G7 Quick Programming Mode
G7 Quick Programming Mode
The minimum user parameters required for drive operation can be monitored and set in quick programming
mode. The user parameters displayed in quick programming mode are listed in the following table. These, and
all other user parameters, are also displayed in advanced programming mode.
Refer to the overview of modes on page 3-5 for an overview of quick programming mode.
Name Control Methods
Change Open Open MODBUS
Parameter Setting Factory V/f
Number
Description Range Setting
during -loop Flux Loop Register
Display Operation V/f with
Vector Vector Vector
PG
1 2
Control Selects the Control Method of the drive.
Method 0: V/F control without PG
Selection 1: V/F control with PG
2: Open Loop Vector
A1-02 0 to 4 2 No Q Q Q Q Q 102H
3: Flux Vector (Closed Loop Vector)
Control 4: Vector 2 wo/PG
Method Note: Does not return to factory
setting when drive is initialized.
Frequency Selects the frequency reference input
Reference source.
Selection 0: Operator - Digital preset speed U1-
01 or d1-01 to d1-17.
1: Terminals - Analog input terminal
A1 (or terminal A2 based on
b1-01 0 to 4 1 No Q Q Q Q Q 180H
parameter H3-09).
Reference 2: Serial Com - Modbus RS-422/485
Source terminals R+, R-, S+, and S-.
3: Option PCB - Option board
connected on 2CN.
4: Pulse Input (Terminal RP)
Run Selects the run command input source.
Command 0: Operator - RUN and STOP keys on
Selection Digital Operator.
1: Terminals - Contact closure on
b1-02 terminals S1 or S2. 0 to 3 1 No Q Q Q Q Q 181H
Run 2: Serial Com - Modbus RS-422/485
Source terminals R+, R-, S+, and S-.
3: Option PCB - Option board
connected on 2CN.
Stopping Selects the stopping method when the
Method run command is removed.
Selection 0: Ramp to Stop
1: Coast to Stop 0 to 3
b1-03 0 No Q Q Q Q Q 182H
2: DC Injection to Stop *13
Stopping 3: Coast with Timer (A new run
Method command is ignored if received
before the timer expires).
Acceleration
Time 1 Sets the time to accelerate from zero to
C1-01 Yes Q Q Q Q Q 200H
Accel maximum frequency.
0.0
Time 1 to
10.0 s
Deceleration 6000.0
Time 1 *1
Sets the time to decelerate from maxi-
C1-02 Yes Q Q Q Q Q 201H
Decel mum frequency to zero.
Time 1
5-4
Digital Operator Display Functions and Levels
5-5
Name Control Methods
Change Open Open MODBUS
Parameter Setting Factory V/f
Number
Description Range Setting
during -loop Flux Loop Register
Display Operation V/f with
Vector Vector Vector
PG
1 2
Input Set to the nominal voltage of the
Voltage incoming line. Sets the maximum and
Setting base voltage used by preset V/F
patterns (E1-03 = 0 to E), adjusts the
levels of drive protective features (e.g.
Overvoltage, braking resistor turn-on,
stall prevention, etc.). 155.0
NOTE: DRIVE INPUT VOLTAGE to
230.0 V
E1-01 (NOT MOTOR VOLTAGE) 255.0 No Q Q Q Q Q 300H
*3
Input MUST BE SET IN E1-01 FOR (240V)
Voltage THE PROTECTIVE *3
FEATURES OF THE DRIVE
TO FUNCTION PROPERLY.
FAILURE TO DO SO MAY
RESULT IN EQUIPMENT
DAMAGE AND/OR
PERSONAL INJURY.
V/f Set to the type of motor being used
Pattern and the type of application.
Selection The drive operates utilizing a set V/F
pattern to determine the appropriate
output voltage level for each
commanded speed. There are 15
different preset V/F patterns to select
from (E1-03 = 0 to E) with varying
voltage profiles, base levels (base
level = frequency at which maximum
voltage is reached), and maximum
frequencies. There are also settings
for Custom V/F patterns that will use
the settings of parameters E1-04
through E1-13. E1-03 = F selects a
custom V/F pattern with an upper
voltage limit and E1-03 = FF selects a
custom V/F pattern without an upper
E1-03 0 to FF F No Q Q No No No 302H
voltage limit.
V/F 0: 50Hz
Selection 1: 60Hz Saturation
2: 50Hz Saturation
3: 72Hz (60Hz Base)
4: 50Hz VT1
5: 50Hz VT2
6: 60Hz VT1
7: 60Hz VT2
8: 50Hz HST1
9: 50Hz HST2
A: 60Hz HST1
B: 60Hz HST2
C: 90Hz (60Hz Base)
D: 120Hz (60Hz Base)
E: 180Hz (60Hz Base)
F: Custom V/F
FF: Custom w/o limit
5-6
Digital Operator Display Functions and Levels
5-7
Name Control Methods
Change Open Open MODBUS
Parameter Setting Factory V/f
Number
Description Range Setting
during -loop Flux Loop Register
Display Operation V/f with
Vector Vector Vector
PG
1 2
Terminal Sets terminal FM output level when
FM Gain selected monitor is at 100%.In order to
Setting adjust the meter, 100% of the
appropriate output is multiplied for the
gain setting, the bias amount is added
and then output.
0.00
See H4-02 when stopped in Quick,
H4-02 to 100% Yes Q Q Q Q Q 41EH
Advanced, or Verify mode. If 03
Terminal 1000.0
appears on the setting screen, then
FM Gain terminal FM is used.
See H4-04 when stopped in Quick,
Advanced, or Verify mode. If 06
appears on the setting screen, then
terminal AM is used.
Terminal Sets terminal AM output voltage (in
AM Gain percent of 10Vdc) when selected
Setting monitor is at 100% output. In order to
adjust the meter, 100% of the
appropriate output is multiplied for the
gain setting, the bias amount is added
and then output. 0.00
H4-05 See H4-02 when stopped in Quick, to 50% Yes Q Q Q Q Q 421H
Terminal Advanced, or Verify mode. If 03 1000.0
AM Gain appears on the setting screen, then
terminal FM is used.
See H4-04 when stopped in Quick,
Advanced, or Verify mode. If 06
appears on the setting screen, then
terminal AM is used.
Motor Sets the motor thermal overload
Overload protection (OL1) based on the cooling
Protectioncapacity of the motor.
L1-01 Selection 0: Disabled 0 to 3 1 No Q Q Q Q Q 480H
1: Standard Fan Cooled (< 10:1 motor)
MOL Fault 2: Standard Blower Cooled (10:1 motor)
Select 3: Vector Motor (1000:1 motor)
5-8
Digital Operator Display Functions and Levels
* 1. The setting ranges for acceleration/deceleration times depends on the setting of C1-10 (Acceleration/deceleration Time Setting Unit). If C1-10 is set to
0, the setting range is 0.00 to 600.00 (s).
* 2. The factory setting depends on the drive capacity.
* 3. These are values for a 200-240V class drive. Values for a 380-480V class drive are double.
* 4. The factory setting will change when the control method is changed. (Open-loop vector 1 factory settings are given.)
* 5. After autotuning, E1-13 will contain the same value as E1-05.
* 6. The factory setting depends on the drive capacity. (The value for a 200-240V class drive for 0.4 kW is given.)
* 7. The setting range is from 10% to 200% of the drive rated output current. (The value for a 200-240V class drive for 0.4 kW is given.)
* 8. L3-04 cannot be set to 3 for flux vector control or open-loop vector control 2.
* 9. The setting range is 0 to 66.0 for open-loop vector control 2. The upper limit for the setting range also depends on the upper limit in E1-04.
The maximum setting is 400.00.
* 10. The same capacity as the drive will be set by initializing the parameters.
* 11. The setting range is 0 to 2 for flux vector control and open-loop vector control 2.
* 12. Quick Settings are used if Multi-Function Input is set for two motors.
* 13. Setting range changes to {1,2} when operating in Flux Vector and in Open Loop Vector.
5-9