The document outlines the details of an assignment that has already been submitted, including specific questions and answers related to electrical engineering concepts such as transmission line impedance and relay protection schemes. It also includes scores for each question, indicating which answers were correct or incorrect. The assignment was due on October 14, 2020, and was submitted on October 11, 2020.
Copyright
© © All Rights Reserved
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2 views

Assignment 4

The document outlines the details of an assignment that has already been submitted, including specific questions and answers related to electrical engineering concepts such as transmission line impedance and relay protection schemes. It also includes scores for each question, indicating which answers were correct or incorrect. The assignment was due on October 14, 2020, and was submitted on October 11, 2020.
Copyright
© © All Rights Reserved
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 3

Assignment 4

The due date for submitting this assignment has passed.


Due on 2020-10-14, 23:59 IST.

Assignment submitted on 2020-10-11, 20:32 IST


1 point
1. For a balanced healthy power system, the positive sequence voltage (V1) is equals to_____. Here, VA, VB and VC are
voltage of phase A, B, and C, respectively. Term α=1∟120°.
V1 =(VA+αVB + α2VC)
V1 =(VA+αVB + α2VC)/3
V1 =3(VA+α2VB + αVC)

V1 =(VA+α2VB + αVC)/3
Yes, the answer is correct.
Score: 1
Accepted Answers:
V1 =(VA+αVB + α2VC)/3
2 points
2. A 132 kV transmission line has an impedance of 4 + j16 Ω. This line is protected by mho type distance relay (having
characteristic angle =600) with CT ratio = 1000/1 A and PT ratio = 132 kV/110 V. The zone-1 of the relay covers 80% of
the line length whereas the zone-2 covers 150% of the line length. The first and second zone setting of the relay are

20 Ω and 10.67 Ω, respectively


11.43 Ω and 21.44 Ω, respectively
10.67 Ω and 20 Ω, respectively

26 Ω and 10.67 Ω, respectively


No, the answer is incorrect.
Score: 0
Accepted Answers:
11.43 Ω and 21.44 Ω, respectively
2 points
3. A transmission line is feed from local end A and remote end B. The impedance of the whole transmission line is 5 + j20 Ω. The
fault occurs at a point F on the line and the impedance from the relaying point A to the fault point F, i.e., Z AF = 2.5 + j10 Ω. The fault
resistance (RF) is15 Ω. The fault current contribution from bus A to the fault, i.e. 200∟76.36°. The contribution of fault current
from bus B to the fault, i.e., 300∟-84.29°. Determine the apparent impedance seen by the relay at A.

20.16∟49.74°
10.16∟29.74°
20.16∟29.74°

20.16∟19.74°
Yes, the answer is correct.
Score: 2
Accepted Answers:
20.16∟29.74°
2 points
4. Which of the following relay have less tendency of undesired operation during the power swing condition?

impedance relay
reactance relay

mho relay

quadrilateral relay
Yes, the answer is correct.
Score: 2
Accepted Answers:
quadrilateral relay
2 points
5. Which of the following relay characteristic has the higher loadability limit?

impedance relay
reactance relay

mho relay

quadrilateral relay
Yes, the answer is correct.
Score: 2
Accepted Answers:
quadrilateral relay
2 points
6. Pilot protection provide which of the following advantage

simultaneous tripping at both ends of line


low cost protection as compared to conventional protection scheme
instantaneous tripping at both ends of line

none of the above


Yes, the answer is correct.
Score: 2
Accepted Answers:
simultaneous tripping at both ends of line
1 point
7. A carrier signal used for protection can also be utilized for

telemetering

supervisory control

communication

all of the above


No, the answer is incorrect.
Score: 0
Accepted Answers:
all of the above
1 point
8. The advantage of fibre optics communication is
high bandwidth

low cost

ease to install and maintain

none of the above


No, the answer is incorrect.
Score: 0
Accepted Answers:
high bandwidth
1 point
9. The frequency of carrier signal transmitted through a microwave channel is in the range of

0.3-3 kHz
0.3-3 GHz
0.3-3 MHz

none of the above


Yes, the answer is correct.
Score: 1
Accepted Answers:
0.3-3 GHz
1 point
10. Wire pilot relaying scheme is used for the protection of

long transmission line


medium transmission line

short transmission line

all of the above


Yes, the answer is correct.
Score: 1
Accepted Answers:
short transmission line