2022 3


Table of Contents

External Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Internal Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Decommission. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Appendix A
Specifications Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Catalog Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Product Labels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Approximate Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Declaration of Conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
CE Conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
UKCA Conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

Appendix B
Accessories Additional Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Interrupt Ignore Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

4 Rockwell Automation Publication 440R-UM008B-EN-P - July 2022


Preface

About This Publication This manual covers the installation and operation of the Guardmaster® MSR42
Safety Module.

ATTENTION: MSR42 safety modules can only achieve functionality if the


instructions and additional documentation that are given in this instruction
manual are exactly followed. You must also consult the valid laws and
regulations at the time of installation. Serious injury or death can occur if you
do not follow these instructions carefully. The installer or system integrator is
fully responsible for a safe integration of this product. This instruction
manual is part of the MSR45E extension module. This instruction must be
accessible together with the other machine documentation during its entire
lifecycle for all personnel responsible for assembly, installation, operation,
and maintenance.

Summary of Changes This publication contains the following new or updated information. This list
includes substantive updates only and is not intended to reflect all changes.
Topic Page
Added UKCA Approvals to Table 2 15
Updated Figure 13 31
Updated Declaration of Conformity 32

Additional Resources These documents contain additional information concerning related products
from Rockwell Automation.
Resource Description
Light Curtains Configuration and Diagnostic Software Tool User Manual, Provides information to configure and diagnose GuardShield™ safety light curtains and
publication SAFETY-UM001 MSR42 safety module products.
Provides guidance on how to conduct security assessments, implement Rockwell
System Security Design Guidelines Reference Manual, SECURE-RM001 Automation products in a secure system, harden the control system, manage user access,
and dispose of equipment.
UL Standards Listing for Industrial Control Products, Assists original equipment manufacturers (OEMs) with construction of panels, to help
publication CMPNTS-SR002 confirm that they conform to the requirements of Underwriters Laboratories.
Industrial Components Preventive Maintenance, Enclosures, and Contact Provides a quick reference tool for Allen-Bradley industrial automation controls and
Ratings Specifications, publication IC-TD002 assemblies.
Designed to harmonize with NEMA Standards Publication No. ICS 1.1-1987 and provides
Safety Guidelines for the Application, Installation, and Maintenance of general guidelines for the application, installation, and maintenance of solid-state control in
Solid-state Control, publication SGI-1.1 the form of individual devices or packaged assemblies incorporating solid-state
components.
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, rok.auto/certifications. Provides declarations of conformity, certificates, and other certification details.

You can view or download publications at rok.auto/literature.

Rockwell Automation Publication 440R-UM008B-EN-P - July 2022 5


Preface

Notes:

6 Rockwell Automation Publication 440R-UM008B-EN-P - July 2022


Chapter 1

Introduction

General Description The MSR4x is a family of compact safety control modules. This main
controlling module allows the connection and the control of the compact
Allen-Bradley® GuardShield™ Micro400 Safety Light Curtain systems.
Depending on the configuration, other safety components can also be
connected and monitored simultaneously.
Figure 1 - MSR42 Safety Module and Safety Components

Safety Light Curtain

Extension Module

Main Safety Module

The MSR41 safety module or MSR42 safety module offer two safety PNP
outputs (OSSD). Additional MSR45E extension modules can be applied, which
require relay contact outputs.

You can attach up to three extension modules, which the base module controls.

We also offer models in special configurations, which are described in


Interrupt Ignore Time on page 36.

Special Features The characteristics of the MSR42 safety module:


• Category 4, PLe according to EN ISO 13849-1
• Type 4 according to EN 61496-1/-2
• SIL 3 according to IEC 61508
• SIL CL 3 according to EN 62061
• Short response times
• Expandable
• Up to three extension modules per main safety module
• Adjustable stop delay time
• Different safety components suitable for connection

Rockwell Automation Publication 440R-UM008B-EN-P - July 2022 7


Chapter 1 Introduction

• Blanking
• Muting
• Single scan selectable

Customer Configurations The configuration of an MSR42 safety module can adapt to the customer
requirements of an individual application with the use of the USB/optical
interface and the Allen-Bradley Guardmaster® software Configuration and
Diagnostic Tool. More information is in publication SAFETY-UM001. The
software generates a configuration control document that lists the
configurations and specifications of the controller and safety light curtain.

WARNING: The resolution and the response time can increase due to the
download of other configuration settings for the Micro400 safety light curtain
and other safety sensors that are connected to an MSR42 safety module.
Consider the relevant resolution and the maximum response time when you
evaluate the safety distance. See Response Time on page 13. All relevant data of
the actual configuration are described in the configuration control document for
that controller. Always store the document near to the control unit.

Typical Applications Typical MSR42 safety module applications are:


• Presses
• Robotic cells with automatic insertion
• Assembly lines
• Indexing tables
• Conveyor systems
• Automatic storage facilities

Application Restrictions
MSR42 safety modules are not intended for application in explosive (EX) or in
radioactive environments.

8 Rockwell Automation Publication 440R-UM008B-EN-P - July 2022


Chapter 2

System Configuration

Wiring Diagrams Basic Configurations


Figure 2…Figure 6 on page 11 show the connection possibilities for the MSR42
safety module with basic configuration. The logic of this basic version is
exemplified in the configuration control document. See Blanking Teach-In on
page 23.
Table 1 - Connection Configurations
Figure Safety Component Start Mode Start Release
Figure 2 Micro400 safety light curtain Manual No
Figure 3 on page 10 Micro400 safety light curtain Manual Yes
Figure 4 on page 10 Micro400 safety light curtain Automatic No
Figure 5 on page 11 Micro400 safety light curtain Automatic Yes

Figure 2 - Basic Configuration, Manual Start


DIN Rail

Start Receiver

Emitter

Rockwell Automation Publication 440R-UM008B-EN-P - July 2022 9


Chapter 2 System Configuration

Figure 3 - Basic Configuration, Manual Start, with Start Release


DIN Rail

Start Receiver

Emitter

Figure 4 - Basic Configuration, Automatic Start


DIN Rail

Receiver

Emitter

10 Rockwell Automation Publication 440R-UM008B-EN-P - July 2022


Chapter 2 System Configuration

Figure 5 - Basic Configuration, Automatic Start, with Start Release


DIN Rail

Receiver

Emitter

Figure 6 - With MSR45E Extension Module, Basic Configuration, Automatic Start, with Start Release

DIN Rail

Receiver

Emitter

Rockwell Automation Publication 440R-UM008B-EN-P - July 2022 11


Chapter 2 System Configuration

Customer Configurations
The configuration of an MSR42 safety module is configured via of the USB/
optical interface and the Allen-Bradley® GuardShield™ software Configuration
and Diagnostic Tool. The configuration procedure is in publication
SAFETY-UM001. Configuration details are in the specific configuration
control document for the MSR42 safety module.

The following features are selectable:


• Stop delay
• Single scan for faster response times
• Configuring GPIO terminals for one or two safety inputs
• Configuring GPIO terminals for E-stop or door switch
• Safety override
• Muting
• Blanking

Authorized personnel must use the USB/optical interface (catalog number


445L-AF6150) to download a new configuration to the MSR42 safety module.

WARNING: If authorized personnel reconfigure the safety module with the USB/
optical interface, the response time or the stop delay time t(delay) can increase,
depending on the configuration. Execute the following steps for every new
configuration.
1. Place the configuration change label (see Figure 14 on page 31) on the control
module.
2. Confirm that the new response time is within the limits that are given by the
risk analysis of the machine.
3. All relevant data of the actual configuration are described in the
configuration control document for that controller. Always store the
document near to the control unit.
4. The use of the Blanking mode reduces the resolution of the Micro400 safety
light curtain. Label the Micro400 safety light curtain with the new resolution.
A label is supplied with the Micro400 safety light curtain mounting kit.

Status Outputs The MSR42 safety module has two status outputs (Info1 and Info2). The logic
of these two outputs depends on the configuration. A description of these
outputs is given in the configuration control document.

Table 2 shows the logic of the two status outputs for the basic configuration.
Status indicators, which are visible on the front side of the main module, show
the state of the status outputs.
Table 2 - Status Outputs
Terminal (Status Indicator) Output High (+24V) Output Low (0V)
Info1 Green: Start OK Red: No start possible
Info2 Green: System OK Red: Error (lock out)

ATTENTION: These outputs cannot perform any safety relevant functions.


They serve only to communicate the status to a machine controller.

12 Rockwell Automation Publication 440R-UM008B-EN-P - July 2022


Chapter 2 System Configuration

Status Indicator Display Table 3 shows information about the status indicator on the front side of an
MSR42 safety module with basic configuration.
Elements
Table 3 - Status Indicator Description
Description Description
Status Indicator
Signal Color Status Signal Color Status
Muting or blanking Muting or blanking
Lamp - Orange - Off
activated not activated
GPIO4 +24V Green Automatic start 0V Off Manual start
Manual start signal high
GPIO3 +24V Green 0V Off Manual start
or automatic start
Teach-in blanking
GPIO2 +24V Green Teach-in blanking active 0V Off inactive
Teach-in blanking
GPIO1 +24V Green Teach-in blanking active 0V Off inactive
Safety light curtain
Safety light curtain not
OSSD2 +24V Green 0V Red activated
activated (interrupted)
Safety light curtain
Safety light curtain not
OSSD1 +24V Green 0V Red activated
activated (interrupted)
Info2 See Table 2 on page 12 See Table 2 on page 12
Info1 See Table 2 on page 12 See Table 2 on page 12
No start release
IN2 +24V Green Start release OK 0V Red signal
IN1 +24V Green No test 0V Red Test
0V - -
No power
+24V +24V Green Power connected 0V Off connected

Response Time General


The response time of an MSR42 safety module depends on the configuration.

Use the following formulas to calculate the relevant maximum response times
for the MSR42 safety module, concerning a specific Micro400 safety light
curtain, MSR45E extension module, and a specific safety component.

The response time can increase if a stop delay time t(delay) is configured for a
safety component or a Micro400 safety light curtain. During this delay, all start
impulses are ignored. The safety outputs switch off at the end of this delay
period.

The safety module ships with the double scan filter. You can select the single
scan filter to reduce the response time. The relevant times are in the
corresponding configuration control document (see the configuration
software manual).

Rockwell Automation Publication 440R-UM008B-EN-P - July 2022 13


Chapter 2 System Configuration

Table 4 - Response Time Calculation Terminology


Symbol Description
Response time for the MSR42 safety module (evaluation time), without safety light curtain
t(C) evaluation time
t(LC) Response time of the safety light curtain (on its label)
t(delay) Stop delay time for the outputs
t(em) Response time for the MSR45E extension module
t(GPIO) Evaluation time for the safety component (GPIO filter time)
t(SCext) Response time of the external safety component (Safe4)
t(totLCOSSD) Max OSSD response time triggered by the safety light curtain
t(totLCEXT) Max relay extension module response time for the safety light curtain
t(totSCOSSD) Maximum OSSD response time for the safety components on GPIO
t(totSCEXT) Maximum relay extension module response time for the safety components on GPIO

Micro400 Safety Light Curtain


The safety light curtain response time t(LC) is a part of the response time for
the OSSD outputs. The label of the Micro400 safety light curtain shows the
worst case response time, which occurs when the MSR42 safety module runs
the active double scan filter (default). Single scan yields a faster response time,
but makes the safety light curtain more vulnerable to ambient light. The safety
light curtain response time t(LC) with the double scan filter is in the Micro400
safety light curtain manual, and with/without the double scan filter in the
configuration control document (see the configuration software manual). The
configuration control document is generated by the MSR42 safety module
software Configuration and Diagnostic Tool (see publication SAFETY-UM001).
You must enter the safety light curtain resolution and protective field height.

The response time for the MSR42 safety module (OSSD safety outputs)
concerning the Micro400 safety light curtain t(totLCOSSD) is the sum of the
controller response time t(C), the response time of the safety light curtain
t(LC), and the stop delay time t(delay) (if a delay is configured and selected for
the Micro400 safety light curtain).

Output OSSD

t(totLCOSSD) = t(C) + t(LC) + t(delay)

Output Relay Extension Module

The response time for the MSR45E extension module (relay safety output)
concerning the Micro400 safety light curtain is the sum of the OSSD response
time and the response time of the extension module.
t(totLCEXT) = t(totLCOSSD) + t(em)

14 Rockwell Automation Publication 440R-UM008B-EN-P - July 2022


Chapter 2 System Configuration

Other Safety Components Connected to GPIO Terminals


The response time of the MSR42 safety module OSSD safety outputs
concerning the safety components that are connected to the GPIO terminals is
the sum of the controller response time, the response time of the Micro400
safety light curtain, the safety component evaluation time, the response time
of the external connected safety components, and the stop delay time (if delay
is configured and selected for the safety components).

t(totSCOSSD) = t(C) + t(LC) + t(GPIO) + t(SCext) + t(delay)

MSR45E Extension Module


The response time for the MSR45E extension module (safety relay output)
concerning the safety components that are connected on the GPIO terminals
t(totSCEXT) is the sum of the main module response time t(totSCOSSD) and
the response time of the extension module t(em).

t(totSCEXT) = t(totSCOSSD) + t(em)

Basic Configuration
The maximum controller response time t(C) for the MSR42 safety module is
given in Response Time on page 13. However, depending on the connected
Micro400 safety light curtain, the response time can be shorter. The exact
value is in the configuration control document that is created with the
Configuration and Diagnostic Tool software (see publication SAFETY-UM001).

IMPORTANT The response can increase when authorized personnel use the USB/
optical interface (catalog number 445L-AF6150) to reconfigure the
controller, depending on the configuration. After every new
configuration, proceed according to Customer Configurations on
page 12.

Rockwell Automation Publication 440R-UM008B-EN-P - July 2022 15


Chapter 2 System Configuration

Notes:

16 Rockwell Automation Publication 440R-UM008B-EN-P - July 2022


Chapter 3

Installation

For professional installation and connection, consult the relevant laws and
regulations, the safety officer of the manufacturing facilities, and the local
authorities (OSHA in USA, HSE in Great Britain) or the respective industry
associations are available for any safety-related queries.

Consider the requirements of the safety regulations of electrical engineering,


the liability insurance association of the local employer, and the international
standard IEC 60204. This chapter describes the installation of all possible
safety components that can generally connect to an MSR42 safety module. The
corresponding configuration control document for the MSR42 safety module
informs which safety component must connect to deliver faultless
functionality.

Mounting Location Mount MSR42 safety modules in a control cabinet that is sealed to at least IP54.
Snap the units onto a grounded 35 mm (1.38 in.) mounting rail. If you use the
unit outside of a control cabinet, we recommend you use a housing with a
protection category of IP54 and a mounting rail.

Cable and Wires Securely separate the wires from the MSR42 safety module and guide the wires
away from the wires of the relay section (MSR45E extension modules).

Supply Voltage To safeguard the controller, protect the +24V terminal with an external 5 A
fuse. The controller and the machine must be offline before you begin the
installation.
The supply voltage must conform to the requirements of EN 60204-1 and must
bridge a 20 ms interruption of the supply network. The supply voltage must be
one of the following, in accordance with IEC 364-4-41:
• SELV (safety extra low voltage)
• PELV (protective extra low voltage)

Earth Connection The earth of each MSR42 safety module connects to the mounting rail.
Confirm that the mounting rail has a good earth connection.

Micro400 Safety Light The two RJ45 sockets on the lower portion of the safety module are for the
connection of an Allen-Bradley® GuardShield™ Micro400 safety light curtain
Curtain Connection (white = E = emitter; blue = R = receiver). To protect the RJ45 connectors, snap
the cables into the provided cable holders at the MSR42safety relay housing.

Rockwell Automation Publication 440R-UM008B-EN-P - July 2022 17


Chapter 3 Installation

Start Mode The MSR42 safety module can be configured to have the following start modes:
• Automatic start
• Manual start

With basic configuration, you can configure the start mode without the
configuration software. Automatic reset enables when you connect +24V to
GPI03 and GPI04 (see Wiring Diagrams on page 9).

Manual Start
When all inputs of the safety system have a safe signal, pressing the Start
button causes the two safety OSSD outputs to change from low to high and, if
the MSR45E extension module is connected, the modules close.
If multiple safety components are configured, then all components must have
safe signals to all inputs before a start is allowed. The Start button is monitored
to help prevent an unintentional start. Pulse length must be 50 ms…5 s. If the
start impulse is longer or shorter, the device ignores the start input. The
configuration control document identifies which terminal the Start button
connects to. If the Start button connects to IN1or IN2, a red status indicator
shows that a start signal is present, a green status indicator shows that no
signal is present.
Table 5 - Status Indicator Description
Description Description
Status Indicator
Color Status Color Status
IN 1 or IN 2 Green No start signal present Red Start signal present (button pressed)

ATTENTION: Mount the Start button so the dangerous area is clearly visible.
That is, confirm that when you press the Start button, no one is detained
within the dangerous area.

Automatic Start
If the MSR42 safety module is configured for automatic start, after the
activation and the deactivation of the safety component, the two OSSD
outputs change automatically from low to high again. Also, if connected, the
MSR45E extension module contacts automatically reclose.

ATTENTION: According to EN 60204 article 9.2.4.4.2, a system cannot


automatically restart, even after the cause of the shutdown is eliminated.
Therefore, another danger can still exist to the operator. If the MSR42 safety
module is configured with an automatic start, take further measures to fulfill
this requirement.

Minimum Off Time According to the standard IEC 61496-2, a safety light curtain must have a
minimum safety output off time of 80 ms. This specification means that even
if a short safety light curtain interruption occurs, the safety outputs stay low
(relays are open) for a minimum of 80 ms. A start signal is only recognized
after the 80 ms duration.

18 Rockwell Automation Publication 440R-UM008B-EN-P - July 2022


Chapter 3 Installation

EDM or Start Release If an MSR42 safety module is used with external relays or contactors, the
contacts of that device must be monitored. An example category 4 application
has two external contactors, each with force guided contacts that must be
inserted. For monitoring the function of these contactors, each relay block
must have at least one NC contact that is fed back in series to IN2 (or IN1
depending on configuration) of the MSR42 safety module (see Figure 3 on
page 10).

Two monitoring options are possible:


1. Start release: The signal at the corresponding input terminal must be
high before the Start button is pressed. This option means the NC
contacts of the external relays must close before allowing a start. The
optional start release is pre-configured in the MSR42 safety module
(catalog number 440R-P226AGS-NNR) (see Figure 3 on page 10).
2. EDM (external device monitoring): The input signal of the EDM terminal
is always monitored. This option means that the signal must be correct,
not only at the beginning before a start. A signal change must also
happen after startup, otherwise an emergency stop occurs. If a high
signal is present for longer than 5 seconds, a lockout occurs.

If the configuration control document shows that EDM or start release must
attach to terminal IN 1 or IN 2, then the meaning of the respective status
indicator is shown in Table 6.
Table 6 - Status Indicator Description
Description Description
Status Indicator
Color Status Color Status
EDM at IN 1 or IN 2 Green EDM signal okay Red EDM signal wrong
Start release at Green Start release signal okay Red Start release signal wrong
IN 1 or IN 2

The start release or EDM input is not cross fault monitored and therefore not a
safety input.

IMPORTANT • In cases where you install the MSR42 safety module without extension
modules, always use the external device monitoring (EDM) or start
release, unless the PNP outputs connect with another safety module or
a safety PLC.
• Use start release or EDM to switch external power contactors within the
safety circuit. Such contactors often deal with large inductive loads,
which during the switching-off phase can create large potential peaks.
For this reason, we highly recommend surge suppressors. Surge
suppressors must connect parallel to the external contactors (see
Figure 2 on page 9). Do not connect surge suppressors parallel to the
contacts of a MSR45E extension module.

Surge suppressors can drastically increase the off-delay time of the contactors.
For this reason, do not use diodes as surge suppressors.
Table 7 - Recommended Surge Suppressors
Supply voltage [V] Resistor R [Ω] Condenser C [µF]
24 100 2.2
115...230 220 0.2

Rockwell Automation Publication 440R-UM008B-EN-P - July 2022 19


Chapter 3 Installation

Safety Components The connected safety components (for example, safety switches, position
switch, E-stop buttons, cable pull safety switches) must satisfy the
requirements of the safety analysis and the relevant standards for application
within safety areas:
• E-stop button: EN 418
• Safety switch: EN 60947-5-1
• Safety light curtains: EN 61496-1/-2

The components must contain two force-guided, normally closed NC contacts


(see Figure 7) that are approved for the relevant safety level or category.
As a basic rule to increase reliability, we recommend that you use safety
components with integrated gold contacts. Safety components, can be
connected to GPIO1 through GPIO4, as shown in Figure 7. The inputs are
short-circuit and cross fault monitored.
Figure 7 - E-stop Connection

In general, the two circuits of dual-channel safety components are cross fault
monitored. A short of these two circuits would lead to an emergency stop of the
MSR42 safety module. The two circuits are also time-monitored, meaning if,
for example, one circuit of an emergency stop changes, the second circuit must
follow within 5 seconds. If the second circuit does not follow in the allotted
time, the MSR42 safety module interprets this action as a fault and the
controller switches off the safety circuit.

Depending on the configuration and the application, there can be more


terminals than the components need. The unused ports can be bridged. We
recommend shielded cables for bridging to reduce the input of EMC.
Table 8 - Status Indicator Description

Status Description Description


Indicator Color Status Color Status
GPIO3 Green Contact GPIO1/GPIO3 closed Off Contact GPIO1/GPIO3 open
GPIO4 Green Contact GPIO2/GPIO4 closed Off Contact GPIO2/GPIO4 open

Safety Override Figure 8 on page 21 shows a safety override keyswitch and a safety override
lamp. With the safety override keyswitch, you can override the safety function
of the Micro400 safety light curtain. This action means that if the override
keyswitch is activated, the safety outputs stay high even if, for example, the
protective field is interrupted.

20 Rockwell Automation Publication 440R-UM008B-EN-P - July 2022


Chapter 3 Installation

Figure 8 - Safety Override Keyswitch and Associated Lamp Connection

Depending on the risk evaluation, when you use a safety override key-operated
keyswitch, you must also connect a corresponding indicator lamp. The
connection for this safety override lamp is configured to be current-controlled
(see Technical Specifications on page 29). This configuration means that the
current (I) of the individual lamp must remain between Imin < I < Imax. If the
monitored current is not within these limits, the safety light curtain is not
overridden although the safety override keyswitch is active.

The safety override lamp that is used must fulfill the requirements of EN 61496
and must mount close to the protective field and be clearly visible to the
machine operator. Safety override only takes place when both circuits close.
Likewise, safety override only takes place when both circuits open before
becoming closed. A cross fault is detected and stops the safety override
function from activating. After one of the circuits opens, the amount of time
until the safety function of a safety component activates again is the maximum
response time of the MSR42 safety module.

If an application does not require a safety override lamp (only allowed after a
safety evaluation corresponding to EN 12100), you can deactivate the
monitoring of the lamp in the configuration.

The lamp still indicates the override function, but is no longer monitored.
Instead of a safety override keyswitch, an enabling switch or two independent,
safety position sensors can be used, depending on the application and the risk
assessment.
Table 9 - Status Indicator Description

Status Description Description


Indicator Color Status Color Status
None
GPIO3 Green Contact GPIO1/GPIO3 closed Contact GPIO1/GPIO3 open
flashing
None
GPIO4 Green Contact GPIO2/GPIO4 closed Contact GPIO2/GPIO4 open
flashing
Lamp Off Safety override circuits opened Orange Safety override circuits closed

IMPORTANT • The use of the safety override function is only allowed in applications
for which the risk analysis (EN ISO 12100-1 and EN14121) permits for the
override of a safety component. Generally, E-stop buttons can never be
overridden. Store the safety override key for this switch securely so that
only authorized personnel have access to this key.
• The function safety override cannot be understood as the function
muting, which is specified as the temporary automatic suspension of a
safety function in the standard IEC 61496-1 A.7 or IEC 62046. You must
fulfill additional requirements (not described in this publication) to
realize the muting function.

Rockwell Automation Publication 440R-UM008B-EN-P - July 2022 21


Chapter 3 Installation

OSSD Connections The overall response time of a system is the sum of the response time of the
OSSD outputs of the connected safety component (for example, safety light
curtains or laser scanners), the response time of the MSR42 safety module,
and, if used, the MSR45E extension modules (see the configuration control
document).

Figure 9 - Connection of Up to Two OSSD Safety Components (a)

IMPORTANT SensaGuard™ safety switch OSSD outputs cannot be connected to the


GPIO1…GPIO4.

Muting Muting is the temporary automatic suspension of a safety function. Use the
USB/optical interface and the Configuration and Diagnostic Software to
configure different types of muting. There are several muting option settings
for safety light curtain systems. Details about the different types of muting
and their characteristics are in the software MSR42 safety module software
Configuration and Diagnostic Tool (see publication SAFETY-UM001), and the
configured muting parameters are listed in the corresponding configuration
control document.

Blanking Blanking is typically used to allow a material to pass through the safety light
curtain during normal operation without causing a fault or stop condition.
This material can include a sheet of metal passing through the safety light
curtain before an operation is performed to form the material. The safety light
curtain permits the material at a specific thickness, but nothing more without
causing the safety outputs to turn off.

The MSR42 safety module supports teach-in fixed blanking via the basic
configuration. There are two types of blanking available through the MSR42
safety module:
• Fixed blanking
• Floating blanking

A display or a lamp indicates when blanking is active. The MSR42 safety


module has only one monitored output available for muting or blanking lamps.
Therefore, muting and blanking cannot be configured simultaneously.

IMPORTANT After configuring one of the blanking functions, the safety light curtain
resolution can change. Therefore, you must attach an updated label to
the safety light curtain that notes the changed resolution.

(a) For example, GuardShield Safe4 safety light curtain systems.

22 Rockwell Automation Publication 440R-UM008B-EN-P - July 2022


Chapter 3 Installation

On cascaded safety light curtains, check especially for the beams in the area of
the end of the protective fields. If faulty settings are present, the blanking
range can be unintentionally on the wrong stick.
Fixed blanking with monitoring requires the material to be present always to
help prevent a fault condition. In many applications, the material can shift
slightly during normal operation. This shift can cause blockage of one
additional beam. Since this blockage can occur during normal operation, the
MSR42 safety module is configured to permit one additional beam to be
blocked without causing a fault (beam tolerance: -1 beam). As a result of adding
one more beam to the configured blanked area, the resolution of the safety
light curtain increases. Table 10 shows the new resolution.
Table 10 - One-beam Tolerance Safety Light Curtain Resolutions
Resolution Standard [mm (in.)] Blanking Area [mm (in.)]
Finger 14 (0.55) 24 (0.94)
Hand 30 (1.18) 55 (2.17)

If you adjoin two blanking areas with fixed or floating blanking with
monitoring, the resolution in this area increases for two beams in the standard
adjoining blanking area.
Table 11 - Two-beam Tolerance Safety Light Curtain Resolutions
Resolution Standard [mm (in.)] Blanking Area [mm (in.)]
Finger 14 (0.55) 34 (1.34)
Hand 30 (1.18) 80 (3.15)

Activate blanking by:


• Downloading a customer configuration
• Using the teach-in blanking function

For additional information on blanking configuration, see the description of


the software Configuration and Diagnostic Tool (see publication
SAFETY-UM001).

Blanking Teach-In Blanking teach-in is a function that allows the ability to set one or two fixed
blanking areas without the use of the configuration tool or configuration
software. You must connect a keyswitch to a pair of GPIO-inputs according to
Figure 10. The keyswitch must have two channels to select this mode.
Figure 10 - Keyswitch with Two Activation Channels

Rockwell Automation Publication 440R-UM008B-EN-P - July 2022 23


Chapter 3 Installation

When the two channels are closed, the Teach-in Blanking mode is active and
the lamp blinks. The safety outputs turn off and the interrupted beams are
stored as the fixed blanking areas. We recommend teaching the MSR42 safety
module blanking areas in the application to verify that the proper beams are
blanked. You can configure up to two different fixed blanking zones via the
external teach-in selector switch.

IMPORTANT Only an authorized person can access the key to do a teach-in. If the
configuration allows for a teach-in of fixed blanking, the following
process takes place:
1. One or more blanked objects must be in the safety light curtain during
the whole teach-in process.
2. The authorized person must set the keyswitch.
3. The teach-in process starts. The teach-in function is shown when the
connected lamp blinks. If the teach-in function finishes and stored in
the MSR42 safety module, the lamp is on. Otherwise the lamp is off and
the configuration is unchanged.
4. If the teach-in blanking function is finishes successfully, the
authorized person must reset the keyswitch so the contacts open and
no longer connect to 24V DC.

Single Scan Filter By default the MSR42 safety module is operating in a Double Scan mode. This
mode is robust against electrical or optical disturbances. The controller scans
the safety light curtain optical elements two times to evaluate the state of the
safety light curtain.

Activate the single scan filter by deselecting the Double Scan mode in the
Micro400 safety light curtain window of the MSR42 safety module
Configuration and Diagnostic Tool software (see publication SAFETY-UM001).

WARNING: Double Scan mode causes a longer response time than Single Scan
mode. Consider the relevant maximum response time when you evaluate the
safety distance.

Test the MSR42 Safety


Module IMPORTANT The MSR42 safety module complies with safety Category 4, PLe Per EN
ISO 13849-1. Test the execution of the security function at regular
intervals via higher-level controllers. The frequency of this check is
based on the results of threat and risk analysis of the machine (EN ISO
12100-1 and EN14121). Furthermore, the MSR42 safety module is certified
according to SIL 3 of IEC 61508. Normally the test input at the main
module is connected to +24V. If an external test is desired according to
the risk analysis, a contact can connect to IN 1. For operation in a Self-
test mode, both OSSD outputs must connect separately to the safety
circuit of the machine.

Figure 11 connections can be used for test inputs.


Figure 11 - Test Input Connection Possibilities

24 Rockwell Automation Publication 440R-UM008B-EN-P - July 2022


Chapter 3 Installation

Table 12 shows the timing of test inputs.


Table 12 - Timing During Testing
Test Time Value [ms]
Response time to test signal t1 ≤ tR
Time to test t2 ≤ t1
Restart time after test t3 ≥ tR

Figure 12 - Test Timing Diagram (a)


Short Circuited

Open
Test Input

OSSD 1 / OSSD 2
T1
T3
T2

tR means the max response time of the total system (see Response Time on
page 13). The machine controller checks the output of the OSSD during such a
test. If the machine controller detects an error, the machine controller does not
allow the machine to restart and stops the machine immediately.

In a test failure, the status output Info2 provides a failure signal.


Table 13 - Status Indicator Description

Status Description Description


Indicator Color Status Color Status
IN 1 or IN 2 Green External test signal high Red External test signal low (test running)

(a) See the configuration control document for the minimum off time.

Rockwell Automation Publication 440R-UM008B-EN-P - July 2022 25


Chapter 3 Installation

Notes:

26 Rockwell Automation Publication 440R-UM008B-EN-P - July 2022


Chapter 4

Maintenance

Diagnostic The following indicate a fault condition:


1. The red status indicators of a connected GuardShield™ Micro400 safety
light curtain blink
2. The blue OptiLink status indicator (on the side of an MSR42 safety
module) is off
3. One of the info outputs (if configured)

In this situation, both safety outputs are low and the relays of the extension
modules are open, and the controller unit is now in the Lockout mode.

Two options exist to leave the Lockout mode:


• Power up. If the fault is still present, the controller shows the Lockout
mode.
• A start impulse longer than 10 s acts like a power-up.

You can obtain more detailed lockout information with the USB/optical
interface (catalog number 445L-AF6150) and the software Configuration and
Diagnostic Tool (see publication SAFETY-UM001).

External Faults The following external faults apply to the out-of-box configurations only.
Table 14 - External Faults
Fault No. Fault profile Fault Description Measures and Instructions
No Power Connection to +24V Check power connections and
1 No power status indicator DC OV power supply
Safety light curtain Rx/Tx are Reverse Rx/Tx connections and
swapped retry
Replace the extension cable on
Safety light curtain status Open/missing safety light
2 the safety light curtain that
indicators flash red curtain cable does not flash
Anomaly in the safety light Replace the safety light curtain
curtain
Missing reset switch for manual Add rest switch with N.O.
reset contact
Missing 24V DC to GPIO3 and Add 24V DC jumper to GPIO3 and
OSSD1 and OSSD2 status GPIO4 for automate reset GPIO4
3 indicators are red No relay
outputs Add 24V DC jumper to IN1 and
Missing 24V DC to IN1 and IN2 IN2
No start release signal from Check wiring and function of
external contactors external contacts

You can obtain programmed configuration diagnostics with the USB/optical


interface (catalog number 445l-AF6150) and the software Configuration and
Diagnostic Tool (see publication SAFETY-UM001).

Rockwell Automation Publication 440R-UM008B-EN-P - July 2022 27


Chapter 4 Maintenance

Internal Faults The following internal faults apply to the out-of-box configurations only.
Table 15 - Internal Faults
Fault No. Fault profile Fault Description Measures and Instructions
Power supply is ok but MSR42 Replace the MSR42 safety
1 No power status indicator safety module does not power module and retry
up
All input and reset status
indicators are ok. No external
Relay is in Lockout mode Will Replace the MSR42 safety
2 faults were detected. Relay
not initialize module and retry
locks upon power-up and will
not release

The Lockout mode of an MSR42 safety module can reset by one of two
methods:
1. Power down, then power up. If the fault is still present, the module
enters lockout.
2. A start signal longer than 10 seconds acts like a power-up.

Further diagnosis possibilities are possible with the software Configuration


and Diagnostic Tool in combination with the USB/optical interface (see
publication SAFETY-UM001). If the MSR42 safety module has a lockout, the
exact fault description can be determined with these tools. An exact
description is available at any time after a lockout, as long as the MSR42 safety
module is still in the lockout condition.

Service MSR42 safety modules are built electronically and do not need preventive
maintenance.

Inspection Qualified and trained personnel must periodically test the MSR42 safety
module, in accordance with valid regulations, to discover prohibited
manipulations or unauthorized modifications.

Decommission Only remove the MSR42 safety module when the machine or the equipment is
shut down completely and can no longer operate without tools. Dismantle a
controller if disposal is necessary. The separated materials can be recycled
according to state-of-the-art technology and the corresponding regulations of
the country where the unit is used.

28 Rockwell Automation Publication 440R-UM008B-EN-P - July 2022


Appendix A

Specifications

Technical Specifications
Table 16 - Technical Specifications
Attribute Value
6.0 E-9 1/h: MSR42 safety module, MSR45E extension module, and Micro400
safety light curtain
Average frequency of a dangerous failure per 9.0 E-10 1/h: MSR42 and MSR41 safety module
hour PFH
3.0 E-10 1/h: MSR45E extension module
4.0 E-9 1/h: Micro400 safety light curtain
Performance Level PL PLe, Cat. 4 (EN ISO 13849-1)
Safety Integrity Level SIL CL 3 (IEC 61508/IEC 62061)
CE Marked for all applicable EU directives, UKCA marked for all applicable
Approvals regulations, cULus Listed, TÜV Certified
rok.auto/certifications
General
Nominal working mode Continuous process
• Operating: 0…55 °C (32…131 °F)
Temperature • Environmental: 0…55 °C (32…131 °F)
• Storage: -25…+70 °C (-13…+158 °F)
• Housing: IP20
Enclosure rating (EN 60529)
• Terminals: IP20
4-pin, terminal strip (plug-in)
Conductor connection, max
Wire cross section: 1 x 2.5 mm2 (14 AWG) stranded, spring clamping technology
• Standard: 35mm (1.38 in.) DIN Rail
Mounting
• Quick mount: 35 mm (1.38 in.) top hat rail (EN 50022) 6
Weight 130 g (0.29 lb)

Housing dimensions 111 mm x 22.5 mm x 125 mm (4.37 in. x 0.89 in. x 4.92 in.) (including plugs), see
Approximate Dimensions on page 32
Enclosure protection rating IP20
Housing material Polyamide
• Amplitude: 0.35 mm (0.1 in.)
Vibration (EN60068-2-6) • Frequency: 10…55 Hz
• Acceleration: 100 ms-2
Shock resistant (EN 60068-2-29) • Impulse length: 16 ms
• Number of shocks: 1000 per direction
Interfaces Optical (OptiLink)
Shipping
Packaging 280 mm x 200 mm x 70 mm (11.02 in. x 7.87 in. x 2.76 in.)
Shipping weight Net + 220 g (8.66 in.)
Inputs
Safety inputs (software configurable) 1 x 2 NC or 2x 2 OSSD, and 1 Micro400 safety light curtain

Power supply (UN) +24V DC (EN 60204-1), see Supply Voltage on page 13
at 5% residual ripple 0.85…1.15 UN

Current consumption Current max 70 mA + 70 mA per relay extension module (semi conductor
outputs unloaded) maximal: 1.7 A depending on attached load
Max power consumption at max supply voltage 2.1 W (semiconductor outputs unloaded)
Controller protection (external) 5 A slow
Control current into IN 1, IN 2 2 mA each (min) (in accordance with EN 61131-2)
Minimum voltage at IN 1, IN 2 11V DC at activated controller (EN 61131-2)
Min: 50 ms
Start pulse duration Max: 5 s (see Safety Components on page 20)

Rockwell Automation Publication 440R-UM008B-EN-P - July 2022 29


Appendix A Specifications

Table 16 - Technical Specifications (Continued)


Attribute Value
Test pulse duration, min Response time x 2
Control current Into GPIO1…GPIO4: 7 mA each at UN (coded)
Safety override lamp, min 0.9 A (at lamp, switched on)
Reset mode Automatic /manual or manual monitored
Cable length, max Safety switches: 50 m (164.04 ft) out and back [total 100 m (328.08 ft)]
Outputs
• GPIO1…GPIO4 (to safety components): UN – 2V (coded) (short circuit
protected)
Voltage • Info 1, Info 2 status outputs (PNP): UN – 2V
• 2 x OSSD semi conductor outputs (PNP): UN – 2V
• GPIO1…GPIO4 (to safety components): 100 mA (short-circuit protected)
Current, max • Info 1, Info 2 Status Outputs (PNP): 100 mA (short-circuit protected)
• 2 x OSSD semi conductor outputs (PNP): 400 mA short-circuit protected and
with cross fault detection
• GPIO1…GPIO4 (to safety components): IMAX Off = 0.5 mA (CLOAD = 100 µF)
Leakage current • Info 1, Info 2 Status Outputs (PNP): IMAX Off = 0.5 mA (CLOAD = 4.7 µF)
• OSSD semi conductor outputs (PNP): IMAX Off = 0.1 mA (CLOAD = 3.3 µF)
2 x OSSD semi conductor outputs (PNP)
Response time, max • t(C) with UN protective mode (see Supply Voltage on page 13): ≤ 15 ms
• t(GPIO) with UN protective mode (see Supply Voltage on page 13): ≤ 130 ms
Minimal off time 2 x OSSD semi conductor outputs (PNP): 82 ms

Catalog Numbers
Table 17 - Catalog Numbers

Cat. No. (1) Description

MSR41 On/Off Safety Module


440R-P221AGS • Mounting: 35 mm (1.34 in.) DIN Rail
• Size: 22.5 mm (0.98 in.)

440R-P226AGS-NNR MSR42 Start/Restart Safety Relay


• Mounting: 35 mm (1.34 in.) DIN Rail
(2) • Size: 22.5 mm (0.98 in.)
445L-104794-Bxxx

440-P4NANS MSR45E Safety Relay Extension Module (optional)


• Input voltage: Supplied by MSR41 or MSR42 safety module
• Reset: Determined by MSR41 or MSR42 safety module
445L-1xxxx (2) • Outputs: Two N.O.

(1) All series.


(2) x = Customer configurable options that do not impact the standards or directives cited in Declaration of Conformity on
page 32.

30 Rockwell Automation Publication 440R-UM008B-EN-P - July 2022


Appendix A Specifications

Product Labels The necessary safety information is on the product label, which is on every
MSR42 safety module.
Figure 13 - Example Product Label

Table 18 - Product Label Explanation


Symbol Description
HW Hardware version
Safety Level Cat. Safety category according to EN ISO 13849-1
Safety Level SIL Safety integrity level according to EN 61508
Safety Level PLe Performance level according to EN ISO 13849-1
Power class Power supply
Temperature range Operating temperature range
OSSD Maximum current available per OSSD output, at the listed voltage

All configuration information is on the configuration control document, which


is included with the delivery of each MSR42 safety module.

If authorized personnel uses the USB/optical interface to reconfigure an


MSR42 safety module, fill out a new configuration control label and apply it
next to the existing label (see Figure 14 on page 31). Details of the new
configuration are in the configuration control document. Position the new
special configuration identification next to the existing label.
Figure 14 - Configuration Changed Label

Rockwell Automation Publication 440R-UM008B-EN-P - July 2022 31


Appendix A Specifications

Approximate Dimensions Figure 15 - MSR42 Safety Module and Extension Modules [mm (in.)]

111
(4.37) 95
(3.74)

110
(4.33)

125
(4.92)

22.5
(0.86)

Declaration of Conformity CE Conformity


Rockwell Automation declares that the products that are shown in this
document conform with the Essential Health and Safety Requirements
(EHSRs) of the European Machinery Directive (2006/42/EC) and
EMC Directive (2014/30/EU).
• EN 61496-1:2012 Safety of machinery – Electro-sensitive protective
equipment – Part 1: General requirements and tests
• IEC 61496-2:2013 Safety of machinery – Electro-sensitive protective
equipment – Part 2: Particular requirements for equipment using active
opto-electronic protective devices (AOPDs)
• EN ISO 13849-1:2015 Safety of machinery – Safety-related parts of control
systems – Part 1: General principles for design
• EN 61508 Parts 1-7:2010 Functional safety of electrical/electronic/
programmable electronic safety-related systems
• EN 954-1:1997 Safety of machinery – Safety-related parts of control
systems – Part 1: General principles for design
• EN 50178:1997 Electronic equipment for use in power installations
• EN 62061:2005 Safety of machinery – Functional safety of safety-related
electrical, electronic, and programmable electronic control systems
• EN 60204-1:2006 Safety of machinery – Electrical equipment of machines
– General requirements
• EN 61000-6-4:2007 Electromagnetic compatibility (EMC) – Part 6-4:
Generic standards – Emission standard for industrial environments
(Class A)
• EN 61000-6-2:2005 Electromagnetic Compatibility (EMC) – Part 6-2:
Generic standards – Immunity for industrial environments

For a comprehensive CE certificate visit: rok.auto/certifications.

32 Rockwell Automation Publication 440R-UM008B-EN-P - July 2022


Appendix A Specifications

UKCA Conformity
Rockwell Automation declares that the products that are shown in this
document are in compliance with the Supply of Machinery (Safety)
Regulations (2008 No. 1597) and Electromagnetic Compatibility Regulations
(2016 No. 1091).
• EN 61496-1:2013 Safety of machinery – Electro-sensitive protective
equipment – Part 1: General requirements and tests
• IEC 61496-2:2013 Safety of machinery – Electro-sensitive protective
equipment – Part 2:
• Particular requirements for equipment using active opto-electronic
protective devices (AOPDs)
• EN ISO 13849-1:2015 Safety of machinery – Safety-related parts of control
systems – Part 1: General principles for design
• EN 61508 Parts 1-7:2010 Functional safety of electrical/electronic/
programmable electronic safety-related systems
• EN 62061:2005 Safety of machinery – Functional safety of safety-related
electrical, electronic, and programmable electronic control systems
• EN 60204-1:2006 Safety of machinery – Electrical equipment of machines
– General requirements
• EN 61000-6-4:2007 Electromagnetic compatibility (EMC) – Part 6-4:
Generic standards – Emission standard for industrial environments
(Class A)
• EN 61000-6-2:2005 Electromagnetic Compatibility (EMC) – Part 6-2:
Generic standards – Immunity for industrial environments

For a comprehensive UKCA certificate visit: rok.auto/certifications.

Rockwell Automation Publication 440R-UM008B-EN-P - July 2022 33


Appendix A Specifications

Notes:

34 Rockwell Automation Publication 440R-UM008B-EN-P - July 2022


Appendix B

Accessories

Additional Components
Table 19 - Catalog Numbers
Cat. No. Description

440R-ACABL1 Ribbon cable – two modules

440R-ACABL2 Ribbon cable – three modules

440R-ACABL3 Ribbon cable – four modules

440R-ATERM1P Terminal block kit for MSR41 safety module replacement

440R-ATERM2P Terminal block kit for MSR42 safety module replacement

440R-ATERM2C Terminal block kit for MSR45E extension module

445L-AF6150 USB/optical Interface

rok.auto/pcdc Software configuration tool

Rockwell Automation Publication 440R-UM008B-EN-P - July 2022 35


Appendix B Accessories

Interrupt Ignore Time This function for existing customers is a MSR42 safety module special feature
not included in the standard version.

The interrupt ignore time function is a limited time that a safety light curtain
interruption is ignored. Use this feature when parts must move through the
safety light curtain at high speed without interruption, but a human can
interrupt the safety light curtain for longer than the configured time.

IMPORTANT The interrupt ignore time function increases the response time. The
response time is given in the corresponding configuration control
document. Recalculate the safety distance.

You must activate the interrupt ignore time function with the MSR42 safety
module Configuration and Diagnostic Tool software (see publication
SAFETY-UM001). Then use the USB/optical interface (catalog number
445LAF6150) to download the function to the MSR42 safety module.

36 Rockwell Automation Publication 440R-UM008B-EN-P - July 2022


Appendix B Accessories

Notes:

Rockwell Automation Publication 440R-UM008B-EN-P - July 2022 37


Appendix B Accessories

Notes:

38 Rockwell Automation Publication 440R-UM008B-EN-P - July 2022


MSR42 Safety Module User Manual

Rockwell Automation Publication 440R-UM008B-EN-P - July 2022 39


Rockwell Automation Support
Use these resources to access support information.
Technical Support Center Find help with how-to videos, FAQs, chat, user forums, and product notification updates. rok.auto/support
Knowledgebase Access Knowledgebase articles. rok.auto/knowledgebase
Local Technical Support Phone Numbers Locate the telephone number for your country. rok.auto/phonesupport
Literature Library Find installation instructions, manuals, brochures, and technical data publications. rok.auto/literature
Product Compatibility and Download Center Download firmware, associated files (such as AOP, EDS, and DTM), and access product rok.auto/pcdc
(PCDC) release notes.

Documentation Feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our
content, complete the form at rok.auto/docfeedback.

Waste Electrical and Electronic Equipment (WEEE)

At the end of life, this equipment should be collected separately from any unsorted municipal waste.

Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.

Allen-Bradley, expanding human possibility, GuardMaster, Guardshield, Rockwell Automation, and SensaGuard are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur

CSA 107 107


Publication 440R-UM008B-EN-P - July 2022 10000172480 Ver 01
Supersedes Publication 440R-UM008A-EN-P - April 2011 Copyright © 2022 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

You might also like