2. A 132 kV transmission line has an impedance of 4 + j16 Ω. This line is protected by mho type distance relay (having
characteristic angle =600) with CT ratio = 1000/1 A and PT ratio = 132 kV/110 V. The zone-1 of the relay covers 80% of
the line length whereas the zone-2 covers 150% of the line length. The first and second zone setting of the relay are
20.16∟49.74°
10.16∟29.74°
20.16∟29.74°
20.16∟19.74°
Yes, the answer is correct.
Score: 2
Accepted Answers:
20.16∟29.74°
2 points
4. Which of the following relay have less tendency of undesired operation during the power swing condition?
impedance relay
reactance relay
mho relay
quadrilateral relay
Yes, the answer is correct.
Score: 2
Accepted Answers:
quadrilateral relay
2 points
5. Which of the following relay characteristic has the higher loadability limit?
impedance relay
reactance relay
mho relay
quadrilateral relay
Yes, the answer is correct.
Score: 2
Accepted Answers:
quadrilateral relay
2 points
6. Pilot protection provide which of the following advantage
telemetering
supervisory control
communication
low cost
0.3-3 kHz
0.3-3 GHz
0.3-3 MHz