F 75 020 - Screen
F 75 020 - Screen
TM
Notification Appliances
F-75-020
GENERAL NOTES:
• Strobes are designed to flash at 1 flash per second minimum over their “Regulated Voltage Range”.
• All candela ratings represent minimum effective strobe intensity based on UL Standard 1971.
• Series Exceder Strobe products are Listed under UL Standards 1971 and 464 for indoor use with a temperature range
of 32°F to 120°F (0°C to 49°C) and maximum humidity of 93% (± 2%) UL 464 (85% UL 1971).
• Series Exceder horns are under UL Standard 464 for audible signal appliances (Indoor use only).
Strobe Rating per UL Standard 1971
UL Max Current*
24 VDC / 24 FWR 12 VDC
Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75
Range VDC
ST 8.0-33.0 0.057 0.070 0.085 0.135 0.163 0.182 0.205 0.253 0.110 0.140
STC 8.0-33.0 0.061 0.085 0.103 0.135 0.163 0.182 0.205 0.253 0.110
Regulated Voltage * UL max current rating is the maximum RMS current within
Model 99 dB 95 dB 90 dB the listed voltage range (16-33 VDC for 24 VDC units). For
Range YDC
strobes, the UL max current is usually at the minimum listed
HN 16-33.0 0.064 0.044 0.022
voltage (16 VDC for 24 VDC units). For audibles, the max
HNC 16-33.0 0.084 0.044 0.022 current is usually at the maximum listed voltage (33 VDC for
HN 8.0-17.5 0.047 0.026 0.017 24 VDC units). For unfiltered ratings, see installation
HNC 8.0-17.5 0.047 0.026 0.017 instructions.
-2-
TM
-3-
ARCHITECTS & ENGINEERS SPECIFICATIONS
The notification appliances shall be Exceder Series HS The Series HS and ST wall models shall have a low profile
Audible Strobe appliances, Series ST Visual Strobe appli- measuring 5.24” H x 4.58” W x 2.19” D. Series HN wall
ances and Series HN Audible appliances or approved shall measure 5.24” H x 4.58” W x 1.6” D. The Series HSC
equals. The Series HS and ST Strobes shall be listed for and STC shall been round and have a low profile with a
UL Standard 1971 (Emergency Devices for the Hearing- diameter of 6.68” x 2.63” D. Series HNC ceiling shall have a
Impaired) for Indoor Fire Protection Service. The Series HS diameter of 6.68” x 1.50” D.
and HN Audibles shall be UL Listed under Standard 464 Synchronization is achieved through Fenwal control panel
(Fire Protective Signaling). All Series shall meet the synchronization protocol. The strobes shall not drift out of
requirements of FCC Part 15 Class B. All inputs shall be synchronization at any time during operation. If the sync
compatible with standard reverse polarity supervision of cir- protocol fails to operate, the strobe shall revert to a non-
cuit wiring by a Fire Alarm Control Panel (FACP) with the synchronized flash-rate and still maintain (1) flash per sec-
ability to operate from 8 to 33 VDC. Indoor wall models ond over its Regulated Voltage Range. The appliance shall
shall incorporate voltage test points for easy voltage also be designed so that the audible signal may be silenced
inspection. while maintaining strobe activation when used with syn-
The Series HS Audible Strobe and ST Strobe appliances chronization protocol.
shall produce a flash rate of one (1) flash per second over Wall Appliances – UL Standard 1971, UL Standard 464,
the Regulated Voltage Range and shall incorporate a California State Fire Marshal (CSFM), ULC
Xenon flashtube enclosed in a rugged Lexan® lens. The Ceiling Appliances – UL Standard 1971, UL Standard
Series shall be of low current design. Where Multi-Candela 464, California State Fire Marshal (CSFM), ULC
appliances are specified, the strobe intensity shall have 8
field selectable settings at 15, 15/75, 30, 75, 95, 110, 135,
185 candela for wall mount and 15, 30, 60, 75, 95, 115,
150, 177 candela for ceiling mount. The selector switch for
selecting the candela shall be tamper resistant. The 15/75
candela strobe shall be specified when 15 candela UL
Standard 1971 Listing with 75 candela on-axis is required
(e.g. ADA compliance). Appliances with candela settings
shall show the candela selection in a visible location at all
times when installed.
The audible shall have a minimum of three (3) field select-
able settings for dBA levels and shall have a choice of con-
tinuous or temporal (Code 3) audible outputs.
The Series HS Audible Strobe, ST Strobe and Series HN
Audible shall incorporate a patented Universal Mounting
Base that shall allow mounting to a single-gang, double-
gang, 4-inch square, 3.5-inch octal, 4-inch octal or 100mm
European type back boxes. Two wire appliance wiring shall
be capable of directly connecting to the mounting base.
Continuity checking of the entire NAC circuit prior to attach-
ing any notification appliances shall be allowed. Product
shall come with Contact Cover to protect contact springs.
Removal of an appliance shall result in a supervision fault
condition by the Fire Alarm Control Panel (FACP). The
mounting base shall be the same base among all horn,
strobe, horn strobe, wall and ceiling models. All notification
appliances shall be backwards compatible.
This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes
no responsibility for the product’s suitability for a particular application. The product must be
properly applied to work correctly. If you need more information on this product, or if you Protection Systems
have a particular question, contact KIDDE-FENWAL, INC., Ashland, MA 01721. 400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
F-75-020 Rev AB © 2013 Kidde-Fenwal Inc. Fax: 508.881.8920