Steam Turbine Protection

The document outlines the protection system for the steam turbine in the conversion of the Az-Zour South Gas Turbines to a Combined Cycle Plant. It details various trip conditions, including overspeed, oil pressure, temperature thresholds, and vibration limits, along with their corresponding set values and results. Additionally, it includes bypass trip conditions and safety measures for turbine operation.

Uploaded by

w hu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
10 views4 pages

Steam Turbine Protection

The document outlines the protection system for the steam turbine in the conversion of the Az-Zour South Gas Turbines to a Combined Cycle Plant. It details various trip conditions, including overspeed, oil pressure, temperature thresholds, and vibration limits, along with their corresponding set values and results. Additionally, it includes bypass trip conditions and safety measures for turbine operation.

Uploaded by

w hu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Project:

Supply, Erection, Operation And Maintenance For the Conversion Of


the Third Stage Az-Zour South Gas Turbines To Combined Cycle Plant
(CCGT-3)
SYSTEM STEAM TURBINE PROTECTION SYSTEM

No. CONTENT Set value Result Remark

1 Trip by operator station from DCS (70MAY10EZ100) /


Overspeed protection trip by governor (70MAY10EZ611.
2 >3330rpm
70MAY10EZ621. 70MAY10EZ631)
Overspeed protection trip by Braun (70MAY10EZ511.
3 >3300 rpm
70MAY10EZ521. 70MAY10EZ531)

Trip by governor (70MAY10EZ021. 70MAY10EZ022.


4 /
70MAY10EZ023)
Trip by LP exhaust differential pressure H delay 30s
5 >-0.75bar
(70MAC10CP050. 70MAC10CP051. 70MAC10CP052)

Safety oil pressure <90bar (70MAX40CP020. 70MAX40CP021.


6 <90bar
70MAX40CP022)

Safety oil pressure 2 of 3 BQ (70MAX40CP020. 70MAX40CP021.


7 /
70MAX40CP022)

Lube oil pressure <1bar delay 3s (70MAV40CP010.


8 <1bar
70MAV40CP011. 70MAV40CP012)

Lube oil pressure 2 of 3 BQ (70MAV40CP010. 70MAV40CP011.


9 /
70MAV40CP012)

Lube oil TEMP>65℃ (70MAV40CT010. 70MAV40CT011.


>65℃
10
70MAV40CT012)

Lube oil TEMP 2 of 3 BQ (70MAV40CT010. 70MAV40CT011.


11 /
70MAV40CT012)

Last stage inlet TEMP >230℃(70MAC10CT040.


12 >230℃
70MAC10CT041. 70MAC10CT042
Last stage inlet TEMP 2 of 3 BQ
13 /
(70MAC10CT040. 70MAC10CT041. 70MAC10CT042)

14 LP exhaust TEMP>110℃ >110℃

Sem restrições
(70MAC10CT050. 70MAC10CT051. 70MAC10CT052)

LP exhaust TEMP 2 of 3 BQ
15 /
(70MAC10CT050. 70MAC10CT051. 70MAC10CT052)

Seal steam temperature cooler difference > 40K


16 >235℃
(70MAW30CT020 70MAW30CT021 70MAW30CT022)
Seal steam temperature2 of 3 BQ
17 /
(70MAW30CT020 70MAW30CT021 70MAW30CT022)
Generator stator winding U TEMP >127℃
18 >127℃
(70MKA10CT010 70MKA10CT011. 70MKA10CT012)
Generator stator winding U TEMP 2 of 3 BQ
19 /
(70MKA10CT010 70MKA10CT011. 70MKA10CT012)
Generator stator winding V TEMP >127℃
20 >127℃
(70MKA10CT020 .70MKA10CT021. 70MKA10CT022)

Generator stator winding V TEMP 2 of 3 BQ


21 /
(70MKA10CT020 .70MKA10CT021. 70MKA10CT022)

Generator stator winding W TEMP >127℃


22 >127℃
(70MKA10CT030 .70MKA10CT031. 70MKA10CT032)

Generator stator winding W TEMP 2 of 3 BQ


23 /
(70MKA10CT030 .70MKA10CT031. 70MKA10CT032)

Trip by bearing TEMP>125℃ MAN-TRIP


(70MAD10CT010 70MKD10CT010 70MAD10CT010
24 70MKD20CT020 70MAD10CT021 70MAD10CT030 >125℃
70MAD10CT031 70MAD20CT010 70MAD30CT010
70MAD40CT010)
Turbine X-AXIS-SHAFT VIB >164um (70MAD10CY011) delay
3s
Turbine Y-AXIS-SHAFT VIB >164um (70MAD10CY012) delay
3s
Turbine X-AXIS-SHAFT VIB >164um (70MAD20CY011) delay
3s
Turbine Y-AXIS-SHAFT VIB >164um (70MAD20CY012) delay
25 >164um
3s
Turbine X-AXIS-SHAFT VIB >164um (70MKD30CY011) delay
3s
Turbine Y-AXIS-SHAFT VIB >164um (70MKD30CY012) delay
3s
Exciter X-AXIS-SHAFT VIB >164um (70MKD20CY011) delay
3s

Sem restrições
Exciter Y-AXIS-SHAFT VIB >164um (70MKD20CY012) delay
3s
End lp turbine X-AXIS-SHAFT VIB>164um (70MAD30CY011)
delay 3s
End lp turbine Y-AXIS-SHAFT VIB>164um (70MAD30CY012)
delay 3s
Front end turbine X-AXIS-SHAFT VIB>164um(70MAD40CY011)
delay 3s
Front end turbine Y-AXIS-SHAFT VIB>164um(70MAD40CY012)
delay 3s
Turbine VERTICAL BRG VIB >11.8mm/s (70MAD10CY020)
Turbine HORIZONTAL BRG VIB >11.8mm/s (70MAD10CY030)
Turbine VERTICAL BRG VIB >11.8mm/s(70MAD20CY020)
Turbine HORIZONTAL BRG VIB >11.8mm/s (70MAD20CY030)
Turbine VERTICAL BRG VIB >11.8mm/s(70MAD30CY020)
Turbine HORIZONTAL BRG VIB >11.8mm/s (70MAD30CY030)
26 >11.8mm/s
Turbine VERTICAL BRG VIB >11.8mm/s(70MAD40CY020)
Turbine HORIZONTAL BRG VIB >11.8mm/s (70MAD40CY030)
Turbine VERTICAL BRG VIB >11.8mm/s(70MKD10CY020)
Turbine HORIZONTAL BRG VIB >11.8mm/s (70MKD10CY030)
Turbine VERTICAL BRG VIB >11.8mm/s(70MKD20CY020)
Turbine HORIZONTAL BRG VIB >11.8mm/s (70MkD20CY030)
Turbine AXIAL SHAFT POS -0.8mm < >0.8mm
27 >0.8mm
(70MAD10CG910)
28 Trip by admission steam protection /
Fire protection (70MAV10EZ310 70MAV10EZ320
29 /
70MAV10EZ330)
30 Trip by turbine sequence /
Generator protection cabinet protection device (70MKY10CE050
31 /
70MKY10CE051)
Main steam temperature drop protection turbine trip by main
32 /
superheating protection
Main steam temperature (70LBA10CT905) compare with shaft
33 /
simulation TEMP
34 Main steam temperature (70LBA10CT905) >570℃ >570℃
Main steam temperature drop protection decrease of Main steam
35 /
temperature too high
Main steam temperature drop protection increase of Main steam
36 /
temperature too high
37 clc-olc watchdog coupling failure /

38 PP ESD push button operate (ESD) /

Sem restrições
39 HOTWELL LVL HHH (ESD) /

40 COND PRESS BQ 2 of 3 (ESD) /

41 COND PRESS HHH (ESD) /

42 11DD HRSG CLOSED

43 GT11 GCB OPEN OR


11HP STP VLV NOT OPENED AND 11LP STP VLV NOT
44
OPENED
AND
45 12DD HRSG CLOSED

46 12 GCB OPEN OR
12HP STP VLV NOT OPENED AND 12LP STP VLV NOT
47
OPENED

BYPASS TRIPS:

- IF turbine speed < 40 rpm OR 2oo3 fault -> bypass not released;

- Gland steam pressure controller interlocked;

- Speed < 200 rpm AND bypass not in operation AND EHSP > -0.4 barg -> bypass not
released;

- Speed > 1500 rpm AND trip by EHSP AND EHSP > -0.45 barg;

- Exhaust steam temperature > 115ºC.

EPC MEW SIEMENS

NAME

SIGNATURE

DATE