Small Signal Stability
Small Signal Stability
Analysis
Dr Praghnesh Bhatt
Associate Professor & Head
Department of Electrical Engineering
School of Technology, PDPU
Physical Structure Power System Components
2
Machine
Synchronous, Induction, or any other
Models
Exciter
Models DC, AC or Static Excitation Systems
Network
Models Line, transformer
Load
Models
Synchronous Machine
5
Synchronous Machine Models
Windings on rotor
Model
Model Name States
6 No
d – axis q –axis
0 0 Classical 0.0 2
1 0 Field Circuit Only 1.0 3
1 1 Field Circuit with one equivalent 1.1 Widely used for 4
damper on q-axis hydro generators
2 1 Field Circuit with one equivalent 2.1 Widely used for 5
damper on d-axis and q-axis hydro generators
each
2 2 Field Circuit with one equivalent 2.2 Widely used in 6
damper on d-axis and two literature
equivalent dampers on q-axis
3 2 Field Circuit with two equivalent 3.2 7
dampers on d-axis and two
equivalent dampers on q-axis
3 3 Field Circuit with two equivalent 3.3 Most detailed 8
damper on d-axis and three model,
equivalent dampers on q-axis applicable to
turbo alternators
7
Small Signal Stability Analysis – Classical Model
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
-3
x 10
2 0.1
Kd = 0
speed deviation (pu)
0 0
-1 -0.05
-2 -0.1
0 5 10 15 0 5 10 15
time (Sec) time (Sec)
100 4000
Kd = -10
speed deviation (pu)
0 0
-50 -2000
-100 -4000
0 5 10 15 0 5 10 15
time (Sec) time (Sec)
25
26
Consideration of Field Circuit Dynamics
27
28
29
Consideration of Field Circuit Dynamics
30
31
32
33
34
35
36
37
The change in air gap torque due to field flux variations caused
by rotor angle is given by
K 2 K3 K 4
1 sT3
In steady state and at a very
41
At oscillating frequencies K 2 K3 K 4
low oscillating frequencies much higher than 1/T3
T3 1 j
T3
if j 1 ,
The field flux variation due to Δδ
T3
ψ at
48
2
ψ ad ψ aq
2
(3.191)
refer derivation from Ch.3 at T 1
I Asat e B sat
(3.189)
ψ ad jψ aq j E t Ra jX l I t
I 0 Asat e Bsat at 0 T 1
ψ ad jψ aq j E a
where , E a Et Ra jX l I t Find: Ksd = Ksq
ψ at 0 ψ 2
ad ψ 2
aq E t Ra jX l I t
at
K sd (3.187)
at I
at 0
K sd ( for initial operating condition)
at 0 I 0
Step 3: Find Xds = Lds and Xqs = Lqs
49
1
r s
0
1
r j
0
1
r j
0
0
j r
67
With increasing KA,
synchronizing torque
increases; from negative, it
Net Ks is
min at KA increases to positive
= 46
decreases
7
x 10
1.5
1 With AVR
0.5
Speed Deviation (pu)
-0.5
-1
-1.5
0 5 10 15 20 25 30 35 40 45 50
t, sec
Observation 1
70
Observation 2
For high values of external system reactance and for the generator operating at high output, a high response
exciter is beneficial in increasing synchronizing torque.
However, in doing so, it introduces negative damping. Thus we have a conflicting requirements with regard to
exciter response.
One possible way is to restrike a compromise and set the exciter response such that it results in sufficient
synchronizing and damping torque components for the expected range of system operating conditions.
This may not always be possible.
It may be necessary to use a high response exciter to provide the required synchronizing torque and transient
stability performance.
With a very high external system reactance, even with low exciter response, the net damping torque coefficient
may be negative.
An effective way to meet the conflicting exciter performance requirements with regard to system stability is
to provide a power system stabilizers (PSS)
71
72
73
74
75
76
77
78
79
80