Assignment 4
The due date for submitting this assignment has passed.
Due on 2020-10-14, 23:59 IST.
Assignment submitted on 2020-10-11, 20:32 IST
1 point
1. For a balanced healthy power system, the positive sequence voltage (V1) is equals to_____. Here, VA, VB and VC are
voltage of phase A, B, and C, respectively. Term α=1∟120°.
V1 =(VA+αVB + α2VC)
V1 =(VA+αVB + α2VC)/3
V1 =3(VA+α2VB + αVC)
V1 =(VA+α2VB + αVC)/3
Yes, the answer is correct.
Score: 1
Accepted Answers:
V1 =(VA+αVB + α2VC)/3
2 points
2. A 132 kV transmission line has an impedance of 4 + j16 Ω. This line is protected by mho type distance relay (having
characteristic angle =600) with CT ratio = 1000/1 A and PT ratio = 132 kV/110 V. The zone-1 of the relay covers 80% of
the line length whereas the zone-2 covers 150% of the line length. The first and second zone setting of the relay are
20 Ω and 10.67 Ω, respectively
11.43 Ω and 21.44 Ω, respectively
10.67 Ω and 20 Ω, respectively
26 Ω and 10.67 Ω, respectively
No, the answer is incorrect.
Score: 0
Accepted Answers:
11.43 Ω and 21.44 Ω, respectively
2 points
3. A transmission line is feed from local end A and remote end B. The impedance of the whole transmission line is 5 + j20 Ω. The
fault occurs at a point F on the line and the impedance from the relaying point A to the fault point F, i.e., Z AF = 2.5 + j10 Ω. The fault
resistance (RF) is15 Ω. The fault current contribution from bus A to the fault, i.e. 200∟76.36°. The contribution of fault current
from bus B to the fault, i.e., 300∟-84.29°. Determine the apparent impedance seen by the relay at A.
20.16∟49.74°
10.16∟29.74°
20.16∟29.74°
20.16∟19.74°
Yes, the answer is correct.
Score: 2
Accepted Answers:
20.16∟29.74°
2 points
4. Which of the following relay have less tendency of undesired operation during the power swing condition?
impedance relay
reactance relay
mho relay
quadrilateral relay
Yes, the answer is correct.
Score: 2
Accepted Answers:
quadrilateral relay
2 points
5. Which of the following relay characteristic has the higher loadability limit?
impedance relay
reactance relay
mho relay
quadrilateral relay
Yes, the answer is correct.
Score: 2
Accepted Answers:
quadrilateral relay
2 points
6. Pilot protection provide which of the following advantage
simultaneous tripping at both ends of line
low cost protection as compared to conventional protection scheme
instantaneous tripping at both ends of line
none of the above
Yes, the answer is correct.
Score: 2
Accepted Answers:
simultaneous tripping at both ends of line
1 point
7. A carrier signal used for protection can also be utilized for
telemetering
supervisory control
communication
all of the above
No, the answer is incorrect.
Score: 0
Accepted Answers:
all of the above
1 point
8. The advantage of fibre optics communication is
high bandwidth
low cost
ease to install and maintain
none of the above
No, the answer is incorrect.
Score: 0
Accepted Answers:
high bandwidth
1 point
9. The frequency of carrier signal transmitted through a microwave channel is in the range of
0.3-3 kHz
0.3-3 GHz
0.3-3 MHz
none of the above
Yes, the answer is correct.
Score: 1
Accepted Answers:
0.3-3 GHz
1 point
10. Wire pilot relaying scheme is used for the protection of
long transmission line
medium transmission line
short transmission line
all of the above
Yes, the answer is correct.
Score: 1
Accepted Answers:
short transmission line