Standard Block Library

The EcoStruxure™ Control Expert Standard Block Library documentation provides technical descriptions and characteristics of Schneider Electric products, emphasizing the need for users to conduct their own risk analysis and testing. It includes a comprehensive table of contents detailing various block types, their applications, and specific functions related to arrays and integer regulation. The document also outlines safety information and usage rights, highlighting the importance of following safety regulations during installation and use.

Uploaded by

rodrigoassismini
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
6 views

Standard Block Library

The EcoStruxure™ Control Expert Standard Block Library documentation provides technical descriptions and characteristics of Schneider Electric products, emphasizing the need for users to conduct their own risk analysis and testing. It includes a comprehensive table of contents detailing various block types, their applications, and specific functions related to arrays and integer regulation. The document also outlines safety information and usage rights, highlighting the importance of following safety regulations during installation and use.

Uploaded by

rodrigoassismini
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 520

EcoStruxure™ Control Expert

33002519 09/2020

EcoStruxure™ Control
Expert
Standard
Block Library
Original instructions

09/2020
33002519.20

www.schneider-electric.com
The information provided in this documentation contains general descriptions and/or technical
characteristics of the performance of the products contained herein. This documentation is not
intended as a substitute for and is not to be used for determining suitability or reliability of these
products for specific user applications. It is the duty of any such user or integrator to perform the
appropriate and complete risk analysis, evaluation and testing of the products with respect to the
relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or
subsidiaries shall be responsible or liable for misuse of the information contained herein. If you
have any suggestions for improvements or amendments or have found errors in this publication,
please notify us.
You agree not to reproduce, other than for your own personal, noncommercial use, all or part of
this document on any medium whatsoever without permission of Schneider Electric, given in
writing. You also agree not to establish any hypertext links to this document or its content.
Schneider Electric does not grant any right or license for the personal and noncommercial use of
the document or its content, except for a non-exclusive license to consult it on an "as is" basis, at
your own risk. All other rights are reserved.
All pertinent state, regional, and local safety regulations must be observed when installing and
using this product. For reasons of safety and to help ensure compliance with documented system
data, only the manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant
instructions must be followed.
Failure to use Schneider Electric software or approved software with our hardware products may
result in injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
© 2020 Schneider Electric. All rights reserved.

2 33002519 09/2020
Table of Contents

Safety Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Part I General information . . . . . . . . . . . . . . . . . . . . . . . . . 21
Chapter 1 Block Types and their Applications. . . . . . . . . . . . . . . . . 23
Block Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
FFB Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
EN and ENO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Chapter 2 Block Availability on Various Hardware Platforms . . . . . 33
Block Availability on the Various Hardware Platforms . . . . . . . . . . . . . 33
Part II Arrays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Chapter 3 ADD_***_***: Addition of a number to elements of an array
or addition of two arrays . . . . . . . . . . . . . . . . . . . . . . . . . 43
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Chapter 4 AND_***_***: Logical AND between arrays and variables 47
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Chapter 5 COPY_***_***: Copy on arrays . . . . . . . . . . . . . . . . . . . . 51
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Chapter 6 DIV_***_***: Division of arrays . . . . . . . . . . . . . . . . . . . . 55
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Chapter 7 EQUAL_***: Comparison of two arrays. . . . . . . . . . . . . . 59
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Chapter 8 FIND_EQ_***: First element of an array equal to a given
value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Chapter 9 FIND_EQP_***: First element of an array equal to a value
starting from a given rank . . . . . . . . . . . . . . . . . . . . . . . 67
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Chapter 10 FIND_GT_***: First element of an array greater than a
given value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Chapter 11 FIND_LT_***: First element of an array less than a given
value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75

33002519 09/2020 3
Chapter 12 LENGTH_***: Length of an array . . . . . . . . . . . . . . . . . . . 79
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Chapter 13 MAX_***: Maximum value of array elements . . . . . . . . . . 83
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Chapter 14 MIN_***: Minimum value of array elements . . . . . . . . . . . 85
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Chapter 15 MOD_***_***: Remainder of division of arrays . . . . . . . . . 87
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Chapter 16 MOVE_***_***: Assignment to arrays . . . . . . . . . . . . . . . . 91
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Chapter 17 MOVE_***_***: Array conversion . . . . . . . . . . . . . . . . . . . 93
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Chapter 18 MUL_***_***: Multiplication of arrays . . . . . . . . . . . . . . . . 95
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Chapter 19 NOT_***: Logical negation of arrays. . . . . . . . . . . . . . . . . 99
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Chapter 20 OCCUR_***: Occurrence of a value in an array . . . . . . . . 101
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Chapter 21 OR_***_***: Logical OR between arrays and variables . . 103
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Chapter 22 ROL_***: Rotate shift to left . . . . . . . . . . . . . . . . . . . . . . . 107
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Chapter 23 ROR_***: Rotate shift to right . . . . . . . . . . . . . . . . . . . . . . 109
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Chapter 24 SORT_***: Ascending or descending sort . . . . . . . . . . . . 111
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Chapter 25 SUB_***_***: Subtraction from arrays. . . . . . . . . . . . . . . . 113
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Chapter 26 SUM_***: Sum of array elements . . . . . . . . . . . . . . . . . . . 117
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Chapter 27 SWAP_***: Permutation of the bytes of an array . . . . . . . 119
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Chapter 28 XOR_***_***: Exclusive OR between arrays. . . . . . . . . . . 121
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121

4 33002519 09/2020
Part III CLC_INT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Chapter 29 Introduction to integer regulation functions. . . . . . . . . . . 127
General Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Principal of the regulation loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Development methodology for a regulation application. . . . . . . . . . . . 130
Programming a regulation function . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Behavior of functions in operating modes . . . . . . . . . . . . . . . . . . . . . . 132
Chapter 30 PID_INT: PID controller . . . . . . . . . . . . . . . . . . . . . . . . . 133
Function description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Description of Derived Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Chapter 31 PWM_INT: Pulse width modulation of a numerical value 141
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Chapter 32 SERVO_INT: Servo drive function . . . . . . . . . . . . . . . . . 145
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Part IV Comparison . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
Chapter 33 EQ: Equal to . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
Chapter 34 GE: Greater than or equal to . . . . . . . . . . . . . . . . . . . . . 155
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
Chapter 35 GT: Greater than. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
Chapter 36 LE: Less than or equal to . . . . . . . . . . . . . . . . . . . . . . . . 163
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Chapter 37 LT: Less than . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
Chapter 38 NE: Not equal to . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
Part V Date & Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
Chapter 39 ADD_***_TIME: Addition of a duration to a date. . . . . . . 175
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
Chapter 40 DIVTIME: Division. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
Chapter 41 MULTIME: Multiplication. . . . . . . . . . . . . . . . . . . . . . . . . 179
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
Chapter 42 SUB_***_***: Calculates the time difference between two
dates or times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181

33002519 09/2020 5
Chapter 43 SUB_***_TIME: Subtraction of a duration from a date . . . 183
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
Part VI Extract . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
Chapter 44 EXTRACT: Copy of a variable part into another variable . 187
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
Chapter 45 SIZEOF: Size of a variable in bytes . . . . . . . . . . . . . . . . . 191
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
Part VII Logic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
Chapter 46 AND: AND function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
Chapter 47 F_TRIG: Falling edge detection . . . . . . . . . . . . . . . . . . . . 197
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
Chapter 48 FE: Detection of Falling Edge. . . . . . . . . . . . . . . . . . . . . . 199
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
Chapter 49 NOT: Negation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
Chapter 50 OR: OR function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
Chapter 51 R_TRIG: Rising edge detection . . . . . . . . . . . . . . . . . . . . 205
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
Chapter 52 RE: Detection of Rising Edge . . . . . . . . . . . . . . . . . . . . . . 207
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207
Chapter 53 RESET: Setting of a bit to 0 . . . . . . . . . . . . . . . . . . . . . . . 209
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209
Chapter 54 ROL: Rotate left . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211
Chapter 55 ROR: Rotate right . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
Chapter 56 RS: Bistable function block, reset dominant . . . . . . . . . . . 217
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
Chapter 57 SET: Setting of a bit to 1 . . . . . . . . . . . . . . . . . . . . . . . . . 219
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
Chapter 58 SHL: Shift left . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 221
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 221
Chapter 59 SHR: Shift right. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
Chapter 60 SR: Bistable function block, set dominant . . . . . . . . . . . . 225
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225

6 33002519 09/2020
Chapter 61 TRIGGER: Detection of all edges. . . . . . . . . . . . . . . . . . 227
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227
Chapter 62 XOR: Exclusive OR function. . . . . . . . . . . . . . . . . . . . . . 229
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
Part VIII Mathematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
Chapter 63 ABS: Absolute value computation . . . . . . . . . . . . . . . . . 233
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233
Chapter 64 ACOS: Arc cosine. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
Chapter 65 ADD: Addition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237
Chapter 66 ADD_TIME: Addition. . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
Chapter 67 ASIN: Arc sine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
Chapter 68 ATAN: Arc tangent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 243
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 243
Chapter 69 COS: Cosine. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245
Chapter 70 DEC: Decrementation of a variable . . . . . . . . . . . . . . . . 247
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 247
Chapter 71 DIV: Division . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 249
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 249
Chapter 72 DIVMOD: Division and Modulo . . . . . . . . . . . . . . . . . . . . 253
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253
Chapter 73 EXP: Natural exponential . . . . . . . . . . . . . . . . . . . . . . . . 255
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
Chapter 74 EXPT_REAL_***: Exponentiation of one value by another
value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
Chapter 75 INC: Incrementation of a variable . . . . . . . . . . . . . . . . . . 261
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261
Chapter 76 LN: Natural logarithm . . . . . . . . . . . . . . . . . . . . . . . . . . . 263
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 263
Chapter 77 LOG : Base 10 logarithm . . . . . . . . . . . . . . . . . . . . . . . . 265
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 265
Chapter 78 MOD: Modulo . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267

33002519 09/2020 7
Chapter 79 MOVE: Assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 269
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 269
Chapter 80 MUL: Multiplication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 271
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 271
Chapter 81 NEG: Negation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 273
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 273
Chapter 82 SATURATION: Saturation . . . . . . . . . . . . . . . . . . . . . . . . 275
SATURATION: Maximum REAL value . . . . . . . . . . . . . . . . . . . . . . . . 275
Chapter 83 SIGN: Sign evaluation . . . . . . . . . . . . . . . . . . . . . . . . . . . 279
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 279
Chapter 84 SIN: Sine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 281
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 281
Chapter 85 SUB: Subtraction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283
Chapter 86 SUB_TIME: Subtraction . . . . . . . . . . . . . . . . . . . . . . . . . . 285
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 285
Chapter 87 SQRT_*** : Square root . . . . . . . . . . . . . . . . . . . . . . . . . . 287
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 287
Chapter 88 TAN: Tangent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 289
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 289
Part IX REF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 291
Chapter 89 REF: Reference a variable . . . . . . . . . . . . . . . . . . . . . . . . 293
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 293
Part X Statistical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 295
Chapter 90 AVE: Averaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 297
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 297
Chapter 91 LIMIT: Limit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 301
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 301
Chapter 92 LIMIT_IND: Limit with indicator. . . . . . . . . . . . . . . . . . . . . 305
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305
Chapter 93 MAX: Maximum value function . . . . . . . . . . . . . . . . . . . . . 309
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309
Chapter 94 MIN: Minimum value function . . . . . . . . . . . . . . . . . . . . . . 311
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 311
Chapter 95 MUX: Multiplexer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 313
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 313
Chapter 96 SEL: Binary selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 317
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 317

8 33002519 09/2020
Part XI Strings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 319
Chapter 97 CONCAT_STR: Concatenation of two character strings 321
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 321
Chapter 98 DELETE_INT: Deletion of a sub-string of characters . . . 323
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 323
Chapter 99 EQUAL_STR: Comparison of two character strings . . . . 325
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 325
Chapter 100 FIND_INT: Finding a sub-string of characters . . . . . . . . 327
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 327
Chapter 101 INSERT_INT: Insertion of a sub-string of characters . . . 329
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 329
Chapter 102 LEFT_INT: Extraction of characters to the left . . . . . . . . 333
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 333
Chapter 103 LEN_INT: Length of character string . . . . . . . . . . . . . . . 335
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 335
Chapter 104 MID_INT: Extraction of a sub-string of characters . . . . . 337
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 337
Chapter 105 REPLACE_INT: Replacement of a sub-string of
characters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 339
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 339
Chapter 106 RIGHT_INT: Extraction of a character string to the right 343
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 343
Part XII Timer & Counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . 345
Chapter 107 CTD, CTD_***: Down counter. . . . . . . . . . . . . . . . . . . . . 347
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 347
Chapter 108 CTU, CTU_***: Up counter . . . . . . . . . . . . . . . . . . . . . . . 349
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 349
Chapter 109 CTUD, CTUD_***: Up/Down counter . . . . . . . . . . . . . . . 351
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 351
Chapter 110 TOF: Off delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 355
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 355
Chapter 111 TON: On delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 357
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 357
Chapter 112 TP: Pulse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 359
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 359

33002519 09/2020 9
Part XIII Type to type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 361
Chapter 113 ARINT_TO_DATE: Convert Integer Array with Date to a
DATE Variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 363
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 363
Chapter 114 ARINT_TO_DT: Convert Integer Array with Date and
Time to a DT Variable . . . . . . . . . . . . . . . . . . . . . . . . . . . 365
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 365
Chapter 115 ARINT_TO_TOD: Convert Integer Array with Time Of Day
to a TOD Variable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 367
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 367
Chapter 116 ASCII_TO_STRING: Type conversion . . . . . . . . . . . . . . . 369
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 369
Chapter 117 ASCII_TO_STRING_INV: Type conversion . . . . . . . . . . . 373
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 373
Chapter 118 BCD_TO_INT: Conversion of a BCD integer into pure
binary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 379
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 379
Chapter 119 BIT_TO_BYTE: Type conversion . . . . . . . . . . . . . . . . . . . 381
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 381
Chapter 120 BIT_TO_WORD: Type conversion . . . . . . . . . . . . . . . . . . 385
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 385
Chapter 121 BOOL_TO_***: Type conversion . . . . . . . . . . . . . . . . . . . 389
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 389
Chapter 122 BYTE_AS_WORD: Type conversion . . . . . . . . . . . . . . . . 391
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 391
Chapter 123 BYTE_TO_BIT: Type conversion . . . . . . . . . . . . . . . . . . . 393
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 393
Chapter 124 BYTE_TO_***: Type conversion . . . . . . . . . . . . . . . . . . . . 397
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 397
Chapter 125 DATE_TO_ARINT: Convert DATE Variable to Integer
Array. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 401
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 401
Chapter 126 DATE_TO_STRING: Conversion of a variable in DATE
format into a character string . . . . . . . . . . . . . . . . . . . . . . 403
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 403
Chapter 127 DBCD_TO_***: Conversion of a double BCD integer into
binary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 405
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 405

10 33002519 09/2020
Chapter 128 DEG_TO_RAD : Conversion of degrees to radians . . . . 407
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 407
Chapter 129 DINT_AS_WORD: Type conversion . . . . . . . . . . . . . . . . 409
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 409
Chapter 130 DINT_TO_***: Type conversion . . . . . . . . . . . . . . . . . . . 411
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 411
Chapter 131 DINT_TO_DBCD: Conversion of a double binary coded
integer into a double Binary Coded Decimal integer . . . 415
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 415
Chapter 132 DT_TO_ARINT: Convert DT Variable to Integer Array . . 417
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 417
Chapter 133 DT_TO_STRING: Conversion of a variable in DT format
into a character string . . . . . . . . . . . . . . . . . . . . . . . . . . . 419
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 419
Chapter 134 DWORD_TO_***: Type conversion. . . . . . . . . . . . . . . . . 421
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 421
Chapter 135 GRAY_TO_INT: Conversion of an integer in Gray code
into a binary coded integer . . . . . . . . . . . . . . . . . . . . . . . 423
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 423
Chapter 136 INT_AS_DINT: Concatenation of two integers to form a
double integer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 425
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 425
Chapter 137 INT_TO_***: Type conversion. . . . . . . . . . . . . . . . . . . . . 427
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 427
Chapter 138 INT_TO_BCD: Conversion of a binary coded integer into
a Binary Coded Decimal integer . . . . . . . . . . . . . . . . . . . 431
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 431
Chapter 139 INT_TO_DBCD: Conversion of a binary coded integer into
a double Binary Coded Decimal integer . . . . . . . . . . . . . 433
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 433
Chapter 140 RAD_TO_DEG: Conversion of radians to degrees . . . . . 435
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 435
Chapter 141 REAL_AS_WORD: Type conversion . . . . . . . . . . . . . . . 437
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 437
Chapter 142 REAL_TO_***: Type conversion . . . . . . . . . . . . . . . . . . . 439
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 439
Chapter 143 REAL_TRUNC_***: Type conversion . . . . . . . . . . . . . . . 443
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 443

33002519 09/2020 11
Chapter 144 STRING_TO_ASCII: Type conversion . . . . . . . . . . . . . . . 445
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 445
Chapter 145 STRING_TO_ASCII_INV: Type conversion . . . . . . . . . . . 451
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 451
Chapter 146 STRING_TO_*** : Conversion of a character string to a
number of the INT, DINT or REAL type . . . . . . . . . . . . . . 457
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 457
Chapter 147 TIME_AS_WORD: Type conversion. . . . . . . . . . . . . . . . . 461
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 461
Chapter 148 TIME_TO_***: Type conversion . . . . . . . . . . . . . . . . . . . . 463
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 463
Chapter 149 TIME_TO_STRING: Conversion of a variable in TIME
format into a character string . . . . . . . . . . . . . . . . . . . . . . 465
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 465
Chapter 150 TOD_TO_ARINT: Convert TOD Variable to Integer Array 467
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 467
Chapter 151 TOD_TO_STRING: Conversion of a variable in TOD
format into a character string . . . . . . . . . . . . . . . . . . . . . . 469
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 469
Chapter 152 UDINT_AS_WORD: Type conversion . . . . . . . . . . . . . . . 471
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 471
Chapter 153 UDINT_TO_***: Type conversion . . . . . . . . . . . . . . . . . . . 473
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 473
Chapter 154 UINT_TO_***: Type conversion . . . . . . . . . . . . . . . . . . . . 477
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 477
Chapter 155 WORD_AS_BYTE: Type conversion . . . . . . . . . . . . . . . . 481
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 481
Chapter 156 WORD_AS_DINT: Type conversion . . . . . . . . . . . . . . . . . 483
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 483
Chapter 157 WORD_AS_REAL: Type conversion . . . . . . . . . . . . . . . . 485
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 485
Chapter 158 WORD_AS_TIME: Type conversion . . . . . . . . . . . . . . . . 487
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 487
Chapter 159 WORD_AS_UDINT: Type conversion . . . . . . . . . . . . . . . 489
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 489
Chapter 160 WORD_TO_BIT: Type conversion . . . . . . . . . . . . . . . . . . 491
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 491

12 33002519 09/2020
Chapter 161 WORD_TO_***: Type conversion . . . . . . . . . . . . . . . . . . 495
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 495
Chapter 162 ***_TO_STRING: Conversion of a variable into a
character string . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 497
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 497
Appendices ......................................... 499
Appendix A EFB Error Codes and Values . . . . . . . . . . . . . . . . . . . . . 501
Tables of Error Codes for the Base Library . . . . . . . . . . . . . . . . . . . . . 502
Common Floating Point Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 504
Glossary ......................................... 505
Index ......................................... 515

33002519 09/2020 13
14 33002519 09/2020
Safety Information

Function Block Library and System User Guide Specific Safety Information

BEFORE YOU BEGIN


Do not use this product on machinery lacking effective point-of-operation guarding. Lack of
effective point-of-operation guarding on a machine can result in serious injury to the operator of
that machine.

WARNING
UNGUARDED EQUIPMENT
 Do not use this software and related automation equipment on equipment which does not have
point-of-operation protection.
 Do not reach into machinery during operation.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

This automation equipment and related software is used to control a variety of industrial processes.
The type or model of automation equipment suitable for each application will vary depending on
factors such as the control function required, degree of protection required, production methods,
unusual conditions, government regulations, etc. In some applications, more than one processor
may be required, as when backup redundancy is needed.
Only you, the user, machine builder or system integrator can be aware of all the conditions and
factors present during setup, operation, and maintenance of the machine and, therefore, can
determine the automation equipment and the related safeties and interlocks which can be properly
used. When selecting automation and control equipment and related software for a particular
application, you should refer to the applicable local and national standards and regulations. The
National Safety Council's Accident Prevention Manual (nationally recognized in the United States
of America) also provides much useful information.
In some applications, such as packaging machinery, additional operator protection such as point-
of-operation guarding must be provided. This is necessary if the operator's hands and other parts
of the body are free to enter the pinch points or other hazardous areas and serious injury can occur.
Software products alone cannot protect an operator from injury. For this reason the software
cannot be substituted for or take the place of point-of-operation protection.

33002519 09/2020 15
Ensure that appropriate safeties and mechanical/electrical interlocks related to point-of-operation
protection have been installed and are operational before placing the equipment into service. All
interlocks and safeties related to point-of-operation protection must be coordinated with the related
automation equipment and software programming.
NOTE: Coordination of safeties and mechanical/electrical interlocks for point-of-operation
protection is outside the scope of the Function Block Library, System User Guide, or other
implementation referenced in this documentation.

START-UP AND TEST


Before using electrical control and automation equipment for regular operation after installation,
the system should be given a start-up test by qualified personnel to verify correct operation of the
equipment. It is important that arrangements for such a check be made and that enough time is
allowed to perform complete and satisfactory testing.

WARNING
EQUIPMENT OPERATION HAZARD
 Verify that all installation and set up procedures have been completed.
 Before operational tests are performed, remove all blocks or other temporary holding means
used for shipment from all component devices.
 Remove tools, meters, and debris from equipment.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

Follow all start-up tests recommended in the equipment documentation. Store all equipment
documentation for future references.
Software testing must be done in both simulated and real environments.
Verify that the completed system is free from all short circuits and temporary grounds that are not
installed according to local regulations (according to the National Electrical Code in the U.S.A, for
instance). If high-potential voltage testing is necessary, follow recommendations in equipment
documentation to prevent accidental equipment damage.
Before energizing equipment:
 Remove tools, meters, and debris from equipment.
 Close the equipment enclosure door.
 Remove all temporary grounds from incoming power lines.
 Perform all start-up tests recommended by the manufacturer.

16 33002519 09/2020
OPERATION AND ADJUSTMENTS
The following precautions are from the NEMA Standards Publication ICS 7.1-1995 (English
version prevails):
 Regardless of the care exercised in the design and manufacture of equipment or in the selection
and ratings of components, there are hazards that can be encountered if such equipment is
improperly operated.
 It is sometimes possible to misadjust the equipment and thus produce unsatisfactory or unsafe
operation. Always use the manufacturer’s instructions as a guide for functional adjustments.
Personnel who have access to these adjustments should be familiar with the equipment
manufacturer’s instructions and the machinery used with the electrical equipment.
 Only those operational adjustments actually required by the operator should be accessible to
the operator. Access to other controls should be restricted to prevent unauthorized changes in
operating characteristics.

NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device
before trying to install, operate, service, or maintain it. The following special messages may appear
throughout this documentation or on the equipment to warn of potential hazards or to call attention
to information that clarifies or simplifies a procedure.

33002519 09/2020 17
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified
personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of
the use of this material.
A qualified person is one who has skills and knowledge related to the construction and operation
of electrical equipment and its installation, and has received safety training to recognize and avoid
the hazards involved.

18 33002519 09/2020
About the Book

At a Glance

Document Scope
This document describes the functions and function blocks of the Standard library.

Validity Note
This document is valid for EcoStruxure™ Control Expert 15.0 or later.

Related Documents

Title of documentation Reference number


EcoStruxure™ Control Expert, Program Languages 35006144 (English),
and Structure, Reference Manual 35006145 (French),
35006146 (German),
35013361 (Italian),
35006147 (Spanish),
35013362 (Chinese)
EcoStruxure™ Control Expert, Operating Modes 33003101 (English),
33003102 (French),
33003103 (German),
33003104 (Spanish),
33003696 (Italian),
33003697 (Chinese)
EcoStruxure™ Control Expert, System Bits and EIO0000002135 (English),
Words, Reference Manual EIO0000002136 (French),
EIO0000002137 (German),
EIO0000002138 (Italian),
EIO0000002139 (Spanish),
EIO0000002140 (Chinese)
EcoStruxure™ Control Expert, Diagnostics, Block 33002523 (English),
Library 33002524 (French),
33002525 (German),
33003680 (Italian),
33002526 (Spanish),
33003681 (Chinese)

You can download these technical publications and other technical information from our website
at www.schneider-electric.com/en/download.

33002519 09/2020 19
Product Related Information

WARNING
UNINTENDED EQUIPMENT OPERATION
The application of this product requires expertise in the design and programming of control
systems. Only persons with such expertise should be allowed to program, install, alter, and apply
this product.
Follow all local and national safety codes and standards.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

20 33002519 09/2020
EcoStruxure™ Control Expert
General information
33002519 09/2020

Part I
General information

General information

Overview
This section contains general information about the Standard library.
NOTE: For a detailed description of system objects (%S and %SW), refer to EcoStruxure™ Control
Expert, System Bits and Words, Reference Manual

What Is in This Part?


This part contains the following chapters:
Chapter Chapter Name Page
1 Block Types and their Applications 23
2 Block Availability on Various Hardware Platforms 33

33002519 09/2020 21
General information

22 33002519 09/2020
EcoStruxure™ Control Expert
Block Types and their Applications
33002519 09/2020

Chapter 1
Block Types and their Applications

Block Types and their Applications

Overview
This chapter describes the different block types and their applications.

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Block Types 24
FFB Structure 26
EN and ENO 30

33002519 09/2020 23
Block Types and their Applications

Block Types

Block Types
Different block types are used in Control Expert. The general term for the block types is FFB.
There are the following types of block:
 Elementary Function (EF)
 Elementary Function Block (EFB)
 Derived Function Block (DFB)
 Procedure

NOTE: Motion Function Blocks are not available on the Quantum platform.

Elementary Function
Elementary functions (EF) have no internal status and one output only. If the input values are the
same, the output value is the same for the executions of the function, for example the addition of
two values gives the same result at every execution.
An elementary function is represented in the graphical languages (FBD and LD) as a block frame
with inputs and an output. The inputs are represented on the left and the outputs on the right of the
block frame. The name of the function, that is the function type, is shown in the center of the block
frame.
The number of inputs can be increased with some elementary functions.
NOTE: Unity Pro is the former name of Control Expert for version 13.1 or earlier.

CAUTION
UNEXPECTED BEHAVIOR OF EQUIPMENT
For Unity Pro V4.0 and earlier versions, do not use links to connect function blocks outputs, when
your application relies on persistent output data of an EF.
Failure to follow these instructions can result in injury or equipment damage.

NOTE: With Unity Pro V4.0 and earlier versions the deactivation of an EF (EN=0) causes links
connected to its Input/Output to be reset. To transfer the state of the signal do not use a link. A
variable must be connected to the EF’s output and must be used to connect the input of the
element. With Unity Pro V4.1 and later versions you can maintain the output links even if an EF is
deactivated by activating the option Maintain output links on disabled EF (EN=0) via the menu
Tools → Program → Languages → Common.

24 33002519 09/2020
Block Types and their Applications

Elementary Function Block


Elementary function blocks (EFB) have an internal status. If the inputs have the same values, the
value on the outputs can have another value during the individual executions. For example, with a
counter, the value on the output is incremented.
An elementary function block is represented in the graphical languages (FBD and LD) as a block
frame with inputs and outputs. The inputs are represented on the left and the outputs on the right
of the block frame. The name of the function block, that is the function block type, is shown in the
center of the block frame. The instance name is displayed above the block frame.

Derived Function Block


Derived function blocks (DFBs) have the same properties as elementary function blocks. They are
created by the user in the programming languages FBD, LD, IL and/or ST.

Procedure
Procedures are functions with several outputs. They have no internal state.
The only difference from elementary functions is that procedures can have more than one output
and they support variables of the VAR_IN_OUT data type.
Procedures do not return a value.
Procedures are a supplement to IEC 61131-3 and must be enabled explicitly.
There is no visual difference between procedures and elementary functions.
NOTE: Unity Pro is the former name of Control Expert for version 13.1 or earlier.

CAUTION
UNEXPECTED BEHAVIOR OF EQUIPMENT
For Unity Pro V4.0 and earlier versions, do not use links to connect function blocks outputs, when
your application relies on persistent output data of an EF.
Failure to follow these instructions can result in injury or equipment damage.

NOTE: With Unity Pro V4.0 and earlier versions the deactivation of an EF (EN=0) causes links
connected to its Input/Output to be reset. To transfer the state of the signal do not use a link. A
variable must be connected to the EF’s output and must be used to connect the input of the
element. With Unity Pro V4.1 and later versions you can maintain the output links even if an EF is
deactivated by activating the option Maintain output links on disabled EF (EN=0) via the menu
Tools → Program → Languages → Common.

33002519 09/2020 25
Block Types and their Applications

FFB Structure

Structure
Each FFB is made up of an operation (name of the FFB), the operands are required for the
operation (formal and actual parameters) and an instance name for elementary/derived function
blocks.
Call of a function block in the FBD programming language:

CAUTION
UNEXPECTED APPLICATION BEHAVIOR
Do not call several times the same block instance within a PLC cycle
Failure to follow these instructions can result in injury or equipment damage.

26 33002519 09/2020
Block Types and their Applications

Formal call of a function block in the ST programming language:

Operation
The operation determines which function is to be executed with the FFB, e.g. shift register,
conversion operations.

Operand
The operand specifies what the operation is to be executed with. With FFBs, this consists of formal
and actual parameters.

Formal/actual parameters
Inputs and outputs are required to transfer values to or from an FFB. These are called formal
parameters.
Objects are linked to formal parameters; these objects contain the current process states. They are
called actual parameters.
At program runtime, the values from the process are transferred to the FFB via the actual
parameters and then output again after processing.
The data type of the actual parameters must match the data type of the input/output (formal
parameters). The only exceptions are generic inputs/outputs whose data type is determined by the
actual parameter. If the actual parameters consist of literals, a suitable data type is selected for the
function block.

33002519 09/2020 27
Block Types and their Applications

FFB Call in IL/ST


In text languages IL and ST, FFBs can be called in formal and in informal form. For detail, refer to
chapter Programming Language (see EcoStruxure™ Control Expert, Program Languages and
Structure, Reference Manual).
Example of a formal function call:
out:=LIMIT (MN:=0, IN:=var1, MX:=5);
Example of an informal function call:
out:=LIMIT (0, var1, 5);
NOTE: The use of EN and ENO is only possible for formal calls.

VAR_IN_OUT variable
FFBs are often used to read a variable at an input (input variables), to process it and to output the
altered values of the same variable (output variables).
This special type of input/output variable is also called a VAR_IN_OUT variable.
The input and output variable are linked in the graphic languages (FBD and LD) using a line
showing that they belong together.
Function block with VAR_IN_OUT variable in FBD:

Function block with VAR_IN_OUT variable in ST:


MY_EXAMP1 (IN1:=Input1, IN2:=Input2, IO1:=Comb_IN_OUT,
OUT1=>Output1, OUT2=>Output2);
The following points must be considered when using FFBs with VAR_IN_OUT variables:
 The VAR_IN_OUT inputs must be assigned a variable.
 Literals or constants cannot be assigned to VAR_IN_OUT inputs/outputs.

The following additional limitations apply to the graphic languages (FBD and LD):
 When using graphic connections, VAR_IN_OUT outputs can only be connected with
VAR_IN_OUT inputs.
 Only one graphical link can be connected to a VAR_IN_OUT input/output.
 Different variables/variable components can be connected to the VAR_IN_OUT input and the
VAR_IN_OUT output. In this case the value of the variables/variable component on the input is
copied to the output variables/variable component.

28 33002519 09/2020
Block Types and their Applications

 No negations can be used on VAR_IN_OUT inputs/outputs.


 A combination of variable/address and graphic connections is not possible for VAR_IN_OUT
outputs.

33002519 09/2020 29
Block Types and their Applications

EN and ENO

Description
An EN input and an ENO output can be configured for the FFBs.
If the value of EN is equal to "0" when the FFB is invoked, the algorithms defined by the FFB are
not executed and ENO is set to "0".
If the value of EN is equal to "1" when the FFB is invoked, the algorithms defined by the FFB will
be executed. After the algorithms have been executed successfully, the value of ENO is set to "1".
If certain error conditions are detected when executing these algorithms, ENO is set to "0".
If the EN pin is not assigned a value, when the FFB is invoked, the algorithm defined by the FFB is
executed (same as if EN equals to "1"), Please refer to Maintain output links on disabled EF
(see EcoStruxure™ Control Expert, Operating Modes).
If the algorithms are executed successfully, then value of ENO is set to "1", else ENO is set to "0".
If ENO is set to "0" (caused by EN=0 or a detected error condition during execution or unsuccessful
algorithm execution):
 Function blocks
 EN/ENO handling with function blocks that (only) have one link as an output parameter:

If EN from FunctionBlock_1 is set to "0", the output connection OUT from Function-
Block_1 retains the status it had in the last correctly executed cycle.
 EN/ENO handling with function blocks that have one variable and one link as output
parameters:

If EN from FunctionBlock_1 is set to "0", the output connection OUT from Function-
Block_1 retains the status it had in the last correctly executed cycle. The variable OUT1 on
the same pin, either retains its previous status or can be changed externally without
influencing the connection. The variable and the link are saved independently of each other.

30 33002519 09/2020
Block Types and their Applications

 Functions/Procedures
NOTE: Unity Pro is the former name of Control Expert for version 13.1 or earlier.

CAUTION
UNEXPECTED BEHAVIOR OF EQUIPMENT
For Unity Pro V4.0 and earlier versions, do not use links to connect function blocks outputs,
when your application relies on persistent output data of an EF.
Failure to follow these instructions can result in injury or equipment damage.

NOTE: With Unity Pro V4.0 and earlier versions the deactivation of an EF (EN=0) causes links
connected to its Input/Output to be reset. To transfer the state of the signal do not use a link. A
variable must be connected to the EF’s output and must be used to connect the input of the
element. With Unity Pro V4.1 and later versions you can maintain the output links even if an EF
is deactivated by activating the option Maintain output links on disabled EF (EN=0) via the menu
Tools → Program → Languages → Common.
As defined in IEC61131-3, the outputs from deactivated functions (EN-input set to "0") is
undefined. (The same applies to procedures.)
Here is an explanation of the output status in this case:
 EN/ENO handling with functions/procedures that (only) have one link as an output
parameter:

If EN from Function/Procedure_1 is set to "0", the output connection OUT from


Function/Procedure_1 is also set to "0".
 EN/ENO handling with function blocks that have one variable and one link as output
parameters:

If EN from Function/Procedure_1 is set to "0", the output connection OUT from


Function/Procedure_1 is also set to "0". The variable OUT1 on the same pin, either
retains its previous status or can be changed externally without influencing the connection.
The variable and the link are saved independently of each other.
The output behavior of the FFBs does not depend on whether the FFBs are called up without
EN/ENO or with EN=1.

33002519 09/2020 31
Block Types and their Applications

Conditional/Unconditional FFB Call


"Unconditional" or "conditional" calls are possible with each FFB. The condition is realized by pre-
linking the input EN.
 EN connected
conditional calls (the FFB is only processed if EN = 1)
 EN shown, hidden, and marked TRUE, or shown and not occupied
unconditional calls (FFB is processed independent from EN)
NOTE: For disabled function blocks (EN = 0) with an internal time function (e.g. DELAY), time
seems to keep running, since it is calculated with the help of a system clock and is therefore
independent of the program cycle and the release of the block.

CAUTION
UNEXPECTED APPLICATION EQUIPMENT
Do not disable function blocks with internal time function during their operation.
Failure to follow these instructions can result in injury or equipment damage.

Note for IL and ST


The use of EN and ENO is only possible in the text languages for a formal FFB call, e.g.
MY_BLOCK (EN:=enable, IN1:=var1, IN2:=var2,
ENO=>error, OUT1=>result1, OUT2=>result2);
Assigning the variables to ENO must be done with the operator =>.
With an informal call, EN and ENO cannot be used.

32 33002519 09/2020
EcoStruxure™ Control Expert
Availability of the blocks
33002519 09/2020

Chapter 2
Block Availability on Various Hardware Platforms

Block Availability on Various Hardware Platforms

Block Availability on the Various Hardware Platforms

Introduction
Not all blocks are available on all hardware platforms. The blocks available on your hardware
platform can be found in the following tables.

Arrays
Availability of the blocks:

Block name Block type M340 M580 Quantum Momentum Premium defined in IEC 61131-3
ADD_***_*** EF + + + + + -
AND_***_*** EF + + + + + -
COPY_***_*** EF + + + + + -
DIV_***_*** EF + + + + + -
EQUAL_*** EF + + + + + -
EXTRACT Procedure + + + + + -
FIND_EQ_*** EF + + + + + -
FIND_EQP_*** EF + + + + + -
FIND_GT_*** EF + + + + + -
FIND_LT_*** EF + + + + + -
LENGHT_*** EF + + + + + -
MAX_*** EF + + + + + -
MIN_*** EF + + + + + -
MOD_***_*** EF + + + + + -
MOVE_***_*** Procedure + + + + + -
(direct assignment)
MOVE_***_*** Procedure + + + + + -
(conversion)
MUL_***_*** EF + + + + + -
NOT_*** EF + + + + + -
OCCUR_*** EF + + + + + -
OR_***_*** EF + + + + + -

33002519 09/2020 33
Availability of the blocks

Block name Block type M340 M580 Quantum Momentum Premium defined in IEC 61131-3
ROL_*** Procedure + + + + + -
ROR_*** Procedure + + + + + -
SIZEOF EF + + + + + -
SORT_*** Procedure + + + + + -
SUB_***_*** EF + + + + + -
SUM_*** EF + + + + + -
SWAP_*** Procedure + + + + + -
XOR_***_*** EF + + + + + -

Legend:
+ Yes
- No

CLC_INT
Availability of the blocks:

Block name Block type M340 M580 Quantum Momentum Premium defined in IEC 61131-3
PID_INT Procedure + + + + + -
PWM_INT Procedure + + + + + -
SERVO_INT Procedure + + + + + -

Legend:
+ Yes
- No

Comparison
Availability of the blocks:

Block name Block type M340 M580 Quantum Momentum Premium defined in IEC 61131-3
EQ EF + + + + + +
GE EF + + + + + +
GT EF + + + + + +
LE EF + + + + + +
LT EF + + + + + +
NE EF + + + + + +

34 33002519 09/2020
Availability of the blocks

Block name Block type M340 M580 Quantum Momentum Premium defined in IEC 61131-3
Legend:
+ Yes
- No

Date & Time


Availability of the blocks:

Block name Block type M340 M580 Quantum Momentum Premium defined in IEC 61131-3
ADD_***_TIME EF + + + + + +
DIVTIME EF + + + + + +
MULTIME EF + + + + + +
SUB_***_*** EF + + + + + +
SUB_***_TIME EF + + + + + +

Legend:
+ Yes
- No

Logic
Availability of the blocks:

Block name Block type M340 M580 Quantum Momentum Premium defined in IEC 61131-3
AND EF + + + + + +
F_TRIG EFB + + + + + +
FE EF + + + + + -
NOT EF + + + + + +
OR EF + + + + + +
R_TRIG EFB + + + + + +
RE EF + + + + + -
RESET Procedure + + + + + -
ROL EF + + + + + +
ROR EF + + + + + +
RS EFB + + + + + +
SET Procedure + + + + + -
SHL EF + + + + + +
SHR EF + + + + + +

33002519 09/2020 35
Availability of the blocks

Block name Block type M340 M580 Quantum Momentum Premium defined in IEC 61131-3
SR EFB + + + + + +
TRIGGER EFB + + + + + -
XOR EF + + + + + +

Legend:
+ Yes
- No

Mathematics
Availability of the blocks:

Block name Block type M340 M580 Quantum Momentum Premium defined in IEC 61131-3
ABS EF + + + + + +
ACOS EF + + + + + +
ADD EF + + + + + +
ADD_TIME EF + + + + + +
ASIN EF + + + + + +
ATAN EF + + + + + +
COS EF + + + + + +
DEC Procedure + + + + + -
DIV EF + + + + + +
DIVMOD Procedure + + + + + -
EXP EF + + + + + +
EXPT_REAL EF + + + + + +
INC Procedure + + + + + -
LN EF + + + + + +
LOG EF + + + + + +
MOD EF + + + + + +
MOVE EF + + + + + +
MUL EF + + + + + +
NEG EF + + + + + -
SATURATION Procedure + + + + + -
(see page 275)
SIGN EF + + + + + -
SIN EF + + + + + +

36 33002519 09/2020
Availability of the blocks

Block name Block type M340 M580 Quantum Momentum Premium defined in IEC 61131-3
SQRT EF + + + + + DINT: -
INT: -
REAL: +
SUB EF + + + + + +
SUB_TIME EF + + + + + +
TAN EF + + + + + +

Legend:
+ Yes
- No

REF
Availability of the blocks:

Block name Block type M340 M580 Quantum Momentum Premium defined in IEC 61131-3
REF EF + + + + + +

Legend:
+ Yes
- No

Statistical
Availability of the blocks:

Block name Block type M340 M580 Quantum Momentum Premium defined in IEC 61131-3
AVE EF + + + + + -
LIMIT EF + + + + + +
LIMIT_IND Procedure + + + + + -
MAX EF + + + + + +
MIN EF + + + + + +
MUX EF + + + + + +
SEL EF + + + + + +

Legend:
+ Yes
- No

33002519 09/2020 37
Availability of the blocks

Strings
Availability of the blocks:

Block name Block type M340 M580 Quantum Momentum Premium defined in IEC 61131-3
CONCAT_STR EF + + + + + -
DELETE_INT EF + + + + + +
EQUAL_STR EF + + + + + +
FIND_INT EF + + + + + +
INSERT_INT EF + + + + + +
LEFT_INT EF + + + + + +
LEN_INT EF + + + + + +
MID_INT EF + + + + + +
REPLACE_INT EF + + + + + +
RIGHT_INT EF + + + + + +

Legend:
+ Yes
- No

Timers & Counter


Availability of the blocks:

Block name Block type M340 M580 Quantum Momentum Premium defined in IEC 61131-3
CTD EFB + + + + + +
CTD_*** EFB + + + + + -
CTU EFB + + + + + +
CTU_*** EFB + + + + + -
CTUD EFB + + + + + +
CTUD_*** EFB + + + + + -
TOF EFB + + + + + +
TON EFB + + + + + +
TP EFB + + + + + +

Legend:
+ Yes
- No

38 33002519 09/2020
Availability of the blocks

Type to Type
Availability of the blocks:

Block name Block type M340 M580 Quantum Momentum Premium defined in IEC 61131-3
ARINT_TO_DATE EF + + + + + -
ARINT_TO_DT EF + + + + + -
ARINT_TO_TOD EF + + + + + -
ASCII_TO_STRING EF + + + + + -
ASCII_TO_STRING_INV EF + + + + + -
BCD_TO_INT EF + + + + + +
BIT_TO_BYTE EF + + + + + -
BIT_TO_WORD EF + + + + + -
BOOL_TO_*** EF + + + + + +
BYTE_AS_WORD EF + + + + + -
BYTE_TO_BIT Procedure + + + + + -
BYTE_TO_*** EF + + + + + +
DATE_TO_ARINT EF + + + + + +
DATE_TO_STRING EF + + + + + +
DBCD_TO_*** EF + + + + + -
DEG_TO_RAD EF + + + + + -
DINT_AS_WORD Procedure + + + + + -
DINT_TO_*** EF + + + + + +
DINT_TO_DBCD EF + + + + + -
DINT_TO_STRING EF + + + + + +
DT_TO_ARINT EF + + + + + +
DT_TO_STRING EF + + + + + +
DWORD_TO_*** EF + + + + + +
GRAY_TO_INT EF + + + + + -
INT_AS_DINT EF + + + + + -
INT_TO_*** EF + + + + + +
INT_TO_BCD EF + + + + + -
INT_TO_DBCD EF + + + + + -
INT_TO_STRING EF + + + + + +
RAD_TO_DEG EF + + + + + -
REAL_AS_WORD Procedure + + + + + -
REAL_TO_*** EF + + + + + +

33002519 09/2020 39
Availability of the blocks

Block name Block type M340 M580 Quantum Momentum Premium defined in IEC 61131-3
REAL_TO_STRING EF + + + + + +
REAL_TRUNC_*** EF + + + + + +
STRING_TO_ASCII EF + + + + + -
STRING_TO_ASCII_INV EF + + + + + -
STRING_TO_*** EF + + + + + +
TIME_AS_WORD Procedure + + + + + -
TIME_TO_*** EF + + + + + +
TIME_TO_STRING EF + + + + + +
TOD_TO_ARINT EF + + + + + +
TOD_TO_STRING EF + + + + + +
UDINT_AS_WORD Procedure + + + + + -
UDINT_TO_*** EF + + + + + +
UINT_TO_*** EF + + + + + +
WORD_AS_BYTE Procedure + + + + + -
WORD_AS_DINT EF + + + + + -
WORD_AS_REAL EF + + + + + -
WORD_AS_TIME EF + + + + + -
WORD_AS_UDINT EF + + + + + -
WORD_TO_BIT Procedure + + + + + -
WORD_TO_*** EF + + + + + +

Legend:
+ Yes
- No

40 33002519 09/2020
EcoStruxure™ Control Expert
Arrays
33002519 09/2020

Part II
Arrays

Arrays

Overview
This section describes the elementary functions and elementary function blocks of the Arrays
family.

What Is in This Part?


This part contains the following chapters:
Chapter Chapter Name Page
3 ADD_***_***: Addition of a number to elements of an array or addition of two 43
arrays
4 AND_***_***: Logical AND between arrays and variables 47
5 COPY_***_***: Copy on arrays 51
6 DIV_***_***: Division of arrays 55
7 EQUAL_***: Comparison of two arrays 59
8 FIND_EQ_***: First element of an array equal to a given value 63
9 FIND_EQP_***: First element of an array equal to a value starting from a given 67
rank
10 FIND_GT_***: First element of an array greater than a given value 71
11 FIND_LT_***: First element of an array less than a given value 75
12 LENGTH_***: Length of an array 79
13 MAX_***: Maximum value of array elements 83
14 MIN_***: Minimum value of array elements 85
15 MOD_***_***: Remainder of division of arrays 87
16 MOVE_***_***: Assignment to arrays 91
17 MOVE_***_***: Array conversion 93
18 MUL_***_***: Multiplication of arrays 95
19 NOT_***: Logical negation of arrays 99
20 OCCUR_***: Occurrence of a value in an array 101
21 OR_***_***: Logical OR between arrays and variables 103
22 ROL_***: Rotate shift to left 107
23 ROR_***: Rotate shift to right 109
24 SORT_***: Ascending or descending sort 111

33002519 09/2020 41
Arrays

Chapter Chapter Name Page


25 SUB_***_***: Subtraction from arrays 113
26 SUM_***: Sum of array elements 117
27 SWAP_***: Permutation of the bytes of an array 119
28 XOR_***_***: Exclusive OR between arrays 121

42 33002519 09/2020
EcoStruxure™ Control Expert
ADD_***_***
33002519 09/2020

Chapter 3
ADD_***_***: Addition of a number to elements of an array or addition of two arrays

ADD_***_***: Addition of a number to elements of an array or


addition of two arrays

Description

Function description
The ADD_***_*** function adds a number to the elements of an array or adds two arrays
together.
The additional parameters EN and ENO can be configured.

Available functions
The available functions for adding a number to the elements of an array are as follows:
 ADD_ARINT_INT (addition of each element of an array of INTs to an INT).
 ADD_ARDINT_DINT (addition of each element of an array of DINTs to a DINT).
The available functions for adding the elements of one array to the elements of another array:
 ADD_ARINT (Sum of the respective elements of both INT arrays).
 ADD_ARDINT (Sum of the respective elements of both DINT arrays).

Representation in FBD
Representation applied to the sum of an integer and an integer array:

33002519 09/2020 43
ADD_***_***

Representation in LD
Representation applied to the sum of an integer and an integer array:

Representation in IL
Representation applied to the sum of an integer and an integer array:
LD Input_IN1
ADD_ARINT_INT Input_IN2
ST Array1

Representation in ST
Representation applied to the sum of an integer and an integer array:
Array1 := ADD_ARINT_INT(Input_IN1,Input_IN2);

44 33002519 09/2020
ADD_***_***

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Input_ IN1 ARRAY [n..m] OF INT, Input_IN1 is either a single or double integer, or an array of
ARRAY [n..m] OF DINT single or double integers, n and m are positive or negative
integers or nil.
Input_IN2 INT, Input_ IN2 is either a single or double integer, or an array of
DINT, single or double integers, n and m are positive or negative
ARRAY [n..m] OF INT, integers or nil.
ARRAY [n..m] OF DINT

The following table describes the output parameters:

Parameter Type Comment


Array1 ARRAY [n..m] OF INT According to the type of Input_ IN1 and Input_IN2, each
ARRAY [n..m] OF DINT element of Array1 is the sum:
 of a single or double integer and the corresponding element
of an array,
 the corresponding elements of two arrays.

Runtime errors
The management of the %S18 system bit is identical to that for operations on words or double
words.
If an operation between two elements sets the %S18 bit (overflow or division by zero), the result
for this operation is incorrect, but the operation on the following elements is carried out correctly.

33002519 09/2020 45
ADD_***_***

46 33002519 09/2020
EcoStruxure™ Control Expert
AND_***_***
33002519 09/2020

Chapter 4
AND_***_***: Logical AND between arrays and variables

AND_***_***: Logical AND between arrays and variables

Description

Function description
The AND_***_*** function carries out a logical AND (bit to bit) between:
 the elements of two arrays,
 between a single type variable and the elements of an array,
 between the elements of an array and a single type variable.
NOTE: The result is always an array.
The additional parameters EN and ENO can be configured.

Available functions
The functions available in the general library are the following:
 AND_AREBOOL (logical AND of two EBOOL arrays).
 AND_ARWORD (logical AND of two WORD arrays).
 AND_ARWORD_WORD (logical AND of each element of a WORD array with a WORD).
 AND_ARDWORD_DWORD (logical AND of each element of a DWORD array with a DWORD).
 AND_ARDWORD (logical AND of two DWORD arrays).
The functions available in the Obsolete library are the following:
 AND_ARINT_INT (logical AND of each element of an INT array with an INT).
 AND_ARDINT_DINT (logical AND of each element of a DINT array with a DINT).
 AND_ARINT (logical AND of each element of an INT array with each element corresponding to
another INT array).
 AND_ARDINT (logical AND of each element of a DINT array with each element corresponding
to another DINT array).

Representation in FBD
Representation applied to a 16-bit string and a 16-bit string array:

33002519 09/2020 47
AND_***_***

Representation in LD
Representation applied to a 16-bit string and a 16-bit string array:

Representation in IL
Representation applied to a 16-bit string and a 16-bit string array:
LD Input_IN1
AND_ARWORD_WORD Input_IN2
ST Array1

Representation in ST
Representation applied to a 16-bit string and a 16-bit string array:
Array1:= AND_ARWORD_WORD(Input_IN1,Input_IN2);

48 33002519 09/2020
AND_***_***

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Input_IN1 ARRAY [n..m] OF EBOOL, n and m maximum and minimum limits.
WORD,
ARRAY [n..m] OF WORD,
DWORD,
ARRAY [n..m] OF DWORD,
INT,
ARRAY [n..m] OF INT,
DINT,
ARRAY [n..m] OF DINT
Input_IN2 ARRAY [n..m] OF EBOOL, n and m are positive or negative integers or
WORD, nil.
ARRAY [n..m] OF WORD,
DWORD,
ARRAY [n..m] OF DWORD,
INT,
ARRAY [n..m] OF INT,
DINT,
ARRAY [n..m] OF DINT

The following table describes the output parameters:

Parameter Type Comment


Array1 ARRAY [n..m] OF EBOOL, The elements of Array1 are the result of the
ARRAY [n..m] OF WORD, logical AND (bit to bit) between Input_IN1
ARRAY [n..m] OF DWORD, and Input_IN2, which can be respectively:
ARRAY [n..m] OF INT,  an array and a single variable,
ARRAY [n..m] OF DINT  an array and an array.

33002519 09/2020 49
AND_***_***

50 33002519 09/2020
EcoStruxure™ Control Expert
COPY_***_***
33002519 09/2020

Chapter 5
COPY_***_***: Copy on arrays

COPY_***_***: Copy on arrays

Description

Function description
The COPY_***_*** function copies a series of contiguous elements from one array into another
array. The arrays are of different or identical types and the target zone is fixed by the parameters
of the function.
The additional parameters EN and ENO can be configured.

WARNING
UNEXPECTED APPLICATION BEHAVIOR
Check that data being written in the target array is valid when using the COPY_***_*** function.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

NOTE: The COPY_***_*** function can result in unintended data values. For example, copying
input values on output values can lead to corrupted data and unexpected behavior of the
application.

Available functions
The available functions are as follows:
 COPY_AREBOOL_ARINT,
 COPY_AREBOOL_AREBOOL,
 COPY_AREBOOL_ARDINT,
 COPY_ARINT_AREBOOL,
 COPY_ARDINT_AREBOOL.

33002519 09/2020 51
COPY_***_***

Representation in FBD
Representation applied to the assignment of a zone of an integer array to a zone of a bit array:

Representation in LD
Representation applied to the assignment of a zone of an integer array to a zone of a bit array:

Representation in IL
Representation applied to the assignment of a zone of an integer array to a zone of a bit array:
LD Array1
COPY_ARINT_AREBOOL Begin_Row, Element_Number, Destination_Row
ST Result_Array

Representation in ST
Representation applied to the assignment of a zone of an integer array to a zone of a bit array:
Result_Array := COPY_ARINT_AREBOOL(Array1, Begin_Row, Element_Number,
Destination_Row);

52 33002519 09/2020
COPY_***_***

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Array1 ARRAY [n..m] OF EBOOL, n and m are positive or negative integers or nil.
ARRAY [n..m] OF INT,
ARRAY [n..m] OF DINT
Begin_Row INT Rank of first element to be copied from the array Array1.

Note: The first element of the array has the rank 0.


Element_Number INT Number of elements to be copied from the array Array1.
Destination_Row INT Target rank in the array Result_Array.

The following table describes the output parameters:

Parameter Type Comment


Result_Array ARRAY [n..m] OF EBOOL, n and m are positive or negative integers or nil.
ARRAY [n..m] OF INT, Target array which contains the elements selected
ARRAY [n..m] OF DINT from Array1.

NOTE: if the number of elements to be extracted is greater than the remaining size, starting from
the rankBegin_Row, the function extracts all the elements fromBegin_Row to the last element of
the array.
If the number of elements to be extracted is greater than the space available starting from the
rankDestination_Row, the copy function runs to the last element of the array.
A negative value of Begin_Row, Element_Number and Destination_Row is interpreted as
null.

33002519 09/2020 53
COPY_***_***

54 33002519 09/2020
EcoStruxure™ Control Expert
DIV_***_***
33002519 09/2020

Chapter 6
DIV_***_***: Division of arrays

DIV_***_***: Division of arrays

Description

Function description
The DIV_***_*** function carries out the division:
 of a number by the elements of an array,
 of the elements of an array by a number,
 of the elements of an array by the respective elements of another array.
The additional parameters EN and ENO can be configured.

Available functions
The available functions for division of a number by the elements of an array are as follows:
 DIV_INT_ARINT,
 DIV_DINT_ARDINT.
The available functions for division of the elements of an array by a number are as follows:
 DIV_ARINT_INT,
 DIV_ARDINT_DINT.
The available functions for division of the elements of an array by the respective elements of
another array are as follows:
 DIV_ARINT,
 DIV_ARDINT.

Representation in FBD
Representation applied to the division of an integer by the elements of an integer array:

33002519 09/2020 55
DIV_***_***

Representation in LD
Representation applied to the division of an integer by the elements of an integer array:

Representation in IL
Representation applied to the division of an integer by the elements of an integer array:
LD Input_IN1
DIV_INT_ARINT Input_IN2
ST Array1

Representation in ST
Representation applied to the division of an integer by the elements of an integer array:
Array1:= DIV_INT_ARINT(Input_IN1,Input_IN2);

56 33002519 09/2020
DIV_***_***

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Input_IN1 INT, Input_IN1 is either a single or double integer,
DINT, or an array of single or double integers, n and m
ARRAY [n..m] OF INT, are positive or negative integers or nil.
ARRAY [n..m] OF DINT
Input_IN2 INT, Input_ IN2 is either a single or double integer,
DINT, or an array of single or double integers, n and m
ARRAY [n..m] OF INT, are positive or negative integers or nil.
ARRAY [n..m] OF DINT

The following table describes the output parameters:

Parameter Type Comment


Array1 ARRAY [n..m] OF INT According to the type of Input_IN1 and Input_IN2, each
ARRAY [n..m] OF DINT element of Array1 is the division:
 of a single or double integer Input_IN1 by the
corresponding element of the array Input_IN2 or else,
 of the elements of the array Input_IN1 by single or double
integers Input_IN2 or else,
 of the elements of the array Input_IN1 by the respective
elements of the array Input_ IN2.

Runtime errors
The management of the %S18 system bit is identical to that for operations on words or double
words. In the case of division by zero, the value of the result is equal to the value of the numerator.
If an operation between two elements sets the %S18 bit (overflow or division by zero), the result
for this operation is incorrect, but the operation on the following elements is carried out correctly.

33002519 09/2020 57
DIV_***_***

58 33002519 09/2020
EcoStruxure™ Control Expert
EQUAL_****
33002519 09/2020

Chapter 7
EQUAL_***: Comparison of two arrays

EQUAL_***: Comparison of two arrays

Description

Function description
The EQUAL_*** function compares two arrays element by element.
The additional parameters EN and ENO can be configured.

Available functions
The available functions are as follows:
 EQUAL_ARWORD,
 EQUAL_ARDWORD,
 EQUAL_ARINT,
 EQUAL_ARDINT,
 EQUAL_ARREAL.

Representation in FBD
Representation applied to integer arrays:

33002519 09/2020 59
EQUAL_****

Representation in LD
Representation applied to integer arrays:

Representation in IL
Representation applied to integer arrays:
LD Array1
EQUAL_ARINT Array2, Position
ST Equal1

Representation in ST
Representation applied to integer arrays:
Equal1:= EQUAL_ARINT(Array1, Array2, Position);

60 33002519 09/2020
EQUAL_****

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Array1 ARRAY [n..m] OF WORD n and m are positive or negative integers or nil.
ARRAY [n..m] OF DWORD
ARRAY [n..m] OF INT
ARRAY [n..m] OF DINT
ARRAY [n..m] OF REAL
Array2 ARRAY [n..m] OF WORD n and m are positive or negative integers or nil.
ARRAY [n..m] OF DWORD
ARRAY [n..m] OF INT
ARRAY [n..m] OF DINT
ARRAY [n..m] OF REAL
Position INT Rank of first element from which the search is launched.

The following table describes the output parameters:

Parameter Type Comment


Equal1 INT Rank of first different elements. If the two arrays are equivalent, Equal1 = -1.

Runtime errors
When the array contains an invalid value, the result of the function contains -2 and the bit %S18 =
1.

33002519 09/2020 61
EQUAL_****

62 33002519 09/2020
EcoStruxure™ Control Expert
FIND_EQ_***
33002519 09/2020

Chapter 8
FIND_EQ_***: First element of an array equal to a given value

FIND_EQ_***: First element of an array equal to a given value

Description

Function description
The FIND_EQ_*** function searches for the first element of an array equal to a given value.
NOTE: Before starting the search, the block immediately writes -1 to its output OUT to indicate that
the value connected to IN2 was not found . Then the block starts the search and updates the
output OUT with the rank value of the first element fullfilling the search criteria.
The additional parameters EN and ENO can be configured.

Available functions
The available functions are as follows:
 FIND_EQ_ARWORD,
 FIND_EQ_ARDWORD,
 FIND_EQ_ARINT,
 FIND_EQ_ARDINT,
 FIND_EQ_ARREAL.

Representation in FBD
Representation applied to an integer array:

33002519 09/2020 63
FIND_EQ_***

Representation in LD
Representation applied to an integer array:

Representation in IL
Representation applied to an integer array:
LD Array1
FIND_EQ_ARINT Value1
ST Row_Value1

Representation in ST
Representation applied to an integer array:
Row_Value1:= FIND_EQ_ARINT(Array1, Value1);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Array1 ARRAY [n..m] OF INT n and m are positive or negative integers or nil.
ARRAY [n..m] OF DINT
ARRAY [n..m] OF WORD
ARRAY [n..m] OF DWORD
ARRAY [n..m] OF REAL
Value1 INT, DINT, WORD, DWORD, Value whose rank is searched for in Array1.
REAL. Of the same type as the elements of the array Array 1.

The following table describes the output parameters:

Parameter Type Comment


Row_Value1 INT Rank of first element of Array1 equal to Value1. If none of the
elements of the array is equal to Value1, Row_Value1 = -1

64 33002519 09/2020
FIND_EQ_***

Runtime errors
When the array contains an invalid value or if Value1 is an invalid value, the result of the function
contains-2 and the bit %S18 = 1.

33002519 09/2020 65
FIND_EQ_***

66 33002519 09/2020
EcoStruxure™ Control Expert
FIND_EQP_***
33002519 09/2020

Chapter 9
FIND_EQP_***: First element of an array equal to a value starting from a given rank

FIND_EQP_***: First element of an array equal to a value


starting from a given rank

Description

Function description
The FIND_EQP_*** function searches for the first element of an array equal to a value starting
from a given rank.
NOTE: Before starting the search, the block immediately writes -1 to its output OUT to indicate that
the value connected to IN2 was not found . Then the block starts the search and updates the
output OUT with the rank value of the first element fullfilling the search criteria.
The additional parameters EN and ENO can be configured.

Available functions
The available functions are as follows:
 FIND_EQP_ARWORD,
 FIND_EQP_ARDWORD,
 FIND_EQP_ARINT,
 FIND_EQP_ARDINT,
 FIND_EQP_ARREAL.

Representation in FBD
Representation applied to an integer array:

33002519 09/2020 67
FIND_EQP_***

Representation in LD
Representation applied to an integer array:

Representation in IL
Representation applied to an integer array:
LD Array1
FIND_EQP_ARINT Value1, Begin1
ST Row_Value1

Representation in ST
Representation applied to an integer array:
Row_Value1:= FIND_EQP_ARINT(Array1, Value1, Begin1);

68 33002519 09/2020
FIND_EQP_***

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Array1 ARRAY [n..m] OF WORD n and m are positive or negative integers or nil.
ARRAY [n..m] OF DWORD
ARRAY [n..m] OF INT
ARRAY [n..m] OF DINT
ARRAY [n..m] OF REAL
Value1 WORD, DWORD, INT, DINT, Value whose rank is searched for in Array1.
REAL. Of the same type as the elements of the array Array 1.
Begin1 INT Rank the search starts from

The following table describes the output parameters:

Parameter Type Comment


Row_Value1 INT Rank of first element of Array1 equal to Value1. If none of the elements of
the array is equal to Value1, Row_Value1 = -1

Note: Row_Value1 indicates the rank in relation to the start of the array.

Runtime errors
When the array contains an invalid value or if Value1 is an invalid value, the result of the function
contains-2 and the bit %S18 = 1.

33002519 09/2020 69
FIND_EQP_***

70 33002519 09/2020
EcoStruxure™ Control Expert
FIND_GT_***
33002519 09/2020

Chapter 10
FIND_GT_***: First element of an array greater than a given value

FIND_GT_***: First element of an array greater than a given


value

Description

Function description
The FIND_GT_*** function searches for the first element of an array greater than a given value.
NOTE: Before starting the search, the block immediately writes -1 to its output OUT to indicate that
the value connected to IN2 was not found . Then the block starts the search and updates the
output OUT with the rank value of the first element fullfilling the search criteria.
The additional parameters EN and ENO can be configured.

Available functions
The available functions are as follows:
 FIND_GT_ARWORD,
 FIND_GT_ARDWORD,
 FIND_GT_ARINT,
 FIND_GT_ARDINT,
 FIND_GT_ARREAL.

Representation in FBD
Representation applied to an integer array:

33002519 09/2020 71
FIND_GT_***

Representation in LD
Representation applied to an integer array:

Representation in IL
Representation applied to an integer array:
LD Array1
FIND_GT_ARINT Value1
ST Row_Value1

Representation in ST
Representation applied to an integer array:
Row_Value1:= FIND_GT_ARINT(Array1, Value1);

Description of parameters
The following table describes the input parameters:

Input Type Comment


Array1 ARRAY [n..m] OF WORD n and m are positive or negative integers or nil.
ARRAY [n..m] OF DWORD
ARRAY [n..m] OF INT
ARRAY [n..m] OF DINT
ARRAY [n..m] OF REAL
Value1 WORD, DWORD, INT , Value for which the rank of the first greater value is searched for in
DINT, REAL Array1.
Of the same type as the elements of the array Array 1.

The following table describes the output parameters:

Output Type Comment


Row_Value1 INT Rank of the first element of Array1 > than Value1. If none of the
elements of the array is greater than Value1, Row_Value1 = -1

72 33002519 09/2020
FIND_GT_***

Runtime errors
When the array contains an invalid value or if Value1 is an invalid value, the result of the function
contains-2 and the bit %S18 = 1.

33002519 09/2020 73
FIND_GT_***

74 33002519 09/2020
EcoStruxure™ Control Expert
FIND_LT_***
33002519 09/2020

Chapter 11
FIND_LT_***: First element of an array less than a given value

FIND_LT_***: First element of an array less than a given value

Description

Function description
The FIND_LT_*** function searches for the first element of an array less than a given value.
NOTE: Before starting the search, the block immediately writes -1 to its output OUT to indicate that
the value connected to IN2 was not found . Then the block starts the search and updates the
output OUT with the rank value of the first element fullfilling the search criteria.
The additional parameters EN and ENO can be configured.

Available functions
The available functions are as follows:
 FIND_LT_ARWORD,
 FIND_LT_ARDWORD,
 FIND_LT_ARINT,
 FIND_LT_ARDINT,
 FIND_LT_ARREAL.

Representation in FBD
Representation applied to an integer array:

33002519 09/2020 75
FIND_LT_***

Representation in LD
Representation applied to an integer array:

Representation in IL
Representation applied to an integer array:
LD Array1
FIND_LT_ARINT Value1
ST Row_Value1

Representation in ST
Representation applied to an integer array:
Row_Value1:= FIND_LT_ARINT(Array1, Value1);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Array1 ARRAY [n..m] OF WORD n and m are positive or negative integers or nil.
ARRAY [n..m] OF DWORD
ARRAY [n..m] OF INT
ARRAY [n..m] OF DINT
ARRAY [n..m] OF REAL
Value1 WORD , DWORD , INT , Value for which a smaller value is searched for in Array1.
DINT, REAL Of the same type as the elements of the array Array 1.

The following table describes the output parameters:

Parameter Type Comment


Row_Value1 INT Rank of the first element of Array1 <
Value1. If none of the elements of the array is
less than Value1, Row_Value1 = -1

76 33002519 09/2020
FIND_LT_***

Runtime errors
When the array contains an invalid value or if Value1 is an invalid value, the result of the function
contains-2 and the bit %S18 = 1.

33002519 09/2020 77
FIND_LT_***

78 33002519 09/2020
EcoStruxure™ Control Expert
LENGTH_***
33002519 09/2020

Chapter 12
LENGTH_***: Length of an array

LENGTH_***: Length of an array

Description

Function description
The LENGTH_*** function calculates the length of an array. It is used mainly with DFBs when the
arrays are not explicitly declared.
The additional parameters EN and ENO can be configured.

Available functions
The available functions are as follows:
 LENGTH_AREBOOL,
 LENGTH_ARWORD,
 LENGTH_ARDWORD,
 LENGTH_ARINT,
 LENGTH_ARDINT,
 LENGTH_ARREAL,
 LENGTH_ARBOOL,
 LENGTH_ARBYTE,
 LENGTH_ARDATE,
 LENGTH_ARDT,
 LENGTH_ARSTRING,
 LENGTH_ARTIME,
 LENGTH_ARTOD,
 LENGTH_ARUINT,
 LENGTH_ARUDINT.

Representation in FBD
Representation applied to an integer array:

33002519 09/2020 79
LENGTH_***

Representation in LD
Representation applied to an integer array:

Representation in IL
Representation applied to an integer array:
LD Array1
LENGTH_ARINT
ST Length_Array1

Representation in ST
Representation:
Length_Array1:= LENGTH_ARINT(Array1);

80 33002519 09/2020
LENGTH_***

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Array1 ARRAY [n..m] OF EBOOL n and m are positive or negative integers or nil.
ARRAY [n..m] OF WORD
ARRAY [n..m] OF DWORD
ARRAY [n..m] OF INT
ARRAY [n..m] OF DINT
ARRAY [n..m] OF REAL
ARRAY [n..m] OF BOOL
ARRAY [n..m] OF BYTE
ARRAY [n..m] OF DATE
ARRAY [n..m] OF DT
ARRAY [n..m] OF STRING
ARRAY [n..m] OF TIME
ARRAY [n..m] OF TOD
ARRAY [n..m] OF UINT
ARRAY [n..m] OF UDINT

The following table describes the output parameters:

Parameter Type Comment


Length_Array1 INT Array length (number of array elements).

33002519 09/2020 81
LENGTH_***

82 33002519 09/2020
EcoStruxure™ Control Expert
MAX_***
33002519 09/2020

Chapter 13
MAX_***: Maximum value of array elements

MAX_***: Maximum value of array elements

Description

Function description
The MAX_*** function searches for the maximum value of the elements of an array.
The additional parameters EN and ENO can be configured.

Available functions
The available functions are as follows:
 MAX_ARWORD,
 MAX_ARDWORD,
 MAX_ARINT,
 MAX_ARDINT,
 MAX_ARREAL.

Representation in FBD
Representation applied to an integer array:

Representation in LD
Representation applied to an integer array:

33002519 09/2020 83
MAX_***

Representation in IL
Representation applied to an integer array:
LD Array1
MAX_ARINT
ST Max1

Representation in ST
Representation applied to an integer array:
Max1:= MAX_ARINT(Array1);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Array1 ARRAY [n..m] OF WORD n and m are positive or negative integers or nil.
ARRAY [n..m] OF DWORD
ARRAY [n..m] OF INT
ARRAY [n..m] OF DINT
ARRAY [n..m] OF REAL

The following table describes the output parameters:

Parameter Type Comment


Max1 WORD, DWORD, INT, DINT, Maximum value contained in the array. This
REAL result is of the same type as the array
elements.

Runtime errors
When the array contains an invalid value, the result of the function contains 1.#INF and the bit
%S18 = 1.

84 33002519 09/2020
EcoStruxure™ Control Expert
MIN_***
33002519 09/2020

Chapter 14
MIN_***: Minimum value of array elements

MIN_***: Minimum value of array elements

Description

Function description
The MIN_*** function searches for the minimum value of the elements of an array.
The additional parameters EN and ENO can be configured.

Available functions
The available functions are as follows:
 MIN_ARWORD,
 MIN_ARDWORD,
 MIN_ARINT,
 MIN_ARDINT,
 MIN_ARREAL.

Representation in FBD
Representation applied to an integer array:

Representation in LD
Representation applied to an integer array:

33002519 09/2020 85
MIN_***

Representation in IL
Representation applied to an integer array:
LD Array1
MIN_ARINT
ST Min1

Representation in ST
Representation applied to an integer array:
Min1:= MIN_ARINT(Array1);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Array1 ARRAY [n..m] OF WORD n and m are positive or negative integers or nil.
ARRAY [n..m] OF DWORD
ARRAY [n..m] OF INT
ARRAY [n..m] OF DINT
ARRAY [n..m] OF REAL

The following table describes the output parameters:

Parameter Type Comment


Min1 WORD, DWORD, DINT, INT, Minimum value contained in the array. This
REAL result is of the same type as the array
elements.

Runtime errors
When the array contains an invalid value, the result of the function contains 1.#NAN and the bit
%S18 = 1.

86 33002519 09/2020
EcoStruxure™ Control Expert
MOD_***_***
33002519 09/2020

Chapter 15
MOD_***_***: Remainder of division of arrays

MOD_***_***: Remainder of division of arrays

Description

Function description
The function MOD_***_*** calculates the remainder of the division:
 of a number by the elements of an array,
 of the elements of an array by a number,
 of the elements of an array by the respective elements of another array.
The additional parameters EN and ENO can be configured.

Available functions
The available functions for calculation of the remainder of the division of a number by the elements
of an array are as follows:
 MOD_INT_ARINT,
 MOD_DINT_ARDINT.
The available functions for the calculation of the remainder of the division of the elements of an
array by a number are as follows:
 MOD_ARINT_INT,
 MOD_ARDINT_DINT.
The available functions for the calculation of the remainder of the division of the elements of an
array by the respective elements of another array are as follows:
 MOD_ARINT,
 MOD_ARDINT.

Representation in FBD
Representation applied to the division of an integer by the elements of an integer array:

33002519 09/2020 87
MOD_***_***

Representation in LD
Representation applied to the division of an integer by the elements of an integer array:

Representation in IL
Representation applied to the division of an integer by the elements of an integer array:
LD Input_IN1
MOD_INT_ARINT Input_IN2
ST Array1

Representation in ST
Representation applied to the division of an integer by the elements of an integer array:
Array1:= MOD_INT_ARINT(Input_IN1,Input_IN2);

88 33002519 09/2020
MOD_***_***

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Input_ IN1 INT, Input_IN1 is either a single or double integer,
DINT, or an array of single or double integers, n and m
ARRAY [n..m] OF INT, are positive or negative integers or nil.
ARRAY [n..m] OF DINT
Input_IN2 INT, Input_IN2 is either a single or double integer,
DINT, or an array of single or double integers, n and m
ARRAY [n..m] OF INT, are positive or negative integers or nil.
ARRAY [n..m] OF DINT

The following table describes the output parameters:

Parameter Type Comment


Array1 ARRAY [n..m] OF INT According to the type of Input_IN1 and
ARRAY [n..m] OF DINT Input_IN2, each element of Array1 is the
remainder of the division:
 of a single or double integer Input_IN1 by
the corresponding element of the array
Input_IN2 or else,
 of the elements of the array Input_IN1 by
the single or double integer Input_IN2 or
else,
 of the elements of the array Input_IN1 by
the respective elements of the array
Input_IN2.

Runtime errors
The management of the %S18 system bit is identical to that for operations on words or double
words. The remainder of a division by zero is zero and the system bit is set to 1.
If an operation between two elements sets the %S18 bit (overflow or division by zero), the result
for this operation is incorrect, but the operation on the following elements is carried out correctly.

33002519 09/2020 89
MOD_***_***

90 33002519 09/2020
EcoStruxure™ Control Expert
MOVE_***_***
33002519 09/2020

Chapter 16
MOVE_***_***: Assignment to arrays

MOVE_***_***: Assignment to arrays

Description

Function description
One of the actions of the MOVE_***_*** function is the assignment of an identical value to each
element of an array.
The additional parameters EN and ENO can be configured.

Available functions
The available functions are as follows:
 MOVE_BOOL_AREBOOL,
 MOVE_WORD_ARWORD,
 MOVE_DWORD_ARDWORD,
 MOVE_INT_ARINT,
 MOVE_DINT_ARDINT,
 MOVE_REAL_ARREAL.

Representation in FBD
Representation applied to the assignment of an integer to an integer array:

Representation in LD
Representation applied to the assignment of an integer to an integer array:

33002519 09/2020 91
MOVE_***_***

Representation in IL
Representation applied to the assignment of an integer to an integer array:
LD Val1
MOVE_INT_ARINT Array1

Representation in ST
Representation applied to the assignment of an integer to an integer array:
MOVE_INT_ARINT(Val1, Array1);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Val1 BOOL, Val1 contains the value to be assigned to
WORD, each element of the array Array1.
DWORD, Of the same type as the elements of the array
INT, Array1.
DINT,
REAL.

The following table describes the output parameters:

Parameter Type Comment


Array1 ARRAY [n..m] OF EBOOL, n and m are positive or negative integers or
ARRAY [n..m] OF WORD, nil.
ARRAY [n..m] OF DWORD, Array1 is an array each element of which is
ARRAY [n..m] OF INT, of the value Val1.
ARRAY [n..m] OF DINT
ARRAY [n..m] OF REAL

92 33002519 09/2020
EcoStruxure™ Control Expert
MOVE_***_***
33002519 09/2020

Chapter 17
MOVE_***_***: Array conversion

MOVE_***_***: Array conversion

Description

Function description
One of the actions of the MOVE_***_*** function is to convert an array into a value or a value into
an array.
The additional parameters EN and ENO can be configured.

Available functions
The available functions are as follows:
 MOVE_AREBOOL_INT (conversion of an EBOOL array into an INT).
 MOVE_AREBOOL_DINT (conversion of an EBOOL array into a DINT).
 MOVE_INT_AREBOOL (conversion of an INT into an EBOOL array).
 MOVE_DINT_AREBOOL (conversion of a DINT into an EBOOL array).

Representation in FBD
Representation applied to the conversion of an EBOOL array into an integer:

Representation in LD
Representation applied to the conversion of an EBOOL array into an integer:

33002519 09/2020 93
MOVE_***_***

Representation in IL
Representation applied to the conversion of an EBOOL array into an integer:
LD IN1
MOVE_AREBOOL_INT OUT1

Representation in ST
Representation applied to the conversion of an EBOOL array into an integer:
MOVE_AREBOOL_INT(IN1, OUT1);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


IN1 INT, n and m are positive or negative integers or
DINT, nil.
ARRAY [n..m] OF EBOOL.

The following table describes the output parameters:

Parameter Type Comment


OUT1 INT, When IN1 is an EBOOL array, OUT1 is an INT
DINT, or DINT containing the elements of IN1.
ARRAY [n..m] OF EBOOL. When IN1 is not an array, OUT1 is a single or
double integer, converted from a Boolean
array.

94 33002519 09/2020
EcoStruxure™ Control Expert
MUL_***_***
33002519 09/2020

Chapter 18
MUL_***_***: Multiplication of arrays

MUL_***_***: Multiplication of arrays

Description

Function description
The MUL_***_*** function carries out the multiplication:
 of the elements of an array by a number,
 of the elements of an array by the respective elements of another array.
The additional parameters EN and ENO can be configured.

Available functions
The available functions for the multiplication of the elements of an array by a number are as follows:
 MUL_ARINT_INT,
 MUL_ARDINT_DINT.
The available functions for the multiplication of the elements of an array by the respective elements
of another array are as follows:
 MUL_ARINT,
 MUL_ARDINT.

Representation in FBD
Representation applied to the multiplication of the elements of an integer array by an integer:

33002519 09/2020 95
MUL_***_***

Representation in LD
Representation applied to the multiplication of the elements of an integer array by an integer:

Representation in IL
Representation applied to the multiplication of the elements of an integer array by an integer:
LD Input_IN1
MUL_ARINT_INT Input_IN2
ST Array1

Representation in ST
Representation applied to the multiplication of an integer by the elements of an integer array:
Array1:= MUL_ARINT_INT(Input_IN1,Input_IN2);

96 33002519 09/2020
MUL_***_***

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Input_IN1 INT, Input_IN1 is either a single or double integer,
DINT, or an array of single or double integers, n and m
ARRAY [n..m] OF INT, are positive or negative integers or nil.
ARRAY [n..m] OF DINT
Input_IN2 INT, Input_IN2 is either a single or double integer,
DINT, or an array of single or double integers, n and m
ARRAY [n..m] OF INT, are positive or negative integers or nil.
ARRAY [n..m] OF DINT

The following table describes the output parameters:

Parameter Type Comment


Array1 ARRAY [n..m] OF INT According to the type of Input_IN1 and
ARRAY [n..m] OF DINT Input_IN2, each element of Array1 is the
multiplication:
 of a single or double integer Input_IN1 by
the corresponding element of the array
Input_IN2 or else,
 of the elements of the array Input_IN1 by
single or double integers Input_IN2 or
else,
 of the elements of the array Input_IN1 by
the respective elements of the array
Input_IN2.

Runtime errors
The management of the %S18 system bit is identical to that for operations on words or double
words.
If an operation between two elements sets the %S18 bit (overflow or division by zero), the result
for this operation is incorrect, but the operation on the following elements is carried out correctly.

33002519 09/2020 97
MUL_***_***

98 33002519 09/2020
EcoStruxure™ Control Expert
NOT_***
33002519 09/2020

Chapter 19
NOT_***: Logical negation of arrays

NOT_***: Logical negation of arrays

Description

Function description
The NOT_*** function carries out a logical negation (bit to bit) for all the elements of an array.
NOTE: The result is always an array.
The additional parameters EN and ENO can be configured.

Available functions
The available functions are as follows:
 NOT_AREBOOL,
 NOT_ARWORD,
 NOT_ARDWORD.

The functions available in the Obsolete library are the following:


 NOT_ARINT (logical negation of each element of an INT array).
 NOT_ARDINT (logical negation of each element of a DINT array).
For example: %M11:3 := NOT_AREBOOL (%M1:3);
when %M1 is 1, %M2 is 0 and %M3 is 1, then %M11 will be 0, %M12 will be 1 and %M13 will be 0.

Representation in FBD
Representation applied to a 16-bit string:

33002519 09/2020 99
NOT_***

Representation in LD
Representation applied to a 16-bit string:

Representation in IL
Representation applied to a 16-bit string:
LD Array1
NOT_ARWORD
ST Result_Array

Representation in ST
Representation applied to a 16-bit string:
Result_Array:= NOT_ARWORD(Array1);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Array1 ARRAY [n..m] OF EBOOL, n and m are positive or negative integers
ARRAY [n..m] OF WORD, or nil.
ARRAY [n..m] OF DWORD

The following table describes the output parameters:

Parameter Type Comment


Result_Array ARRAY [n..m] OF EBOOL, The elements of Result_Array are the
ARRAY [n..m] OF WORD, result of the logical NOT (bit to bit) on
ARRAY [n..m] OF DWORD Array1.
Of the same type as the elements of the
array Array 1.

100 33002519 09/2020


EcoStruxure™ Control Expert
OCCUR_***
33002519 09/2020

Chapter 20
OCCUR_***: Occurrence of a value in an array

OCCUR_***: Occurrence of a value in an array

Description

Function description
The OCCUR_*** function gives the number of elements of an array equal to a given value.
The additional parameters EN and ENO can be configured.

Available functions
The available functions are as follows:
 OCCUR_ARWORD,
 OCCUR_ARDWORD,
 OCCUR_ARINT,
 OCCUR_ARDINT,
 OCCUR_ARREAL.

Representation in FBD
Representation applied to an integer array:

Representation in LD
Representation applied to an integer array:

33002519 09/2020 101


OCCUR_***

Representation in IL
Representation applied to an integer array:
LD Array1
OCCUR_ARINT Value1
ST Occur_Number

Representation in ST
Representation applied to an integer array:
Occur_Number:= OCCUR_ARINT(Array1,Value1);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Array1 ARRAY [n..m] OF WORD, n and m are positive or negative integers or
ARRAY [n..m] OF DWORD, nil.
ARRAY [n..m] OF INT,
ARRAY [n..m] OF DINT
ARRAY [n..m] OF REAL
Value1 WORD, Value of which we wish to know the number
DWORD, of occurrences in the arrayArray1.
INT, Of the same type as the elements of the
DINT, array Array 1.
REAL

The following table describes the output parameters:

Parameter Type Comment


Occur_Number INT Number of occurrences of Value1 in the
array Array1.

102 33002519 09/2020


EcoStruxure™ Control Expert
OR_***_***
33002519 09/2020

Chapter 21
OR_***_***: Logical OR between arrays and variables

OR_***_***: Logical OR between arrays and variables

Description

Function description
The OR_***_*** function carries out a logical OR (bit to bit) between:
 the elements of two arrays,
 between a single type variable and the elements of an array,
 between the elements of an array and a single type variable.
NOTE: The result is always an array.
The additional parameters EN and ENO can be configured.

Available functions
The functions available in the general library are the following:
 OR_AREBOOL (logical OR of two BOOL arrays).
 OR_ARWORD (logical OR of two WORD arrays).
 OR_ARWORD_WORD (logical OR of each element of a WORD array with a WORD).
 OR_ARDWORD_DWORD (logical OR of each element of a DWORD array with a DWORD).
 OR_ARDWORD (logical OR of two DWORD arrays).
The functions available in the Obsolete library are the following:
 OR_ARINT_INT (logical OR of each element of an INT array with an INT).
 OR_ARDINT_DINT (logical OR of each element of a DINT array with a DINT).
 OR_ARINT (logical OR of each element of an INT array with each element corresponding to
another INT array).
 OR_ARDINT (logical OR of each element of a DINT array with each element corresponding to
another DINT array).

Representation in FBD
Representation applied to a 16-bit string array and a 16-bit string:

33002519 09/2020 103


OR_***_***

Representation in LD
Representation applied to a 16-bit string array and a 16-bit string:

Representation in IL
Representation applied to a 16-bit string array and a 16-bit string:
LD IN1
OR_ARWORD_WORD Input_IN2
ST Array1

Representation in ST
Representation applied to a 16-bit string and a 16-bit string array:
Array1:= OR_ARWORD_WORD(Input_IN1,Input_IN2);

104 33002519 09/2020


OR_***_***

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Input_IN1 ARRAY [n..m] OF BOOL, n and m are positive or negative integers or
ARRAY [n..m] OF WORD, nil.
ARRAY [n..m] OF DWORD,
ARRAY [n..m] OF INT,
ARRAY [n..m] OF DINT
Input_IN2 WORD, n and m are positive or negative integers or
DWORD, nil.
INT,
DINT,
ARRAY [n..m] OF BOOL,
ARRAY [n..m] OF WORD,
ARRAY [n..m] OF DWORD,
ARRAY [n..m] OF INT,
ARRAY [n..m] OF DINT

The following table describes the output parameters:

Parameter Type Comment


Array1 ARRAY [n..m] OF BOOL, The elements of Array1 are the result of the
ARRAY [n..m] OF WORD, logical OR (bit to bit) between Input_IN1
ARRAY [n..m] OF DWORD, and Input_IN2, which can be respectively:
ARRAY [n..m] OF INT,  an array and a single variable,
ARRAY [n..m] OF DINT  an array and an array.

33002519 09/2020 105


OR_***_***

106 33002519 09/2020


EcoStruxure™ Control Expert
ROL_***
33002519 09/2020

Chapter 22
ROL_***: Rotate shift to left

ROL_***: Rotate shift to left

Description

Function description
The ROL_*** function carries out a rotate shift of the elements of an array in the ascending
direction of the indices.
The additional parameters EN and ENO can be configured.

Available functions
The functions available in the general library are the following:
 ROL_ARWORD,
 ROL_ARDWORD,
 ROL_ARINT,
 ROL_ARDINT,
 ROL_ARREAL.

Representation in FBD
Representation applied to an integer array:

33002519 09/2020 107


ROL_***

Representation in LD
Representation applied to an integer array:

Representation in IL
Representation applied to an integer array:
LD Positions
ROL_ARINT Array1

Representation in ST
Representation applied to an integer array:
ROL_ARINT(Positions, Array1);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Positions INT Shift value according to the ascending indices of the array.

Example: Positions = 2.
Note: if the value of Positions is negative or nil, no shift is carried out.

The following table describes the input/output parameters:

Parameter Type Comment


Array1 ARRAY [n..m] OF WORD, The elements of Array1 are moved a number of positions
ARRAY [n..m] OF DWORD, equal to Positions. The shift is carried out according to the
ARRAY [n..m] OF INT, ascending indices.
ARRAY [n..m] OF DINT
ARRAY [n..m] OF REAL Example: With a shift register of 2, the element previously
situated in first position goes to third (1+2), the second goes
to fourth (2+2), ..., the second last goes to first position and
the last goes to second position.

108 33002519 09/2020


EcoStruxure™ Control Expert
ROR_***
33002519 09/2020

Chapter 23
ROR_***: Rotate shift to right

ROR_***: Rotate shift to right

Description

Function description
The ROR_*** function carries out a rotate shift of the elements of an array in the descending
direction of the indices.
The additional parameters EN and ENO can be configured.

Available functions
The functions available in the general library are the following:
 ROR_ARWORD,
 ROR_ARDWORD,
 ROR_ARINT,
 ROR_ARDINT.
 ROR_ARREAL.

Representation in FBD
Representation applied to an integer array:

Representation in LD
Representation applied to an integer array:

33002519 09/2020 109


ROR_***

Representation in IL
Representation applied to an integer array:
LD Positions
ROR_ARINT Array1

Representation in ST
Representation applied to an integer array:
ROR_ARINT(Positions, Array1);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Positions INT Shift value according to the descending
indices of the array.

Example: Positions = 2.
Note: if the value of Positions is negative
or nil, no shift is carried out.

The following table describes the input/output parameters:

Parameter Type Comment


Array1 ARRAY [n..m] OF WORD, The elements of Array1 are moved a
ARRAY [n..m] OF DWORD, number of positions equal to Positions.
ARRAY [n..m] OF INT, The shift is carried out according to the
ARRAY [n..m] OF DINT descending indicators.
ARRAY [n..m] OF REAL
Example: With a shift register of 2, the
element previously situated in first position
goes to second last, the second goes to last,
the third goes to first (3-2), the fourth to
second (4 -2), etc.

110 33002519 09/2020


EcoStruxure™ Control Expert
SORT_***
33002519 09/2020

Chapter 24
SORT_***: Ascending or descending sort

SORT_***: Ascending or descending sort

Description

Function description
The SORT_*** function sorts an array in ascending or descending order and arranges the sorted
elements in this same array.
The additional parameters EN and ENO can be configured.

Available functions
The available functions are as follows:
 SORT_ARWORD,
 SORT_ARDWORD,
 SORT_ARINT,
 SORT_ARDINT,
 SORT_ARREAL.

Representation in FBD
Representation applied to an integer array:

Representation in LD
Representation applied to an integer array:

33002519 09/2020 111


SORT_***

Representation in IL
Representation applied to an integer array:
LD Direction
SORT_ARINT Array1

Representation in ST
Representation applied to an integer array:
SORT_ARINT(Direction, Array1);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Direction INT Direction of sort to be carried out:
 Direction ≥ 0: ascending sort,
 Direction < 0: descending sort.

The following table describes the input/output parameters:

Parameter Type Comment


Array1 ARRAY [n..m] OF WORD, Array sorted in the direction specified in
ARRAY [n..m] OF DWORD, Direction, n and m are positive or negative
ARRAY [n..m] OF INT, integers, or nil.
ARRAY [n..m] OF DINT
ARRAY [n..m] OF REAL

112 33002519 09/2020


EcoStruxure™ Control Expert
SUB_***_***
33002519 09/2020

Chapter 25
SUB_***_***: Subtraction from arrays

SUB_***_***: Subtraction from arrays

Description

Function description
The SUB_***_*** function carries out the subtraction:
 of the elements of an array from a number,
 of a number from the elements of an array,
 of the elements of an array from the respective elements of another array.
The additional parameters EN and ENO can be configured.

Available functions
The available functions for the subtraction of the elements of an array from a number or of a
number from the elements of an array are as follows:
 SUB_INT_ARINT (Subtraction of each element of an INT array from an INT).
 SUB_DINT_ARDINT (Subtraction of each element of an array of DINTs from a DINT).
 SUB_ARINT_INT (Subtraction of an INT from the elements of an array of INTs).
 SUB_ARDINT_DINT (Subtraction of a DINT from the elements of an array of DINTs).
The available functions for the subtraction of the elements of an array from the respective elements
of another array are as follows:
 SUB_ARINT (Subtraction of the respective elements of both arrays of INTs).
 SUB_ARDINT (Subtraction of the respective elements of both arrays of DINTs).

Representation in FBD
Representation applied to the subtraction of the elements of an array of integers from an integer:

33002519 09/2020 113


SUB_***_***

Representation in LD
Representation applied to the subtraction of the elements of an array of integers from an integer:

Representation in IL
Representation applied to the subtraction of the elements of an array of integers from an integer:
LD Input_IN1
SUB_INT_ARINT Input_IN2
ST Array1

Representation in ST
Representation applied to the subtraction of the elements of an array of integers from an integer:
Array1:= SUB_INT_ARINT(Input_IN1,Input_IN2);

114 33002519 09/2020


SUB_***_***

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Input_IN1 INT, Input_IN1 is either a single or double integer,
DINT, or an array of single or double integers, n and m
ARRAY [n..m] OF INT, are positive or negative integers or nil.
ARRAY [n..m] OF DINT
Input_IN2 INT, Input_ IN2 is either a single or double integer,
DINT, or an array of single or double integers, n and m
ARRAY [n..m] OF INT, are positive or negative integers or nil.
ARRAY [n..m] OF DINT

The following table describes the output parameters:

Parameter Type Comment


Array1 ARRAY [n..m] OF INT According to the type of Input_IN1 and
ARRAY [n..m] OF DINT Input_IN2, each element of Array1 is the
subtraction:
 from a single or double integer Input_IN1
of the corresponding element of the array
Input_IN2 or else,
 from the elements of the array Input_IN1
of the single or double integer Input_IN2 or
else,
 from the elements of the array Input_IN1
of the respective elements of the array
Input_IN2.

Runtime errors
The management of the %S18 system bit is identical to that for operations on words or double
words.
If an operation between two elements sets the %S18 bit (overflow or division by zero), the result
for this operation is incorrect, but the operation on the following elements is carried out correctly.

33002519 09/2020 115


SUB_***_***

116 33002519 09/2020


EcoStruxure™ Control Expert
SUM_***
33002519 09/2020

Chapter 26
SUM_***: Sum of array elements

SUM_***: Sum of array elements

Description

Function description
The SUM_*** function calculates the sum of the elements of an array.
The additional parameters EN and ENO can be configured.

Available functions
The available functions are as follows:
 SUM_ARINT,
 SUM_ARDINT,
 SUM_ARREAL.

Formula
The formula is as follows:

Description:

Element Signification
Array1 Array declared in the following way:
ARRAY [n..m] OF ...

Representation in FBD
Representation applied to an integer array:

33002519 09/2020 117


SUM_***

Representation in LD
Representation applied to an integer array:

Representation in IL
Representation applied to an integer array:
LD Array1
SUM_ARINT
ST Sum1

Representation in ST
Representation applied to an integer array:
Sum1:= SUM_ARINT(Array1);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Array1 ARRAY [n..m] OF INT Double or single integer arrays or arrays of reals,
ARRAY [n..m] OF DINT n and m are positive or negative integers, or nil.
ARRAY [n..m] OF REAL

The following table describes the output parameters:

Parameter Type Comment


Sum1 INT, DINT, REAL Sum of array elements assigned to input. The
sum is of the same type as the array elements.

Runtime errors
When the array contains an invalid value, the sum of its elements contains 0.0 and the bit %S18 =
1.
When the sum of elements is greater than the maximum authorized value, its value becomes
1.#INF and the bit %S18 = 1

118 33002519 09/2020


EcoStruxure™ Control Expert
SWAP_***
33002519 09/2020

Chapter 27
SWAP_***: Permutation of the bytes of an array

SWAP_***: Permutation of the bytes of an array

Description

Function description
The SWAP_*** function carries out a permutation of the least significant bytes and the most
significant bytes of the elements of an array.
The additional parameters EN and ENO can be configured.

Available functions
The available functions are as follows:
 SWAP_ARINT,
 SWAP_ARWORD.

Representation in FBD
Representation applied to an integer array:

Representation in LD
Representation applied to an integer array:

Representation in IL
Representation applied to an integer array:
LD Array1
SWAP_ARINT

33002519 09/2020 119


SWAP_***

Representation in ST
Representation applied to an integer array:
SWAP_ARINT(Array1);

Description of parameters
The following table describes the input/output parameters:

Parameter Type Comment


Array1 ARRAY [n..m] OF INT n and m are positive or negative integers or nil.
ARRAY [n..m] OF WORD On output, the bytes of Array1 have been
permutated.

120 33002519 09/2020


EcoStruxure™ Control Expert
XOR_***_***
33002519 09/2020

Chapter 28
XOR_***_***: Exclusive OR between arrays

XOR_***_***: Exclusive OR between arrays

Description

Function description
The XOR_***_*** function carries out an exclusive logical OR (bit to bit) between:
 the elements of two arrays,
 between a single type variable and the elements of an array,
 between the elements of an array and a single type variable.
NOTE: The result is always an array.
The additional parameters EN and ENO can be configured.

Available functions
The functions available in the general library are the following:
 XOR_AREBOOL (exclusive logical OR of two BOOL arrays).
 XOR_ARWORD (exclusive logical OR of two WORD arrays).
 XOR_ARWORD_WORD (exclusive logical OR of each element of a WORD array with a WORD).
 XOR_ARDWORD_WORD (exclusive logical OR of each element of a DWORD array with a
DWORD).
 XOR_ARDWORD (exclusive logical OR of two DWORD arrays).
The functions available in the Obsolete library are the following:
 XOR_ARINT_INT (exclusive logical OR of each element of an INT array with an INT).
 XOR_ARDINT_DINT (exclusive logical OR of each element of an DINT array with an DINT).
 XOR_ARINT (exclusive logical OR of each element of an INT array with each element
corresponding to another INT array).
 XOR_ARDINT (exclusive logical OR of each element of a DINT array with each element
corresponding to another DINT array).

Representation in FBD
Representation applied to a 16-bit string array and a 16-bit string:

33002519 09/2020 121


XOR_***_***

Representation in LD
Representation applied to a 16-bit string array and a 16-bit string:

Representation in IL
Representation applied to a 16-bit string array and a 16-bit string:
LD Input_IN1
XOR_ARWORD_WORD Input_IN2
ST Array1

Representation in ST
Representation applied to a 16-bit string array and a 16-bit string:
Array1:= XOR_ARWORD_WORD(Input_IN1,Input_IN2);

122 33002519 09/2020


XOR_***_***

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Input_IN1 ARRAY [n..m] OF BOOL, n and m are positive or negative integers or nil.
ARRAY [n..m] OF WORD,
ARRAY [n..m] OF DWORD,
ARRAY [n..m] OF INT,
ARRAY [n..m] OF DINT
Input_IN2 WORD, n and m are positive or negative integers or nil.
DWORD,
INT,
DINT,
ARRAY [n..m] OF BOOL,
ARRAY [n..m] OF WORD,
ARRAY [n..m] OF DWORD,
ARRAY [n..m] OF INT,
ARRAY [n..m] OF DINT

The following table describes the output parameters:

Parameter Type Comment


Array1 ARRAY [n..m] OF BOOL, The elements of Array1 are the result of the
ARRAY [n..m] OF WORD, exclusive logical OR (bit to bit) between
ARRAY [n..m] OF DWORD, Input_ IN1 and Input_IN2, which can be
ARRAY [n..m] OF INT, respectively:
ARRAY [n..m] OF DINT  an array and a single variable,
 a single variable and an array,
 an array and an array.

33002519 09/2020 123


XOR_***_***

124 33002519 09/2020


EcoStruxure™ Control Expert
CLC_INT
33002519 09/2020

Part III
CLC_INT

CLC_INT

Overview
This section describes the elementary functions and elementary function blocks of the CLC_INT
family.

What Is in This Part?


This part contains the following chapters:
Chapter Chapter Name Page
29 Introduction to integer regulation functions 127
30 PID_INT: PID controller 133
31 PWM_INT: Pulse width modulation of a numerical value 141
32 SERVO_INT: Servo drive function 145

33002519 09/2020 125


CLC_INT

126 33002519 09/2020


EcoStruxure™ Control Expert
Introduction to regulation EFs
33002519 09/2020

Chapter 29
Introduction to integer regulation functions

Introduction to integer regulation functions

Subject of this Chapter


This chapter provides the basic notions necessary for the use and implementation of the following
integer regulation functions:
 PID_INT,
 PWM_INT,
 SERVO_INT.

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
General Introduction 128
Principal of the regulation loop 129
Development methodology for a regulation application 130
Programming a regulation function 131
Behavior of functions in operating modes 132

33002519 09/2020 127


Introduction to regulation EFs

General Introduction

General
The regulation functions are the standard elements of the language.
They are used to program regulation loops.
These functions are particularly adapted to:
 meeting the requirements of sequential processes which need auxiliary regulation functions
(e.g.: plastic film packaging machines, finishing treatment machines, presses etc.)
 meeting the requirements of simple regulation processes (e.g.: metal furnaces, ceramic
furnaces, small refrigerating units etc.),
 meeting the specific requirements of mechanical regulation or feedback control where sampling
time is critical (e.g.: torque regulation, speed regulation).
NOTE: There is no limit on the number of PID_INT functions that are available in an application.
In practice, it is the maximum number of input and output modules which are accepted by the PLC
that limits the number of loops.

Available functions
The basic regulation functions are the following:
 the PID_INT function to execute a mixed PID_INT correction (serial – parallel),
 the PWM_INT function to execute the modulation adjustment period on the discrete outputs,
 the SERVO_INT function to execute the motor command adaptations.

128 33002519 09/2020


Introduction to regulation EFs

Principal of the regulation loop

At a Glance
A regulation loop has three distinct operating phases:
 the acquisition of data:
 measurements from the process’ sensors (analog, encoders),
 setpoint(s) generally from PLC internal variables or from data from the operator terminal.

 execution of the PID regulation algorithm,


 the sending of commands adapted to the characteristics of the actuators to be driven via the
discrete or analog outputs.
The PID algorithm generates the command signal from:
 the measurement sampled by the input nodule,
 the setpoint value fixed by either the operator or the program,
 the values of the different corrector parameters.
The signal from the corrector is either directly handled by an analog output card of the PLC linked
to the actuator, or handled via the PWM or SERVO adjustments depending on the types of actuator
to be driven on a discrete output card of the PLC.

Illustration
The following diagram schematizes the principal of a regulation loop.

33002519 09/2020 129


Introduction to regulation EFs

Development methodology for a regulation application

Flow diagram
The following diagram shows the links between tasks to be carried out during the creation and
debugging of a regulation application (the order shown here is for information purposes only).

130 33002519 09/2020


Introduction to regulation EFs

Programming a regulation function

Programming rules
The regulation function parameters must all be entered. The functions use 3 kinds of parameters:
 read only parameters, considered at the beginning of the function’s execution,
 write only parameters, positioned at the conclusion of the function’s execution,
 the read and write parameters, whose contents are considered at the beginning of the function’s
execution, are then updated by the results of the function.
NOTE: The regulation functions must be programmed in a periodic task (periodic MAST or FAST).
These functions do not operate in a cyclic MAST task configuration. The logic section containing
these functions must not be conditioned.

Parametering
The word type input parameters are analog dimensions expressed on the scale [0, +10000] and
can be directly connected to measurement sensors via the %IWr.m.c words of the analog inputs.
The bit type output parameters can be used to control discrete actuators and can be directly
connected to the %Qr.m.c. type variables.
In the same way, the word type output parameters can be used to control analog actuators on the
scale [0, +10000] and can be directly assigned to %QWr.m.c type variables.
The ARRAY [0..n] OF INT or %MWi:L integer table type parameters contain the user parameters
and data necessary to the internal operation of the function.
If the length of a table is insufficient, the function is not executed.
NOTE: In order to keep the adjustment parameters of the regulation on cold start function, it is
necessary to delete the %MWi reset to zero option (in the processor’s configuration screen)

33002519 09/2020 131


Introduction to regulation EFs

Behavior of functions in operating modes

Introduction
This paragraph describes the behavior of the functions in different start-up scenarios:
 cold start (new application, change of cartridge…),
 warm restart (power return without changing the application context),
 first execution after adding a function via modification in connected mode.

Cold start
This type of start occurs for a new application or a change of cartridge
On a cold start, the PLC can start automatically in RUN (according to the application’s
configuration). The function correctors have the following security behavior: manual mode, outputs
at 0. In addition, this supports the switching of the PLC into RUN mode without carrying out the PID
adjustment, then its debugging with the operator terminal (the adjustment can only be performed
in RUN).

Warm restart
This type of restart occurs for a power return, without changing the application context.
With a power return after an outage (regardless of how long it lasted) and if the application context
is not lost or modified, the functions go back to their state before the outage. If the user wants to
use another type of behavior, it is his responsibility to test the %S1 system bit and to associate the
required processing with it (forcing in manual mode…).
NOTE: The PLC’s time-and-date stamp allows you find out the duration of the last outage.

Adding a new call in connected mode


Following the addition of a new function regulation call in connected mode, an identical initialization
to the case of the cold start is carried out.
NOTE: In order to be seen as a new function, this must use a new parameter table. Therefore, the
removal of a PID_INT function, followed by the addition of a PID_INT function that uses the same
parameter table is not considered as an addition of a new PID. In this case the PID is executed in
the same state and with the same parameters as the preceding PID.

132 33002519 09/2020


EcoStruxure™ Control Expert
PID_INT
33002519 09/2020

Chapter 30
PID_INT: PID controller

PID_INT: PID controller

Subject of this Chapter


This chapter describes the PID_INT function.

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Function description 134
Description of Derived Data 138

33002519 09/2020 133


PID_INT

Function description

Function description
The PID_INT function carries out PID-type regulation on INT type inputs and outputs.
The measurement and the setpoint are analog data in [0-10000] format and generate an analog
command in the same format.
The PID_INT EF comprises the following functions:
 serial / parallel PID algorithm,
 forward / backward action (according to the KP gain sign),
 action derived from measurement or from distance,
 high and low limitation of the setpoint to [0-10000],
 high and low limitation of the output in automatic mode,
 anti-saturation of the integral action,
 Manual/Automatic operating modes without step by step on change,
 PID access control through the Human Machine Interface,
 operating in integrator for (KP = TD =0).

NOTE:
 The display parameters used by the operator terminal are shown in physical units.
 For a correct PID operation, you must stay within the scale of [0-1000] for the measurement and
the setpoint.
 The PID function must be programmed in a periodic task (periodic MAST or FAST). The function
does not operate in a cyclic MAST task configuration. The logic section containing this function
must not be conditioned.
The additional parameters EN and ENO can be configured.

134 33002519 09/2020


PID_INT

Operating synoptic
The following illustration provides the operating synoptic for the PID function.

33002519 09/2020 135


PID_INT

Representation in FBD
Representation:

Representation in LD
Representation:

Representation in IL
Representation:
LD Input_Tag
PID_INT Input_Unit, Input_PV, In_Out_Auto, In_Out_Para, PID_Out

Representation in ST
Representation:
PID_INT(Input_Tag, Input_Unit, Input_PV, In_Out_Auto, In_Out_Para,
PID_Out);

136 33002519 09/2020


PID_INT

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Input_Tag STRING Name of PID used by the terminal.
String of 8 characters
Input_Unit STRING Unit of measurement used by the terminal.
String of 6 characters
Input_PV INT Process value input
Measurement format [0..10000].

The following table describes the input/output parameters:

Parameter Type Comment


In_Out_Auto EBOOL Input/output bit which indicates and manages the
operating modes of the PID and the terminal:
 0 : manual,
 1 : auto.
In_Out_Para ARRAY [n..m] OF INT n and m are positive or negative integers or nil. PID
parameter input/output table, the first 16 values of
which are described below, the other values being
used for internal processing.
Table of 43 integers.

The following table describes the output parameters:

Parameter Type Comment


PID_Out INT Analog output of PID, if TI = 0, an offset of 5000 is added
to the OUT output in auto mode.
Output format [0;+10000].

33002519 09/2020 137


PID_INT

Description of Derived Data

Description of PARA Table


The table below presents the different parameters of the PARA table:

Parameter Rank Function


SP PARA[0] Internal setpoint in 0 - 10000 format.
OUT_MAN PARA[1] Value of the manual output of the PID (between 0 and 10000).
KP PARA[2] Proportional gain of the PID (x100), signed without unit (-10000<KP<+10000).
The Kp sign determines the direction of the PID’s action (negative: forward,
positive: reverse).
TI PARA[3] The PID’s integral time (between 0 and 20000) is shown in 0.1 seconds.
TD PARA[4] The PID’s derivative time (between 0 and 10000) is shown in 0.1 seconds.
TS PARA[5] The PID’s sampling period (between 1 and 32000) is shown in 0.01 seconds.
The real sampling period will be the multiple of the period of the task in which
the PID closest to the TS is introduced.
OUT_MAX PARA[6] Upper limit of the PID’s output in automatic (between 0 and 10000).
OUT_MIN PARA[7] Lower limit of the PID’s output in automatic (between 0 and 10000).
PV_DEV PARA[8].0 Derived action choice 0 = on process variable, 1 = on deviation.
NO_BUMP PARA[8].4 Bumpless or non-bumpless mode.
0 = non-bumpless, 1 = bumpless.
PV_SUP* PARA[9] Upper limit of the measurement scale’s range, in a physical unit (x100)
(between –9 999 999 and +9 999 999).
PV_INF* PARA[11] These two integers are, respectively, the most significant and least significant
PARA[12] of a double integer, that is the lower limit of the measurement scale's range, in
a physical unit (x100) (between -9 99 999 and + 9 999 999).
PV_MMI* PARA[13] These two integers are, respectively, the most significant and least significant
PARA[14] of a double integer, that is the image of the measurement in a physical unit
(x100).
SP_MMI* PARA[15] These two integers are, respectively, the most significant and least significant
PARA[16] of a double integer, that is the operator setpoint and image of the setpoint in a
physical unit (x100).
* Value used by the operator terminal.

138 33002519 09/2020


PID_INT

NOTE: The PL7 parameter DEVAL_MMI is not available in Control Expert.

WARNING
UNEXPECTED APPLICATION BEHAVIOR
Do not modify parameters used by the PID’s internal management by the application.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

NOTE: The values used by the terminal are multiplied by 100 in order to support a display with 2
figures after the decimal point on the terminal (the terminal does not use floating point format but
supports a fixed comma format).

Rules
There is no internal setpoint alignment on the measurement in manual mode.
The settings on the scale only take place on modification of one of the setpoints (SP or DOP_SP).
The algorithm without the integral action (TI = 0) carries out the following operation:

For Then the output With


Dt = derived action
OUT = KP [ t+ Dt] / 100 + 5000

The algorithm with the integral action (TI <0) carries out the following operation:

For Then the output With


Dt = derived action
OUT = KP [ t+(TS/10.TI). t+ Dt]/100

OUT = OUT + OUT

On a cold start, the PID starts off again in manual, with the output at 0. To impose the automatic
mode or a manual output that is not at 0 after a cold start, you will have to program the initialization
sequence after the PID call.

33002519 09/2020 139


PID_INT

140 33002519 09/2020


EcoStruxure™ Control Expert
PWM_INT
33002519 09/2020

Chapter 31
PWM_INT: Pulse width modulation of a numerical value

PWM_INT: Pulse width modulation of a numerical value

Description

Function description
The PWM_INT function carries out pulse width regulation on a Discrete output. It is a function that
formats a PID output.
The pulse width depends on the PID’s output (The PWM function’s INP input) and the modulation
period.
NOTE: The PWM_INT function must be programmed in a periodic task (periodic MAST or FAST).
The function does not operate in a cyclic MAST task configuration. The logic section containing this
function must not be conditioned.
The additional parameters EN and ENO can be configured.

Operating synoptic
The following diagram shows the operating synoptic of the PWM function:

33002519 09/2020 141


PWM_INT

Representation in FBD
Representation:

Representation in LD
Representation:

Representation in IL
Representation:
LD Input_INP
PWM_INT In_Out_Para, PW_O_Out

Representation in ST
Representation:
PWM_INT(Input_INP, In_Out_Para, PW_O_Out);

142 33002519 09/2020


PWM_INT

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Input_INP INT Analog value to be modulated in pulse width
(format [0 – 10000]).

The following table describes the input/output parameters:

Parameter Type Comment


In_Out_Para ARRAY [n..m] OF INT n and m are positive or negative integers or nil.
Input/output table of function parameters. The
first word corresponds to the parameter T_MOD.
Modulation period expressed in 1/100ths of
seconds (between 0 and 32767). T_MOD must be
greater than or equal to the current task period,
and is adjusted by the system to be an integer
that is a multiple of this.
The following integers are used internally by the
function and must never be modified by the
application.
Table of 5 integers.

The following table describes the output parameters:

Parameter Type Comment


PW_O_Out EBOOL Analog output of PID, if TI = 0, an offset of 5000
is added to the OUT output in auto mode.

33002519 09/2020 143


PWM_INT

Pulse widths
To each Top of the T_MOD modulation period, the activation period in 10-3 seconds of the
PW_O_Out (PW_O) output is calculated according to the following formula:

State 1 of the gap (shown in 10-2 seconds) = INP * T_MOD / 1000


The following timing diagram illustrates this formula:

Practical rules
T_MOD = TS (where TS is the sampling period of the upstream PID).

The period of the current task (expressed in 10-3 seconds) is equal to:
(Required resolution)* 10 * T_MOD.

The PID is in the MAST task, the MAST’s period is 50*10-3 s, TS = 500*10-2 s and the required
resolution is 1/50 (a T_MOD period must contain at least 50 periods of the current task).

Let T_MOD = TS = 500.


The period of the task in which the PWM is introduced must be less than
500 * 10 / 50 =100 10-3 s.
The PWM function can therefore be programmed in the MAST task.
The resolution will be 1/100.

144 33002519 09/2020


EcoStruxure™ Control Expert
SERVO_INT
33002519 09/2020

Chapter 32
SERVO_INT: Servo drive function

SERVO_INT: Servo drive function

Description

Function description
The SERVO_INT function carries out a regulation with a motor-type actuator driven by two Discrete
outputs (UP and DOWN).
NOTE:
 The SERVO_INT function must be programmed in a periodic task (periodic MAST or FAST). The
function does not operate in a cyclic MAST task configuration. The logic section containing this
function must not be conditioned.
 It must be connected in tandem with the analog output of a PID. It cannot be used alone.

When there is a copy of a position, the valve’s position is locked via the Input_Inp (setpoint) and
Input_Pot (position measurement) inputs.
When the copy does not physically exist, the algorithm no longer uses the PID’s absolute output
but the output’s variation. The Out_Up output (or Out_Down, according to the variation sign) is set
to 1 for a length of time proportional to the actuator opening time and to the variation of the value.
Also, the notion of minimum pulse time is introduced.
The additional parameters EN and ENO can be configured.

Representation in FBD
Representation:

33002519 09/2020 145


SERVO_INT

Representation in LD
Representation:

Representation in IL
Representation:
LD Input_Inp
SERVO_INT Input_Pot, In_Out_Pid, In_Out_Para, Out_Up, Out_Down

Representation in ST
Representation:
SERVO_INT(Input_Inp, Input_Pot, In_Out_Pid, In_Out_Para, Out_Up,
Out_Down);

146 33002519 09/2020


SERVO_INT

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Input_Inp INT Position setpoint ([0 -10000] format) that has to be connected to
the PID output.
Input_Pot INT Position copy, ([0 -10000] format)
0 : closed valve; 10000: open valve.
If the copy does not exist, Input_POT must be initialized at -
10000. This particular value indicates "no copy".

The following table describes the input/output parameters:

Parameter Type Comment


In_Out_Pid ARRAY [n..m] OF INT n and m are positive or negative integers or nil.
Parameter table of upstream PID (see page 138), used if there
are no copy words for the synchronization with the upstream
PID.
Table of 43 integers.
In_Out_Para ARRAY [n..m] OF INT n and m are positive or negative integers or nil.
The first three parameters are used if the copy does not exist
(Input_POT = -10000):
 In_Out_PARA[0] also called T_MOTOR is the valve opening
time expressed in 10-2 s.
 In_Out_PARA[1] also called T_MINI is the minimum pulse
expressed in 10-2 s.
 In_Out_PARA[2] also called HYST is the hysteresis value
in [0-10000] format.
Note: the other parameters that are used by the function’s
internal management must never be modified by the application.
All the parameters are obligatory, regardless of the operating
mode.
Table of 10 integers.

The following table describes the output parameters:

Parameter Type Comment


Out_Up EBOOL Output signal for the motor’s Out_Up operating direction.
Out_Down EBOOL Output signal for the motor’s Out_Down operating direction.

33002519 09/2020 147


SERVO_INT

Principle of operating with a position copy


The SERVO_INT function locks the motor’s position according to a setpoint of the Input_Inp
(INP) position from a PID’s output in [0 - 10000] format, and to a Input_Pot (POT) position
measurement.
The locking algorithm is a relay with hysteresis.
In this case, the PID, T_MOTOR and T_MINI parameters are not used.

Principle of operating without a position copy (POT= -10000)


In this case, the SERVO_INT function is synchronized with the upstream PID by using the PID
parameter table passed on to the SERVO_INT function as a parameter.
The algorithm receives in input the PID’s variation output and converts it into pulse period,
according to the following formula:
T_IMP (expressed in 10-3 s) = OUT x T_MOTOR / 1000
The acquired period is added to the remaining period of the preceding cycles: In fact, what is not
"consumed" in a cycle is memorized for the following cycles. This ensures correct operation,
especially where there are sudden variations in the command (e.g.: PID setpoint scale division)
and in manual mode.

148 33002519 09/2020


SERVO_INT

Example
The example below is in Ladder language:

Label Description
1 The PID output variation is +20 % (T_MOTOR pulse =25 s for a 100 % variation).
In this case, the pulse affects the UP output for a period of 5 s.
2 The PID variation is +2 %, which would correspond to a pulse of 0.5 s. This pulse
is less than T_MINI (=1 s.), and it does not affect the outputs.
3 A second variation of +2 % appears and the function adds this variation to the
previous one (which corresponded to a variation less than the minimal value),
which corresponds to a positive global variation of +4 %, and therefore to a pulse
of 1 s on the UP output.
4 A variation of -24 % appears and the activated pulse is therefore of 6 s on the
DOWN output.
5 Before the following second has elapsed, another variation of +22 % brings the
system back to a global variation of 2 % < the variation of T_MINI (4 %). The
function finishes carrying out the minimal pulse of 1 s.

Note 1: The SERVO_INT function does not manage the position limits. These must be managed
by the application. If a limit is detected, you must force the corresponding output to 0 (UP for the
high limit, DOWN for the low limit).

33002519 09/2020 149


SERVO_INT

Example: in Ladder language

Note 2: It is possible to switch from the operating mode with copy to the mode without copy (for
example: when a copy error occurs, go to mode without copy).

150 33002519 09/2020


EcoStruxure™ Control Expert
Comparison
33002519 09/2020

Part IV
Comparison

Comparison

Overview
This section describes the elementary functions and elementary function blocks of the
Comparison family.

What Is in This Part?


This part contains the following chapters:
Chapter Chapter Name Page
33 EQ: Equal to 153
34 GE: Greater than or equal to 155
35 GT: Greater than 159
36 LE: Less than or equal to 163
37 LT: Less than 167
38 NE: Not equal to 171

33002519 09/2020 151


Comparison

152 33002519 09/2020


EcoStruxure™ Control Expert
EQ
33002519 09/2020

Chapter 33
EQ: Equal to

EQ: Equal to

Description

Function description
This function checks the inputs for equality, i.e. the output becomes "1" if there is equality at all
inputs; otherwise, the output remains at "0".
The data types of all input values must be identical.
The number of inputs can be increased to a maximum of 32.
EN and ENO can be configured as additional parameters.

Formula
OUT = 1, if (IN1 = IN2) & (IN2 = IN3) & .. & (IN (n-1) = IN n)

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 153


EQ

Representation in IL
Representation:
LD Value1
EQ Value2
ST Result

Representation in ST
Representation:
Result := EQ (Value1, Value2) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


Value1 BOOL, BYTE, WORD, DWORD, STRING, INT, DINT, 1. Input
UINT, UDINT, REAL, TIME, DATE, DT, TOD
Value2 BOOL, BYTE, WORD, DWORD, STRING, INT, DINT, 2. Input
UINT, UDINT, REAL, TIME, DATE, DT, TOD
Valuen BOOL, BYTE, WORD, DWORD, STRING, INT, DINT, n. input
UINT, UDINT, REAL, TIME, DATE, DT, TOD n = max 32

Description of the output parameter:

Parameter Data type Meaning


Result BOOL Output

Runtime error
If an unauthorized floating point number is created for an input parameter of data type REAL, the
system bit %S18 is set to 1 and the status is placed in %SW17.

154 33002519 09/2020


EcoStruxure™ Control Expert
GE
33002519 09/2020

Chapter 34
GE: Greater than or equal to

GE: Greater than or equal to

Description

Function description
The function checks the values of successive inputs for a decreasing sequence or equality.
The data types of all input values must be identical.
The number of inputs can be increased to a maximum of 32.
When comparing variables of the BOOL, BYTE, WORD, DWORD, INT, DINT, UINT, UDINT, REAL,
TIME, DATE, DT and TOD data types, the values are compared with each other.
STRING variables are compared using the alphabet; variables at the end of the alphabet are higher
priority expressions than those at the front.
EN and ENO can be configured as additional parameters.

Formula
OUT = 1, if (IN1 ≥ IN2) & (IN2 ≥ IN3) & .. & (IN (n-1) ≥ IN n)

Representation in FBD
Representation:

33002519 09/2020 155


GE

Representation in LD
Representation:

Representation in IL
Representation:
LD Value1
GE Value2
ST Result

Representation in ST
Representation:
Result := GE (Value1, Value2) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


Value1 BOOL, BYTE, WORD, DWORD, STRING, INT, DINT, UINT, 1. Input
UDINT, REAL, TIME, DATE, DT, TOD
Value2 BOOL, BYTE, WORD, DWORD, STRING, INT, DINT, UINT, 2. Input
UDINT, REAL, TIME, DATE, DT, TOD
Valuen BOOL, BYTE, WORD, DWORD, STRING, INT, DINT, UINT, n. input
UDINT, REAL, TIME, DATE, DT, TOD n = max 32

Description of the output parameter:

Parameter Data type Meaning


Result BOOL Output

156 33002519 09/2020


GE

Runtime error
If an unauthorized floating point number is created for an input parameter of data type REAL, the
system bit %S18 is set to 1 and the status is placed in %SW17.

33002519 09/2020 157


GE

158 33002519 09/2020


EcoStruxure™ Control Expert
GT
33002519 09/2020

Chapter 35
GT: Greater than

GT: Greater than

Description

Function description
The function checks the values of successive inputs for a decreasing sequence.
The data types of all input values must be identical.
The number of inputs can be increased to a maximum of 32.
When comparing variables of the BOOL, BYTE, WORD, DWORD, INT, DINT, UINT, UDINT, REAL,
TIME, DATE, DT and TOD data types, the values are compared with each other.
STRING variables are compared using the alphabet; variables at the end of the alphabet are higher
priority expressions than those at the front.
EN and ENO can be configured as additional parameters.

Formula
OUT = 1, if (IN1 > IN2) & (IN2 > IN3) & .. (IN (n-1) > IN n)

Representation in FBD
Representation:

33002519 09/2020 159


GT

Representation in LD
Representation:

Representation in IL
Representation:
LD Value1
GT Value2
ST Result

Representation in ST
Representation:
Result := GT (Value1, Value2) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


Value1 BOOL, BYTE, WORD, DWORD, STRING, INT, DINT, 1. Input
UINT, UDINT, REAL, TIME, DATE, DT, TOD
Value2 BOOL, BYTE, WORD, DWORD, STRING, INT, DINT, 2. Input
UINT, UDINT, REAL, TIME, DATE, DT, TOD
Valuen BOOL, BYTE, WORD, DWORD, STRING, INT, DINT, n. input
UINT, UDINT, REAL, TIME, DATE, DT, TOD n = max 32

Description of the output parameter:

Parameter Data type Meaning


Result BOOL Output

160 33002519 09/2020


GT

Runtime error
If an unauthorized floating point number is created for an input parameter of data type REAL, the
system bit %S18 is set to 1 and the status is placed in %SW17.

33002519 09/2020 161


GT

162 33002519 09/2020


EcoStruxure™ Control Expert
LE
33002519 09/2020

Chapter 36
LE: Less than or equal to

LE: Less than or equal to

Description

Function description
The function checks the values of successive inputs for an increasing sequence or equality.
The data types of all input values must be identical.
The number of inputs can be increased to a maximum of 32.
When comparing variables of the BOOL, BYTE, WORD, DWORD, INT, DINT, UINT, UDINT, REAL,
TIME, DATE, DT and TOD data types, the values are compared with each other.
STRING variables are compared using the alphabet; variables at the end of the alphabet are higher
priority expressions than those at the front.
EN and ENO can be configured as additional parameters.

Formula
OUT = 1, if (IN1 ≤ IN2) & (IN2 ≤ IN3) & .. & (IN (n-1) ≤ IN n)

Representation in FBD
Representation:

33002519 09/2020 163


LE

Representation in LD
Representation:

Representation in IL
Representation:
LD Value1
LE Value2
ST Result

Representation in ST
Representation:
Result := LE (Value1, Value2) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


Value1 BOOL, BYTE, WORD, DWORD, STRING, INT, DINT, 1. Input
UINT, UDINT, REAL, TIME, DATE, DT, TOD
Value2 BOOL, BYTE, WORD, DWORD, STRING, INT, DINT, 2. Input
UINT, UDINT, REAL, TIME, DATE, DT, TOD
Valuen BOOL, BYTE, WORD, DWORD, STRING, INT, DINT, n. input
UINT, UDINT, REAL, TIME, DATE, DT, TOD n = max 32

Description of the output parameter:

Parameter Data type Meaning


Result BOOL Output

164 33002519 09/2020


LE

Runtime error
If an unauthorized floating point number is created for an input parameter of data type REAL, the
system bit %S18 is set to 1 and the status is placed in %SW17.

33002519 09/2020 165


LE

166 33002519 09/2020


EcoStruxure™ Control Expert
LT
33002519 09/2020

Chapter 37
LT: Less than

LT: Less than

Description

Function description
The function checks the values of successive inputs for an increasing sequence.
The data types of all input values must be identical.
The number of inputs can be increased to a maximum of 32.
When comparing variables of the BOOL, BYTE, WORD, DWORD, INT, DINT, UINT, UDINT, REAL,
TIME, DATE, DT and TOD data types, the values are compared with each other.
STRING variables are compared using the alphabet; variables at the end of the alphabet are higher
priority expressions than those at the front.
EN and ENO can be configured as additional parameters.

Formula
OUT = 1, if (IN1 < IN2) & (IN2 < IN3) & .. & (IN (n-1) < IN n)

Representation in FBD
Representation:

33002519 09/2020 167


LT

Representation in LD
Representation:

Representation in IL
Representation:
LD Value1
LT Value2
ST Result

Representation in ST
Representation:
Result := LT (Value1, Value2) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


Value1 BOOL, BYTE, WORD, DWORD, STRING, INT, 1. Input value
DINT, UINT, UDINT, REAL, TIME, DATE, DT,
TOD
Value2 BOOL, BYTE, WORD, DWORD, STRING, INT, 2. Input value
DINT, UINT, UDINT, REAL, TIME, DATE, DT,
TOD
Valuen BOOL, BYTE, WORD, DWORD, STRING, INT, n. input value
DINT, UINT, UDINT, REAL, TIME, DATE, DT, n = max 32
TOD

Description of the output parameter:

Parameter Data type Meaning


Result BOOL Output value

168 33002519 09/2020


LT

Runtime error
If an unauthorized floating point number is created for an input parameter of data type REAL, the
system bit %S18 is set to 1 and the status is placed in %SW17.

33002519 09/2020 169


LT

170 33002519 09/2020


EcoStruxure™ Control Expert
NE
33002519 09/2020

Chapter 38
NE: Not equal to

NE: Not equal to

Description

Function description
The function checks the input values for inequality.
The data types of the input values must be identical.
EN and ENO can be configured as additional parameters.

Formula
OUT = 1, if IN1 < > IN2

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 171


NE

Representation in IL
Representation:
LD Value1
NE Value2
ST Result

Representation in ST
Representation:
Result := NE (Value1, Value2) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


Value1 BOOL, BYTE, WORD, 1. Input
DWORD, STRING, INT,
DINT, UINT, UDINT,
REAL, TIME, DATE,
DT, TOD
Value2 BOOL, BYTE, WORD, 2. Input
DWORD, STRING, INT,
DINT, UINT, UDINT,
REAL, TIME, DATE,
DT, TOD

Description of the output parameter:

Parameter Data type Meaning


Result BOOL Output

Runtime error
If an unauthorized floating point number is created for an input parameter of data type REAL, the
system bit %S18 is set to 1 and the status is placed in %SW17.

172 33002519 09/2020


EcoStruxure™ Control Expert
Date & Time
33002519 09/2020

Part V
Date & Time

Date & Time

Overview
This section describes the elementary functions and elementary function blocks of the Date &
Time family.

What Is in This Part?


This part contains the following chapters:
Chapter Chapter Name Page
39 ADD_***_TIME: Addition of a duration to a date 175
40 DIVTIME: Division 177
41 MULTIME: Multiplication 179
42 SUB_***_***: Calculates the time difference between two dates or times 181
43 SUB_***_TIME: Subtraction of a duration from a date 183

33002519 09/2020 173


Date & Time

174 33002519 09/2020


EcoStruxure™ Control Expert
ADD_***_TIME
33002519 09/2020

Chapter 39
ADD_***_TIME: Addition of a duration to a date

ADD_***_TIME: Addition of a duration to a date

Description

Function description
The ADD_***_TIME function adds a duration to a date or a time.
The additional parameters EN and ENO can be configured.

Available functions
The available functions are as follows:
 ADD_DT_TIME,
 ADD_TOD_TIME.

Representation in FBD
Representation applied to a time of day:

Representation in LD
Representation applied to a time of day:

33002519 09/2020 175


ADD_***_TIME

Representation in IL
Representation applied to a time of day:
LD Source_Value
ADD_TOD_TIME Time_to_Add
ST Result_Value

Representation in ST
Representation applied to a time of day:
Result_Value:= ADD_TOD_TIME(Source_Value, Time_to_Add);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Source_Value DT, TOD Date or time.
Time_to_Add TIME Duration to be added to Source_Value

Note: this duration is expressed in TIME format with a


precision to the order of tenths of a second. As the types
DT and TOD are expressed to the nearest second,
Time_to_Add is rounded off to the second.

The following table describes the output parameters:

Parameter Type Comment


Result_Value DT, TOD Result_Value is of the same type as Source_Value.

NOTE: the management of leap years is to be provided for in the application.

Runtime errors
For the type TOD, there is a change of day if Result_Value is outside the authorized values. In
this case, the system bit %S18 is set at 1 and the value of Result_Value is only significant with
a modulo 24:00:00.
For the type DT, if Result_Value is outside the interval of authorized values, the system bit
%S18 is set to 1 and the value of Result_Value is equal to the maximum limit.
If one of the input parameters cannot be interpreted and is inconsistent with the function format
then the system bit %S18 is set at 1 and Result_Value applies:
 00:00:00 for the type TOD.
 00001-01-01-00:00:00 for the type DT.

176 33002519 09/2020


EcoStruxure™ Control Expert
DIVTIME
33002519 09/2020

Chapter 40
DIVTIME: Division

DIVTIME: Division

Description

Function description
The function divides the value at the TIME_variable (data type TIME) input with the value at the
Divisor input and assigns the result to the output.
EN and ENO can be configured as additional parameters.

Formula

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 177


DIVTIME

Representation in IL
Representation:
LD TIME_variable
DIVTIME Divisor
ST Quotient

Representation in ST
Representation:
Quotient := DIVTIME (TIME_variable, Divisor) ;

Parameter description
Description of input parameters:

Parameter Data type Meaning


TIME_variable TIME Dividend
Divisor INT, DINT, UINT, Divisor
UDINT, REAL

Description of output parameters:

Parameter Data type Meaning


Quotient TIME Quotient

Runtime error
The system bit %S18 is set to 1, if
 an invalid division by 0 is executed (all available data types)
or
 an unauthorized floating point number is set at an input parameter of data type REAL. The status
%SW17 is not updated for this function.
NOTE: For a list of all block error codes and values, see Date & Time, page 502.

178 33002519 09/2020


EcoStruxure™ Control Expert
MULTIME
33002519 09/2020

Chapter 41
MULTIME: Multiplication

MULTIME: Multiplication

Description

Function description
The function multiplies the input values and assigns the result to the output.
The data type of the 1st input value (TIME_variable) must be a TIME data type.
EN and ENO can be configured as additional parameters.

Formula
OUT = IN1 x IN2

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 179


MULTIME

Representation in IL
Representation:
LD TIME_variable
MULTIME Factor
ST Product

Representation in ST
Representation:
Product := MULTIME (TIME_variable, Factor) ;

Parameter description
Description of input parameters:

Parameter Data type Meaning


TIME_variable TIME Multiplicand (factor)
Factor INT, DINT, UINT, Multiplier (factor)
UDINT, REAL

Description of output parameters:

Parameter Data type Meaning


Product TIME Product

Runtime error
The system bit %S18 is set to 1, if
 the value range at the output has been exceeded (all available data types)
or
 an unauthorized floating-point number is set at an input parameter of data type REAL. In this
case, the status is also placed in %SW17.
NOTE: For a list of all block error codes and values, see Date & Time, page 502.

180 33002519 09/2020


EcoStruxure™ Control Expert
SUB_***_***
33002519 09/2020

Chapter 42
SUB_***_***: Calculates the time difference between two dates or times

SUB_***_***: Calculates the time difference between two dates


or times

Description

Function description
The SUB_***_*** function calculates the time difference between two dates or times.
The additional parameters EN and ENO can be configured.

Available functions
The available functions are as follows:
 SUB_DATE_DATE,
 SUB_DT_DT,
 SUB_TOD_TOD.

Representation in FBD
Representation applied to a time of day:

Representation in LD
Representation applied to a time of day:

33002519 09/2020 181


SUB_***_***

Representation in IL
Representation applied to a time of day:
LD Input_IN1
SUB_TOD_TOD Input_IN2
ST Delay1

Representation in ST
Representation applied to a time of day:
Delay1:= =SUB_TOD_TOD(Input_IN1, Input_IN2);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Input_IN1 DATE, DT, Date or time for which we wish to calculate the
TOD difference with Input_IN2.
Input_IN2 DATE, DT, Date or time for which we wish to calculate the
TOD difference with Input_IN2.
Of the same type as the elements of the table
Input_IN1.

NOTE: Input_IN1 and Input_IN2 must be of the same type.


The following table describes the output parameters:

Parameter Type Comment


Delay1 TIME Delay1 contains the time expressed as an absolute
value elapsed between the two entries Input_IN1 and
Input_IN2.

Runtime errors
If Delay1 exceeds the maximum value allowed for a TIME format, there is overrun, then Delay1
= 0 and the system bit %S18 is set to 1.
If one of the input parameters is not interpretable and coherent in the function format, then Delay1
= 0 and the system bit %S18 is set to 1.

182 33002519 09/2020


EcoStruxure™ Control Expert
SUB_***_TIME
33002519 09/2020

Chapter 43
SUB_***_TIME: Subtraction of a duration from a date

SUB_***_TIME: Subtraction of a duration from a date

Description

Function description
The SUB_***_TIME function removes a duration from a date or a time.
The additional parameters EN and ENO can be configured.

Available functions
The available functions are as follows:
 SUB_DT_TIME,
 SUB_TOD_TIME.

Representation in FBD
Representation applied to a time of day:

Representation in LD
Representation applied to a time of day:

33002519 09/2020 183


SUB_***_TIME

Representation in IL
Representation applied to a time of day:
LD Source_Value
SUB_TOD_TIME Time_to_Sub
ST Result_Value

Representation in ST
Representation applied to a time of day:
Result_Value:= SUB_TOD_TIME(Source_Value, Time_to_Sub);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Source_Value DT, TOD Date or time.
Time_to_Sub TIME Duration to subtract from Source_Value

Note: this duration is expressed in TIME format (with a


precision to the order of tenths of a second). As the
types DT and TOD are expressed to the nearest
second, Time_to_Sub is rounded off to the second.

The following table describes the output parameters:

Parameter Type Comment


Result_Value DT, TOD Result_Value is of the same type as Source_Value.

NOTE: the management of leap years is to be provided for in the application.

Runtime errors
For the type TOD, there is a change of day if Result_Value is outside the interval of authorized
values. In this case the system bit %S18 is set at 1 and the value of Result_Value is only
significant with a modulo 24:00:00.
For the type DT, if Result_Value is outside the interval of authorized values, the system bit
%S18 is set to 1 and the value of Result_Value is equal to the minimum limit.
If one of the input parameters cannot be interpreted and is inconsistent with the function format
then the system bit %S18 is set at 1 and Result_Value applies:
 00:00:00 for the type TOD.
 00001-01-01-00:00:00 for the type DT.

184 33002519 09/2020


EcoStruxure™ Control Expert
Extract
33002519 09/2020

Part VI
Extract

Extract

Overview
This section describes the elementary functions and elementary function blocks of the Extract
family.

What Is in This Part?


This part contains the following chapters:
Chapter Chapter Name Page
44 EXTRACT: Copy of a variable part into another variable 187
45 SIZEOF: Size of a variable in bytes 191

33002519 09/2020 185


Extract

186 33002519 09/2020


EcoStruxure™ Control Expert
EXTRACT
33002519 09/2020

Chapter 44
EXTRACT: Copy of a variable part into another variable

EXTRACT: Copy of a variable part into another variable

Description

Function description
The EXTRACT function copies a defined part out of a source variable (SRC) into a destination
variable (DST).
NOTE: Parts of Arrays of EBOOL and IODDTs can not be copied because SRC and DST are of
data type ANY.
Data types of source and destination variables can be different.
As SRC and DST are of data type ANY and you can copy any part of a variable to any another
variable, there will be no validity check for the copy operation.

WARNING
UNINTENDED EQUIPMENT OPERATION
Check the results of all modified variables before re-starting your process application.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

The memory size of the source variable (SRC) is identified by the function block (in bytes) internally.
Depending on the alignment of the different PLC platforms the memory size can differ from
platform to platform.
SRC_NELEM defines the number of parts of the source variable. The memory size of the source
variable (in bytes) is divided by SRC_NELEM, and so the size of every part is defined.
Example

Variable SRC_NELEM Size of part


ARRAY[0..9] OF WORD 5 DWORD (4 bytes)
10 WORD (2 bytes)
20 BYTE

The value of SRC_NELEM must allow the division of the memory size of the source variable without
remainder.

33002519 09/2020 187


EXTRACT

The number of elements to be copied (CPY_NELEM) out of the source variable starts from a defined
position (SRC_POS) and is copied to a defined position in the destination variable (DST_POS).
NOTE: SRC_POS and DST_POS define the position of the parts to be copied based on 0 to n.
Example with SRC_NELEM = 10

Variable SRC_POS Position in ARRAY


ARRAY[0..9] OF WORD 2 2
ARRAY[5..14] OF WORD 2 7

The additional parameters EN and ENO can be configured.


You can use the SIZEOF function (see page 191) to set the value of SRC_NELEM input to the
number of bytes of the source variable.

Representation in FBD
Representation:

Representation in LD
Representation:

188 33002519 09/2020


EXTRACT

Representation in IL
Representation:
LD Array1_10_of_DDT
EXTRACT Source_Num_Ele, Source_Pos, Dest_Pos, Copy_Num_Ele,
Array_1_20_of_DDT, Copy_Status

Representation in ST
Representation:
EXTRACT(Array1_10_of_DDT, Source_Num_Ele, Source_Pos, Dest_Pos,
Copy_Num_Ele, Array1_20_of_DDT, Copy_Status);

Description of Parameters
The following table describes the input parameters:

Parameter Type Comment


Array1_10_of_DDT ANY Source variable from which a defined number of parts
(Copy_Num_Ele) is copied to the destination variable
(Array_1_20_of_DDT).
Source_Num_Ele UDINT number of parts of the source variable
The memory size of the source variable (in bytes) is
divided by Source_Num_Ele, and so the size of every
part is defined.
Source_Pos UDINT position of the first part to be copied from the source
variable
The position is based on 0 to n.
Dest_Pos UDINT position of the first part to be copied to the destination
variable
The position is based on 0 to n.
Copy_Num_Ele UDINT number of parts of the source variable which is copied
to the destination variable

The following table describes the output parameters:

Parameter Type Comment


Array_1_20_of_DDT ANY Destination variable to which a defined number of parts
(Copy_Num_Ele) is copied from the source variable
(Array_1_10_of_DDT).
ERR INT runtime errors
For the values see table below

33002519 09/2020 189


EXTRACT

Runtime Detected Errors


Values of ERR

Value Description
0 Copy action has been successful.
<0 invalid parameters
Copy action has not been performed.
>0 Parameters are suspect but valid.
Copy action has been performed.
-1 Number of parts of source (SRC_NELEM) not defined.
-2 Number of parts does not match the size of the source variable.
Memory size of the source variable is not divisible without remainder.
-3 SRC_POS is outside source variable bounds.
-4 DST_POS is outside destination variable bounds.
1 CPY_NELEM = 0, no parts to be copied
Parameter is suspect but valid.
2 Not all parts could be copied to the destination variable for lack of space. Parts
to be copied have been shortened.

190 33002519 09/2020


EcoStruxure™ Control Expert
SIZEOF
33002519 09/2020

Chapter 45
SIZEOF: Size of a variable in bytes

SIZEOF: Size of a variable in bytes

Description

Function description
The SIZEOF function delivers the memory size of a variable in bytes.
Depending on the alignment of the different PLC platforms the memory size can differ from
platform to platform.
The additional parameters EN and ENO can be configured.

Representation in FBD
Representation:

Representation in LD
Representation:

Representation in IL
Representation:
LD Array1_10_of_DDT
SIZEOF
ST Size_Struct

33002519 09/2020 191


SIZEOF

Representation in ST
Representation:
Size_Struct:= SIZEOF(Array1_10_of_DDT);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Array1_10_of_DDT ANY variable, whose memory size in bytes should be
detected

The following table describes the output parameter

Parameter Type Comment


Size_Struct UDINT number of bytes detected for the variable connected
to the IN pin

192 33002519 09/2020


EcoStruxure™ Control Expert
Logic
33002519 09/2020

Part VII
Logic

Logic

Overview
This section describes the elementary functions and elementary function blocks of the Logic
family.

What Is in This Part?


This part contains the following chapters:
Chapter Chapter Name Page
46 AND: AND function 195
47 F_TRIG: Falling edge detection 197
48 FE: Detection of Falling Edge 199
49 NOT: Negation 201
50 OR: OR function 203
51 R_TRIG: Rising edge detection 205
52 RE: Detection of Rising Edge 207
53 RESET: Setting of a bit to 0 209
54 ROL: Rotate left 211
55 ROR: Rotate right 215
56 RS: Bistable function block, reset dominant 217
57 SET: Setting of a bit to 1 219
58 SHL: Shift left 221
59 SHR: Shift right 223
60 SR: Bistable function block, set dominant 225
61 TRIGGER: Detection of all edges 227
62 XOR: Exclusive OR function 229

33002519 09/2020 193


Logic

194 33002519 09/2020


EcoStruxure™ Control Expert
AND
33002519 09/2020

Chapter 46
AND: AND function

AND: AND function

Description

Function description
The function for a bit-by-bit AND link of the bit sequences at the inputs and assigns the result to
the output.
The data types of all input values and output values must be identical.
The number of inputs can be increased to a maximum of 32.
EN and ENO can be configured as additional parameters.

Further available functions


When using a Premium PLC, the following functions are also available in the Obsolete library:
 AND_DINT
 AND_INT

The functionality of these functions is identical to the function AND.

Formula
OUT = IN1 & IN2 & ... & INn

Representation in FBD
Representation:

33002519 09/2020 195


AND

Representation in LD
Representation:

Representation in IL
Representation:
LD Value_1
AND Value_2
ST Result

Representation in ST
Representation:
Result := AND (Value_1, Value_2) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


Value_1 BOOL, BYTE, WORD, DWORD Input bit sequence
Value_2 BOOL, BYTE, WORD, DWORD Input bit sequence
Value_n BOOL, BYTE, WORD, DWORD Input bit sequence (n = max. 32)

Description of the output parameter:

Parameter Data type Meaning


Result BOOL, BYTE, WORD, Output bit sequence
DWORD

196 33002519 09/2020


EcoStruxure™ Control Expert
F_TRIG
33002519 09/2020

Chapter 47
F_TRIG: Falling edge detection

F_TRIG: Falling edge detection

Description

Function description
This function block is used for the detection of falling edges 1 -> 0.
Output Q becomes "1" if there is a transition from "1" to "0" at the CLK input. The output will remain
at "1" from one function block execution to the next; the output subsequently returns to "0".
EN and ENO can be configured as additional parameters.

Representation in FBD
Representation:

Representation in LD
Representation:

Representation in IL
Representation:
CAL F_TRIG_Instance (CLK:=ClockInput, Q=>Output)

33002519 09/2020 197


F_TRIG

Representation in ST
Representation:
F_TRIG_Instance (CLK:=ClockInput, Q=>Output) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


CLK BOOL Clock input

Description of the output parameter:

Parameter Data type Meaning


Q BOOL Output

198 33002519 09/2020


EcoStruxure™ Control Expert
FE
33002519 09/2020

Chapter 48
FE: Detection of Falling Edge

FE: Detection of Falling Edge

Description

Function description
The FE function detects the passage from 1 to 0 (Falling Edge) of the bit associated with it. For
additional information see also chapter Edge Recognition (see EcoStruxure™ Control Expert,
Program Languages and Structure, Reference Manual).
The additional parameters EN and ENO can be configured.
NOTE: You can alternatively use for EBOOL also R_TRIG, F_TRIG and TRIGGER, which are
working independant from the history bit of the EBOOL type.

Representation in FBD
Representation:

Representation in LD
The FE function cannot be used in LD. You have to use equivalent LD functions.
Representation:

Representation in IL
Representation:
LD Start_Button
FE
ST Start_Pulse

33002519 09/2020 199


FE

Representation in ST
Representation:
Start_Pulse:= FE (Start_Button);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Start_Button EBOOL Discrete input or output or internal bit whose Falling
Edge we wish to detect.

The following table describes the output parameters:

Parameter Type Comment


Start_Pulse BOOL Internal bit or output representing the Falling Edge.

The EBOOL variable has to be written once in every scan of the CPU. In all other cases a
malfunction is possible. Only the discrete input can be used without restrictions, because it is
written from the I/O management of the CPU.

Trend diagram
Timing diagram:

T T is equal to a PLC cycle time for an input and is the delay between two assignments for a discrete output
or an internal bit.

200 33002519 09/2020


EcoStruxure™ Control Expert
NOT
33002519 09/2020

Chapter 49
NOT: Negation

NOT: Negation

Description

Function description
The function negates the input bit sequence bit-by-bit and assigns the result to the output.
The data types of the input and output values must be identical.
EN and ENO can be configured as additional parameters.

Further available functions


The Obsolete library provides the following additional functions:
 NOT_DINT
 NOT_INT

The functionality of these functions is identical to the function NOT.

Formula
OUT = NOT IN

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 201


NOT

Representation in IL
Representation:
LD Value
NOT
ST NegValue

Representation in ST
Representation:
NegValue := NOT (Value) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


Value BOOL, BYTE, WORD, DWORD Input bit sequence

Description of the output parameter:

Parameter Data type Meaning


NegValue BOOL, BYTE, WORD, DWORD Negated bit sequence

202 33002519 09/2020


EcoStruxure™ Control Expert
OR
33002519 09/2020

Chapter 50
OR: OR function

OR: OR function

Description

Function description
The function for a bit OR link of the bit sequences at the inputs and returns the result at the output.
The data types of all input values and output values must be identical.
The number of inputs can be increased to a maximum of 32.
EN and ENO can be configured as additional parameters.

Further available functions


When using a Premium PLC, the following functions are also available in the Obsolete library:
 OR_DINT
 OR_INT

The functionality of these functions is identical to the function OR.

Formula
OUT = IN1 OR IN2 OR ... OR INn

Representation in FBD
Representation:

33002519 09/2020 203


OR

Representation in LD
Representation:

Representation in IL
Representation:
LD Value_1
OR Value_2
ST Result

Representation in ST
Representation:
Result := OR (Value_1, Value_2) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


Value_1 BOOL, BYTE, WORD, DWORD Input bit sequence
Value_2 BOOL, BYTE, WORD, DWORD Input bit sequence
Value_n BOOL, BYTE, WORD, DWORD Input bit sequence
n = max. 32

Description of the output parameter:

Parameter Data type Meaning


Result BOOL, BYTE, WORD, DWORD Output bit sequence

204 33002519 09/2020


EcoStruxure™ Control Expert
R_TRIG
33002519 09/2020

Chapter 51
R_TRIG: Rising edge detection

R_TRIG: Rising edge detection

Description

Function description
This function block is used for the detection of rising edges 0 -> 1.
Output Q becomes "1" if there is a transition from "0" to "1" at the CLK input. The output remains at
"1" from one function block execution to the next (one cycle); the output subsequently returns to
"0".
EN and ENO can be configured as additional parameters.

Representation in FBD
Representation:

Representation in LD
Representation:

Representation in IL
Representation:
CAL R_TRIG_Instance (CLK:=ClockInput, Q=>Output)

33002519 09/2020 205


R_TRIG

Representation in ST
Representation:
R_TRIG_Instance (CLK:=ClockInput, Q=>Output) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


CLK BOOL Clock input

Description of the output parameter:

Parameter Data type Meaning


Q BOOL Output

206 33002519 09/2020


EcoStruxure™ Control Expert
RE
33002519 09/2020

Chapter 52
RE: Detection of Rising Edge

RE: Detection of Rising Edge

Description

Function description
The RE function detects the passage from 0 to 1(Rising Edge) of the bit associated with it. For
additional information see also chapter Edge Recognition (see EcoStruxure™ Control Expert,
Program Languages and Structure, Reference Manual).
The additional parameters EN and ENO can be configured.
NOTE: You can alternatively use for EBOOL also R_TRIG, F_TRIG and TRIGGER, which are
working independant from the history bit of the EBOOL type.

Representation in FBD
Representation:

Representation in LD
The RE function cannot be used in LD. You have to use equivalent LD functions
Representation:

Representation in IL
Representation:
LD Start_Button
RE
ST Start_Pulse

33002519 09/2020 207


RE

Representation in ST
Representation:
Start_Pulse := RE (Start_Button);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Start_Button EBOOL Discrete input or output, internal bit whose Rising
Edge we wish to detect

The following table describes the output parameters:

Parameter Type Comment


Start_Pulse BOOL Internal bit or output representing the Rising Edge.

The EBOOL variable has to be written once in every scan of the CPU. In all other cases a
malfunction is possible. Only the discrete input can be used without restrictions, because it is
written from the I/O management of the CPU.

Trend diagram
Timing diagram:

T T is equal to a PLC cycle time for an input and is the delay between two assignments for a discrete output
or an internal bit.

208 33002519 09/2020


EcoStruxure™ Control Expert
RESET
33002519 09/2020

Chapter 53
RESET: Setting of a bit to 0

RESET: Setting of a bit to 0

Description

Function description
The RESET function sets the bit associated with it to zero.

Representation in FBD
Representation:

Representation in LD
Representation:

Representation in IL
Representation:
CAL RESET(Bit_to_Reset)

Representation in ST
Representation:
RESET (Bit_to_Reset);

33002519 09/2020 209


RESET

Description of parameters
The following table describes the output parameters:

Parameter Type Comment


Bit_to_Reset BOOL Discrete input or output or internal bit we wish to set to 0.

210 33002519 09/2020


EcoStruxure™ Control Expert
ROL
33002519 09/2020

Chapter 54
ROL: Rotate left

ROL: Rotate left

Description

Function description
This function rotates the bit pattern at the IN input circularly to the left by n bits (value at input
Number).
System bit %S17 is used as CARRY bit, i.e. the status of the bit that is shifted out is stored there.
The data types of the IN input and OUT output must be identical.
NOTE: Because of IEC 61131-3 conformity, this function also works with the BOOL data type. This
is not significant here.
EN and ENO can be configured as additional parameters.

Available Functions
List of available functions
 ROL_BOOL
 ROL_BYTE
 ROL_WORD
 ROL_DWORD

Further available functions


When using a Premium PLC, the following functions are also available in the Obsolete library:
 ROL_DINT
 ROL_INT

The functionality of these functions is identical to the function ROL.

Representation in FBD
Representation:

33002519 09/2020 211


ROL

Representation in LD
Representation:

Representation in IL
Representation:
LD InputPattern
ROL Number
ST OutputPattern

Representation in ST
Representation:
OutputPattern := ROL (InputPattern, Number) ;

212 33002519 09/2020


ROL

Parameter description
Description of the input parameters:

Parameter Data type Meaning


InputPattern For ROL: BOOL, BYTE, WORD, DWORD, INT, DINT this is the bit pattern to be
For ROL_BOOL: BOOL rotated
For ROL_BYTE: BYTE
For ROL_WORD: WORD
For ROL_DWORD: DWORD
For ROL_INT: INT
For ROL_DINT: DINT
Number For ROL, ROL_BOOL, ROL_BYTE, ROL_WORD, this is the number of
ROL_DWORD: UINT spaces to be rotated
For ROL_INT, ROL_DINT: INT

Description of the output parameter:

Parameter Data type Meaning


OutputPattern For ROL: BOOL, BYTE, WORD, DWORD, INT, DINT this is the bit pattern rotated
For ROL_BOOL: BOOL
For ROL_BYTE: BYTE
For ROL_WORD: WORD
For ROL_DWORD: DWORD
For ROL_INT: INT
For ROL_DINT: DINT

33002519 09/2020 213


ROL

Function Block Behavior


The maximum number of rotation should be less or equal to the size of the operand:
 for BYTE, the maximum number of rotations is 8.
 for WORD and INT, the maximum number of rotations is 16.
 for DWORD and DINT, the maximum number of rotations is 32.

The table below gives the output value of the rotate function block depending on the number of
rotations and the size of the operand:

Type Number of rotations Output value %S17


BYTE 0 = Input value 0
1...31 = Rotated input value MSB
>31 =0 0
WORD/INT 0 = Input value 0
1...16 = Rotated input value MSB
17...31 = Incorrect value •• (1)
>31 =0 0
DWORD/DINT 0 = Input value 0
1...32 = Rotated input value MSB
>32 =0 0
(1) unpredictable

214 33002519 09/2020


EcoStruxure™ Control Expert
ROR
33002519 09/2020

Chapter 55
ROR: Rotate right

ROR: Rotate right

Description

Function description
This function rotates the bit pattern at the In input circularly to the right by n bits (value at input
Number).
System bit %S17 is used as CARRY bit, i.e. the status of the bit that is shifted out is stored there.
The data types of the IN input and OUT output must be identical.
NOTE: Because of IEC 61131-3 conformity, this function also works with the BOOL data type. This
is not significant here.
EN and ENO can be configured as additional parameters.

Further available functions


When using a Premium PLC, the following functions are also available in the Obsolete library:
 ROR_DINT
 ROR_INT

The functionality of these functions is identical to the function ROR.

Representation in FBD
Representation:

33002519 09/2020 215


ROR

Representation in LD
Representation:

Representation in IL
Representation:
LD InputPattern
ROR Number
ST OutputPattern

Representation in ST
Representation:
OutputPattern := ROR (InputPattern, Number) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


InputPattern For ROR: BOOL, BYTE, WORD, DWORD this is the bit pattern to be rotated
For ROR_INT: INT
For ROR_DINT: DINT
Number For ROR: UINT this is the number of spaces to be rotated
For ROR_INT, ROR_DINT: INT

Description of the output parameter:

Parameter Data type Meaning


OutputPattern For ROR: BOOL, BYTE, WORD, DWORD this is the bit pattern rotated
For ROR_INT: INT
For ROR_DINT: DINT

216 33002519 09/2020


EcoStruxure™ Control Expert
RS
33002519 09/2020

Chapter 56
RS: Bistable function block, reset dominant

RS: Bistable function block, reset dominant

Description

Function description
The function block is used as RS memory with the property "Reset dominant".
Output Q1 becomes "1" when the S input becomes "1". This state remains even if input S reverts
back to "0". Output Q1 changes back to "0" when input R1 becomes "1". If the inputs S and R1 are
"1" simultaneously, the dominating input R1 will set the output Q1 to "0".
When the function block is called for the first time, the initial state of Q1 is "0".
EN and ENO can be configured as additional parameters.

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 217


RS

Representation in IL
Representation:
CAL RS_Instance (S:=Set, R1:=Reset, Q1=>Output)

Representation in ST
Representation:
RS_Instance (S:=Set, R1:=Reset, Q1=>Output) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


S BOOL Set
R1 BOOL Reset (dominant)

Description of the output parameter:

Parameter Data type Meaning


Q1 BOOL Output

218 33002519 09/2020


EcoStruxure™ Control Expert
SET
33002519 09/2020

Chapter 57
SET: Setting of a bit to 1

SET: Setting of a bit to 1

Description

Function description
The SET function sets the bit associated with it to 1.

Representation in FBD
Representation:

Representation in LD
Representation:

Representation in IL
Representation:
CAL SET(Bit_to_Set)

Representation in ST
Representation:
SET (Bit_to_Set);

33002519 09/2020 219


SET

Description of parameters
The following table describes the output parameters:

Parameter Type Comment


Bit_to_Set BOOL Discrete input or output or internal bit we wish to set to 1.

220 33002519 09/2020


EcoStruxure™ Control Expert
SHL
33002519 09/2020

Chapter 58
SHL: Shift left

SHL: Shift left

Description

Function description
This function shifts the bit pattern at the IN input to the left by n bits (value at input N).
System bit %S17 is used as CARRY bit, i.e. the status of the bit that is shifted out is stored there.
Zeros are filled in from the right.
The data types of the IN input and OUT output must be identical.
NOTE: Because of IEC 61131-3 conformity, this function also works with the BOOL data type. This
is not significant here.
EN and ENO can be configured as additional parameters.

Further available functions


Additionally, the Obsolete library provides the following functions:
 SHL_DINT
 SHL_INT

The functionality of these functions is identical to the function SHL.

Representation in FBD
Representation:

33002519 09/2020 221


SHL

Representation in LD
Representation:

Representation in IL
Representation:
LD IntputPattern
SHL Number
ST ShiftedPattern

Representation in ST
Representation:
ShiftedPattern := SHL (IntputPattern, Number) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


IntputPattern For SHL: BOOL, BYTE, WORD, this is the bit pattern to be shifted
DWORD For example: IntputPattern =
For SHL_INT: INT 2#0100000011110001.
For SHL_DINT: DINT
Number For SHL: UINT this is the number of spaces to be shifted
For SHL_INT, SHL_DINT: INT Example: Number = 4.

Description of the output parameter:

Parameter Data type Meaning


ShiftedPattern For SHL: BOOL, BYTE, this is the bit pattern shifted
WORD, DWORD For example: with the data from the previous table,
For SHL_INT: INT the result is: ShiftedPattern =
For SHL_DINT: DINT 2#0000111100010000

222 33002519 09/2020


EcoStruxure™ Control Expert
SHR
33002519 09/2020

Chapter 59
SHR: Shift right

SHR: Shift right

Description

Function description
This function shifts the bit pattern at the IN input to the right by n bits (value at input N).
System bit %S17 is used as CARRY bit, i.e. the status of the bit that is shifted out is stored there.
Zeros are filled in from the left.
NOTE: If in the dialog box Tools → Project Settings → Language extensions, the option INT/DINT
is activated instead of ANY_BIT is selected, the input IN uses data types INT or DINT.
The data types of the IN input and OUT output must be identical.
NOTE: Because of IEC 61131-3 conformity, this function also works with the BOOL data type. This
is not significant here.
EN and ENO can be configured as additional parameters.

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 223


SHR

Representation in IL
Representation:
LD IntputPattern
SHR Number
ST ShiftedPattern

Representation in ST
Representation:
ShiftedPattern := SHR (IntputPattern, Number) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


IntputPattern BOOL, BYTE, WORD, DWORD this is the bit pattern to be shifted
For example: IntputPattern =
2#0100000011110001.
Number UINT this is the number of spaces to be shifted
Example: Number = 4.

Description of the output parameter:

Parameter Data type Meaning


ShiftedPattern BOOL, BYTE, WORD, this is the bit pattern shifted
DWORD For example: with the data from the previous table,
the result is: ShiftedPattern = 2#0000010000001111

224 33002519 09/2020


EcoStruxure™ Control Expert
SR
33002519 09/2020

Chapter 60
SR: Bistable function block, set dominant

SR: Bistable function block, set dominant

Description

Function description
The function block is used as SR memory with the property "Set dominant".
Output Q1 becomes "1" when the S1 input becomes "1". This state remains even if input S1 reverts
back to "0". Output Q1 changes back to "0" when input R becomes "1". If the inputs S1 and R are
both "1" simultaneously, the dominating input S1 will set the output Q1 to "1".
When the function block is called for the first time, the initial state of Q1 is "0".
EN and ENO can be configured as additional parameters.

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 225


SR

Representation in IL
Representation:
CAL SR_Instance (S1:=Set, R:=Reset, Q1=>Output)

Representation in ST
Representation:
SR_Instance (S1:=Set, R:=Reset, Q1=>Output) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


S1 BOOL Set (dominant)
R BOOL Reset

Description of the output parameter:

Parameter Data type Meaning


Q1 BOOL Output

226 33002519 09/2020


EcoStruxure™ Control Expert
TRIGGER
33002519 09/2020

Chapter 61
TRIGGER: Detection of all edges

TRIGGER: Detection of all edges

Description

Function description
The function block recognizes all types of edges (1 -> 0 and 0 -> 1) at the CLK input.
At a rising edge, a transition from "0" to "1"occurs on the CLK input; at a falling edge, a transition
from "1" to "0" occurs on the CLK input.
At any edge, the EDGE output becomes "1".
At a rising edge, the EDGE output and the RISE output become "1".
At a falling edge, the EDGE output and the FALL output become "1". If no edge occurs, all outputs
are "0".
EN and ENO can be configured as additional parameters.

Representation in FBD
Representation:

33002519 09/2020 227


TRIGGER

Representation in LD
Representation:

Representation in IL
Representation:
CAL TRIGGER_Instance (CLK:=ClockInput, RISE=>RisingEdge,
EDGE=>AnyEdge, FALL=>FallingEdge)

Representation in ST
Representation:
TRIGGER_Instance (CLK:=ClockInput, RISE=>RisingEdge,
EDGE=>AnyEdge, FALL=>FallingEdge) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


CLK BOOL Clock input

Description of the output parameter:

Parameter Data type Meaning


RISE BOOL Indicator of a rising edge
EDGE BOOL Indicator of all types of edges
FALL BOOL Indicator of a falling edge

228 33002519 09/2020


EcoStruxure™ Control Expert
XOR
33002519 09/2020

Chapter 62
XOR: Exclusive OR function

XOR: Exclusive OR function

Description

Function description
The function for a bit XOR link of the bit sequences at the inputs and returns the result at the output.
The data types of all input values and output values must be identical.
The number of inputs can be increased to a maximum of 32.
EN and ENO can be configured as additional parameters.

Further available functions


When using a Premium PLC, the following functions are also available in the Obsolete library:
 XOR_DINT
 XOR_INT

The functionality of these functions is identical to the function XOR.

Formula
OUT = IN1 XOR IN2 XOR .. XOR INn

Representation in FBD
Representation:

33002519 09/2020 229


XOR

Representation in LD
Representation:

Representation in IL
Representation:
LD Value_1
XOR Value_2
ST Result

Representation in ST
Representation:
Result := XOR (Value_1, Value_2) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


Value_1 BOOL, BYTE, WORD, Input bit sequence
DWORD
Value_2 BOOL, BYTE, WORD, Input bit sequence
DWORD
Value_n BOOL, BYTE, WORD, Input bit sequence
DWORD n = max 32

Description of the output parameter:

Parameter Data type Meaning


Result BOOL, BYTE, WORD, Output bit sequence
DWORD

230 33002519 09/2020


EcoStruxure™ Control Expert
Mathematics
33002519 09/2020

Part VIII
Mathematics

Mathematics

Overview
This section describes the elementary functions and elementary function blocks of the
Mathematics family.

What Is in This Part?


This part contains the following chapters:
Chapter Chapter Name Page
63 ABS: Absolute value computation 233
64 ACOS: Arc cosine 235
65 ADD: Addition 237
66 ADD_TIME: Addition 239
67 ASIN: Arc sine 241
68 ATAN: Arc tangent 243
69 COS: Cosine 245
70 DEC: Decrementation of a variable 247
71 DIV: Division 249
72 DIVMOD: Division and Modulo 253
73 EXP: Natural exponential 255
74 EXPT_REAL_***: Exponentiation of one value by another value 257
75 INC: Incrementation of a variable 261
76 LN: Natural logarithm 263
77 LOG : Base 10 logarithm 265
78 MOD: Modulo 267
79 MOVE: Assignment 269
80 MUL: Multiplication 271
81 NEG: Negation 273
82 SATURATION: Saturation 275
83 SIGN: Sign evaluation 279
84 SIN: Sine 281
85 SUB: Subtraction 283
86 SUB_TIME: Subtraction 285

33002519 09/2020 231


Mathematics

Chapter Chapter Name Page


87 SQRT_*** : Square root 287
88 TAN: Tangent 289

232 33002519 09/2020


EcoStruxure™ Control Expert
ABS
33002519 09/2020

Chapter 63
ABS: Absolute value computation

ABS: Absolute value computation

Description

Function description
The function computes the absolute value of the input value and assigns the result to the output.
The data types of the input and output values must be identical.
NOTE: Because of IEC 61131-3 conformity, this function also works with the UINT and UDINT data
types. This is not significant here.
EN and ENO can be configured as additional parameters.

Formula

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 233


ABS

Representation in IL
Representation:
LD Value
ABS
ST Result

Representation in ST
Representation:
Result := ABS (Value) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


Value INT, DINT, UINT, Input value
UDINT, REAL

Description of the output parameter:

Parameter Data type Meaning


Result INT, DINT, UINT, Output value
UDINT, REAL

Runtime error
The system bit %S18 is set to 1, if
 a value is below a limit value (data types INT and DINT)
or
 an unauthorized floating point number is set at an input parameter of data type REAL. In this
case, the status is also placed in %SW17.

234 33002519 09/2020


EcoStruxure™ Control Expert
ACOS
33002519 09/2020

Chapter 64
ACOS: Arc cosine

ACOS: Arc cosine

Description

Function description
The ACOS function calculates the principal arc cosine of a real value. The result is given in the form
of an angle in radians.
The function call can also be carried out by ACOS_REAL.
The additional parameters EN and ENO can be configured.

Formula
The formula is as follows:

Representation in FBD
Representation:

Representation in LD
Illustration:

33002519 09/2020 235


ACOS

Representation in IL
Representation:
LD Cos_Value
ACOS_REAL
ST Angle

Representation in ST
Representation:
Angle:= ACOS_REAL(Cos_Value);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Cos_Value REAL Cosine of angle calculated at block output.
-1 ≤ Cos_Value ≤ 1

The following table describes the output parameters:

Parameter Type Comment


Angle REAL Angle expressed in radians, whose cosine has the
value Cos_Value.
0 ≤ Angle ≤ π

Runtime errors
When the absolute value Cos_Value is greater than 1, the system bit %S18 changes to 1 and the
system word %SW17 indicates the type of fault.

236 33002519 09/2020


EcoStruxure™ Control Expert
ADD
33002519 09/2020

Chapter 65
ADD: Addition

ADD: Addition

Description

Function description
The function adds the input values and assigns the result to the output.
The data types of all input values and output values must be identical.
The number of inputs can be increased to a maximum of 32 for all functions.
For addition with values of the TIME data type, there is the block ADD_TIME (see page 239)
EN and ENO can be configured as additional parameters.

Formula
INT, DINT, UINT, UDINT, REAL:
OUT = IN1 + IN2 + ... + INn

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 237


ADD

Representation in IL
Representation:
LD Value1
ADD Value2
ST Sum

Representation in ST
Representation:
Sum := ADD (Value1, Value2) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


Value1 INT, DINT, UINT, Summand
UDINT, REAL
Value2 INT, DINT, UINT, Summand
UDINT, REAL
Valuen INT, DINT, UINT, Summand
UDINT, REAL n = max 32

Description of the output parameter:

Parameter Data type Meaning


Sum INT, DINT, UINT, Sum
UDINT, REAL

Runtime error
The system bit %S18 is set to 1, if
 the value range on the output is exceeded (all available data types)
or
 an unauthorized floating point number is set at an input parameter of data type REAL. In this
case, the status is also placed in %SW17.

238 33002519 09/2020


EcoStruxure™ Control Expert
ADD_TIME
33002519 09/2020

Chapter 66
ADD_TIME: Addition

ADD_TIME: Addition

Description

Function description
This function adds 2 input values of data type TIME and assigns the result to the output (also data
type TIME).
EN and ENO can be configured as additional parameters.

Formula
OUT = IN1 + IN2

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 239


ADD_TIME

Representation in IL
Representation:
LD TimeValue1
ADD_TIME TimeValue2
ST Sum

Representation in ST
Representation:
Sum := ADD_TIME (TimeValue1, TimeValue2) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


TimeValue1 TIME Summand
TimeValue2 TIME Summand

Description of the output parameter:

Parameter Data type Meaning


Sum TIME Sum

Runtime error
System bit %S18 is set to 1 if the value range at the output is exceeded.

240 33002519 09/2020


EcoStruxure™ Control Expert
ASIN
33002519 09/2020

Chapter 67
ASIN: Arc sine

ASIN: Arc sine

Description

Function description
The ASIN function calculates the principal sine arc of a real value. The result is given in the form
of an angle in radians.
The function call can also be carried out by ASIN_REAL.
The additional parameters EN and ENO can be configured.

Formula
The formula is as follows:

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 241


ASIN

Representation in IL
Representation:
LD Sin_Value
ASIN_REAL
ST Angle

Representation in ST
Representation:
Angle:= ASIN_REAL(Sin_Value);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Sin_Value REAL Sine of angle calculated at block output.
-1 ≤ Sin_Value ≤ 1

The following table describes the output parameters:

Parameter Type Comment


Angle REAL Angle expressed in radians, whose sine has the value
Sin_Value.
- π/2 ≤ Angle ≤ + π/2

Runtime errors
When the absolute value Sin_Value is greater than 1, the system bit %S18 changes to 1 and the
system word %SW17 indicates the type of fault.

242 33002519 09/2020


EcoStruxure™ Control Expert
ATAN
33002519 09/2020

Chapter 68
ATAN: Arc tangent

ATAN: Arc tangent

Description

Function description
The ACOS function calculates the principal arc tangent of a real value. The result is given in the
form of an angle in radians.
The function call can also be carried out by ATAN_REAL.
The additional parameters EN and ENO can be configured.

Formula
The formula is as follows:

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 243


ATAN

Representation in IL
Representation:
LD Tan_Value
ATAN_REAL
ST Angle

Representation in ST
Representation:
Angle:= ATAN_REAL(Tan_Value);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Tan_Value REAL Tangent of angle calculated at block output.
-1.#INF < Tan_Value < +1.#INF

The following table describes the output parameters:

Parameter Type Comment


Angle REAL Angle expressed in radians, whose tangent has the
value Tan_Value.
- π/2 < Angle < +π/2

Runtime errors
When the absolute value Tan_Value is greater than 1, the system bit %S18 changes to 1 and the
system word %SW17 indicates the type of fault.

244 33002519 09/2020


EcoStruxure™ Control Expert
COS
33002519 09/2020

Chapter 69
COS: Cosine

COS: Cosine

Description

Function description
The COS function calculates the cosine of an angle.
The function call can also be carried out by COS_REAL.
The additional parameters EN and ENO can be configured.

Formula
The formula is as follows:
Cos_Value = Cos(Angle)

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 245


COS

Representation in IL
Representation:
LD Angle
COS_REAL
ST Cos_Value

Representation in ST
Representation:
Cos_Value:= COS_REAL(Angle);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Angle REAL Angle expressed in radians.
-2 63 < Angle < +2 63

The following table describes the output parameters:

Parameter Type Comment


Cos_Value REAL Cosine of Angle expressed in radians.
-1 ≤ Cos_Value ≤ 1

Runtime errors
When the absolute value of Angle is greater than 2 63, the system bit %S18 changes to 1 and the
system word %SW17 indicates the type of fault.

246 33002519 09/2020


EcoStruxure™ Control Expert
DEC
33002519 09/2020

Chapter 70
DEC: Decrementation of a variable

DEC: Decrementation of a variable

Description

Function description
The DEC function decrements a variable by 1.
The parameter of this function can be declared of type ANY_INT.
The additional parameters EN and ENO can be configured.

Representation in FBD
Representation applied to an integer:

Representation in LD
Representation applied to an integer:

Representation in IL
Representation applied to an integer:
CAL DEC(Value1)

33002519 09/2020 247


DEC

Representation in ST
Representation applied to an integer:
DEC(Value1);

Description of parameters
The following table describes the input/output parameters:

Parameter Type Comment


Value1 INT, DINT, UINT, Each time the program uses this EF the variable
UDINT. Value1 is decremented by one unit.

Runtime errors
In the case of overrun, the system bit %S18 is set to 1 and the decremented value becomes
positive (32767 for an integer for example).

248 33002519 09/2020


EcoStruxure™ Control Expert
DIV
33002519 09/2020

Chapter 71
DIV: Division

DIV: Division

Description

Function description
The function divides the value at the Dividend with the value at the Divisor input and assigns
the result to the output.
The data types of the input values and the output values must be identical.
For division with values of the TIME data type, you can use the block DIVTIME (see page 177).
When dividing INT, DINT, UINT and UDINT data types, any decimal places in the result are
omitted, e.g.

EN and ENO can be configured as additional parameters.

Formula

Representation in FBD
Representation:

33002519 09/2020 249


DIV

Representation in LD
Representation:

Representation in IL
Representation:
LD Dividend
DIV Divisor
ST Quotient

Representation in ST
Representation:
Quotient := DIV (Dividend, Divisor) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


Dividend INT, DINT, UINT, Dividend
UDINT, REAL
Divisor INT, DINT, UINT, Divisor
UDINT, REAL

Description of the output parameter:

Parameter Data type Meaning


Quotient INT, DINT, UINT, Quotient
UDINT, REAL

250 33002519 09/2020


DIV

Runtime error
The system bit %S18 is set to 1, if
 an invalid division by 0 is executed (all available data types)
or
 an unauthorized floating point number is set at an input parameter of data type REAL. In this
case, the status is also placed in %SW17.

33002519 09/2020 251


DIV

252 33002519 09/2020


EcoStruxure™ Control Expert
DIVMOD
33002519 09/2020

Chapter 72
DIVMOD: Division and Modulo

DIVMOD: Division and Modulo

Description

Function description
This procedure divides the value at the Dividend input by the value at the Divisor input. The
result of the division is delivered at the Quotient output. The remainder of the division is delivered
at the Modulo output.
If there is a decimal place in the division result, the division will truncate it.
The data types of all input and output values must be identical.
EN and ENO can be configured as additional parameters.

Formula
Block formula:
DV = IN1 / IN2
MD = IN1 mod IN2

Representation in FBD
Representation:

33002519 09/2020 253


DIVMOD

Representation in LD
Representation:

Representation in IL
Representation:
LD Dividend
DIVMOD Divisor, Quotient, Modulo

Representation in ST
Representation:
DIVMOD (Dividend, Divisor, Quotient, Modulo);

Parameter description
Description of the input parameters:

Parameter Data type Meaning


Dividend INT, DINT, UINT, Dividend
UDINT
Divisor INT, DINT, UINT, Divisor
UDINT

Description of the output parameter:

Parameter Data type Meaning


Quotient INT, DINT, UINT, Quotient
UDINT
Modulo INT, DINT, UINT, Modulo
UDINT

Runtime error
The system bit %S18 is set to 1, if an invalid division by 0 is executed.

254 33002519 09/2020


EcoStruxure™ Control Expert
EXP
33002519 09/2020

Chapter 73
EXP: Natural exponential

EXP: Natural exponential

Description

Function description
The EXP function calculates the natural exponential of a real.
The function call can also be carried out by EXP_REAL.
The additional parameters EN and ENO can be configured.

Formula
The formula is as follows:

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 255


EXP

Representation in IL
Representation:
LD Real_Value
EXP_REAL
ST Exp_Real_Value

Representation in ST
Representation:
Log_Real_Value:= EXP_REAL(Real_Value);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Real_Value REAL Real value of which we wish to obtain the Natural
exponential
-87.33654 < Real_Value < 88.72283

The following table describes the output parameters:

Parameter Type Comment


Exp_Real_Value REAL Natural exponential of Real_Value
0 < Exp_Real_Value < 1.#INF

Runtime errors
When Real_Value is situated outside the interval ]-87.33654, 88.72283[, the system bit %S18
changes to 1 and the system word %SW17 indicates the type of fault.

256 33002519 09/2020


EcoStruxure™ Control Expert
EXPT_REAL_***
33002519 09/2020

Chapter 74
EXPT_REAL_***: Exponentiation of one value by another value

EXPT_REAL_***: Exponentiation of one value by another value

Description

Function Description
The EXPT_REAL_*** function calculates the exponentiation of one value by another value.
The additional parameters EN and ENO can be configured.

Available functions
The available functions are as follows:
 EXPT_REAL_INT,
 EXPT_REAL_DINT,
 EXPT_REAL_UINT,
 EXPT_REAL_UDINT,
 EXPT_REAL_REAL.

Formula
The formula is as follows:

Representation in FBD
Representation applied to a real number:

33002519 09/2020 257


EXPT_REAL_***

Representation in LD
Representation applied to a real number:

Representation in IL
Representation applied to a real number:
LD Value1
EXPT_REAL_REAL Exponent
ST Expt_Real_Value

Representation in ST
Representation applied to a real number:
Expt_Real_Value := EXPT_REAL_REAL(Value1, Exponent);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Value1 REAL Value for which you want to find the exponential by
Exponent
0 ≤ Value1 < INF
Exponent INT, Exponent of the exponential
UINT, -INF < Exponent < +INF
DINT,
UDINT,
REAL.

The following table describes the output parameters:

Parameter Type Comment


Expt_Real__Value REAL Natural exponential of Value1
-1 < Expt_Real_Value < +INF

258 33002519 09/2020


EXPT_REAL_***

Runtime Errors
When Value1 is negative or when there is an Expt_Real_Value overrun the system bit %S18
changes to 1 and the system word %SW17 indicates the type of fault.

33002519 09/2020 259


EXPT_REAL_***

260 33002519 09/2020


EcoStruxure™ Control Expert
INC
33002519 09/2020

Chapter 75
INC: Incrementation of a variable

INC: Incrementation of a variable

Description

Function description
The INC function increments a variable by 1.
The parameter of this function can be declared of type ANY_INT.
The additional parameters EN and ENO can be configured.

Representation in FBD
Representation applied to an integer:

Representation in LD
Representation applied to an integer:

Representation in IL
Representation applied to an integer:
CAL INC(Value1)

33002519 09/2020 261


INC

Representation in ST
Representation applied to an integer:
INC(Value1);

Description of parameters
The following table describes the input/output parameters:

Parameter Type Comment


Value1 INT, DINT, UINT, Each time the program uses this EF, the variable
UDINT. Value1 is incremented by one unit.

Runtime errors
In the case of overrun, the system bit %S18 is set to 1 and the incremented value becomes
negative (-32768 for an integer for example).

262 33002519 09/2020


EcoStruxure™ Control Expert
LN
33002519 09/2020

Chapter 76
LN: Natural logarithm

LN: Natural logarithm

Description

Function description
The LN function calculates the natural logarithm of a real.
The function call can also be carried out by LN_REAL.
The additional parameters EN and ENO can be configured.

Formula
The formula is as follows:

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 263


LN

Representation in IL
Representation:
LD Real_Value
LN_REAL
ST Ln_Real_Value

Representation in ST
Representation:
Ln_Real_Value := LN_REAL(Real_Value);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Real_Value REAL Real value for which we wish to obtain the natural
logarithm.
0 < Real_Value < +INF

The following table describes the output parameters:

Parameter Type Comment


Ln_Real_Value REAL Natural logarithm of Real_Value
-INF < Ln_Real_Value < +INF

Runtime errors
WhenReal_Value is negative, the system bit %S18 changes to 1 and the system word %SW17
indicates the type of fault.

264 33002519 09/2020


EcoStruxure™ Control Expert
LOG
33002519 09/2020

Chapter 77
LOG : Base 10 logarithm

LOG : Base 10 logarithm

Description

Function description
The LOG function calculates the base 10 logarithm of a real number.
The function call can also be carried out by LOG_REAL.
The additional parameters EN and ENO can be configured.

Formula
The formula is as follows:

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 265


LOG

Representation in IL
Representation:
LD Real_Value
LOG_REAL
ST Log_Real_Value

Representation in ST
Representation:
Log_Real_Value:= LOG_REAL(Real_Value);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Real_Value REAL Real value of which we wish to obtain the natural
logarithm.
0 < Real_Value < 1.#INF

The following table describes the output parameters:

Parameter Type Comment


Log_Real_Value REAL Natural logarithm of Real_Value
-1.#INF < Log_Real_Value < +1.#INF

Runtime errors
WhenReal_Value is negative, the system bit %S18 changes to 1 and the system word %SW17
indicates the type of fault.

266 33002519 09/2020


EcoStruxure™ Control Expert
MOD
33002519 09/2020

Chapter 78
MOD: Modulo

MOD: Modulo

Description

Function description
The function divides the value at the Dividend with the value at the Divisor input and assigns
the modulo to the output.
The data types of all input values and output values must be identical.
EN and ENO can be configured as additional parameters.

Formula
OUT = IN1 mod IN2

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 267


MOD

Representation in IL
Representation:
LD Dividend
MOD Divisor
ST Rest

Representation in ST
Representation:
Rest := MOD (Dividend, Divisor) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


Dividend INT, DINT, UINT, Dividend
UDINT
Divisor INT, DINT, UINT, Divisor
UDINT

Description of the output parameter:

Parameter Data type Meaning


Remainder INT, DINT, UINT, Modulo
UDINT

Runtime error
The system bit %S18 is set to 1, if an invalid division by 0 is executed.

268 33002519 09/2020


EcoStruxure™ Control Expert
MOVE
33002519 09/2020

Chapter 79
MOVE: Assignment

MOVE: Assignment

Description

Function description
The function assigns the input value to the output.
This is a generic function, i.e. the data type to be processed will be determined by the variable that
was first assigned to the function.
If a direct address of a variable must be assigned or vice versa, always assign the variable to the
function first. A direct address at input and output of the function is not authorized since this does
not allow a clear definition of the data type. Variables address overlapping is not supported by this
function and only applies to Quantum Legacy CPUs and PLC Simulator.
The data types of the input and output values must be identical.
NOTE: It is not possible to copy an array of EBOOL elements using the MOVE function, since the
MOVE would not update the assignment history of the array elements. To copy an array of EBOOL
elements, use the COPY_AREBOOL_AREBOOL (see page 51) function.
EN and ENO can be configured as additional parameters.

Formula
OUT = IN

Representation in FBD
Representation:

33002519 09/2020 269


MOVE

Representation in LD
This function can not be used in the LD (Ladder Diagram) programming language with the BOOL
data type, since the same functionality can be achieved there with contacts and coils.
Representation:

Representation in IL
Representation:
LD Input
MOVE
ST Output

Representation in ST
Representation:
Output := MOVE (Input) ;

Parameter description
Description of the input parameter:

Parameter Data type Meaning


Input ANY Input value

Description of the output parameter:

Parameter Data type Meaning


Output ANY Output value

270 33002519 09/2020


EcoStruxure™ Control Expert
MUL
33002519 09/2020

Chapter 80
MUL: Multiplication

MUL: Multiplication

Description

Function description
The function multiplies the input values and assigns the result to the output.
The data types of all input values and output values must be identical.
The number of inputs can be increased to a maximum of 32.
For multiplication with values of the TIME data type, you can use the block MULTIME
(see page 179).
EN and ENO can be configured as additional parameters.

Formula
OUT = IN1 x IN2 x .. x IN n

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 271


MUL

Representation in IL
Representation:
LD Factor1
MUL Factor2
ST Product

Representation in ST
Representation:
Product := MUL (Factor1, Factor2) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


Factor1 INT, DINT, UINT, Multiplicand (factor)
UDINT, REAL
Factor2 INT, DINT, UINT, Multiplier (factor)
UDINT, REAL
Factorn INT, DINT, UINT, Multiplier (factor)
UDINT, REAL n = max 32

Description of the output parameter:

Parameter Data type Meaning


Product INT, DINT, UINT, Product
UDINT, REAL

Runtime error
The system bit %S18 is set to 1, if
 the value range at the output has been exceeded (all available data types)
or
 an unauthorized floating point number is set at an input parameter of data type REAL. In this
case, the status is also placed in %SW17.

272 33002519 09/2020


EcoStruxure™ Control Expert
NEG
33002519 09/2020

Chapter 81
NEG: Negation

NEG: Negation

Description

Function description
The function negates the input value and delivers the result at the NegatedOutput output.
The negation causes a sign reversal, e.g.
6 -> -6
-4 -> 4
NOTE: When the INT and DINT data types are processed, it is not possible to convert very long
negative values into positive ones. However, the ENO output is not set to 0 when this error occurs.
NOTE: When the UINT and UDINT data types are processed, an error message is always
returned.
The data types of the input and output values must be identical.
EN and ENO can be configured as additional parameters.

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 273


NEG

Representation in IL
Representation:
LD Input
NEG
ST NegatedOutput

Representation in ST
Representation:
NegatedOutput := NEG (Input) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


Input INT, DINT, UINT, Input
UDINT, REAL

Description of the output parameter:

Parameter Data type Meaning


NegatedOutput INT, DINT, UINT, Negated output
UDINT, REAL

Runtime error
The system bit %S18 is set to 1, if
 a violation of the value range at the input occurs during the execution of the function ( data types
INT and DINT)
or
 an input value of the data type UDINT or UINT is to be converted.

274 33002519 09/2020


EcoStruxure™ Control Expert
Saturation
33002519 09/2020

Chapter 82
SATURATION: Saturation

SATURATION: Saturation

SATURATION: Maximum REAL value

Function Description
There is a risk of a wrong result when adding a very large and a very small value. The SATURATION
function calculates the maximum REAL value (L, the saturation limit) that give a correct result when
added to a very small REAL value (P, the precision). The function output gives the maximum REAL
value (L) and a boolean error bit that indicates if the addition is OK (0) or not (1).
EN and ENO can be configured as additional parameters.

Formula
The formula below is an explanation of how is calculated the Limit (maximum REAL value) for a
given Precision (small REAL value).After this Limit, the Precision will be lost and the result of an
addition for both values is indicated by an error of the EF.
X = Int(Abs(Ln(P * 223) / Ln(2)))
L = 2X+2
Where P is the Precision and L is the Limit.

Representation in FBD
Representation:

33002519 09/2020 275


Saturation

Representation in LD
Representation:

Representation in IL
Representation:
LD Precision
SATURATION Value, Error, Limit

Representation in ST
Representation:
SATURATION (Precision, Value, Error, Limit);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Precision REAL Very small REAL value
Value REAL Large REAL value

The following table describes the output parameters:

Parameter Type Comment


Error BOOL Saturation limit status:
 0: Saturation limit not reached
(addition results correct)
 1: Saturation limit reached
(addition results wrong)
Limit REAL The Limit output provides the
calculated saturation limit for the
given Precision, which is also a
valuable information.

276 33002519 09/2020


Saturation

Example
Example representation:

The following table gives examples with output parameters that correspond to the addition of the
input parameters:

Input parameters Outputs parameters


Value Value (HEX) Precision Limit Limit (HEX) Error
(REAL) (REAL) (REAL)
32767.5 16#46FF_FF00 0.001 32768.0 16#46FF_FF01 0 (good result)
32768.0 16#4700_0000 0.001 32768.0 16#4700_0000 1 (wrong result)
32768.5 16#4700_0080 0.001 32768.0 16#4700_0080 1 (wrong result)

NOTE: The REAL value displayed in the animation table may differ from the encoded binary value
because of rounding.

33002519 09/2020 277


Saturation

278 33002519 09/2020


EcoStruxure™ Control Expert
SIGN:
33002519 09/2020

Chapter 83
SIGN: Sign evaluation

SIGN: Sign evaluation

Description

Function description
The function is used for the detection of negative signs.
With a value ≥ 0 at the input, the output becomes "0". With a value < 0 at the input, the output
becomes "1".
NOTE: Because of IEC 61131-3 conformity, this function also works with the UINT and UDINTdata
types. This is not significant since these functions always return a 0 result.
EN and ENO can be configured as additional parameters.

Formula
Block formula:
OUT = 1, if IN < 0
OUT = 0, if IN ≥ 0
NOTE: Because of the different processing of REAL and INT values, the following behavior results
for signed 0 (+/-0):
 -0.0 -> SIGN_REAL -> 1
 +0.0 -> SIGN_REAL -> 0
 -0 -> SIGN_INT/DINT -> 0
 +0 -> SIGN_INT/DINT -> 0

Representation in FBD
Representation:

33002519 09/2020 279


SIGN:

Representation in LD
Representation:

Representation in IL
Representation:
LD Value
SIGN
ST Negativ

Representation in ST
Representation:
Negativ := SIGN (Value) ;

Parameter description
Description of input parameters:

Parameter Data type Meaning


Value INT, DINT, REAL Signed input

Description of output parameters:

Parameter Data type Meaning


Negative BOOL Sign evaluation

Runtime error
The system bit %S18 is set to 1 and ENO to 0 if
 an input value of the data type UINT or UDINT is to set.

280 33002519 09/2020


EcoStruxure™ Control Expert
SIN
33002519 09/2020

Chapter 84
SIN: Sine

SIN: Sine

Description

Function description
The SIN function calculates the sine of an angle.
The function call can also be carried out by SIN_REAL.
The additional parameters EN and ENO can be configured.

Formula
The formula is as follows:
Sin_Value = Sin(Angle)

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 281


SIN

Representation in IL
Representation:
LD Angle
SIN_REAL
ST Sin_Value

Representation in ST
Representation:
Sin_Value:= SIN_REAL(Angle);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Angle REAL Angle expressed in radians.
-2 63 < Angle < +2 63

The following table describes the output parameters:

Parameter Type Comment


Sin_Value REAL Sine of Angle.
-1 ≤ Sin_Value ≤ 1

Runtime errors
When the absolute value of Angle is greater than 2 63, the system bit %S18 changes to 1 and the
system word %SW17 indicates the type of fault.

282 33002519 09/2020


EcoStruxure™ Control Expert
SUB
33002519 09/2020

Chapter 85
SUB: Subtraction

SUB: Subtraction

Description

Function description
The function subtracts the value at the Value2 input from the value at the Value1 input and
assigns the result to the output.
The data types of the input values and the output values must be identical.
For subtraction with values of the TIME data type, you can use the block SUB_TIME
(see page 285).
EN and ENO can be configured as additional parameters.

Formula
Difference = Value1 - Value2

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 283


SUB

Representation in IL
Representation:
LD Value1
SUB Value2
ST Difference

Representation in ST
Representation:
Difference := SUB (Value1, Value2) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


Value1 INT, DINT, UINT, Minuend
UDINT, REAL
Value2 INT, DINT, UINT, Subtrahend
UDINT, REAL

Description of the output parameter:

Parameter Data type Meaning


Difference INT, DINT, UINT, Difference
UDINT, REAL

Runtime error
The system bit %S18 is set to 1, if
 the value range at the output has been exceeded (all available data types)
or
 an unauthorized floating point number is set at an input parameter of data type REAL. In this
case, the status is also placed in %SW17.

284 33002519 09/2020


EcoStruxure™ Control Expert
SUB_TIME
33002519 09/2020

Chapter 86
SUB_TIME: Subtraction

SUB_TIME: Subtraction

Description

Function description
The function subtracts the value at the TimeValue2 input from the value at the TimeValue1 input
and assigns the result to the output.
The data types of the input values and the output be TIME.
EN and ENO can be configured as additional parameters.

Formula
Difference = TimeValue1 - TimeValue2

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 285


SUB_TIME

Representation in IL
Representation:
LD TimeValue1
SUB TimeValue2
ST Difference

Representation in ST
Representation:
Difference := SUB (TimeValue1, TimeValue2) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


TimeValue1 TIME Minuend
TimeValue2 TIME Subtrahend

Description of the output parameter:

Parameter Data type Meaning


Difference TIME Difference

Runtime error
The system bit %S18 is set to 1, if
 the value range at the output has been exceeded

286 33002519 09/2020


EcoStruxure™ Control Expert
SQRT_***
33002519 09/2020

Chapter 87
SQRT_*** : Square root

SQRT_*** : Square root

Description

Function description
The SQRT_*** function extracts the square root from a variable. This function can be called using
its generic name or one of the function names described below.
The additional parameters EN and ENO can be configured.

Available functions
The available functions are as follows:
 SQRT_INT,
 SQRT_DINT,
 SQRT_REAL.

Representation in FBD
Representation applied to an integer:

Representation in LD
Representation applied to an integer:

33002519 09/2020 287


SQRT_***

Representation in IL
Representation applied to an integer:
LD Value1
SQRT_REAL
ST Sqrt_Value1

Representation in ST
Representation applied to an integer:
Sqrt_Value1 := SQRT_REAL(Value1);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Value1 INT, DINT, REAL. Variable whose square root you want to extract.
0 ≤ Value1

The following table describes the output parameters:

Parameter Type Comment


Sqrt_Value1 INT, DINT, REAL. Sqrt_Value1 contains the square root of Value1.
Sqrt_Value1 is of the same type as Value1.
When the type is INT, Sqrt_Value1 is rounded down to
the lower value, for Value1 = 15, Sqrt_Value1 = 3.

Runtime errors
When Value1 is of REAL type and negative, the result of the function contains -1.#NAN and bit
%S18 = 1.
When Value1 is of INT or DINT type and negative, the result of the function contains the negative
value Value1 and bit %S18 = 1.
In case of %S18 = 1 the system word %SW17 indicates the type of fault.

288 33002519 09/2020


EcoStruxure™ Control Expert
TAN
33002519 09/2020

Chapter 88
TAN: Tangent

TAN: Tangent

Description

Function description
The TAN function calculates the tangent of an angle.
The function call can also be carried out by TAN_REAL.
The additional parameters EN and ENO can be configured.

Formula
The formula is as follows:

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 289


TAN

Representation in IL
Representation:
LD Angle
TAN_REAL
ST Tan_Value

Representation in ST
Representation:
Tan_Value:= TAN_REAL(Angle);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Angle REAL Angle expressed in radians.
-2 63 < Angle < +2 63

The following table describes the output parameters:

Parameter Type Comment


Tan_Value REAL Tangent of Angle
-1.#INF < Tan_Value < +1.#INF

Runtime errors
When the absolute value of Angle is greater than 2 63, the system bit %S18 changes to 1 and the
system word %SW17 indicates the type of fault.

290 33002519 09/2020


EcoStruxure™ Control Expert
REF
33002519 09/2020

Part IX
REF

REF

33002519 09/2020 291


REF

292 33002519 09/2020


EcoStruxure™ Control Expert
REF
33002519 09/2020

Chapter 89
REF: Reference a variable

REF: Reference a variable

Description

Function description
The EF, REF, gives a reference to (the address of) ANY variable.
NOTE: To have more information about the Reference use, refer to the chapter Reference Data
Type Declarations (see EcoStruxure™ Control Expert, Program Languages and Structure,
Reference Manual).

EN and ENO can be configured as additional parameters.

Representation in FBD
Representation:

Representation in LD
Representation:

Representation in IL
Representation:
LD Variable_1
REF
ST Ref_to_Variable_1

Representation in ST
Representation:
Ref_to_Variable_1 := REF (Variable_1) ;

33002519 09/2020 293


REF

Parameter description
Description of the input parameters:

Parameter Data type Meaning


Variable_1 ANY Variable to reference.

Description of the output parameter:

Parameter Data type Meaning


Ref_to_Variable_1 REF_ANY Reference variable to be linked to Variable_1.After the
execution of the function, Ref_to_Variable_1 make
reference to Variable_1.

294 33002519 09/2020


EcoStruxure™ Control Expert
Statistical
33002519 09/2020

Part X
Statistical

Statistical

Overview
This section describes the elementary functions and elementary function blocks of the
Statistical group.

What Is in This Part?


This part contains the following chapters:
Chapter Chapter Name Page
90 AVE: Averaging 297
91 LIMIT: Limit 301
92 LIMIT_IND: Limit with indicator 305
93 MAX: Maximum value function 309
94 MIN: Minimum value function 311
95 MUX: Multiplexer 313
96 SEL: Binary selection 317

33002519 09/2020 295


Statistical

296 33002519 09/2020


EcoStruxure™ Control Expert
AVE
33002519 09/2020

Chapter 90
AVE: Averaging

AVE: Averaging

Description

Function description
The procedure calculates the average of weighted input values and gives the result at the output.
Two successive inputs (K_Xn) represent one pair of values. The first K_Xn input corresponds to
K1, the next to X1, the one after that to K2, etc.
The number of K_Xn inputs can be increased to 32 by vertically modifying the size of the block
frame. This corresponds to a maximum of 16 value pairs.
The number of inputs must be even, otherwise AVE generates a system error and sets ENO to false.
The data types of all input and output values must be identical.
EN and ENO can be configured as additional parameters.

Formula
Block formula:

Representation in FBD
Representation:

33002519 09/2020 297


AVE

Representation in LD
Representation:

Representation in IL
Representation:
LD FactorFirstValue
AVE FirstValue, FactorSecondValue, SecondValue
ST Result

Representation in ST
Representation:
Result := AVE (FactorFirstValue, FirstValue,
FactorSecondValue, SecondValue) ;

298 33002519 09/2020


AVE

Parameter description
Description of input parameters:

Parameter Data type Meaning


FactorFirstValue INT, DINT, UINT, Factor (K1) for first value
UDINT, REAL
FirstValue INT, DINT, UINT, First value (X1)
UDINT, REAL
FactorSecondValue INT, DINT, UINT, Factor (K2) for second value
UDINT, REAL
FactorSecondValue INT, DINT, UINT, Second value (X2)
UDINT, REAL
:
FactorHalfnValue INT, DINT, UINT,
UDINT, REAL
Factor for value of (K_X(n-1))
HalfnValue INT, DINT, UINT,
UDINT, REAL
Value of (K_X(n)
n = max 32

Description of output parameters:

Parameter Data type Meaning


Result INT, DINT, UINT, Average value
UDINT, REAL

Runtime error
The system bit %S18 is set to 1, if
 the value range of the output is exceeded (all available data types)
or
 an invalid division by 0 is executed (all available data types)
or
 an unauthorized floating point number is set at an input parameter of data type REAL. In this
case, the status is also placed in %SW17.
Note: %SW17.1 (Denormalized operand / result is acceptable) flag is not managed by AVE
procedure.
NOTE: For a list of all block error codes and values, see Statistical, page 503.

33002519 09/2020 299


AVE

300 33002519 09/2020


EcoStruxure™ Control Expert
LIMIT
33002519 09/2020

Chapter 91
LIMIT: Limit

LIMIT: Limit

Description

Function description
This function transfers the unchanged input value (Input) to the output if the input value is not less
than the minimum value (LowerLimit) and does not exceed the maximum value (UpperLimit).
If the input value (Input) is less than the minimum value (LowerLimit), the minimum value will
be transferred to the output. If the input value (Input) exceeds the maximum value
(UpperLimit), the maximum value will be transferred to the output.
The data types of all input values and output values must be identical.
EN and ENO can be configured as additional parameters.

Formula
OUT = IN, if (IN ≥ MN) & (IN ≤ MX)
OUT = MN, if (IN < MN)
OUT = MX, if (IN > MX)

Representation in FBD
Representation:

33002519 09/2020 301


LIMIT

Representation in LD
Representation:

Representation in IL
Representation:
LD LowerLimit
LIMIT Input, UpperLimit
ST Output

Representation in ST
Representation:
Output := LIMIT (LowerLimit, Input, UpperLimit) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


MN BOOL, BYTE, WORD, DWORD, INT, DINT, UINT, Lower limit
UDINT, REAL, TIME
IN BOOL, BYTE, WORD, DWORD, INT, DINT, UINT, Input
UDINT, REAL, TIME
MX BOOL, BYTE, WORD, DWORD, INT, DINT, UINT, Upper limit
UDINT, REAL, TIME

Description of the output parameter:

Parameter Data type Meaning


OUT BOOL, BYTE, WORD, DWORD, INT, DINT, UINT, Output
UDINT, REAL, TIME

302 33002519 09/2020


LIMIT

Runtime error
If there is an unauthorized floating point number at the input, an error message is returned.
NOTE: When the input parameter of data type REAL is out of range (outside range -1,175494e-38
and +1,175494e-38), the system bit %S18 and %SW17 are not updated.

33002519 09/2020 303


LIMIT

304 33002519 09/2020


EcoStruxure™ Control Expert
LIMIT_IND
33002519 09/2020

Chapter 92
LIMIT_IND: Limit with indicator

LIMIT_IND: Limit with indicator

Description

Function description
This procedure transfers the unchanged input value (Input) to the (Output), if the input value is
not less than the minimum value (LimitMinimum) and does not exceed the maximum value
(LimitMaximum). If the input value (Input) is less than the minimum value (LimitMinimum),
the minimum value will be transferred to the output. If the input value (Input) exceeds the
maximum value (LimitMaximum), the maximum value will be transferred to the output.
Additionally, a indication is given if the minimum or maximum value is violated. If the value at the
(Input) input is less than the value at the (LimitMinimum) input, the (MinimumViolation)
output becomes "1". If the value at the (Input) input is more than the value at the
(LimitMaximum) input, the (MaximumViolation) output becomes "1".
The data types of the (LimitMinimum, Input, LimitMaximum) input values and the (Output)
output value must be identical.
EN and ENO can be configured as additional parameters.

Formula
Block formula:
OUT = IN, if (IN ≤ MX) & IN ≥ MN
OUT = MN, if (IN < MN)
OUT = MX, if (IN > MX)
MN_IND = 0, if IN ≥ MN
MN_IND = 1, if IN < MN
MX_IND = 0, if IN ≤ MX
MX_IND = 1, if IN > MX

33002519 09/2020 305


LIMIT_IND

Representation in FBD
Representation:

Representation in LD
Representation:

Representation in IL
Representation:
LD LimitMinimum
LIMIT_IND Input, LimitMaximum, MinimumViolation,
Output, MaximumViolation

Representation in ST
Representation:
LIMIT_IND (LimitMinimum, Input, LimitMaximum,
MinimumViolation, Output, MaximumViolation);

306 33002519 09/2020


LIMIT_IND

Parameter description
Description of the input parameters:

Parameter Data type Meaning


LimitMinimum BOOL, BYTE, WORD, DWORD, INT, Limit of minimum value
DINT, UINT, UDINT, REAL, TIME
Input BOOL, BYTE, WORD, DWORD, INT, Input
DINT, UINT, UDINT, REAL, TIME
LimitMaximum BOOL, BYTE, WORD, DWORD, INT, Limit of maximum value
DINT, UINT, UDINT, REAL, TIME

Description of the output parameter:

Parameter Data type Meaning


MinimumViolation BOOL Display of minimum value violation
Output BOOL, BYTE, WORD, DWORD, Output
INT, DINT, UINT, UDINT,
REAL, TIME
MaximumViolation BOOL Display of maximum value violation

33002519 09/2020 307


LIMIT_IND

308 33002519 09/2020


EcoStruxure™ Control Expert
MAX
33002519 09/2020

Chapter 93
MAX: Maximum value function

MAX: Maximum value function

Description

Function description
The function assigns the largest input value to the output.
The data types of all input values and output values must be identical.
The number of inputs can be increased.
EN and ENO can be configured as additional parameters.

Formula
OUT = MAX {IN1, IN2, ..., INn}

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 309


MAX

Representation in IL
Representation:
LD Value1
MAX Value2
ST Maximum

Representation in ST
Representation:
Maximum := MAX (Value1, Value2) ;

Parameter description
Description of input parameters:

Parameter Data type Meaning


Value1 BOOL, BYTE, WORD, 1. Input value
DWORD, INT, DINT,
UINT, UDINT, REAL,
TIME
Value2 BOOL, BYTE, WORD, 2. Input value
DWORD, INT, DINT,
UINT, UDINT, REAL,
TIME
Valuen BOOL, BYTE, WORD, n. Input value
DWORD, INT, DINT, n = max 32
UINT, UDINT, REAL,
TIME

Description of output parameters:

Parameter Data type Meaning


Maximum BOOL, BYTE, WORD, Maximum value
DWORD, INT, DINT,
UINT, UDINT, REAL,
TIME

Runtime error
When the input parameter of data type REAL is out of range (outside range -1,175494e-38 and
+1,175494e-38), the system bit %S18 and %SW17 are not updated.
NOTE: For a list of all the block error messages and values, see Common Floating Point Errors,
page 504.

310 33002519 09/2020


EcoStruxure™ Control Expert
MIN
33002519 09/2020

Chapter 94
MIN: Minimum value function

MIN: Minimum value function

Description

Function description
The function assigns the smallest input value to the output.
The data types of all input values and output values must be identical.
The number of inputs can be increased.
EN and ENO can be configured as additional parameters.

Formula
OUT = MIN {IN1, IN2, ..., INn}

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 311


MIN

Representation in IL
Representation:
LD Value1
MIN Value2
ST Minimum

Representation in ST
Representation:
Minimum := MIN (Value1, Value2) ;

Parameter description
Description of input parameters:

Parameter Data type Meaning


Value1 BOOL, BYTE, WORD, 1. Input value
DWORD, INT, DINT,
UINT, UDINT, REAL,
TIME
Value2 BOOL, BYTE, WORD, 2. Input value
DWORD, INT, DINT,
UINT, UDINT, REAL,
TIME
Valuen BOOL, BYTE, WORD, n. Input value
DWORD, INT, DINT, n = max 32
UINT, UDINT, REAL,
TIME

Description of output parameters:

Parameter Data type Meaning


Minimum BOOL, BYTE, WORD, Minimum value
DWORD, INT, DINT,
UINT, UDINT, REAL,
TIME

Runtime error
If an unauthorized floating point number is created for an input parameter of data type REAL, the
system bit %S18 is set to 1 and the status is placed in %SW17.
NOTE: For a list of all the block error messages and values, see Common Floating Point Errors,
page 504.

312 33002519 09/2020


EcoStruxure™ Control Expert
MUX
33002519 09/2020

Chapter 95
MUX: Multiplexer

MUX: Multiplexer

Description

Function description
This function transfers the respective input to the output depending on the value at the K input.
The number of inputs can be increased.
EN and ENO can be configured as additional parameters.

Example
K = 0: Input IN0 is transferred to the output
K = 1: Input IN1 is transferred to the output
K = 5: Input IN5 is transferred to the output
K= n: Input INn is transferred to the output

Data types
The data types at the inputs Input0 to Inputn and at the output must be identical.

Representation in FBD
Representation:

33002519 09/2020 313


MUX

Representation in LD
Representation:

Representation in IL
Representation:
LD Selection
MUX Input0, Input1
ST Output

Representation in ST
Representation:
Output := MUX (Selection, Input0, Input1) ;

Parameter description
Description of input parameters:

Parameter Data type Meaning


K INT, DINT, UINT, Selection input
UDINT K = 0...30
IN0 ANY 1. Input
IN1 ANY 2. Input
IN2 ANY 3. Input
INn ANY n+1. input, n = max. 30

Description of output parameters:

Parameter Data type Meaning


OUT ANY Output

314 33002519 09/2020


MUX

Runtime error
If the value range of the Kinput (selector) is exceeded, an error message is displayed in the
Diagnostic Viewer (see EcoStruxure™ Control Expert, Diagnostics, Block Library) and %SW125
(see EcoStruxure™ Control Expert, System Bits and Words, Reference Manual) contains the error
code value.
NOTE: For a list of all block error codes and values, see Statistical, page 503.

33002519 09/2020 315


MUX

316 33002519 09/2020


EcoStruxure™ Control Expert
SEL
33002519 09/2020

Chapter 96
SEL: Binary selection

SEL: Binary selection

Description

Function description
The function is used for binary selection between two input values.
Depending on the state of the Selection input, either the Input0 input or Input1 input is
transferred to the Output output.
Selection = 0 -> Output = Input0
Selection = 1 -> Output = Input1
The data types of the Input0 and Input1 input values and the Output output values must be
identical.
EN and ENO can be configured as additional parameters.

Representation in FBD
Representation:

33002519 09/2020 317


SEL

Representation in LD
Representation:

Representation in IL
Representation:
LD Selection
SEL Input0, Input1
ST Output

Representation in ST
Representation:
Output := SEL (Selection, Input0, Input1) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


Selection BOOL Selection input
Input0 ANY Input 0
Input1 ANY Input 1

Description of the output parameter:

Parameter Data type Meaning


Output ANY Output

318 33002519 09/2020


EcoStruxure™ Control Expert
Strings
33002519 09/2020

Part XI
Strings

Strings

Overview
This section describes the elementary functions and elementary function blocks of the Strings
family.

What Is in This Part?


This part contains the following chapters:
Chapter Chapter Name Page
97 CONCAT_STR: Concatenation of two character strings 321
98 DELETE_INT: Deletion of a sub-string of characters 323
99 EQUAL_STR: Comparison of two character strings 325
100 FIND_INT: Finding a sub-string of characters 327
101 INSERT_INT: Insertion of a sub-string of characters 329
102 LEFT_INT: Extraction of characters to the left 333
103 LEN_INT: Length of character string 335
104 MID_INT: Extraction of a sub-string of characters 337
105 REPLACE_INT: Replacement of a sub-string of characters 339
106 RIGHT_INT: Extraction of a character string to the right 343

33002519 09/2020 319


Strings

320 33002519 09/2020


EcoStruxure™ Control Expert
CONCAT_STR
33002519 09/2020

Chapter 97
CONCAT_STR: Concatenation of two character strings

CONCAT_STR: Concatenation of two character strings

Description

Function description
The CONCAT_STR function concatenates two character strings.
The additional parameters EN and ENO can be configured.

Representation in FBD
Representation:

Representation in LD
Representation:

Representation in IL
Representation:
LD String1
CONCAT_STR String2
ST Result_String

33002519 09/2020 321


CONCAT_STR

Representation in ST
Representation:
Result_String:= CONCAT_STR(String1, String2);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


String1 STRING First character string to concatenate.
Example: String1 contains "SWITCH TO "
String2 STRING Second character string to concatenate.
Example: String2 contains "RUN"

NOTE: CONCAT_STR does not insert a blank space between the input strings. To make
Result_String easier to read, It may be necessary to add a blank space at the end of String1
or at the beginning of String2.
The following table describes the output parameters:

Parameter Type Comment


Result_String STRING Resulting string is equal to the content of the two strings
String1 and String2.
Example: for the values in the example provided in the
previous table, Result_String contains ‘SWITCH
TO RUN’

Runtime errors
The system bit %S15 is set to 1 in the following cases:
 If the Result_String is too short to contain the result, the result is truncated. Otherwise, the
string Result_String is completed by the characters NUL (16#00).
 If the Result_String is used as an input on IN2.

322 33002519 09/2020


EcoStruxure™ Control Expert
DELETE_INT
33002519 09/2020

Chapter 98
DELETE_INT: Deletion of a sub-string of characters

DELETE_INT: Deletion of a sub-string of characters

Description

Function description
The DELETE_INT function removes a certain number of characters starting from a certain rank.
The result is a character string.
The additional parameters EN and ENO can be configured.
NOTE: If the Result_String of this function is located on %MW, then the Result_String is
not completed with NUL (16#00) characters. It is recommended to erase the content of the
Result_String before using this function.

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 323


DELETE_INT

Representation in IL
Representation:
LD String1
DELETE_INT Length_Str, Position
ST Result_String

Representation in ST
Representation:
Result_String:= DELETE_INT(String1, Length_Str, Position);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


String1 STRING Original character string from which we wish to delete
certain elements.

Example: String1 contains "SWITCH TO STOP"


Length_Str INT Length of string to be deleted.

Example: Length_Str =10


Position INT Rank of first character of the string to be deleted.

Example: Position =1

The following table describes the output parameters:

Parameter Type Comment


Result_String STRING Resulting string equal to content of String1 from
which have been removed Length_Str characters
starting from the rank Position.

Example: for the values in the example provided in the


previous table, Result_String contains ‘STOP’
(10 characters are deleted starting from position 1).

324 33002519 09/2020


EcoStruxure™ Control Expert
EQUAL_STR
33002519 09/2020

Chapter 99
EQUAL_STR: Comparison of two character strings

EQUAL_STR: Comparison of two character strings

Description

Function description
The EQUAL_STR function compares two character strings.
The additional parameters EN and ENO can be configured.

Representation in FBD
Representation:

Representation in LD
Representation:

Representation in IL
Representation:
LD String1
EQUAL_STR String2
ST Position

33002519 09/2020 325


EQUAL_STR

Representation in ST
Representation:
Position:= EQUAL_STR(String1, String2);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


String1 STRING First character string to compare.

Example: String1 contains "SWITCH TO STOP"


String2 STRING Second character string to compare.

Example: String2 contains "SWITCH TO RUN"

The following table describes the output parameters:

Parameter Type Comment


Position INT Position of first character that differs between the two
strings String1 and String2.
When the two strings are identical,
Position = -1.

Example: with the values indicated in the example in the


previous table, Position = 11

Note: upper case characters are treated as different to


lower case characters.

326 33002519 09/2020


EcoStruxure™ Control Expert
FIND_INT
33002519 09/2020

Chapter 100
FIND_INT: Finding a sub-string of characters

FIND_INT: Finding a sub-string of characters

Description

Function description
The FIND_INT function searches for the occurrence of a character string in another string.
The additional parameters EN and ENO can be configured.

Representation in FBD
Representation:

Representation in LD
Representation:

Representation in IL
Representation:
LD String1
FIND_INT String2
ST Position

33002519 09/2020 327


FIND_INT

Representation in ST
Representation:
Position:= FIND_INT(String1, String2);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


String1 STRING Character string in which the search is carried out.

Example: String1 contains "SWITCH TO STOP"


String2 STRING Character string containing the text to find

Example: String2 contains ‘STOP’

The following table describes the output parameters:

Parameter Type Comment


Position INT If String2 is contained in String1, Position
contains the rank of the first character of String2
found in String1.
When String2 is not contained in String1,
Position = -1.

Example: with the values indicated in the example in the


previous table, Position = 11

328 33002519 09/2020


EcoStruxure™ Control Expert
INSERT_INT
33002519 09/2020

Chapter 101
INSERT_INT: Insertion of a sub-string of characters

INSERT_INT: Insertion of a sub-string of characters

Description

Function description
The INSERT_INT function inserts a character string into another character string starting from a
given rank. The result is a character string.
The additional parameters EN and ENO can be configured.

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 329


INSERT_INT

Representation in IL
Representation:
LD String1
INSERT_INT String2, Position
ST Result_String

Representation in ST
Representation:
Result_String:= INSERT_INT(String1, String2, Position);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


String1 STRING Original character string to which another character
string is added starting from a certain position.

Example: String1 contains ‘START CYCLE’


String2 STRING Character string to be inserted in String1.

Example: String2 contains ‘ AUTO’


Position INT Rank of character after which String2 is inserted.

Example: Position =5

The following table describes the output parameters:

Parameter Type Comment


Result_String STRING The string String2 has been inserted in the string
String1 after the position Position to form
Result_String.

Example: for the values in the example provided in the


previous table, Result_String contains ‘START
AUTO CYCLE’.

Note: it is impossible to make an insertion at the start of


a string with this function (use the CONCAT_STR
(see page 321) function).

330 33002519 09/2020


INSERT_INT

Runtime errors
The bit %S15 is set to 1 in the following cases:
 Position ≤ 0, Result_String then contains the end of string characters (16#00).
 The maximum size of the string Result_String is too small to insert String2.
Result_String is truncated.
 If the Result_String is used as an input on IN1 or IN2.

33002519 09/2020 331


INSERT_INT

332 33002519 09/2020


EcoStruxure™ Control Expert
LEFT_INT
33002519 09/2020

Chapter 102
LEFT_INT: Extraction of characters to the left

LEFT_INT: Extraction of characters to the left

Description

Function description
The LEFT_INT function extracts a certain number of characters situated to the leftmost of a string.
The result is a character string.
The additional parameters EN and ENO can be configured.
NOTE: If the Result_String of this function is located on %MW, then the Result_String is not
completed with NUL (16#00) characters. It is recommended to erase the content of the
Result_String before using this function.

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 333


LEFT_INT

Representation in IL
Representation:
LD String1
LEFT_INT Length_Str
ST Result_String

Representation in ST
Representation:
Result_String:= LEFT_INT(String1, Length_Str);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


String1 STRING String of characters from which we wish to extract the
Length_Str leftmost characters.
Example: String1 contains "SWITCH TO STOP"
Length_Str INT Number of characters to be extracted.
Example: Length_Str =9.

The following table describes the output parameters:

Parameter Type Comment


Result_String STRING String containing the Length_Str leftmost characters
of String1.
Example: for the values in the example provided in the
previous table, Result_String contains ‘SWITCH
TO’ (9 leftmost characters of String1).

Runtime errors
The bit %S15 is set to 1 in the following cases:
 String1 is empty or Length_Str < 0.
 The maximum size of the string Result_String is less than Length_Str
 The size of the string String1 is less than Length_Str.
 If the String1 is not valued and the Length is 0, %S15 is set to 1
NOTE: In all these cases, the content of Result_String is undefined and should be treated as
such by further processing.

334 33002519 09/2020


EcoStruxure™ Control Expert
LEN_INT
33002519 09/2020

Chapter 103
LEN_INT: Length of character string

LEN_INT: Length of character string

Description

Function description
The LEN_INT function calculates the number of characters of a character string.
The additional parameters EN and ENO can be configured.

Representation in FBD
Representation:

Representation in LD
Representation:

Representation in IL
Representation:
LD String1
LEN_INT
ST Length_Str

33002519 09/2020 335


LEN_INT

Representation in ST
Representation:
Length_Str:= LEN_INT(String1);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


String1 STRING String of characters for which the length is to be
determined.

Example: String1 contains "SWITCH TO STOP"

The following table describes the output parameters:

Parameter Type Comment


Length_Str INT Length_Str contains the length of the character string
String1.

Example: with the values indicated in the example in the


previous table, Length_Str = 14

336 33002519 09/2020


EcoStruxure™ Control Expert
MID_INT
33002519 09/2020

Chapter 104
MID_INT: Extraction of a sub-string of characters

MID_INT: Extraction of a sub-string of characters

Description

Function description
The MID_INT function extracts a sub-string of characters starting from a certain rank. The result
is a character string.
The additional parameters EN and ENO can be configured.

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 337


MID_INT

Representation in IL
Representation:
LD String1
MID_INT Length_Str, Position
ST Result_String

Representation in ST
Representation:
Result_String:= MID_INT(String1, Length_Str, Position);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


String1 STRING Original string containing the sub-string to be extracted.

Example: String1 contains "SWITCH TO STOP"


Length_Str INT Length of the sub-string to be extracted.

Example: Length_Str =4
Position INT Rank of first character of the sub-string to be extracted.

Example: Position =11

The following table describes the output parameters:

Parameter Type Comment


Result_String STRING Sub-string of String1 starting from rank Position
over a length of Length_Str.

Example: for the values in the example provided in the


previous table, Result_String contains ‘STOP’.

338 33002519 09/2020


EcoStruxure™ Control Expert
REPLACE_INT
33002519 09/2020

Chapter 105
REPLACE_INT: Replacement of a sub-string of characters

REPLACE_INT: Replacement of a sub-string of characters

Description

Function description
The REPLACE_INT function replaces a character string in another character string starting from a
certain rank and for a certain length. The result is a character string.
The additional parameters EN and ENO can be configured.
NOTE: If the Result_String of this function is located on %MW, then the Result_String is
not completed with NUL (16#00) characters. It is recommended to erase the content of the
Result_String before using this function.

Representation in FBD
Representation:

33002519 09/2020 339


REPLACE_INT

Representation in LD
Representation:

Representation in IL
Representation:
LD String1
REPLACE_INT String2, Length_Str, Position
ST Result_String

Representation in ST
Representation:
Result_String:= REPLACE_INT(String1, String2, Length_Str, Position);

340 33002519 09/2020


REPLACE_INT

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


String1 STRING Original string of characters into which is inserted a sub-
string of characters starting from Position over a
length of Length_Str.

Example: String1 contains "SWITCH TO RUN"

Note: the length Length_Str is the length of the text to


be replaced and not the length of the string String2.
As it happens, the replacement string can be of a
different length to the string that is replaced.
String2 STRING Character string to be inserted in String1 to replace
the existing characters.

Example: String2 contains ‘STOP’


Length_Str INT Number of characters to be replaced in String1 by
String2

Example: Length_Str =3
Position INT Rank of first character of the sub-string to be replaced

Example: Position =11

The following table describes the output parameters:

Parameter Type Comment


Result_String STRING The string string2 has replaced the Length_Str
characters starting from the rank Position in the
string String1 to form Result_String.

Example: for the values in the example provided in the


previous table, Result_String contains ‘SWITCH
TO STOP’.

33002519 09/2020 341


REPLACE_INT

Runtime errors
The bit %S15 is set to 1 in the following cases:
 Position ≤ 0, Result_String then contains the end of string characters (16#00).
 The maximum size of the string Result_String is too small to insert String2.
Result_String is truncated.
 Position is greater than the length of String1. Result_String is equal to String1 in this
case.
 If Result_String is used as an input on IN2.

342 33002519 09/2020


EcoStruxure™ Control Expert
RIGHT_INT
33002519 09/2020

Chapter 106
RIGHT_INT: Extraction of a character string to the right

RIGHT_INT: Extraction of a character string to the right

Description

Function description
The RIGHT_INT function extracts a certain number of characters situated to the rightmost of a
string. The result is a character string.
The additional parameters EN and ENO can be configured.

Representation in FBD
Representation:

Representation in LD
Representation:

Representation in IL
Representation:
LD String1
RIGHT_INT Length_Str
ST Result_String

33002519 09/2020 343


RIGHT_INT

Representation in ST
Representation:
Result_String:= RIGHT_INT(String1, Length_Str);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


String1 STRING String of characters from which we wish to extract the
Length_Str rightmost characters.
Example: String1 contains "SWITCH TO STOP"
Length_Str INT Number of characters to be extracted.
Example: Length_Str =4

The following table describes the output parameters:

Parameter Type Comment


Result_String STRING String containing the Length_Str rightmost
characters of String1.
Example: for the values in the example provided in the
previous table, Result_String contains ‘STOP’ (4
rightmost characters of String1).

Runtime errors
The bit %S15 is set to 1 in the following cases:
 String1 is empty or Length_Str < 0.
 The maximum size of the string Result_String is less than Length_Str
 The size of the string String1 is less than Length_Str.
 If the String1 is not valued and the Length is 0, %S15 is set to 1
NOTE: In all these cases, the content of Result_String is undefined and should be treated as such
by further processing.

344 33002519 09/2020


EcoStruxure™ Control Expert
Timer & Counter
33002519 09/2020

Part XII
Timer & Counter

Timer & Counter

Overview
This section describes the elementary functions and elementary function blocks of the Timer &
Counter family.

What Is in This Part?


This part contains the following chapters:
Chapter Chapter Name Page
107 CTD, CTD_***: Down counter 347
108 CTU, CTU_***: Up counter 349
109 CTUD, CTUD_***: Up/Down counter 351
110 TOF: Off delay 355
111 TON: On delay 357
112 TP: Pulse 359

33002519 09/2020 345


Timer & Counter

346 33002519 09/2020


EcoStruxure™ Control Expert
CTD, CTD_***
33002519 09/2020

Chapter 107
CTD, CTD_***: Down counter

CTD, CTD_***: Down counter

Description

Function description
The function blocks are used for downwards counting.
A "1" signal at the LD input causes the value of the PV input to be allocated to the CV output. With
each transition from "0" to "1" at the CD input, the value of CV is reduced by 1.
When CV ≤ 0, the Q output becomes "1".
NOTE: The counter only works to the minimum values of the data type being used. No overflow
occurs.
EN and ENO can be configured as additional parameters.

Available functions
There are two different specifications of the function block:
 CTD
This function block specification is defined in IEC 61131-3 and only works with the INT data
type.
 CTD_***
This function block specification is an expansion that conforms to IEC 61131-3 to cover other
data types. The following blocks are available:
 CTD_INT
 CTD_DINT
 CTD_UINT
 CTD_UDINT

Representation in FBD
Representation:

33002519 09/2020 347


CTD, CTD_***

Representation in LD
Representation:

Representation in IL
Representation:
CAL CTD_Instance (CD:=Trigger, LD:=Load,
PV:=PresetValue, Q=>Output, CV=>CountValue)

Representation in ST
Representation:
CTD_Instance (CD:=Trigger, LD:=Load, PV:=PresetValue,
Q=>Output, CV=>CountValue) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


CD BOOL Trigger input
LD BOOL Load data
PV When CTD: INT Preset value
When CTD_***: INT, DINT, UINT, UDINT

Description of the output parameter:

Parameter Data type Meaning


Q BOOL Output
CV When CTD: INT Count value (actual value)
When CTD_***: INT, DINT, UINT, UDINT

348 33002519 09/2020


EcoStruxure™ Control Expert
CTU, CTU_***
33002519 09/2020

Chapter 108
CTU, CTU_***: Up counter

CTU, CTU_***: Up counter

Description

Function description
The function blocks are used for upwards counting.
A "1" signal at the R input causes the value "0" to be assigned to the CV output. With each transition
from "0" to "1" at the CU input, the value of CV is incremented by 1. When CV ≥ PV, the Q output is
set to "1".
NOTE: The counter only works to the maximum values of the data type being used. No overflow
occurs.
EN and ENO can be configured as additional parameters.

Available functions
There are two different specifications of the function block:
 CTU
This function block specification is defined in IEC 61131-3 and only works with the INT data
type.
 CTU_***
This function block specification is an expansion that conforms to IEC 61131-3 to cover other
data types. The following blocks are available
 CTU_INT
 CTU_DINT
 CTU_UINT
 CTU_UDINT

Representation in FBD
Representation:

33002519 09/2020 349


CTU, CTU_***

Representation in LD
Representation:

Representation in IL
Representation:
CAL CTU_Instance (CU:=Trigger, R:=Reset,
PV:=PresetValue, Q=>Output, CV=>CountValue)

Representation in ST
Representation:
CTU_Instance (CU:=Trigger, R:=Reset, PV:=PresetValue,
Q=>Output, CV=>CountValue) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


CU BOOL Trigger input
R BOOL Reset
PV When CTU: INT Preset value
When CTU_***: INT, DINT, UINT, UDINT

Description of the output parameter:

Parameter Data type Meaning


Q BOOL Output
CV When CTU: INT Count value (actual value)
When CTU_***: INT, DINT, UINT, UDINT

350 33002519 09/2020


EcoStruxure™ Control Expert
CTUD, CTUD_***
33002519 09/2020

Chapter 109
CTUD, CTUD_***: Up/Down counter

CTUD, CTUD_***: Up/Down counter

Description

Function description
The function blocks are used for upwards and downwards counting.
A "1" signal at the R input causes the value "0" to be assigned to the CV output. A "1" signal at the
LD input causes the value of the PV input to be allocated to the CV output. With each transition from
"0" to "1" at the CU input, the value of CV is incremented by 1. With each transition from "0" to "1"
at the CD input, the value of CV is reduced by 1.
If there is a simultaneous "1" signal at inputs R and LD, input R has precedence.
When CV ≥ PV, output QU is "1".
When CV ≤ 0, the QD output becomes "1".
NOTE: The down counter only works to the minimum values of the data type being used, and the
up counter only to the maximum values of the data type being used. No overflow occurs.
EN and ENO can be configured as additional parameters.

Available functions
There are two different specifications of the function block:
 CTUD
This function block specification is defined in IEC 61131-3 and only works with the INT data
type.
 CTUD_***
This function block specification is an expansion that conforms to IEC 61131-3 to cover other
data types. The following blocks are available
 CTUD_INT
 CTUD_DINT
 CTUD_UINT
 CTUD_UDINT

33002519 09/2020 351


CTUD, CTUD_***

Representation in FBD
Representation:

Representation in LD
Representation:

Representation in IL
Representation:
CAL CTUD_Instance (CU:=UpTrigger, CD:=DownTrigger,
R:=Reset, LD:=Load, PV:=PresetValue, QU=>UpDisplay,
QD=>DownDisplay, CV=>CountValue)

Representation in ST
Representation:
CTUD_Instance (CU:=UpTrigger, CD:=DownTrigger,
R:=Reset, LD:=Load, PV:=PresetValue, QU=>UpDisplay,
QD=>DownDisplay, CV=>CountValue) ;

352 33002519 09/2020


CTUD, CTUD_***

Parameter description
Description of the input parameters:

Parameter Data type Meaning


CU BOOL Up counter trigger input
CD BOOL Down counter trigger input
R BOOL Reset
LD BOOL Load data
PV When CTUD: INT, Preset value
When CTUD_***: INT,
DINT, UINT, UDINT

Description of the output parameter:

Parameter Data type Meaning


QU BOOL Up display
QD BOOL Down display
CV When CTUD: INT Count value (actual value)
When CTUD_***: INT,
DINT, UINT, UDINT

33002519 09/2020 353


CTUD, CTUD_***

354 33002519 09/2020


EcoStruxure™ Control Expert
TOF
33002519 09/2020

Chapter 110
TOF: Off delay

TOF: Off delay

Description

Function description
The function block is used as the Off delay.
When the function block is called for the first time, the initial state of ET is "0".
EN and ENO can be configured as additional parameters.

Representation in FBD
Representation:

Representation in LD
Representation:

Representation in IL
Representation:
CAL TOF_Instance (IN:=StartDelay, PT:=PresetDelayTime,
Q=>Output, ET=>InternalTime)

33002519 09/2020 355


TOF

Representation in ST
Representation:
TOF_Instance (IN:=StartDelay, PT:=PresetDelayTime,
Q=>Output, ET=>InternalTime) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


IN BOOL Start delay
PT TIME Preset delay time

Description of the output parameter:

Parameter Data type Meaning


Q BOOL Output
ET TIME Internal time

Timing diagram
Representation of the OFF delay TOF:

(1) If IN becomes "1", Q becomes "1".


(2) If IN becomes "0", the internal time (ET) is started.
(3) If the internal time reaches the value of PT, Q becomes "0".
(4) If IN becomes "1", Q becomes "1", and the internal time is stopped/reset.
(5) If IN becomes "1" before the internal time has reached the value of PT, the internal time is stopped/reset
without Q being set back to "0".

356 33002519 09/2020


EcoStruxure™ Control Expert
TON
33002519 09/2020

Chapter 111
TON: On delay

TON: On delay

Description

Function description
The function block is used as the On delay.
When the function block is called for the first time, the initial state of ET is "0".
EN and ENO can be configured as additional parameters.

Representation in FBD
Representation:

Representation in LD
Representation:

Representation in IL
Representation:
CAL TON_Instance (IN:=StartDelay, PT:=PresetDelayTime,
Q=>Output, ET=>InternalTime)

33002519 09/2020 357


TON

Representation in ST
Representation:
TON_Instance (IN:=StartDelay, PT:=PresetDelayTime,
Q=>Output, ET=>InternalTime) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


IN BOOL Start delay
PT TIME Preset delay time

Description of the output parameter:

Parameter Data type Meaning


Q BOOL Output
ET TIME Internal time

Timing diagram
Representation of the ON delay TON:

(1) If IN becomes "1", the internal time (ET) starts.


(2) If the internal time reaches the value of PT, Q becomes "1".
(3) If IN becomes "0", Q becomes "0" and the internal time is stopped/reset.
(4) If IN becomes "0" before the internal time has reached the value of PT, the internal time stops/resets
without Q going to "1".

358 33002519 09/2020


EcoStruxure™ Control Expert
TP
33002519 09/2020

Chapter 112
TP: Pulse

TP: Pulse

Description

Function description
The function block is used for the generation of a pulse with defined duration.
When the function block is called for the first time, the initial state of ET is "0".
EN and ENO can be configured as additional parameters.

Representation in FBD
Representation:

Representation in LD
Representation:

Representation in IL
Representation:
CAL TP_Instance (IN:=TriggerPulse, PT:=PulseDuration,
Q=>Output, ET=>InternalTime)

33002519 09/2020 359


TP

Representation in ST
Representation:
TP_Instance (IN:=TriggerPulse, PT:=PulseDuration,
Q=>Output, ET=>InternalTime) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


IN BOOL Trigger pulse
PT TIME Preset pulse duration

Description of the output parameter:

Parameter Data type Meaning


Q BOOL Output
ET TIME Internal time

Timing diagram
Representation of the TP pulse:

(1) If IN becomes "1", Q becomes "1" and the internal time (ET) starts.
(2) If the internal time reaches the value of PT, Q becomes "0" (independent of IN).
(3) The internal time stops/is reset if IN becomes "0".
(4) If the internal time has not reached the value of PT yet, the internal time is not affected by a clock at IN.
(5) If the internal time has reached the value of PT and IN is "0", the internal time stops/is reset and Q becomes
"0".

360 33002519 09/2020


EcoStruxure™ Control Expert
Type to type
33002519 09/2020

Part XIII
Type to type

Type to type

Overview
This section describes the elementary functions and elementary function blocks of the Type to
type family.

What Is in This Part?


This part contains the following chapters:
Chapter Chapter Name Page
113 ARINT_TO_DATE: Convert Integer Array with Date to a DATE Variable 363
114 ARINT_TO_DT: Convert Integer Array with Date and Time to a DT Variable 365
115 ARINT_TO_TOD: Convert Integer Array with Time Of Day to a TOD Variable 367
116 ASCII_TO_STRING: Type conversion 369
117 ASCII_TO_STRING_INV: Type conversion 373
118 BCD_TO_INT: Conversion of a BCD integer into pure binary 379
119 BIT_TO_BYTE: Type conversion 381
120 BIT_TO_WORD: Type conversion 385
121 BOOL_TO_***: Type conversion 389
122 BYTE_AS_WORD: Type conversion 391
123 BYTE_TO_BIT: Type conversion 393
124 BYTE_TO_***: Type conversion 397
125 DATE_TO_ARINT: Convert DATE Variable to Integer Array 401
126 DATE_TO_STRING: Conversion of a variable in DATE format into a character 403
string
127 DBCD_TO_***: Conversion of a double BCD integer into binary 405
128 DEG_TO_RAD : Conversion of degrees to radians 407
129 DINT_AS_WORD: Type conversion 409
130 DINT_TO_***: Type conversion 411
131 DINT_TO_DBCD: Conversion of a double binary coded integer into a double 415
Binary Coded Decimal integer
132 DT_TO_ARINT: Convert DT Variable to Integer Array 417
133 DT_TO_STRING: Conversion of a variable in DT format into a character string 419
134 DWORD_TO_***: Type conversion 421

33002519 09/2020 361


Type to type

Chapter Chapter Name Page


135 GRAY_TO_INT: Conversion of an integer in Gray code into a binary coded 423
integer
136 INT_AS_DINT: Concatenation of two integers to form a double integer 425
137 INT_TO_***: Type conversion 427
138 INT_TO_BCD: Conversion of a binary coded integer into a Binary Coded 431
Decimal integer
139 INT_TO_DBCD: Conversion of a binary coded integer into a double Binary 433
Coded Decimal integer
140 RAD_TO_DEG: Conversion of radians to degrees 435
141 REAL_AS_WORD: Type conversion 437
142 REAL_TO_***: Type conversion 439
143 REAL_TRUNC_***: Type conversion 443
144 STRING_TO_ASCII: Type conversion 445
145 STRING_TO_ASCII_INV: Type conversion 451
146 STRING_TO_*** : Conversion of a character string to a number of the INT, 457
DINT or REAL type
147 TIME_AS_WORD: Type conversion 461
148 TIME_TO_***: Type conversion 463
149 TIME_TO_STRING: Conversion of a variable in TIME format into a character 465
string
150 TOD_TO_ARINT: Convert TOD Variable to Integer Array 467
151 TOD_TO_STRING: Conversion of a variable in TOD format into a character 469
string
152 UDINT_AS_WORD: Type conversion 471
153 UDINT_TO_***: Type conversion 473
154 UINT_TO_***: Type conversion 477
155 WORD_AS_BYTE: Type conversion 481
156 WORD_AS_DINT: Type conversion 483
157 WORD_AS_REAL: Type conversion 485
158 WORD_AS_TIME: Type conversion 487
159 WORD_AS_UDINT: Type conversion 489
160 WORD_TO_BIT: Type conversion 491
161 WORD_TO_***: Type conversion 495
162 ***_TO_STRING: Conversion of a variable into a character string 497

362 33002519 09/2020


EcoStruxure™ Control Expert
ARINT_TO_DATE
33002519 09/2020

Chapter 113
ARINT_TO_DATE: Convert Integer Array with Date to a DATE Variable

ARINT_TO_DATE: Convert Integer Array with Date to a DATE


Variable

Description

Function description
The function converts an Integer Array with the date in BCD format to a DATE (d#) variable.
For the input you have 2 options:
 If you want to assign the system date, assign %SW52 to the input.
In this case the content of %SW52 and %SW53 is assigned.
 If you want to assign a different date, create an Integer Array of 2 elements and enter the date
in BCD format.
Example:
If the input is:
 Date_ARRAY[1] = 16#0511
 Date_ARRAY[2] = 16#2006

Then the output is:


 DATE_Variable = d#2006-05-11

EN and ENO can be configured as additional parameters.

Representation in FBD

33002519 09/2020 363


ARINT_TO_DATE

Representation in LD

Representation in IL
LD Date_ARRAY
ARINT_TO_DATE
ST DATE_Variable

Representation in ST
DATE_Variable := ARINT_TO_DATE (Date_ARRAY) ;

Parameter description
Description of input parameters:

Parameter Data type Meaning


Date_ARRAY ARRAY [n..m] OF Integer ARRAY of 2 elements with the
INT date in BCD format:
 month, day (16#mmdd),
corresponds to %SW52
 year (16#yyyy),
corresponds to %SW53

Description of output parameters:

Parameter Data type Meaning


DATE_Variable DATE Date assigned to the input as DATE
(d#) variable (if input is valid).

Runtime errors
If input Date_ARRAY is invalid, ENO = 0 and OUT remains unchanged.

364 33002519 09/2020


EcoStruxure™ Control Expert
ARINT_TO_DT
33002519 09/2020

Chapter 114
ARINT_TO_DT: Convert Integer Array with Date and Time to a DT Variable

ARINT_TO_DT: Convert Integer Array with Date and Time to a


DT Variable

Description

Function description
The function converts an Integer Array with date and time in BCD format to a DATE_AND_TIME
(dt#) variable.
For the input you have 2 options:
 If you want to assign the system time, assign %SW50 to the input.
In this case the content of %SW50 to %SW53 is assigned.
 If you want to assign a different time, create an Integer Array of 4 elements and enter time and
date in BCD format.
Example:
If the input is:
 DateAndTime_ARRAY[1] = 16#1600
 DateAndTime_ARRAY[2] = 16#1046
 DateAndTime_ARRAY[3] = 16#0511
 DateAndTime_ARRAY[4] = 16#2006

Then the output is:


 DT_Variable = dt#2006-05-11-10:46:16

EN and ENO can be configured as additional parameters.

Representation in FBD

33002519 09/2020 365


ARINT_TO_DT

Representation in LD

Representation in IL
LD DateAndTime_ARRAY
ARINT_TO_DT
ST DT_Variable

Representation in ST
DT_Variable := ARINT_TO_DT (DateAndTime_ARRAY) ;

Parameter description
Description of input parameters:

Parameter Data type Meaning


DateAndTime_ARRAY ARRAY [n..m] OF Integer ARRAY of 4 elements with the
INT date and time in BCD format:
 seconds,-- (16#ss,--),
corresponds to %SW50
 hour, minute (16#hhmm),
corresponds to %SW51
 month, day (16#mmdd),
corresponds to %SW52
 year (16#yyyy),
corresponds to %SW53

Description of output parameters:

Parameter Data type Meaning


DT_Variable DT Date and time assigned to the input
as DATE_AND_TIME (dt#) variable (if
input is valid).

Runtime errors
If input DateAndTime_ARRAY is invalid, ENO = 0 and OUT remains unchanged.

366 33002519 09/2020


EcoStruxure™ Control Expert
ARINT_TO_TOD
33002519 09/2020

Chapter 115
ARINT_TO_TOD: Convert Integer Array with Time Of Day to a TOD Variable

ARINT_TO_TOD: Convert Integer Array with Time Of Day to a


TOD Variable

Description

Function description
The function converts an Integer Array with the time of day in BCD format to a TIME_OF_DAY
(tod#) variable.
For the input you have 2 options:
 If you want to assign the system time, assign %SW50 to the input.
In this case the content of %SW50 and %SW51 is assigned.
 If you want to assign a different time, create an Integer Array of 2 elements and enter the time
of day in BCD format.
Example:
If the input is:
 Time_ARRAY[1] = 16#1600
 Time_ARRAY[2] = 16#1046

Then the output is:


 TOD_Variable = tod#10:46:16

EN and ENO can be configured as additional parameters.

Representation in FBD

33002519 09/2020 367


ARINT_TO_TOD

Representation in LD

Representation in IL
LD Time_ARRAY
ARINT_TO_TOD
ST TOD_Variable

Representation in ST
TOD_Variable := ARINT_TO_TOD (Time_ARRAY) ;

Parameter description
Description of input parameters:

Parameter Data type Meaning


Time_ARRAY ARRAY [n..m] OF Integer ARRAY of 2 elements with the
INT date and time in BCD format:
 seconds,-- (16#ss,--),
corresponds to %SW50
 hour, minute (16#hhmm),
corresponds to %SW51

Description of output parameters:

Parameter Data type Meaning


TOD_Variable TOD Time of day assigned to the input as
TIME_OF_DAY (tod#) variable (if
input is valid).

Runtime errors
If input Time_ARRAY is invalid, ENO = 0 and OUT remains unchanged.

368 33002519 09/2020


EcoStruxure™ Control Expert
ASCII_TO_STRING
33002519 09/2020

Chapter 116
ASCII_TO_STRING: Type conversion

ASCII_TO_STRING: Type conversion

Description

Function description
The function copies the content (ASCII values) of the INT array at the input (without conversion)
to the output of the data type STRING.
This function is used to transfer any ASCII values (16#01...16#FF). The only exception is 16#00
(Value 0). It is used to end the copy operation.
Since each ASCII value requires 1 Byte, 2 ASCII values can be transferred to the output per integer
element of the input array. The transfer sequence is high byte, low byte.

If an uneven number of ASCII values is transferred to the output, only the high byte of the last
element is theoretically needed. But since the entire element is always transferred, the value 0
must be entered in the low byte in this case; see Example 2, page 371.
The copy operation ends when
 the end of the input array is reached.
 the value 0 (16#00) is transferred,
 the end of the output string is reached.

As additional parameters, EN and ENO are projected.

Representation in FBD
Representation:

33002519 09/2020 369


ASCII_TO_STRING

Representation in LD
Appearance:

Representation in IL
Appearance:
LD AsciiValueArray
ASCII_TO_STRING
ST StringOutput

Representation in ST
Appearance:
StringOutput := ASCII_TO_STRING (AsciiValueArray) ;

Parameter description
Description of input parameters:

Parameter Data type Description


AsciiValueArray ARRAY[n..m] OF INT Integer array with ASCII values

Description of output parameters:

Parameter Data type Description


StringOutput STRING String of ASCII characters

Runtime error
If the size of the string variables at the output is insufficient to represent all ASCII values of the input
array ENO is set to 0 and system bit %S15 is set to 1.

370 33002519 09/2020


ASCII_TO_STRING

Example 1
In the example, 4 ASCII values are to be transferred to a string of 4 characters. This requires an
integer array with 2 elements.

Example 2
In the example, 3 ASCII values are to be transferred to a string of 4 characters. This requires an
integer array with 2 elements; the low byte of the second element is not required, and it therefore
must contain the value 0.

Example 3
In the example, 4 ASCII values are to be transferred to a string of 8 characters. This requires an
integer array with 2 elements. The unneeded 4 characters at the output remain empty in this case.

33002519 09/2020 371


ASCII_TO_STRING

Example 4
In the example the first 4 ASCII values of an integer array with 8 elements are to be transferred to
a string of 4 characters. This requires that the high byte of the third element of the integer array
contains the value 0 to mark the end of the characters to be transferred. All other ASCII values are
no longer considered.

Example 5
In the example, 16 ASCII values are to be transferred to a string of 4 characters. Since the output
string is too small for that, ENO is set to 0 and Systembit %S15 is set to 1.

372 33002519 09/2020


EcoStruxure™ Control Expert
ASCII_TO_STRING_INV
33002519 09/2020

Chapter 117
ASCII_TO_STRING_INV: Type conversion

ASCII_TO_STRING_INV: Type conversion

Description

Function description
The function copies the content (ASCII values) of the INT array at the input (without conversion)
to the output of the data type STRING.
This function is used to transfer any ASCII values (16#01...16#FF). The only exception is 16#00
(Value 0). It is used to end the copy operation.
Since each ASCII value requires 1 Byte, 2 ASCII values can be transferred to the output per integer
element of the input array. The transfer sequence is low byte, high byte.

If an uneven number of ASCII values is transferred to the output, only the low byte of the last
element is theoretically needed. But since the entire element is always transferred, the value 0
must be entered in the high byte in this case; see Example 2, page 375.
The copy operation ends when
 the end of the input array is reached.
 the value 0 (16#00) is transferred,
 the end of the output string is reached.

As additional parameters, EN and ENO are projected.

33002519 09/2020 373


ASCII_TO_STRING_INV

Representation in FBD
Representation:

Representation in LD
Appearance:

Representation in IL
Appearance:
LD AsciiValueArray
ASCII_TO_STRING_INV
ST StringOutput

Representation in ST
Appearance:
StringOutput := ASCII_TO_STRING_INV (AsciiValueArray) ;

Parameter description
Description of input parameters:

Parameter Data type Description


AsciiValueArray ARRAY[n..m] OF INT Integer array with ASCII values

Description of output parameters:

Parameter Data type Description


StringOutput STRING String of ASCII characters

374 33002519 09/2020


ASCII_TO_STRING_INV

Runtime error
If the size of the string variables at the output is insufficient to represent all ASCII values of the input
array ENO is set to 0 and system bit %S15 is set to 1.

Example 1
In the example, 4 ASCII values are to be transferred to a string of 4 characters. This requires an
integer array with 2 elements.

Example 2
In the example, 3 ASCII values are to be transferred to a string of 4 characters. This requires an
integer array with 2 elements; the low byte of the second element is not required, and it therefore
must contain the value 0.

33002519 09/2020 375


ASCII_TO_STRING_INV

Example 3
In the example, 4 ASCII values are to be transferred to a string of 8 characters. This requires an
integer array with 2 elements. The unneeded 4 characters at the output remain empty in this case.

Example 4
In the example the first 4 ASCII values of an integer array with 8 elements are to be transferred to
a string of 4 characters. This requires that the high byte of the third element of the integer array
contains the value 0 to mark the end of the characters to be transferred. All other ASCII values are
no longer considered.

376 33002519 09/2020


ASCII_TO_STRING_INV

Example 5
In the example, 16 ASCII values are to be transferred to a string of 4 characters. Since the output
string is too small for that, ENO is set to 0 and Systembit %S15 is set to 1.

33002519 09/2020 377


ASCII_TO_STRING_INV

378 33002519 09/2020


EcoStruxure™ Control Expert
BCD_TO_INT
33002519 09/2020

Chapter 118
BCD_TO_INT: Conversion of a BCD integer into pure binary

BCD_TO_INT: Conversion of a BCD integer into pure binary

Description

Function description
The BCD_TO_INT function converts an integer in Binary Coded Decimal (BCD) format into a binary
coded integer.
The additional parameters EN and ENO can be configured.

Representation in FBD
Representation:

Representation in LD
Representation:

Representation in IL
Representation:
LD BCD_Int
BCD_TO_INT
ST Result_Int

33002519 09/2020 379


BCD_TO_INT

Representation in ST
Representation:
Result_Int:= BCD_TO_INT(BCD_Int);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


BCD_Int INT Integer in BCD format.

Example: BCD_Int = 16#99

The following table describes the output parameters:

Parameter Type Comment


Result_Int INT Result_Int is a binary coded integer.

Example: with the value provided in the example in the


previous table, Result_Int = 99

Runtime errors
The bit %S18 is set to 1 when the value to be converted is not a value coded in BCD. The result
of the function then returns the value of the input parameter.

380 33002519 09/2020


EcoStruxure™ Control Expert
BIT_TO_BYTE:
33002519 09/2020

Chapter 119
BIT_TO_BYTE: Type conversion

BIT_TO_BYTE: Type conversion

Description

Function description
The function converts 8 input values of the data type BOOL to an output of the BYTE data type.
The input values are assigned to the individual bits of the byte at the output according to the input
names.

EN and ENO can be configured as additional parameters.

Formula
Block formula:

Representation in FBD
Representation:

33002519 09/2020 381


BIT_TO_BYTE:

Representation in LD
Representation:

Representation in IL
Representation:
LD InputBit0
BIT_TO_BYTE InputBit1, InputBit2, InputBit3, InputBit4,
InputBit5, InputBit6, InputBit7
ST OutputByte

Representation in ST
Representation:
OutputByte := BIT_TO_BYTE (InputBit0, InputBit1,
InputBit2, InputBit3, InputBit4, InputBit5, InputBit6,
InputBit7) ;

382 33002519 09/2020


BIT_TO_BYTE:

Parameter description
Description of the input parameters:

Parameter Data type Meaning


InputBit0 BOOL Input bit 0
InputBit1 BOOL Input bit 1
: : :
InputBit7 BOOL Input bit 7

Description of the output parameter:

Parameter Data type Meaning


OutputByte BYTE Output value

33002519 09/2020 383


BIT_TO_BYTE:

384 33002519 09/2020


EcoStruxure™ Control Expert
BIT_TO_WORD
33002519 09/2020

Chapter 120
BIT_TO_WORD: Type conversion

BIT_TO_WORD: Type conversion

Description

Function description
The function converts 16 input values of the BOOL data type to an output value of the WORD data
type.
The input values are assigned to the individual bits of the word at the output according to the input
names.

EN and ENO can be configured as additional parameters.

Formula
Block formula:

Representation in FBD
Representation:

33002519 09/2020 385


BIT_TO_WORD

Representation in LD
Representation:

Representation in IL
Representation:
LD InputBit0
BIT_TO_WORD InputBit1, InputBit2, InputBit3, InputBit4,
InputBit5, InputBit6, InputBit7,InputBit8,
InputBit9, InputBit10, InputBit11, InputBit12,
InputBit13, InputBit14, InputBit15
ST WORD_Output

Representation in ST
Representation:
WORD_Output := BIT_TO_WORD (InputBit0, InputBit1,
InputBit2, InputBit3, InputBit4, InputBit5,
InputBit6, InputBit7, InputBit8, InputBit9,
InputBit10, InputBit11, InputBit12, InputBit13,
InputBit14, InputBit15) ;

386 33002519 09/2020


BIT_TO_WORD

Parameter description
Description of the input parameters:

Parameter Data type Meaning


InputBit0 BOOL Input bit 0
: : :
InputBit15 BOOL Input bit 15

Description of the output parameter:

Parameter Data type Meaning


WORD_Output WORD Output value

33002519 09/2020 387


BIT_TO_WORD

388 33002519 09/2020


EcoStruxure™ Control Expert
BOOL_TO_***
33002519 09/2020

Chapter 121
BOOL_TO_***: Type conversion

BOOL_TO_***: Type conversion

Description

Function description
The function converts an input value of the BOOL data type to a BYTE, WORD, DWORD, INT, DINT,
UINT, UDINT, REAL or TIME data type.
The input value is written in the lowest bit of the output. All other output bits are set to zero.
EN and ENO can be configured as additional parameters.
(The output ENO is not used for BOOL_TO_REAL; it always has the value "1".)

Available functions
List of available functions:
 BOOL_TO_BYTE
 BOOL_TO_WORD
 BOOL_TO_DWORD
 BOOL_TO_INT
 BOOL_TO_DINT
 BOOL_TO_UINT
 BOOL_TO_UDINT
 BOOL_TO_REAL
 BOOL_TO_TIME

Representation in FBD
Representation of an Integer application:

33002519 09/2020 389


BOOL_TO_***

Representation in LD
Representation of an Integer application:

Representation in IL
Representation of an Integer application:
LD BOOL_variable
BOOL_TO_INT
ST ConvertedVariable

Representation in ST
Representation of an Integer application:
ConvertedVariable := BOOL_TO_INT (BOOL_variable) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


BOOL_variable BOOL Input value

Description of the output parameter:

Parameter Data type Meaning


ConvertedVariable BYTE, WORD, DWORD, INT, DINT, Output value
UINT, UDINT, REAL, TIME

390 33002519 09/2020


EcoStruxure™ Control Expert
BYTE_AS_WORD
33002519 09/2020

Chapter 122
BYTE_AS_WORD: Type conversion

BYTE_AS_WORD: Type conversion

Description

Function description
The function converts 2 input values of the BYTE data type to an output value of the WORD data type.
The input values are assigned to the word at the output according to the input names.
EN and ENO can be configured as additional parameters.

Formula
Block formula:

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 391


BYTE_AS_WORD

Representation in IL
Representation:
LD BYTE_variable1
BYTE_AS_WORD BYTE_variable2
ST WORD_Output

Representation in ST
Representation:
WORD_Output := BYTE_AS_WORD (BYTE_variable1,
BYTE_variable2) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


BYTE_variable1 BYTE least significant byte
BYTE_variable2 BYTE most significant byte

Description of the output parameter:

Parameter Data type Meaning


WORD_Output WORD Output value

392 33002519 09/2020


EcoStruxure™ Control Expert
BYTE_TO_BIT
33002519 09/2020

Chapter 123
BYTE_TO_BIT: Type conversion

BYTE_TO_BIT: Type conversion

Description

Function description
The procedure converts an input value of the BYTE data type to 8 output values of the BOOL data
type.
The individual bits of the byte at the input are assigned to the outputs according to the output
names.

EN and ENO can be configured as additional parameters.

Representation in FBD
Representation:

33002519 09/2020 393


BYTE_TO_BIT

Representation in LD
Representation:

Representation in IL
Representation:
LD BYTE_variable
BYTE_TO_BIT BOOL_variable1, BOOL_variable2, BOOL_variable3,
BOOL_variable4, BOOL_variable5, BOOL_variable6,
BOOL_variable7, BOOL_variable8

Representation in ST
Representation:
BYTE_TO_BIT (BYTE_variable, BOOL_variable1, BOOL_variable2,
BOOL_variable3, BOOL_variable4, BOOL_variable5,
BOOL_variable6, BOOL_variable7, BOOL_variable8);

394 33002519 09/2020


BYTE_TO_BIT

Parameter description
Description of the input parameters:

Parameter Data type Meaning


BYTE_variable BYTE Input

Description of the output parameter:

Parameter Data type Meaning


BOOL_variable1 BOOL Output bit 0
BOOL_variable2 BOOL Output bit 1
: : :
BOOL_variable8 BOOL Output bit 7

33002519 09/2020 395


BYTE_TO_BIT

396 33002519 09/2020


EcoStruxure™ Control Expert
BYTE_TO_***
33002519 09/2020

Chapter 124
BYTE_TO_***: Type conversion

BYTE_TO_***: Type conversion

Description

Function description
The function converts an input value of the BYTE data type to a BOOL, WORD, DWORD, INT, DINT,
UINT, UDINT, REAL or TIME data type.
When converting the data type BYTE to the data type WORD, DWORD, INT, DINT, UINT, UDINT,
REAL or TIME, the bit pattern of the input is transferred to the least significant bits of the output.
The most significant bits of the output are set to zero.
When converting the data type BYTE into the data type BOOL, the least significant bit of the input
value is transferred to the output.
EN and ENO can be configured as additional parameters.
(The output ENO is not used for BYTE_TO_REAL; it always has the value "1".)

Available functions
List of available functions:
 BYTE_TO_BOOL
 BYTE_TO_WORD
 BYTE_TO_DWORD
 BYTE_TO_INT
 BYTE_TO_DINT
 BYTE_TO_UINT
 BYTE_TO_UDINT
 BYTE_TO_REAL
 BYTE_TO_TIME

Representation in FBD
Representation of an Integer application:

33002519 09/2020 397


BYTE_TO_***

Representation in LD
Representation of an Integer application:

Representation in IL
Representation of an Integer application:
LD BYTE_variable
BYTE_TO_INT
ST ConvertedVariable

Representation in ST
Representation of an Integer application:
ConvertedVariable := BYTE_TO_INT (BYTE_variable) ;

Parameter description
Description of input parameters:

Parameter Data type Meaning


BYTE_variable BYTE Input value

Description of output parameters:

Parameter Data type Meaning


ConvertedVariable BOOL, WORD, DWORD, Output value
INT, DINT, UINT,
UDINT, REAL, TIME

398 33002519 09/2020


BYTE_TO_***

Runtime error
Error handling is dependent on the function:
 BYTE_TO_REAL
The system bit %S18 is set to 1 and the status is stored in %SW17 , if an illegal floating-point
decimal is generated during the conversion process.
 all other Functions
The system bit %S18 and system word %SW17 are not used.

33002519 09/2020 399


BYTE_TO_***

400 33002519 09/2020


EcoStruxure™ Control Expert
DATE_TO_ARINT
33002519 09/2020

Chapter 125
DATE_TO_ARINT: Convert DATE Variable to Integer Array

DATE_TO_ARINT: Convert DATE Variable to Integer Array

Description

Function description
The function converts a DATE (d#) variable to an Integer Array of 2 elements with the date in BCD
format.
Example:
If the input is:
 DATE_Variable = d#2006-05-11
Then the output is:
 Date_ARRAY[3] = 16#0511
 Date_ARRAY[4] = 16#2006

EN and ENO can be configured as additional parameters.

Representation in FBD

Representation in LD

33002519 09/2020 401


DATE_TO_ARINT

Representation in IL
LD DATE_Variable
DATE_TO_ARINT
ST Date_ARRAY

Representation in ST
Date_ARRAY := DATE_TO_ARINT (DATE_Variable) ;

Parameter description
Description of input parameters:

Parameter Data type Meaning


DATE_Variable DATE Date as DATE (d#) variable.

Description of output parameters:

Parameter Data type Meaning


Date_ARRAY ARRAY [n..m] OF INT Integer ARRAY of 2 elements with the
date in BCD format:
 month, day (16#mmdd)
corresponds to %SW52
 year (16#yyyy)
corresponds to %SW53

Runtime errors
If the size of output Date_ARRAY is too small, ENO = 0 and OUT remains unchanged.

402 33002519 09/2020


EcoStruxure™ Control Expert
DATE_TO_STRING
33002519 09/2020

Chapter 126
DATE_TO_STRING: Conversion of a variable in DATE format into a character string

DATE_TO_STRING: Conversion of a variable in DATE format


into a character string

Description

Function description
The DATE_TO_STRING function converts a variable in DATE format into a character string.
The additional parameters EN and ENO can be configured.

Representation in FBD
Representation:

Representation in LD
Representation:

Representation in IL
Representation:
LD Date1
DATE_TO_STRING
ST Result_Str

33002519 09/2020 403


DATE_TO_STRING

Representation in ST
Representation:
Result_Str:= DATE_TO_STRING(Date1);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Date1 DATE Date to be converted into character string format.

The following table describes the output parameters:

Parameter Type Comment


Result_Str STRING Result_Str is a string of 10 characters which
contains a date (not including hours) in the following
format: YYYY-MM-DD.

Example: ‘2000-12-27’
Note: if the maximum size of the string Result_Str is
greater than 10, Result_Str is completed by the end
of string characters (16#00).

Runtime errors
If the string Result_Str is too short to contain the date (length of less than 10 characters), the
date is truncated and the bit %S15 is set to 1.
If Date1 in not interpretable and coherent in DATE format, the system bit %S18 is set to 1 and
Result_Str =’****-**-**’

404 33002519 09/2020


EcoStruxure™ Control Expert
DBCD_TO_***
33002519 09/2020

Chapter 127
DBCD_TO_***: Conversion of a double BCD integer into binary

DBCD_TO_***: Conversion of a double BCD integer into binary

Description

Function description
The DBCD_TO_*** function converts a double integer in Binary Code Decimal (DBCD) format into
a double binary coded integer.
The additional parameters EN and ENO can be configured.

Available functions
The available functions are as follows:
 DBCD_TO_INT,
 DBCD_TO_DINT.

Representation in FBD
Representation applied to an integer:

Representation in LD
Representation applied to an integer:

33002519 09/2020 405


DBCD_TO_***

Representation in IL
Representation applied to an integer:
LD DBCD_Value
DBCD_TO_INT
ST Result_Value

Representation in ST
Representation applied to an integer:
Result_Value:= DBCD_TO_INT(DBCD_Value);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


DBCD_Value DINT Double integer in BCD format.

Example: DBCD_Value = 16#32767

The following table describes the output parameters:

Parameter Type Comment


Result_Value INT, DINT Result_Value is an integer or double integer in binary
code.

Example: with the value provided in the example in the


previous table, Result_Value = 32767

Runtime errors
The bit %S18 is set to 1 when:
 the value to be converted is not a value coded in BCD. The result of the function then returns
the value of the first half-byte by default.
 for the function DBCD_TO_INT, the value to be converted is greater in BCD than 32767. The
result of the function is then -1.

406 33002519 09/2020


EcoStruxure™ Control Expert
DEG_TO_RAD
33002519 09/2020

Chapter 128
DEG_TO_RAD : Conversion of degrees to radians

DEG_TO_RAD : Conversion of degrees to radians

Description

Function description
The DEG_TO_RAD function converts an angle expressed in degrees into radians.
The additional parameters EN and ENO can be configured.

Formula
The formula is as follows:

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 407


DEG_TO_RAD

Representation in IL
Representation:
LD Angle_in_Degree
DEG_TO_RAD
ST Angle_in_Radian

Representation in ST
Representation:
Angle_in_Radian:= DEG_TO_RAD(Angle_in_Degree);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Angle_in_Degree REAL Angle expressed in degrees.
-737280.0 < Angle_in_Degree < +737280.0.

The following table describes the output parameters:

Parameter Type Comment


Angle_in_Radian REAL Value of Angle expressed in radians.
-π ≤ Angle_in_Radian ≤ +π.

Runtime errors
When Angle_in_Degree is situated outside the interval ]-737280.0, +73780.0[, the system bit
%S18 changes to 1, the system word %SW17 indicates the type of fault and the result displayed
is 1.#NAN.

408 33002519 09/2020


EcoStruxure™ Control Expert
DINT_AS_WORD
33002519 09/2020

Chapter 129
DINT_AS_WORD: Type conversion

DINT_AS_WORD: Type conversion

Description

Function description
The procedure converts an input value of the DINT data type to 2 output values of the WORD data
type.
The individual words of the DINT input are assigned to the outputs according to the output names.
EN and ENO can be configured as additional parameters.

Representation in FBD
Representation:

Representation in LD
Representation:

Representation in IL
Representation:
LD DINT_variable
DINT_AS_WORD LowWord, HighWord

33002519 09/2020 409


DINT_AS_WORD

Representation in ST
Representation:
DINT_AS_WORD (DINT_variable, LowWord, HighWord);

Parameter description
Description of the input parameters:

Parameter Data type Meaning


DINT_variable DINT Input

Description of the output parameter:

Parameter Data type Meaning


LowWord WORD least significant word
HighWord WORD most significant word

410 33002519 09/2020


EcoStruxure™ Control Expert
DINT_TO_***
33002519 09/2020

Chapter 130
DINT_TO_***: Type conversion

DINT_TO_***: Type conversion

Description

Function description
The function converts an input value of the DINT data type to a BOOL, BYTE, WORD, DWORD, INT,
UINT UDINT, REAL or TIME output value.
NOTE: The function converts strictly in accordance with IEC rules. Since this function has been
realized as a generic function, there will also be a few illogical conversions, e.g. DINT_TO_BOOL.
When converting the data type DINT to the BOOL, BYTE, WORD, INT or UINT data type, the least
significant bits of the input value are transferred to the output.
Negative input values cannot be converted into data types UINT, UDINT or TIME.
EN and ENO can be configured as additional parameters.

Available functions
List of available functions:
 DINT_TO_BOOL
 DINT_TO_BYTE
 DINT_TO_WORD
 DINT_TO_DWORD
 DINT_TO_INT
 DINT_TO_UINT
 DINT_TO_UDINT
 DINT_TO_REAL
 DINT_TO_TIME

Representation in FBD
Representation of an Integer application:

33002519 09/2020 411


DINT_TO_***

Representation in LD
Representation of an Integer application:

Representation in IL
Representation of an Integer application:
LD DINT_variable
DINT_TO_INT
ST ConvertedVariable

Representation in ST
Representation of an Integer application:
ConvertedVariable := DINT_TO_INT (DINT_variable) ;

Parameter description
Description of input parameters:

Parameter Data type Meaning


DINT_variable DINT, Input value

Description of output parameters:

Parameter Data type Meaning


ConvertedVariable BOOL, BYTE, WORD, Output value
DWORD, INT, UINT,
UDINT, REAL, TIME

412 33002519 09/2020


DINT_TO_***

Runtime error
The system bit %S18 is set to 1, if
 the value range on the output is exceeded (numeric data types)
 a negative input value is to be converted into an UDINT-, UINT or TIME output value.
 an unauthorized floating point number is created during the conversion into the REAL data type.
In this case, the status is also placed in %SW17.
The system bit %S18 and system word %SW17 are not used when data types are converted:
 BOOL
 BYTE
 WORD
 DWORD

33002519 09/2020 413


DINT_TO_***

414 33002519 09/2020


EcoStruxure™ Control Expert
DINT_TO_DBCD
33002519 09/2020

Chapter 131
DINT_TO_DBCD: Conversion of a double binary coded integer into a double Binary Coded Decimal integer

DINT_TO_DBCD: Conversion of a double binary coded integer


into a double Binary Coded Decimal integer

Description

Function description
The DINT_TO_DBCD function carries out the conversion of a double binary coded integer into an
integer in Double Binary Coded Decimal (DBCD) format.
The additional parameters EN and ENO can be configured.

Representation in FBD
Representation:

Representation in LD
Representation:

Representation in IL
Representation:
LD D_Integer_1
DINT_TO_BCD
ST DBCD_Result

33002519 09/2020 415


DINT_TO_DBCD

Representation in ST
Representation:
DBCD_Result:= DINT_TO_BCD(D_Integer_1);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


D_Integer_1 DINT Double binary coded integer between 0 and 99999999.

Example: D_Integer_1 = 888888

The following table describes the output parameters:

Parameter Type Comment


DBCD_Result DINT DBCD_Result is a double integer in BCD format.

Example: with the value provided in the example in the


previous table, DBCD_Result = 16#00888888

Runtime errors
The bit %S18 is set to 1 when the value to be converted is not a value between 0 and 99999999.
The result of the function then returns the value of the input parameter.

416 33002519 09/2020


EcoStruxure™ Control Expert
DT_TO_ARINT
33002519 09/2020

Chapter 132
DT_TO_ARINT: Convert DT Variable to Integer Array

DT_TO_ARINT: Convert DT Variable to Integer Array

Description

Function description
The function converts a DATE_AND_TIME (dt#) variable to an Integer Array of 4 elements with date
and time in BCD format.
Example:
If the input is:
 DT_Variable = dt#2006-05-11-10:46:16
Then the output is:
 DateAndTime_ARRAY[1] = 16#1600
 DateAndTime_ARRAY[2] = 16#1046
 DateAndTime_ARRAY[3] = 16#0511
 DateAndTime_ARRAY[4] = 16#2006

EN and ENO can be configured as additional parameters.

Representation in FBD

Representation in LD

33002519 09/2020 417


DT_TO_ARINT

Representation in IL
LD DT_Variable
DT_TO_ARINT
ST DateAndTime_ARRAY

Representation in ST
DateAndTime_ARRAY := DT_TO_ARINT (DT_Variable) ;

Parameter description
Description of input parameters:

Parameter Data type Meaning


DT_Variable DT Date and time as DATE_AND_TIME
(dt#) variable.

Description of output parameters:

Parameter Data type Meaning


DateAndTime_ARRAY ARRAY [n..m] OF Integer ARRAY of 4 elements with the
INT date and time in BCD format:
 seconds,-- (16#ss,--)
corresponds to %SW50
 hour, minute (16#hhmm)
corresponds to %SW51
 month, day (16#mmdd)
corresponds to %SW52
 year (16#yyyy)
corresponds to %SW53

Runtime errors
If the size of output DateAndTime_ARRAY is too small, ENO = 0 and OUT remains unchanged.

418 33002519 09/2020


EcoStruxure™ Control Expert
DT_TO_STRING
33002519 09/2020

Chapter 133
DT_TO_STRING: Conversion of a variable in DT format into a character string

DT_TO_STRING: Conversion of a variable in DT format into a


character string

Description

Function description
The DT_TO_STRING function converts a variable in DT format into a character string.
The additional parameters EN and ENO can be configured.

Representation in FBD
Representation:

Representation in LD
Representation:

Representation in IL
Representation:
LD Date1
DT_TO_STRING
ST Result_Str

33002519 09/2020 419


DT_TO_STRING

Representation in ST
Representation:
Result_Str:= DT_TO_STRING(Date1);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Date1 DT Date to be converted into character string format.

The following table describes the output parameters:

Parameter Type Comment


Result_Str STRING Result_Str is a string of 19 characters which
contains a date (including hours) in the following format:
YYYY-MM-DD-HH:MM.

Example: ‘2000-12-27-23:15’
Note: if the maximum size of the string Result_Str is
greater than 19, Result_Str is completed by the end
of string characters (16#00).

Runtime errors
If the string Result_Str is too short to contain the date (length of less than 19 characters), the
date is truncated and the bit %S15 is set to 1.
If Date1 in not interpretable and coherent in format DT, the system bit %S18 is set to 1 and
Result_Str =’****-**-**-**:**:**’.

420 33002519 09/2020


EcoStruxure™ Control Expert
DWORD_TO_***
33002519 09/2020

Chapter 134
DWORD_TO_***: Type conversion

DWORD_TO_***: Type conversion

Description

Function description
The function converts an input value of the DWORD data type to a BOOL, BYTE, WORD, INT, DINT,
UINT, UDINT, REAL or TIME data type.
NOTE: The function converts strictly in accordance with IEC rules. Since this function has been
realized as a generic function, there will also be a few illogical conversions, e.g. DWORD_TO_BOOL.
When converting the data type DWORD to the BOOL, BYTE, WORD, INT or UINT data type, the least
significant bits of the input value are transferred to the output.
EN and ENO can be configured as additional parameters.
(The output ENO is not used for DWORD_TO_REAL; it always has the value "1".)

Available functions
List of available functions:
 DWORD_TO_BOOL
 DWORD_TO_BYTE
 DWORD_TO_WORD
 DWORD_TO_INT
 DWORD_TO_DINT
 DWORD_TO_UINT
 DWORD_TO_UDINT
 DWORD_TO_REAL
 DWORD_TO_TIME

Representation in FBD
Representation of an Integer application:

33002519 09/2020 421


DWORD_TO_***

Representation in LD
Representation of an Integer application:

Representation in IL
Representation of an Integer application:
LD DWORD_variable
DWORD_TO_INT
ST ConvertedVariable

Representation in ST
Representation of an Integer application:
ConvertedVariable := DWORD_TO_INT (DWORD_variable) ;

Parameter description
Description of input parameters:

Parameter Data type Meaning


DWORD_variable DWORD Input value

Description of output parameters:

Parameter Data type Meaning


ConvertedVariable BOOL, BYTE, WORD, INT, DINT, UINT, Output value
UDINT, REAL, TIME

Runtime error
Error handling is dependent on the function:
 DWORD_TO_REAL
The system bit %S18 is set to 1 and the status is stored in %SW17 , if an illegal floating-point
decimal is generated during the conversion process.
 all other Functions
The system bit %S18 and system word %SW17 are not used.

422 33002519 09/2020


EcoStruxure™ Control Expert
GRAY_TO_INT
33002519 09/2020

Chapter 135
GRAY_TO_INT: Conversion of an integer in Gray code into a binary coded integer

GRAY_TO_INT: Conversion of an integer in Gray code into a


binary coded integer

Description

Function description
The GRAY_TO_INT function converts an integer expressed in GRAY code into a binary coded
integer.
The additional parameters EN and ENO can be configured.

Representation in FBD
Representation:

Representation in LD
Representation:

Representation in IL
Representation:
LD GRAY_Int
GRAY_TO_INT
ST Result_Int

33002519 09/2020 423


GRAY_TO_INT

Representation in ST
Representation:
Result_Int:= GRAY_TO_INT(GRAY_Int);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


GRAY_Int INT Integer expressed in GRAY code.

The following table describes the output parameters:

Parameter Type Comment


Result_Int INT Result_Int is a binary coded integer.

424 33002519 09/2020


EcoStruxure™ Control Expert
INT_AS_DINT
33002519 09/2020

Chapter 136
INT_AS_DINT: Concatenation of two integers to form a double integer

INT_AS_DINT: Concatenation of two integers to form a double


integer

Description

Function description
The INT_AS_DINT function concatenates two integers to form a double integer.
The additional parameters EN and ENO can be configured.

Representation in FBD
Representation:

Representation in LD
Representation:

Representation in IL
Representation:
LD Low_Word
INT_AS_DINT High_Word
ST Double_Word

33002519 09/2020 425


INT_AS_DINT

Representation in ST
Representation:
Double_Word:= INT_AS_DINT(Low_Word, High_Word);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Low_Word INT Integer which must become the least significant word of
a double integer Double_Word.

Example: Low_Word contains 16#5678.


High_Word INT Integer which must become the most significant word of
a double integer Double_Word.

Example: High_Word contains 16#1234.

The following table describes the output parameters:

Parameter Type Comment


Double_Word DINT Double integer composed of two integers Low_Word for
the least significant and High_Word for the most
significant.

Example: for the values in the example provided in the


previous table, Double_Word contains 16#12345678.

426 33002519 09/2020


EcoStruxure™ Control Expert
INT_TO_***
33002519 09/2020

Chapter 137
INT_TO_***: Type conversion

INT_TO_***: Type conversion

Description

Function description
The function converts an input value of the INT data type to a BOOL, BYTE, WORD, DWORD, DINT,
UINT, UDINT, REAL or TIME output value.
NOTE: The function converts strictly in accordance with IEC rules. Since this function has been
realized as a generic function, there will also be a few illogical conversions, e.g. INT_TO_BOOL.
Negative input values cannot be converted into data types UINT, UDINT or TIME.
When converting an input value from the data type INT into data type WORD, the bit pattern from
the input is transferred to the output without being modified.
When converting an input value of data type INT into the data types BOOL or BYTE, the least
significant bits of the input are transferred to the output.
EN and ENO can be configured as additional parameters.

Available functions
List of available functions:
 INT_TO_BOOL
 INT_TO_BYTE
 INT_TO_WORD
 INT_TO_DWORD
 INT_TO_DINT
 INT_TO_UINT
 INT_TO_UDINT
 INT_TO_REAL
 INT_TO_TIME

Representation in FBD
Representation of a double integer application:

33002519 09/2020 427


INT_TO_***

Representation in LD
Representation of a double integer application:

Representation in IL
Representation of a double integer application:
LD INT_variable
INT_TO_DINT
ST ConvertedVariable

Representation in ST
Representation of a double integer application:
ConvertedVariable := INT_TO_DINT (INT_variable) ;

Parameter description
Description of input parameters:

Parameter Data type Meaning


INT_variable INT Input value

Description of output parameters:

Parameter Data type Meaning


ConvertedVariable BOOL, BYTE, DWORD, Output value
WORD, DINT, UINT,
UDINT, REAL, TIME

428 33002519 09/2020


INT_TO_***

Runtime error
The system bit %S18 is set to 1, if
 the value range on the output is exceeded (numeric data types)
 a negative input value is to be converted into an UDINT-, UINT or TIME output value.
 an unauthorized floating point number is created during the conversion into the REAL data type.
In this case, the status is also placed in %SW17.
The system bit %S18 and system word %SW17 are not used when data types are converted:
 BOOL
 BYTE
 WORD
 DWORD

33002519 09/2020 429


INT_TO_***

430 33002519 09/2020


EcoStruxure™ Control Expert
INT_TO_BCD
33002519 09/2020

Chapter 138
INT_TO_BCD: Conversion of a binary coded integer into a Binary Coded Decimal integer

INT_TO_BCD: Conversion of a binary coded integer into a


Binary Coded Decimal integer

Description

Function description
The INT_TO_BCD function carries out the conversion of a binary coded integer into an integer in
Binary Coded Decimal (BCD) format.
The additional parameters EN and ENO can be configured.

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 431


INT_TO_BCD

Representation in IL
Representation:
LD Integer_1
INT_TO_BCD
ST BCD_Result

Representation in ST
Representation:
BCD_Result := INT_TO_BCD(Integer_1);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Integer_1 INT Binary coded integer between 0 and 9999.

Example: Integer_1 = 99

The following table describes the output parameters:

Parameter Type Comment


BCD_Result INT BCD_Result is a BCD integer.

Example: with the value provided in the example in the


previous table, BCD_Result = 16#99

Runtime errors
The bit %S18 is set to 1 when the value to be converted is not a value between 0 and 9999. The
result of the function then returns the value of the input parameter.

432 33002519 09/2020


EcoStruxure™ Control Expert
INT_TO_DBCD
33002519 09/2020

Chapter 139
INT_TO_DBCD: Conversion of a binary coded integer into a double Binary Coded Decimal integer

INT_TO_DBCD: Conversion of a binary coded integer into a


double Binary Coded Decimal integer

Description

Function description
The INT_TO_DBCD function carries out the conversion of a binary coded integer into an integer in
Double Binary Coded Decimal (DBCD) format. This function converts numbers with BCD coding up
to 32767.
NOTE: This function is useful when converting numbers greater than 9999 (by comparison to
INT_TO_BCD function).
The additional parameters EN and ENO can be configured.

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 433


INT_TO_DBCD

Representation in IL
Representation:
LD Integer_1
INT_TO_DBCD
ST DBCD_Result

Representation in ST
Representation:
DBCD_Result:= INT_TO_DBCD(Integer_1);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Integer_1 INT Binary coded integer between 0 and 32767.

Example: Integer_1 = 30000

The following table describes the output parameters:

Parameter Type Comment


DBCD_Result DINT DBCD_Result is a double integer in BCD format.

Example: with the value provided in the example in the


previous table, DBCD_Result = 16#00030000

Runtime errors
The bit %S18 is set to 1 when the value to be converted is not between 0 and 32767. The result of
the function then returns the value of the input parameter.

434 33002519 09/2020


EcoStruxure™ Control Expert
RAD_TO_DEG
33002519 09/2020

Chapter 140
RAD_TO_DEG: Conversion of radians to degrees

RAD_TO_DEG: Conversion of radians to degrees

Description

Function description
The RAD_TO_DEG function converts an angle expressed in radians into degrees.
The additional parameters EN and ENO can be configured.

Formula
The formula is as follows:

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 435


RAD_TO_DEG

Representation in IL
Representation:
LD Angle_in_Radian
RAD_TO_DEG
ST Angle_in_Degree

Representation in ST
Representation:
Angle_in_Degree:= RAD_TO_DEG(Angle_in_Radian);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Angle_in_Radian REAL Value of Angle expressed in radians.
-4096π ≤ Angle_in_Radian ≤ +4096π

The following table describes the output parameters:

Parameter Type Comment


Angle_in_Degree REAL Angle expressed in degrees.
-360 < Angle_in_Degree < +360.

Runtime errors
When Angle_in_Degree is situated outside the interval ]-4096 π, 4096 π[, the system bit %S18
changes to 1 and the system bit %SW17 indicates the type of fault.

436 33002519 09/2020


EcoStruxure™ Control Expert
REAL_AS_WORD
33002519 09/2020

Chapter 141
REAL_AS_WORD: Type conversion

REAL_AS_WORD: Type conversion

Description

Function description
The procedure converts an input value of the REAL data type to 2 output values of the WORD data
type.
The individual words of the REAL input are assigned to the outputs according to the output names.
EN and ENO can be configured as additional parameters.

Representation in FBD
Representation:

Representation in LD
Representation:

Representation in IL
Representation:
LD REAL_variable
REAL_AS_WORD LowWord, HighWord

33002519 09/2020 437


REAL_AS_WORD

Representation in ST
Representation:
REAL_AS_WORD (REAL_variable, LowWord, HighWord);

Parameter description
Description of input parameters:

Parameter Data type Meaning


REAL_variable REAL Input

Description of output parameters:

Parameter Data type Meaning


LowWord WORD least significant word
HighWord WORD most significant word

Runtime error
The system bit %S18 is set to 1, if an unauthorized floating point number is set at the input.

438 33002519 09/2020


EcoStruxure™ Control Expert
REAL_TO_***
33002519 09/2020

Chapter 142
REAL_TO_***: Type conversion

REAL_TO_***: Type conversion

Description

Function description
The function converts an input value of the REAL data type to a BOOL, BYTE, WORD , DWORD, INT,
DINT, UINT, UDINT data type or into the TIME data type.
NOTE: The function converts strictly in accordance with IEC rules. Since this function has been
realized as a generic function, there will also be a few illogical conversions, e.g. REAL_TO_BOOL.
When converting to BOOL, BYTE, WORD, the least significant bits of the input value are transferred
to the output. A runtime error message is not given and ENO remains 1.
When converting to INT, DINT, UINT, UDINT and TIME, the IEC 559 rules for rounding are
applied.
EN and ENO can be configured as additional parameters.
(The output ENO is not used for REAL_TO_BOOL, REAL_TO_BYTE, REAL_TO_WORD and
REAL_TO_DWORD; it always has the value "1".)

Available functions
List of available functions:
 REAL_TO_BOOL
 REAL_TO_BYTE
 REAL_TO_WORD
 REAL_TO_DWORD
 REAL_TO_INT
 REAL_TO_DINT
 REAL_TO_UINT
 REAL_TO_UDINT
 REAL_TO_TIME

33002519 09/2020 439


REAL_TO_***

Example
The following example shows how the IEC 559 rounding is applied.
1,4 -> 1
1,5 -> 2
2,5 -> 2
3,5 -> 4
4,5 -> 4
4,6 -> 5

Negative input values


Negative input values cannot be converted into data types UINT, UDINT or TIME.

Representation in FBD
Representation of an Integer application:

Representation in LD
Representation of an Integer application:

Representation in IL
Representation of an Integer application:
LD REAL_variable
REAL_TO_INT
ST ConvertedVariable

440 33002519 09/2020


REAL_TO_***

Representation in ST
Representation of an Integer application:
ConvertedVariable := REAL_TO_INT (REAL_variable) ;

Parameter description
Description of input parameters:

Parameter Data type Meaning


REAL_variable REAL Input value

Description of output parameters:

Parameter Data type Meaning


ConvertedVariable BOOL, BYTE, WORD, DWORD, INT, Output value
DINT, UINT, UDINT, TIME

Runtime error
The system bit %S18 is set to 1, if
 an unauthorized floating point number is set at the input
 the value range on the output is exceeded (numeric data types)
 a negative input value is to be converted into an UDINT-, UINT or TIME output value.
 an unauthorized floating point number is created during the conversion into the REAL data type.
In this case, the status is also placed in %SW17.
The system bit %S18 and system word %SW17 are not used when data types are converted:
 BOOL
 BYTE
 WORD
 DWORD

33002519 09/2020 441


REAL_TO_***

442 33002519 09/2020


EcoStruxure™ Control Expert
REAL_TRUNC_***
33002519 09/2020

Chapter 143
REAL_TRUNC_***: Type conversion

REAL_TRUNC_***: Type conversion

Description

Function description
The function converts (by truncating towards zero) a REAL data type input value to a output value
of the INT, DINT, UINT or UDINT data type.
EN and ENO can be configured as additional parameters.

Available functions
List of available functions:
 REAL_TRUNC_INT
 REAL_TRUNC_DINT
 REAL_TRUNC_UINT
 REAL_TRUNC_UDINT

Example
The following example shows the converting procedure.
1,6 -> 1
-1,6 -> -1
1,4 -> 1
-1,4 -> -1

Data type
Negative input values cannot be converted into data types UDINT or UINT.

Representation in FBD
Representation of an Integer application:

33002519 09/2020 443


REAL_TRUNC_***

Representation in LD
Representation of an Integer application:

Representation in IL
Representation of an Integer application:
LD REAL_variable
REAL_TRUNC_INT
ST ConvertedVariable

Representation in ST
Representation of an Integer application:
ConvertedVariable := REAL_TRUNC_INT (REAL_variable) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


REAL_variable REAL Input value

Description of the output parameter:

Parameter Data type Meaning


ConvertedVariable INT, DINT, UINT, Output value
UDINT

Runtime error
The system bit %S18 is set to 1 and the status is stored in %SW17 if
 a negative input value is to be converted into an UDINT or UINT output value
or
 an unauthorized floating point number is set at the input.

444 33002519 09/2020


EcoStruxure™ Control Expert
STRING_TO_ASCII
33002519 09/2020

Chapter 144
STRING_TO_ASCII: Type conversion

STRING_TO_ASCII: Type conversion

Description

Function description
The function copies the string from the data type STRING at the input (without conversion) as ASCII
values into the INT array at the output.
This function is used to transfer different characters (all correspond with ASCII values 16#01...
16#FF). The only exception is 16#00 (Value 0). It is used to fill in empty (unused) bits.
Since each ASCII character only requires 1 Byte, 2 ASCII characters can be transferred per
Integer element of the output array. The transfer sequence is high byte, low byte.

When the ASCII characters in the string at the input are not sufficient to completely fill the integer
array with ASCII values, the remaining elements are filled with the value 0, see Example 3,
page 448.
The copy operation ends when
 the end of the input string is reached,
 the end of the output array is reached.

As additional parameters, EN and ENO are projected.

Representation in FBD
Representation:

33002519 09/2020 445


STRING_TO_ASCII

Representation in LD
Appearance:

Representation in IL
Appearance:
LD StringInput
STRING_TO_ASCII
ST AsciiValueArray

Representation in ST
Appearance:
AsciiValueArray := STRING_TO_ASCII (StringInput) ;

Parameter description
Description of input parameters:

Parameter Data type Description


StringInput STRING String of ASCII characters

Description of output parameters:

Parameter Data type Description


AsciiValueArray ARRAY[n..m] OF INT Integer array with ASCII values

Runtime error
If the size of array variables at the output is insufficient to represent all ASCII characters of the input
string ENO is set to 0 and system bit %S15 is set to 1.

446 33002519 09/2020


STRING_TO_ASCII

Example 1
In the example, a string of 4 ASCII characters is to be transferred to an integer array. This requires
an integer array with 2 elements.

Example 2
In the example, a string of 3 ASCII characters is to be transferred to an integer array. This requires
an integer array with 2 elements; the low byte of the second element is not required, and it therefore
contains the value 0.

33002519 09/2020 447


STRING_TO_ASCII

Example 3
When the ASCII characters in the string at the input are not sufficient to completely fill the integer
array with ASCII values, the remaining elements are filled with the value 0.

Example 4
When an empty string is transferred, the elements of the integer array are filled with the value 0 .

448 33002519 09/2020


STRING_TO_ASCII

Example 5
In the example, 8 ASCII characters are to be transferred. Since the output array is too small for
that, ENO is set to 0 and Systembit %S15 is set to 1.

33002519 09/2020 449


STRING_TO_ASCII

450 33002519 09/2020


EcoStruxure™ Control Expert
STRING_TO_ASCII_INV
33002519 09/2020

Chapter 145
STRING_TO_ASCII_INV: Type conversion

STRING_TO_ASCII_INV: Type conversion

Description

Function description
The function copies the string from the data type STRING at the input (without conversion) as ASCII
values into the INT array at the output.
This function is used to transfer different characters (all correspond with ASCII values 16#01...
16#FF). The only exception is 16#00 (Value 0). It is used to fill in empty (unused) bits.
Since each ASCII character only requires 1 Byte, 2 ASCII characters can be transferred per
Integer element of the output array. The transfer sequence is low byte, high byte.

When the ASCII characters in the string at the input are not sufficient to completely fill the integer
array with ASCII values, the remaining elements are filled with the value 0, see Example 3,
page 454.
The copy operation ends when
 the end of the input string is reached,
 the end of the output array is reached.

As additional parameters, EN and ENO are projected.

Representation in FBD
Representation:

33002519 09/2020 451


STRING_TO_ASCII_INV

Representation in LD
Appearance:

Representation in IL
Appearance:
LD StringInput
STRING_TO_ASCII_INV
ST AsciiValueArray

Representation in ST
Appearance:
AsciiValueArray := STRING_TO_ASCII_INV (StringInput) ;

Parameter description
Description of input parameters:

Parameter Data type Description


StringInput STRING String of ASCII characters

Description of output parameters:

Parameter Data type Description


AsciiValueArray ARRAY[n..m] OF INT Integer array with ASCII values

Runtime error
If the size of array variables at the output is insufficient to represent all ASCII characters of the input
string ENO is set to 0 and system bit %S15 is set to 1.

452 33002519 09/2020


STRING_TO_ASCII_INV

Example 1
In the example, a string of 4 ASCII characters is to be transferred to an integer array. This requires
an integer array with 2 elements.

Example 2
In the example, a string of 3 ASCII characters is to be transferred to an integer array. This requires
an integer array with 2 elements; the high byte of the second element is not required, and it
therefore contains the value 0.

33002519 09/2020 453


STRING_TO_ASCII_INV

Example 3
When the ASCII characters in the string at the input are not sufficient to completely fill the integer
array with ASCII values, the remaining elements are filled with the value 0.

Example 4
When an empty string is transferred, the elements of the integer array are filled with the value 0 .

454 33002519 09/2020


STRING_TO_ASCII_INV

Example 5
In the example, 8 ASCII characters are to be transferred. Since the output array is too small for
that, ENO is set to 0 and Systembit %S15 is set to 1.

33002519 09/2020 455


STRING_TO_ASCII_INV

456 33002519 09/2020


EcoStruxure™ Control Expert
STRING_TO_***
33002519 09/2020

Chapter 146
STRING_TO_*** : Conversion of a character string to a number of the INT, DINT or REAL type

STRING_TO_*** : Conversion of a character string to a number


of the INT, DINT or REAL type

Description

Description of the function


The STRING_TO_*** function converts a character string into a one- or two-digit integer or into a
real number.
This function is IEC 1131.
The additional parameters EN and ENO can be configured.

Available functions
The available functions are as follows:
 STRING_TO_INT,
 STRING_TO_DINT,
 STRING_TO_REAL.

Representation en FBD
Representation applied to an integer:

33002519 09/2020 457


STRING_TO_***

Representation in LD
Representation applied to an integer:

Representation in IL
Representation applied to an integer:
LD String_1
STRING_TO_INT
ST Result_Value

Representation in ST
Representation applied to an integer:
Result_Value := STRING_TO_INT(String_1);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


String_1 STRING Character string

Example : String_1 = ‘-32500’

The following table describes the output parameters:

Parameter Type Comment


Result_Value INT, DINT, Result_Value is an integer, a two-digit integer or a
REAL real number according to the function used. This result
is the conversion of the character string String_1 in
accordance with the recommendations of standard IEC
1131.

Example : with the value of the example in the above


table, Result_Value = -32500.

458 33002519 09/2020


STRING_TO_***

Execution errors
The %S18 bit is positioned at 1 when the content of the string to be converted is positioned outside
of the boundaries of the type chosen (INT, DINT or REAL) or when one of the characters in the
string is incorrect.

33002519 09/2020 459


STRING_TO_***

460 33002519 09/2020


EcoStruxure™ Control Expert
TIME_AS_WORD
33002519 09/2020

Chapter 147
TIME_AS_WORD: Type conversion

TIME_AS_WORD: Type conversion

Description

Function description
The procedure converts an input value of the TIME data type to 2 output values of the WORD data
type.
The individual words of the TIME input are assigned to the outputs according to the output names.
EN and ENO can be configured as additional parameters.

Representation in FBD
Representation:

Representation in LD
Representation:

Representation in IL
Representation:
LD TIME_variable
TIME_AS_WORD LowWord, HighWord

33002519 09/2020 461


TIME_AS_WORD

Representation in ST
Representation:
TIME_AS_WORD (REAL_variable, LowWord, HighWord);

Parameter description
Description of input parameters:

Parameter Data type Meaning


TIME_variable TIME Input

Description of output parameters:

Parameter Data type Meaning


LowWord WORD least significant word
HighWord WORD most significant word

462 33002519 09/2020


EcoStruxure™ Control Expert
TIME_TO_***
33002519 09/2020

Chapter 148
TIME_TO_***: Type conversion

TIME_TO_***: Type conversion

Description

Function description
The function converts an input value of the TIME data type to a BOOL, BYTE, WORD, DWORD, INT,
DINT, UINT, UDINT or REAL data type.
NOTE: The function converts strictly in accordance with IEC rules. Since this function has been
realized as a generic function, there will also be a few illogical conversions, e.g. TIME_TO_BOOL.
While converting an input value of data type TIME into an output value of data type BOOL, BYTE,
WORD, INT or UINT, the least significant bits, respectively, are transferred from the input to the
output.
EN and ENO can be configured as additional parameters.

Available functions
List of available functions:
 TIME_TO_BOOL
 TIME_TO_BYTE
 TIME_TO_WORD
 TIME_TO_DWORD
 TIME_TO_INT
 TIME_TO_DINT
 TIME_TO_UINT
 TIME_TO_UDINT
 TIME_TO_REAL

Representation in FBD
Representation of an Integer application:

33002519 09/2020 463


TIME_TO_***

Representation in LD
Representation of an Integer application:

Representation in IL
Representation of an Integer application:
LD TIME_variable
TIME_TO_INT
ST ConvertedVariable

Representation in ST
Representation of an Integer application:
ConvertedVariable := TIME_TO_INT (TIME_variable) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


TIME_variable TIME Input value

Description of the output parameter:

Parameter Data type Meaning


ConvertedVariable BOOL, BYTE, WORD, DWORD, Output value
INT, DINT, UINT, UDINT, REAL

Runtime error
The system bit %S18 is set to 1, if
 the value range is exceeded at the output during the execution of the function.

464 33002519 09/2020


EcoStruxure™ Control Expert
TIME_TO_STRING
33002519 09/2020

Chapter 149
TIME_TO_STRING: Conversion of a variable in TIME format into a character string

TIME_TO_STRING: Conversion of a variable in TIME format


into a character string

Description

Function description
The TIME_TO_STRING function converts a variable in TIME format into a character string.
The additional parameters EN and ENO can be configured.

Representation in FBD
Representation:

Representation in LD
Representation:

Representation in IL
Representation:
LD Time1
TIME_TO_STRING
ST Result_Str

33002519 09/2020 465


TIME_TO_STRING

Representation in ST
Representation:
Result_Str:= TIME_TO_STRING(Time1);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Time1 TIME Duration to be converted into character string format.

The following table describes the output parameters:

Parameter Type Comment


Result_Str STRING Result_Str is a string of 15 characters which
contains a duration in the following format:
HHHHHH:MM:SS.D.

Example: ‘119304:38:49.5’
Note: if the maximum size of the string Result_Str is
greater than 15, Result_Str is completed by the end
of string characters (16#00).

Runtime errors
If the string Result_Str is too short to contain the converted value (less than 15 characters in
length), it is truncated and the bit %S15 is set to 1.

466 33002519 09/2020


EcoStruxure™ Control Expert
TOD_TO_ARINT
33002519 09/2020

Chapter 150
TOD_TO_ARINT: Convert TOD Variable to Integer Array

TOD_TO_ARINT: Convert TOD Variable to Integer Array

Description

Function description
The function converts a TIME_OF_DAY (tod#) variable to an Integer Array of 2 elements with the
time of day in BCD format.
Example:
If the input is:
 TOD_Variable = tod#10:46:16

Then the output is:


 Time_ARRAY[1] = 16#1600
 Time_ARRAY[2] = 16#1046

EN and ENO can be configured as additional parameters.

Representation in FBD

Representation in LD

33002519 09/2020 467


TOD_TO_ARINT

Representation in IL
LD TOD_Variable
TOD_TO_ARINT
ST Time_ARRAY

Representation in ST
Time_ARRAY := TOD_TO_ARINT (TOD_Variable) ;

Parameter description
Description of input parameters:

Parameter Data type Meaning


TOD_Variable TIME_OF_DAY Time of day as TIME_OF_DAY (tod#)
variable.

Description of output parameters:

Parameter Data type Meaning


Time_ARRAY ARRAY [n..m] OF Integer ARRAY of 2 elements with the
INT date and time in BCD format:
 seconds,-- (16#ss,--),
corresponds to %SW50
 hour, minute (16#hhmm)
corresponds to %SW51

Runtime errors
If the size of output Time_ARRAY is too small, ENO = 0 and OUT remains unchanged.

468 33002519 09/2020


EcoStruxure™ Control Expert
TOD_TO_STRING
33002519 09/2020

Chapter 151
TOD_TO_STRING: Conversion of a variable in TOD format into a character string

TOD_TO_STRING: Conversion of a variable in TOD format


into a character string

Description

Function description
The TOD_TO_STRING function converts a variable in TOD format into a character string.
The additional parameters EN and ENO can be configured.

Representation in FBD
Representation:

Representation in LD
Representation:

Representation in IL
Representation:
LD Time1
TOD_TO_STRING
ST Result_Str

33002519 09/2020 469


TOD_TO_STRING

Representation in ST
Representation:
Result_Str:= =TOD_TO_STRING(Time1);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Time1 TOD Time of day to be converted into character string format.

The following table describes the output parameters:

Parameter Type Comment


Result_Str STRING Result_Str is a string of 8 characters which contains
a time of day in the following format: HH:MM:SS.

Example: ‘04:38:49’
Note: if the maximum size of the string Result_Str is
greater than 8, Result_Str is completed by the end of
string characters (16#00).

Runtime errors
If the string Result_Str is too short to contain the converted value (less than 8 characters in
length), it is truncated and the bit %S15 is set to 1.

470 33002519 09/2020


EcoStruxure™ Control Expert
UDINT_AS_WORD
33002519 09/2020

Chapter 152
UDINT_AS_WORD: Type conversion

UDINT_AS_WORD: Type conversion

Description

Function description
The procedure converts an input value of the UDINT data type to 2 output values of the WORD data
type.
The individual words of the UDINT input are assigned to the outputs according to the output names.
EN and ENO can be configured as additional parameters.

Representation in FBD
Representation:

Representation in LD
Representation:

Representation in IL
Representation:
LD UDINT_variable
UDINT_AS_WORD LowWord, HighWord

33002519 09/2020 471


UDINT_AS_WORD

Representation in ST
Representation:
UDINT_AS_WORD (UDINT_variable, LowWord, HighWord);

Parameter description
Description of input parameters:

Parameter Data type Meaning


UDINT_variable UDINT Input

Description of output parameters:

Parameter Data type Meaning


LowWord WORD least significant word
HighWord WORD most significant word

472 33002519 09/2020


EcoStruxure™ Control Expert
UDINT_TO_***
33002519 09/2020

Chapter 153
UDINT_TO_***: Type conversion

UDINT_TO_***: Type conversion

Description

Function description
The function converts an input value of the UDINT data type to an output value of the BOOL, BYTE,
WORD, DWORD, INT, DINT, UINT, REAL or TIME data type.
NOTE: The function converts strictly in accordance with IEC rules. Since this function has been
realized as a generic function, there will also be a few illogical conversions, e.g. UDINT_TO_BOOL.
When converting the data type DINT to the BOOL, BYTE, WORD, INT or UINT data type, the least
significant bits of the input value are transferred to the output.
EN and ENO can be configured as additional parameters.

Available functions
List of available functions:
 UDINT_TO_BOOL
 UDINT_TO_BYTE
 UDINT_TO_WORD
 UDINT_TO_DWORD
 UDINT_TO_INT
 UDINT_TO_DINT
 UDINT_TO_UINT
 UDINT_TO_REAL
 UDINT_TO_TIME

Representation in FBD
Representation of an Integer application:

33002519 09/2020 473


UDINT_TO_***

Representation in LD
Representation of an Integer application:

Representation in IL
Representation of an Integer application:
LD UDINT_variable
UDINT_TO_INT
ST ConvertedVariable

Representation in ST
Representation of an Integer application:
ConvertedVariable := UDINT_TO_INT (UDINT_variable) ;

Parameter description
Description of input parameters:

Parameter Data type Meaning


UDINT_variable UDINT Input value

Description of output parameters:

Parameter Data type Meaning


ConvertedVariable BOOL, BYTE, WORD, DWORD, INT, Output value
DINT, UINT, REAL, TIME

474 33002519 09/2020


UDINT_TO_***

Runtime error
The system bit %S18 is set to 1, if
 the value range on the output is exceeded (numeric data types)
 a negative input value is to be converted into an UDINT-, UINT or TIME output value.
 an unauthorized floating point number is created during the conversion into the REAL data type.
In this case, the status is also placed in %SW17.
The system bit %S18 and system word %SW17 are not used when data types are converted:
 BOOL
 BYTE
 WORD
 DWORD

33002519 09/2020 475


UDINT_TO_***

476 33002519 09/2020


EcoStruxure™ Control Expert
UINT_TO_***
33002519 09/2020

Chapter 154
UINT_TO_***: Type conversion

UINT_TO_***: Type conversion

Description

Function description
The function converts an input value of the UINT data type to an output value of the BOOL, BYTE,
WORD, DWORD, INT, DINT, UDINT, REAL or TIME.data type.
NOTE: The function converts strictly in accordance with IEC rules. Since this function has been
realized as a generic function, there will also be a few illogical conversions, e.g. UINT_TO_BOOL.
When converting an input value from the data type UINT into data type WORD, the bit pattern from
the input is transferred to the output without being modified.
When converting an input value of data type UINT into the data types BOOL or BYTE, the least
significant bits of the input are transferred to the output.
EN and ENO can be configured as additional parameters.

Available functions
List of available functions:
 UINT_TO_BOOL
 UINT_TO_BYTE
 UINT_TO_WORD
 UINT_TO_DWORD
 UINT_TO_INT
 UINT_TO_DINT
 UINT_TO_UDINT
 UINT_TO_REAL
 UINT_TO_TIME

Representation in FBD
Representation of an Integer application:

33002519 09/2020 477


UINT_TO_***

Representation in LD
Representation of an Integer application:

Representation in IL
Representation of an Integer application:
LD UINT_variable
UINT_TO_INT
ST ConvertedVariable

Representation in ST
Representation of an Integer application:
ConvertedVariable := UINT_TO_INT (UINT_variable) ;

Parameter description
Description of input parameters:

Parameter Data type Meaning


UINT_variable UINT Input value

Description of output parameters:

Parameter Data type Meaning


ConvertedVariable BOOL, BYTE, WORD, Output value
DWORD, INT, DINT,
UDINT, REAL, TIME

478 33002519 09/2020


UINT_TO_***

Runtime error
The system bit %S18 is set to 1, if
 the value range on the output is exceeded (numeric data types)
 a negative input value is to be converted into an UDINT-, UINT or TIME output value.
 an unauthorized floating point number is created during the conversion into the REAL data type.
In this case, the status is also placed in %SW17.
The system bit %S18 and system word %SW17 are not used when data types are converted:
 BOOL
 BYTE
 WORD
 DWORD

33002519 09/2020 479


UINT_TO_***

480 33002519 09/2020


EcoStruxure™ Control Expert
WORD_AS_BYTE
33002519 09/2020

Chapter 155
WORD_AS_BYTE: Type conversion

WORD_AS_BYTE: Type conversion

Description

Function description
The procedure converts an input value of the WORD data type to 2 output values of the BYTE data
type.
The individual bytes of the word at the input are assigned to the outputs according to the output
names.
EN and ENO can be configured as additional parameters.

Representation in FBD
Representation:

Representation in LD
Representation:

Representation in IL
Representation:
LD WORD_variable
WORD_AS_BYTE LowByte, HighByte

33002519 09/2020 481


WORD_AS_BYTE

Representation in ST
Representation:
WORD_AS_BYTE (WORD_variable, LowByte, HighByte);

Parameter description
Description of the input parameters:

Parameter Data type Meaning


WORD_variable WORD Input

Description of the output parameter:

Parameter Data type Meaning


LowByte BYTE least significant byte
HighByte BYTE most significant byte

482 33002519 09/2020


EcoStruxure™ Control Expert
WORD_AS_DINT
33002519 09/2020

Chapter 156
WORD_AS_DINT: Type conversion

WORD_AS_DINT: Type conversion

Description

Function description
The function converts 2 input values of the WORD data type to an output of the DINT data type.
The input values are assigned to the word at the output according to the input names.
EN and ENO can be configured as additional parameters.

Formula
Block formula:

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 483


WORD_AS_DINT

Representation in IL
Representation:
LD WORD_variable1
WORD_AS_DINT WORD_variable2
ST DINT_variable

Representation in ST
Representation:
DINT_variable := WORD_AS_DINT (WORD_variable1,
WORD_variable2) ;

Parameter description
Description of the input parameters:

Parameter Data type Meaning


WORD_variable1 WORD least significant word
WORD_variable2 WORD most significant word

Description of the output parameter:

Parameter Data type Meaning


DINT_variable DINT Output value

484 33002519 09/2020


EcoStruxure™ Control Expert
WORD_AS_REAL
33002519 09/2020

Chapter 157
WORD_AS_REAL: Type conversion

WORD_AS_REAL: Type conversion

Description

Function description
The function converts an input value of the 2 WORD data type to output values of the REAL
data type.
The input values are assigned to the word at the output according to the input names.
EN and ENO can be configured as additional parameters.

Formula
Block formula:

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 485


WORD_AS_REAL

Representation in IL
Representation:
LD WORD_variable1
WORD_AS_REAL WORD_variable2
ST REAL_Output

Representation in ST
Representation:
REAL_Output := WORD_AS_REAL (WORD_variable1, WORD_variable2);

Parameter description
Description of input parameters:

Parameter Data type Meaning


WORD_variable1 WORD least significant byte
WORD_variable2 WORD most significant byte

Description of output parameters:

Parameter Data type Meaning


REAL_Output REAL Output value

Runtime error
The system bit %S18 is set to 1, if
 an unauthorized floating-point number is set at the input
 an unauthorized floating-point number is created during the conversion into the REAL data type.
In this case, the status is also placed in %SW17.

486 33002519 09/2020


EcoStruxure™ Control Expert
WORD_AS_TIME
33002519 09/2020

Chapter 158
WORD_AS_TIME: Type conversion

WORD_AS_TIME: Type conversion

Description

Function description
The function converts 2 input values of the WORD data type to an output value of the TIME data type.
The input values are assigned to the word at the output according to the input names.
EN and ENO can be configured as additional parameters.

Formula
Block formula:

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 487


WORD_AS_TIME

Representation in IL
Representation:
LD WORD_variable1
WORD_AS_TIME WORD_variable2
ST TIME_Output

Representation in ST
Representation:
TIME_Output := WORD_AS_TIME (WORD_variable1,
WORD_variable2) ;

Parameter description
Description of input parameters:

Parameter Data type Meaning


WORD_variable1 WORD least significant byte
WORD_variable2 WORD most significant byte

Description of output parameters:

Parameter Data type Meaning


TIME_Output TIME Output value

488 33002519 09/2020


EcoStruxure™ Control Expert
WORD_AS_UDINT
33002519 09/2020

Chapter 159
WORD_AS_UDINT: Type conversion

WORD_AS_UDINT: Type conversion

Description

Function description
The function converts 2 input values of the WORD data type to an output value of the UDINT data
type.
The input values are assigned to the word at the output according to the input names.
EN and ENO can be configured as additional parameters.

Formula
Block formula:

Representation in FBD
Representation:

Representation in LD
Representation:

33002519 09/2020 489


WORD_AS_UDINT

Representation in IL
Representation:
LD WORD_variable1
WORD_AS_UDINT WORD_variable2
ST UDINT_Output

Representation in ST
Representation:
UDINT_Output := WORD_AS_UDINT (WORD_variable1,
WORD_variable2) ;

Parameter description
Description of input parameters:

Parameter Data type Meaning


WORD_variable1 WORD least significant byte
WORD_variable2 WORD most significant byte

Description of output parameters:

Parameter Data type Meaning


UDINT_Output UDINT Output value

490 33002519 09/2020


EcoStruxure™ Control Expert
WORD_TO_BIT
33002519 09/2020

Chapter 160
WORD_TO_BIT: Type conversion

WORD_TO_BIT: Type conversion

Description

Function description
The procedure converts an input value of the WORD data type to 16 output values of the BOOL data
type.
The individual bits of the word at the input are assigned to the outputs according to the output
names.

EN and ENO can be configured as additional parameters.

Representation in FBD
Representation:

33002519 09/2020 491


WORD_TO_BIT

Representation in LD
Representation:

Representation in IL
Representation:
LD WORD_variable
WORD_TO_BIT BOOL_variable1, BOOL_variable2,
BOOL_variable3, BOOL_variable4, BOOL_variable5,
BOOL_variable6, BOOL_variable7, BOOL_variable8,
BOOL_variable9, BOOL_variable10, BOOL_variable11,
BOOL_variable12, BOOL_variable13, BOOL_variable14,
BOOL_variable15, BOOL_variable16

Representation in ST
Representation:
WORD_TO_BIT (WORD_variable, BOOL_variable1
BOOL_variable2, BOOL_variable3, BOOL_variable4,
BOOL_variable5, BOOL_variable6, BOOL_variable7,
BOOL_variable8, BOOL_variable9, BOOL_variable10,
BOOL_variable11, BOOL_variable12, BOOL_variable13,
BOOL_variable14, BOOL_variable15, BOOL_variable16);

492 33002519 09/2020


WORD_TO_BIT

Parameter description
Description of the input parameters:

Parameter Data type Meaning


WORD_variable WORD Input

Description of the output parameter:

Parameter Data type Meaning


BOOL_variable1 BOOL Output BIT0
: : :
BOOL_variable16 BOOL Output BIT15

33002519 09/2020 493


WORD_TO_BIT

494 33002519 09/2020


EcoStruxure™ Control Expert
WORD_TO_***
33002519 09/2020

Chapter 161
WORD_TO_***: Type conversion

WORD_TO_***: Type conversion

Description

Function description
The function converts an input value of the WORD data type to a BOOL, BYTE, DWORD, INT, DINT,
UINT, UDINT, REAL or TIME data type.
When converting the WORD data type to the DWORD, DINT, UDINT, REAL or TIME data type, the bit
pattern of the input is transferred to the least significant bits of the output. The most significant bits
of the output are set to zero.
When converting the data type WORD to the data type BOOL or BYTE, the least significant bits of the
input value are transferred to the output.
EN and ENO can be configured as additional parameters.
(The output ENO is not used for WORD_TO_REAL; it always has the value "1".)

Available functions
List of available functions:
 WORD_TO_BOOL
 WORD_TO_BYTE
 WORD_TO_DWORD
 WORD_TO_INT
 WORD_TO_DINT
 WORD_TO_UINT
 WORD_TO_UDINT
 WORD_TO_REAL
 WORD_TO_TIME

Representation in FBD
Representation of an Integer application:

33002519 09/2020 495


WORD_TO_***

Representation in LD
Representation of an Integer application:

Representation in IL
Representation of an Integer application:
LD WORD_variable
WORD_TO_INT
ST ConvertedVariable

Representation in ST
Representation of an Integer application:
ConvertedVariable := WORD_TO_INT (WORD_variable) ;

Parameter description
Description of input parameters:

Parameter Data type Meaning


WORD_variable WORD Input value

Description of output parameters:

Parameter Data type Meaning


ConvertedVariable BOOL, BYTE, DWORD, INT, DINT, Output value
UINT, UDINT, REAL, TIME

Runtime error
The system bit %S18 is set to 1 and the status is stored in %SW17 if
 an unauthorized floating-point number is created during the conversion into the REAL data type.

496 33002519 09/2020


EcoStruxure™ Control Expert
***_TO_STRING
33002519 09/2020

Chapter 162
***_TO_STRING: Conversion of a variable into a character string

***_TO_STRING: Conversion of a variable into a character


string

Description

Function description
The ***_TO_STRING function converts an INT, DINT or REAL variable into a character string.
The additional parameters EN and ENO can be configured.

Available functions
The available functions are as follows:
 INT_TO_STRING,
 DINT_TO_STRING,
 REAL_TO_STRING.

Representation in FBD
Representation applied to a real:

Representation in LD
Representation applied to a real:

33002519 09/2020 497


***_TO_STRING

Representation in IL
Representation applied to a real:
LD Value1
REAL_TO_STRING
ST Result_Str

Representation in ST
Representation applied to a real:
Result_Str:= REAL_TO_STRING(Value1);

Description of parameters
The following table describes the input parameters:

Parameter Type Comment


Value1 INT, DINT, Variable to be converted into character string format.
REAL

The following table describes the output parameters:

Parameter Type Comment


Result_Str STRING Result_Str is a character string whose length depends on the
type of Value1:
 5 figures plus the sign making 6 characters for one INT
(example: ‘-00045’),
 10 figures plus the sign, making 11 characters for one DINT
(example: ‘-0000678911’),
Note: under PL7, the result is on 11 figures plus the sign, making
12 characters for one DINT (example: ‘-00006789110’).
 14 characters for a REAL (example:
‘-3.1234560e+25’).

Runtime errors
If, during the conversion of a value of REAL type, Value1 is not between -3.402824e+38 and -
1.175494e-38 or +1.175494e-38 and +3.402824e+38, the bit %S18 is set to 1 and the contents of
the string Result_Str is not significant.

498 33002519 09/2020


EcoStruxure™ Control Expert

33002519 09/2020

Appendices

33002519 09/2020 499


500 33002519 09/2020
EcoStruxure™ Control Expert
EFB Error Codes and Values
33002519 09/2020

Appendix A
EFB Error Codes and Values

EFB Error Codes and Values

Introduction
The following tables show the error codes and error values created for the EFBs of the Base
Library.

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Tables of Error Codes for the Base Library 502
Common Floating Point Errors 504

33002519 09/2020 501


EFB Error Codes and Values

Tables of Error Codes for the Base Library

Introduction
The following tables show the error codes and error values created for the EFBs of the Base
Library.

Date & Time


Table of error codes and errors values created for EFBs of the Date & Time family.

EFB Error code ENO Error Error Error description


name state in value value in
case of in Dec Hex
error
DIVTIME E_DIVIDE_BY_ZERO F -30176 16#8A20 Divide by zero
DIVTIME E_NEGATIVE_INPUT_ F -30177 16#8A1F A negative value cannot be converted
FOR_TIME_OPERATION to data type TIME
DIVTIME E_ARITHMETIC_ ERROR F -30170 16#8A26 Arithmetic error
DIVTIME E_ERR_ARITHMETIC F -30003 16#8ACD Arithmetic overflow (%S18 set)
DIVTIME FP_ERROR F - - See table Common Floating Point
Errors, page 504
MULTIME E_ERR_ARITHMETIC F -30003 16#8ACD Arithmetic overflow (%S18 set)
MULTIME E_ARITHMETIC_ERROR_MUL_ F -30172 16#8A24 Arithmetic error / Muliplication overflow
OV
MULTIME E_ARITHMETIC_ERROR_ADD_ F -30173 16#8A23 Arithmetic error / Addition overflow
OV
MULTIME E_ARITHMETIC_ERROR_BIG_ F -30171 16#8A25 Arithmetic error / Parameter exceeds
PAR range
MULTIME E_NEGATIVE_INPUT_FOR_ F -30177 16#8A1F A negative value cannot be converted
TIME_OPERATION to data type TIME
MULTIME FP_ERROR F - - See table Common Floating Point
Errors, page 504

502 33002519 09/2020


EFB Error Codes and Values

Statistical
Table of error codes and errors values created for EFBs of the Statistical family.

EFB Error code ENO Error Error Error description


name state in value value in
case of in Dec Hex
error
AVE E_INPUT_VALUE_OUT_OF_RANGE F -30183 Input value is out of range
16#8A19
AVE E_DIVIDE_BY_ZERO F -30176 Divide by zero
16#8A20
AVE FP_ERROR F - - See table Common Floating Point
Errors, page 504
AVE E_ARITHMETIC_ ERROR F -30170 16#8A26 Arithmetic error
AVE E_FP_STATUS_FAILED F -30150 Illegal floating point operation
16#8A3A
AVE E_ARITHMETIC_ ERROR_MUL_OV F -30172 16#8A24 Arithmetic error / Muliplication
overflow
AVE E_ARITHMETIC_ ERROR_ADD_OV F -30173 16#8A23 Arithmetic error / Addition overflow
AVE E_ARITHMETIC_ ERROR_BIG_PAR F -30171 16#8A25 Arithmetic error / Parameter
exceeds range
AVE E_ARITHMETIC_ERROR_UNSIGN_OV F -30174 16#8A22 Arithmetic error / Unsigned overflow
MAX FP_ERROR F - - See table Common Floating Point
Errors, page 504
MIN FP_ERROR F - - See table Common Floating Point
Errors, page 504
MUX E_SELECTOR_OUT_OF_RANGE F -30175 Selector is out of range
16#8A21

33002519 09/2020 503


EFB Error Codes and Values

Common Floating Point Errors

Introduction
The following table shows the common error codes and error values created for floating point
errors. These error information are displayed in the Diagnostic Viewer and the error code values
are written in %SW125 (see EcoStruxure™ Control Expert, System Bits and Words, Reference
Manual).

Common Floating Point Errors


Table of common floating point errors

Error codes Error value in Error value Error description


Dec in Hex
FP_ERROR -30150 16#8A3A Base value (not apearing as an error value)
E_FP_STATUS_FAILED_IE -30151 16#8A39 Illegal floating point operation
E_FP_STATUS_FAILED_DE -30152 16#8A38 Operand is denormalized - not a valid REAL
number
E_FP_STATUS_FAILED_ZE -30154 16#8A36 Illegal divide by zero
E_FP_STATUS_FAILED_ZE_IE -30155 16#8A35 Illegal floating point operation / Divide by zero
E_FP_STATUS_FAILED_OE -30158 16#8A32 Floating point overflow
E_FP_STATUS_FAILED_OE_IE -30159 16#8A31 Illegal floating point operation / Overflow
E_FP_STATUS_FAILED_OE_ZE -30162 16#8A2E Floating point overflow / Divide by zero
E_FP_STATUS_FAILED_OE_ZE_IE -30163 16#8A2D Illegal floating point operation / Overflow /
Divide by zero
E_FP_NOT_COMPARABLE -30166 16#8A2A Internal error

504 33002519 09/2020


EcoStruxure™ Control Expert
Glossary
33002519 09/2020

Glossary

A
ANY
There is a hierarchy among the various data types. In the DFBs, it is sometimes possible to declare
variables that can contain several types of values. In that case we use ANY_xxx types.
The figure below describes this hierarchical structure:

ARRAY
An ARRAY is a table containing elements of a single type.
The syntax is as follows: ARRAY [<limits>] OF <Type>
Example:
ARRAY [1..2] OF BOOL is a one-dimensional table with two elements of type BOOL.
ARRAY [1..10, 1..20] OF INT is a two-dimensional table with 10x20 elements of type INT.

33002519 09/2020 505


Glossary

B
BCD
BCD is the abbreviation of the Binary Coded Decimal format.
BCD can be used to represent decimal numbers between 0 and 9 using a set of four bits (nybble).
In this format, the four bits used to encode decimal numbers have an unused range of
combinations.
Example of BCD encoding:
 The number 2,450
 is encoded: 0010 0100 0101 0000

BOOL
BOOL is the abbreviation for the Boolean type. This is the basic data type in computing. A BOOL
variable can have either of the following two values: 0 (FALSE) or 1 (TRUE).
A bit extracted from a word is of type BOOL, for example: %MW10.4.

BYTE
When 8 bits are grouped together, they are called a BYTE. You can enter a BYTE either in binary
mode or in base 8.
The BYTE type is encoded in an 8 bit format which, in hexadecimal format, ranges from 16#00 to
16#FF.

D
DATE
The DATE type, encoded in BCD in a 32 bit format, contains the following information:
 the year encoded in a 16 bit field;
 the month encoded in an 8 bit field;
 the day encoded in an 8 bit field.
The DATE type must be entered as follows: D#<Year>-<Month>-<Day>
This table shows the upper/lower limits of each field:

Field Limits Comment


Year [1990,2099] Year
Month [01,12] The leading 0 is displayed; it can be omitted during data entry.
Day [01,31] For months 01/03/05/07/08/10/12
[01,30] For months 04/06/09/11
[01,29] For month 02 (leap years)
[01,28] For month 02 (non-leap years)

506 33002519 09/2020


Glossary

DBCD
Representation of a double integer in double BCD format.
BCD format can be used to represent decimal numbers between 0 and 9 using a set of four bits.
In this format, the four bits used to encode decimal numbers have an unused range of
combinations.
Example of DBCD encoding:
 The number 78,993,016
 is encoded: 0111 1000 1001 1001 0011 0000 0001 0110

DFB
DFB is the abbreviation of Derived Function Block.
DFB types are function blocks that can be defined by the user in ST, IL, LD or FBD language.
Using these DFB types in an application makes it possible to:
 simplify the design and entry of the program;
 make the program easier to read;
 make it easier to debug;
 reduce the amount of code generated.
DINT
DINT is the abbreviation of Double INTeger (encoded in 32 bits).
The upper/lower limits are as follows: -(2 to the power of 31) to (2 to the power of 31) - 1.
Example:
-2147483648, 2147483647, 16#FFFFFFFF.

DT
DT is the abbreviation of Date and Time.
The DT type, encoded in BCD in a 64 bit format, contains the following information:
 the year encoded in a 16 bit field;
 the month encoded in an 8 bit field;
 the day encoded in an 8 bit field;
 the time encoded in an 8 bit field;
 the minutes encoded in an 8 bit field;
 the seconds encoded in an 8 bit field.
NOTE: The 8 least significant bits are not used.
The DT type must be entered as follows:
DT#<Year>-<Month>-<Day>-<Hour>:<Minutes>:<Seconds>

33002519 09/2020 507


Glossary

This table shows the upper/lower limits of each field:

Field Limits Comment


Year [1990,2099] Year
Month [01,12] The leading 0 is displayed; it can be omitted during
data entry.
Day [01,31] For months 01/03/05/07/08/10/12
[01,30] For months 04/06/09/11
[01,29] For month 02 (leap years)
[01,28] For month 02 (non-leap years)
Hour [00,23] The leading 0 is displayed; it can be omitted during
data entry.
Minute [00,59] The leading 0 is displayed; it can be omitted during
data entry.
Second [00,59] The leading 0 is displayed; it can be omitted during
data entry.

DWORD
DWORD is the abbreviation of Double Word.
The DWORD type is encoded in a 32 bit format.
This table shows the upper/lower limits of each of the bases that can be used:

Base Lower limit Upper limit


Hexadecimal 16#0 16#FFFFFFFF
Octal 8#0 8#37777777777
Binary 2#0 2#11111111111111111111111111111111

Examples of representation:

Data Representation in one of the bases


00000000000010101101110011011110 16#ADCDE
00000000000000010000000000000000 8#200000
00000000000010101011110011011110 2#10101011110011011110

508 33002519 09/2020


Glossary

E
EBOOL
EBOOL is the abbreviation of Extended BOOLean. An EBOOL type has a value (0 (FALSE) or 1
(TRUE), but also rising or falling edges and forcing functions.
An EBOOL variable occupies one byte in memory.
The byte contains the following information:
 one bit for the value;
 one bit for the history (whenever the object changes state, the value is copied to the history bit);
 one bit for forcing (equal to 0 if the object is not forced, or 1 if the bit is forced).
The default value of each bit is 0 (FALSE).

EN
EN stands for ENable; it is an optional block input. When the EN input is enabled, an ENO output is
set automatically.
If EN = 0, the block is not enabled; its internal program is not executed, and ENO is set to 0.
If EN = 1, the block's internal program is run and ENO is set to 1. If an error occurs, ENO is set to 0.
If the EN input is not connected, it is set automatically to 1.

ENO
ENO stands for Error NOtification; this is the output associated with the optional input EN.
If ENO is set to 0 (because EN = 0 or in case of an execution error):
 the status of the function block outputs remains the same as it was during the previous scanning
cycle that executed correctly;
 the output(s) of the function, as well as the procedures, are set to "0".

33002519 09/2020 509


Glossary

G
GRAY
The Gray code, or "reflected binary", is used to encode a numerical value developed in a string of
binary configurations that may be differentiated by changing the status of a single bit.
For example, this code can be used to avoid the following random event: in pure binary, changing
the value 0111 to 1000 may produce a range number between 0 and 1,000, given that the bits do
not all change value at the same time.
Equivalence between decimal, BCD and Gray:

I
INF
Used to indicate that a number exceeds the authorized limits.
For an integer, the value ranges (shown in gray) are as follows:

When a result is:


 less than -3.402824e+38, the symbol -INF (for -infinity) is displayed;
 greater than +3.402824e+38, the symbol INF (for +infinity) is displayed;

INT
INT is the abbreviation of single INTeger (encoded in 16 bits).
The upper/lower limits are as follows: -(2 to the power of 15) to (2 to the power of 15) - 1.
Example:
-32768, 32767, 2#1111110001001001, 16#9FA4.

510 33002519 09/2020


Glossary

N
NAN
Used to indicate that the result of an operation is not a number (NAN = Not A Number).
Example: calculating the square root of a negative number.
NOTE: The CEI 559 standard defines two classes of NAN: the silent NAN (QNAN) and the
signaling NAN (SNAN). A QNAN is a NAN with a most significant fraction bit while an SNAN is a
NAN without a most significant fraction bit (bit number 22). QNANs can be propagated via most
arithmetic operations without throwing an exception. As for SNANs, they generally indicate an
invalid operation when they are used as operands in arithmetic operations (see %SW17 and
%S18).

R
REAL
The REAL type is encoded in a 32 bit format.
The possible value ranges are shown in the figure below:

When a result is:


 between -1,175494e-38 and 1,175494e-38, it is considered to be a DEN;
 less than -3.402824e+38, the symbol -INF (for - infinity) is displayed;
 greater than +3.402824e+38, the symbol INF (for + infinity) is displayed;
 undefined (square root of a negative number), the symbolNAN is displayed.
NOTE: The IEC 559 standard defines two classes of NAN: the silent NAN (QNAN) and the
signaling NAN (SNAN). A QNAN is a NAN with a most significant fraction bit while an SNAN is a
NAN without a most significant fraction bit (bit number 22). QNANs can be propagated via most
arithmetic operations without throwing an exception. As for SNANs, they generally indicate n invalid
operation when they are used as operands in arithmetic operations (see %SW17 and %S18).
NOTE: When a DEN (non-standardized number) is used as an operand, the result is not significant.

S
STRING
A STRING variable is a series of ASCII characters. The maximum length of a string is 65,534
characters.

33002519 09/2020 511


Glossary

T
TIME
The TIME type expresses a time in milliseconds. Encoded in 32 bits, this type can be used to
obtain times from 0 to 2 32-1 milliseconds.
The TIME type has the following units: days (d), hours (h), minutes (m), seconds (s) and
milliseconds (ms). A literal value of type TIME is represented by a combination of the preceding
types prefixed with T#, t#, TIME# or time#.
Examples: T#25h15m, t#14,7S, TIME#5d10h23m45s3ms

TOD
TOD is the abbreviation of Time Of Day.
The TOD type, encoded in BCD in a 32 bit format, contains the following information:
 the hour encoded in an 8 bit field;
 the minutes encoded in an 8 bit field;
 the seconds encoded in an 8 bit field.
NOTE: The 8 least significant bits are not used.
The TOD type must be entered as follows: TOD#<Hour>:<Minutes>:<Seconds>
This table shows the upper/lower limits of each field:

Field Limits Comment


Hour [00,23] The leading 0 is displayed; it can be omitted during data entry.
Minute [00,59] The leading 0 is displayed; it can be omitted during data entry.
Second [00,59] The leading 0 is displayed; it can be omitted during data entry.

Example: TOD#23:59:45.

U
UDINT
UDINT is the abbreviation of Unsigned Double INTeger (encoded in 32 bits). The upper/lower limits
are as follows: 0 to (2 to the power of 32) - 1.
Example:
0, 4294967295, 2#11111111111111111111111111111111, 8#37777777777,
16#FFFFFFFF.

512 33002519 09/2020


Glossary

UINT
UINT is the abbreviation of the Unsigned INTeger format (encoded in 16 bits). The upper/lower
limits are as follows: 0 to (2 to the power of 16) - 1.
Example:
0, 65535, 2#1111111111111111, 8#177777, 16#FFFF.

W
WORD
The type WORD is encoded in a 16 bit format and is used to perform processing on series of bits.
This table shows the upper/lower limits of each of the bases that can be used:

Base Lower limit Upper limit


Hexadecimal 16#0 16#FFFF
Octal 8#0 8#177777
Binary 2#0 2#1111111111111111

Examples of representation

Data Representation in one of the bases


0000000011010011 16#D3
1010101010101010 8#125252
0000000011010011 2#11010011

33002519 09/2020 513


Glossary

514 33002519 09/2020


EcoStruxure™ Control Expert
Index
33002519 09/2020

Index

A array - instructions
SWAP_***, 119
ABS, 233
ADD_***_***, 43
ACOS, 235
AND_***_***, 47
ACOS_REAL, 235
ARINT_TO_DATE, 363
ADD, 237
ARINT_TO_DT, 365
ADD_***_***, 43
ARINT_TO_TOD, 367
ADD_***_TIME, 175
COPY_***_***, 51
ADD_TIME, 239
DATE_TO_ARINT, 401
AND, 195
DIV_***_***, 55
AND_***_***, 47
DT_TO_ARINT, 417
ARINT_TO_DATE, 363
EQUAL_***, 59
ARINT_TO_DT, 365
FIND_EQ_***, 63
ARINT_TO_TOD, 367
FIND_EQP_***, 67
FIND_GT_***, 71
FIND_LT_***, 75
LENGTH_***, 79
MAX_***, 83
MIN_***, 85
MOD_***_***, 87
MOVE_***_***, 91, 93
MUL_***_***, 95
NOT_***, 99
OCCUR_***, 101
OR_***_***, 103
ROL_***, 107
ROR_***, 109
SORT_***, 111
SUB_***_***, 113
SUM_***, 117
TOD_TO_ARINT, 467
XOR_***_***, 121
ASCII_TO_STRING, 369
ASCII_TO_STRING_INV, 373
ASIN, 241
ASIN_REAL, 241
ATAN, 243
ATAN_REAL, 243
availability of the instructions, 33
AVE, 297
AVE_DINT, 297

33002519 09/2020 515


Index

AVE_INT, 297 conversion - instructions


AVE_REAL, 297 BCD_TO_INT, 379
AVE_UDINT, 297 DATE_TO_STRING, 403
AVE_UINT, 297 DBCD_TO_***, 405
DEG_TO_RAD, 407
DINT_TO_DBCD, 415
B DT_TO_STRING, 419
BCD_TO_INT, 379 GRAY_TO_INT, 423
BIT_TO_BYTE, 381 INT_AS_DINT, 425
BIT_TO_WORD, 385 INT_TO_BCD, 431
BOOL_TO_***, 389 INT_TO_DBCD, 433
BYTE_AS_WORD, 391 RAD_TO_DEG, 435
BYTE_TO_***, 397 STRING_TO_***, 457
BYTE_TO_BIT, 393 ARINT_TO_DATE, 363
ARINT_TO_DT, 365
ARINT_TO_TOD, 367
C ASCII_TO_STRING, 369
comparison - instructions ASCII_TO_STRING_INV, 373
EQ, 153 BIT_TO_BYTE, 381
EQUAL_***, 59 BIT_TO_WORD, 385
EQUAL_STR, 325 BOOL_TO_***, 389
FIND_EQ_***, 63 BYTE_AS_WORD, 391
FIND_EQP_***, 67 BYTE_TO_***, 397
FIND_GT_***, 71 BYTE_TO_BIT, 393
FIND_LT_***, 75 DATE_TO_ARINT, 401
GE, 155 DINT_AS_WORD, 409
GT, 159 DINT_TO_***, 411
LE, 163 DINT_TO_STRING, 497
LT, 167 DT_TO_ARINT, 417
NE, 171 DWORD_TO_***, 421
OCCUR_***, 101 INT_TO_***, 427
CONCAT_STR, 321 INT_TO_STRING, 497
controller - instructions MOVE_***_***, 93
general information, 127 REAL_AS_WORD, 437
PID_INT, 133 REAL_TO_***, 439
PWM_INT, 141 REAL_TO_STRING, 497
SERVO_INT, 145 REAL_TRUNC_***, 443
STRING_TO_ASCII, 445
STRING_TO_ASCII_INV, 451
TIME_AS_WORD, 461
TIME_TO_***, 463
TIME_TO_STRING, 465
TOD_TO_ARINT, 467
TOD_TO_STRING, 469
UDINT_AS_WORD, 471

516 33002519 09/2020


Index

UDINT_TO_***, 473 E
UINT_TO_***, 477
EQ, 153
WORD_AS_BYTE, 481
EQUAL_***, 59
WORD_AS_DINT, 483
EQUAL_STR, 325
WORD_AS_REAL, 485
error codes, 501
WORD_AS_TIME, 487
EXP, 255
WORD_AS_UDINT, 489
EXP_REAL, 255
WORD_TO_***, 495
EXPT_REAL_***, 257
WORD_TO_BIT, 491
EXTRACT, 187
COPY_***_***, 51
extract - instructions
COS, 245
EXTRACT, 187
COS_REAL, 245
SIZEOF, 191
counter - instructions
CTD, 347
CTD_***, 347 F
CTU, 349
F_TRIG, 197
CTU_***, 349
FE, 199
CTUD, 351
FIND_EQ_***, 63
CTUD_***, 351
FIND_EQP_***, 67
CTD, 347
FIND_GT_***, 71
CTD_***, 347
FIND_INT, 327
CTU, 349
FIND_LT_***, 75
CTU_***, 349
CTUD, 351
CTUD_***, 351
G
GE, 155
D GRAY_TO_INT, 423
GT, 159
DATE_TO_ARINT, 401
DATE_TO_STRING, 403
DBCD_TO_***, 405
DEC, 247
I
DEG_TO_RAD, 407 INC, 261
DELETE_INT, 323 INSERT_INT, 329
DINT_AS_WORD, 409 instructions
DINT_TO_***, 411 availability, 33
DINT_TO_DBCD, 415 INT_AS_DINT, 425
DINT_TO_STRING, 497 INT_TO_***, 427
DIV, 249 INT_TO_BCD, 431
DIV_***_***, 55 INT_TO_DBCD, 433
DIVMOD, 253 INT_TO_STRING, 497
DIVTIME, 177
DT_TO_ARINT, 417
DT_TO_STRING, 419
DWORD_TO_***, 421

33002519 09/2020 517


Index

L M
LE, 163 mathematical - instructions
LEFT_INT, 333 ABS, 233
LEN_INT, 335 ACOS, 235
LENGTH_***, 79 ACOS_REAL, 235
LIMIT, 301 ADD, 237
LIMIT_IND, 305 ADD_***_***, 43
LN, 263 ADD_***_TIME, 175
LN_REAL, 263 ADD_TIME, 239
LOG, 265 ASIN, 241
LOG_REAL, 265 ASIN_REAL, 241
logical - instructions Assignment to arrays, 91
AND, 195 ATAN, 243
AND_***_***, 47 ATAN_REAL, 243
F_TRIG, 197 AVE, 297
FE, 199 COS, 245
NOT, 201 COS_REAL, 245
NOT_***, 99 DEC, 247
OR, 203 DIV, 249
OR_***_***, 103 DIV_***_***, 55
R_TRIG, 205 DIVMOD, 253
RE, 207 DIVTIME, 177
RESET, 209 EXP, 255
ROL, 211 EXP_REAL, 255
ROL_***, 107 EXPT_REAL_***, 257
ROR, 215 INC, 261
ROR_***, 109 LENGTH_***, 79
RS, 217 LIMIT, 301
SET, 219 LIMIT_IND, 305
SHL, 221 LN, 263
SHR, 223 LN_REAL, 263
SR, 225 LOG, 265
TRIGGER, 227 LOG_REAL, 265
XOR, 229 MAX, 309
XOR_***_***, 121 MAX_***, 83
LT, 167 MIN, 311
MIN_***, 85
MOD, 267
MOD_***_***, 87
MOVE, 269
MUL, 271
MUL_***_***, 95
MULTIME, 179
MUX, 313
NEG, 273

518 33002519 09/2020


Index

SATURATION, 275 P
SEL, 317
PID_INT, 133
SIGN, 279
PWM_INT, 141
SIN, 281
SIN_REAL, 281
SQRT_***, 287 R
SUB, 283
R_TRIG, 205
SUB_***_***, 113, 181
RAD_TO_DEG, 435
SUB_***_TIME, 183
RE, 207
SUB_TIME, 285
REAL_AS_WORD, 437
SUM_ARINT, 117
REAL_TO_***, 439
TAN, 289
REAL_TO_STRING, 497
TAN_REAL, 289
REAL_TRUNC_***, 443
MAX, 309
REF, 293
MAX_***, 83
REF - instructions
MID_INT, 337
REF, 293
MIN, 311
REPLACE_INT, 339
MIN_***, 85
RESET, 209
MOD, 267
RIGHT_INT, 343
MOD_***_***, 87
ROL, 211
MOVE, 269
ROL_***, 107
MOVE_***_***, 91, 93
ROR, 215
MUL, 271
ROR_***, 109
MUL_***_***, 95
RS, 217
MULTIME, 179
MUX, 313
S
N SATURATION, 275
SEL, 317
NE, 171
SERVO_INT, 145
NEG, 273
SET, 219
NOT, 201
SHL, 221
NOT_***, 99
SHR, 223
SIGN, 279
O SIN, 281
SIN_REAL, 281
OCCUR_***, 101
SIZEOF, 191
OR, 203
SORT_***, 111
OR_***_***, 103
SQRT_***, 287
output processing - instructions
SR, 225
PWM_INT, 141
SERVO_INT, 145

33002519 09/2020 519


Index

string management - instructions TOF, 355


CONCAT_STR, 321 TON, 357
DATE_TO_STRING, 403 TP, 359
DELETE_INT, 323 TRIGGER, 227
FIND_INT, 327
INSERT_INT, 329
LEFT_INT, 333 U
LEN_INT, 335 UDINT_AS_WORD, 471
MID_INT, 337 UDINT_TO_***, 473
REPLACE_INT, 339 UINT_TO_***, 477
RIGHT_INT, 343
STRING_TO_***, 457
TIME_TO_STRING, 465 W
TOD_TO_STRING, 469 WORD_AS_BYTE, 481
ASCII_TO_STRING, 369 WORD_AS_DINT, 483
ASCII_TO_STRING_INV, 373 WORD_AS_REAL, 485
DINT_TO_STRING, 497 WORD_AS_TIME, 487
EQUAL_STR, 325 WORD_AS_UDINT, 489
INT_TO_STRING, 497 WORD_TO_***, 495
REAL_TO_STRING, 497 WORD_TO_BIT, 491
STRING_TO_ASCII, 445
STRING_TO_ASCII_INV, 451
STRING_TO_***, 457 X
STRING_TO_ASCII, 445 XOR, 229
STRING_TO_ASCII_INV, 451 XOR_***_***, 121
SUB, 283
SUB_***_***, 113, 181
SUB_***_TIME, 183
SUB_TIME, 285
SUM_***, 117
SWAP_***, 119

T
TAN, 289
TAN_REAL, 289
TIME_AS_WORD, 461
TIME_TO_***, 463
TIME_TO_STRING, 465
timer - instructions
TOF, 355
TON, 357
TP, 359
TOD_TO_ARINT, 467
TOD_TO_STRING, 469

520 33002519 09/2020

You might also like