FusionModule800 Smart Small Data Center V100R001 Product Description (Latin America)

The document provides a detailed description of the FusionModule800 Smart Small Data Center, including its application scenarios, configurations, and system architecture. It is designed for small data center solutions in various sectors such as government and finance, featuring integration, safety, reliability, and energy conservation. The document is intended for sales and technical support engineers and includes information on product specifications and installation guidelines.

Uploaded by

kam.luisgallo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
3 views94 pages

FusionModule800 Smart Small Data Center V100R001 Product Description (Latin America)

The document provides a detailed description of the FusionModule800 Smart Small Data Center, including its application scenarios, configurations, and system architecture. It is designed for small data center solutions in various sectors such as government and finance, featuring integration, safety, reliability, and energy conservation. The document is intended for sales and technical support engineers and includes information on product specifications and installation guidelines.

Uploaded by

kam.luisgallo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 94

FusionModule800 Smart Small Data Center

V100R001
Product Description (Latin
America)

Issue 06

Date 2020-03-20

HUAWEI TECHNOLOGIES CO., LTD.


Copyright © Huawei Technologies Co., Ltd. 2020. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.

Trademarks and Permissions

and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.

Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees or
representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.

Huawei Technologies Co., Ltd.


Address: Huawei Industrial Base
Bantian, Longgang
Shenzhen 518129
People's Republic of China

Website: https://e.huawei.com

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. i


FusionModule800 Smart Small Data Center
Product Description (Latin America) About This Document

About This Document

Purpose
This document describes the FusionModule800 Smart Small Data Center (smart module for
short) as well as its typical application scenarios, typical configurations, and system
architecture.
The matching ECC800 version is ECC800 V100R002C10.

Intended Audience
This document is intended for:
 Sales engineers
 Technical support engineer
 System engineer

Symbol Conventions
The symbols that may be found in this document are defined as follows.

Symbol Description
Indicates a hazard with a high level of risk which, if not
avoided, will result in death or serious injury.
Indicates a hazard with a medium level of risk which, if not
avoided, could result in death or serious injury.
Indicates a hazard with a low level of risk which, if not
avoided, could result in minor or moderate injury.
Indicates a potentially hazardous situation which, if not
avoided, could result in equipment damage, data loss,
performance deterioration, or unanticipated results.
NOTICE is used to address practices not related to personal
injury.
Supplements the important information in the main text.
NOTE is used to address information not related to personal

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. ii


FusionModule800 Smart Small Data Center
Product Description (Latin America) About This Document

Symbol Description
injury, equipment damage, and environment deterioration.

Change History
Changes between document issues are cumulative. The latest document issue contains all
updates made in previous issues.

Issue 06 (2020-03-20)
Optimized the WiFi Module section.

Issue 05 (2019-03-10)
Updated the manual name and so on.

Issue 04 (2018-09-26)
Deleted the hot aisle containment scenario.
Deleted the configuration of the 800 mm wide network cabinet.
Deleted the Converged Cabinet scenario (1) section of the power supply and distribution
system.

Issue 03 (2018-08-30)
Added VCN540 and changed VCN500 to VCN.
Changed CIM to iBOX and BIM to iBAT.

Issue 02 (2018-06-15)
Added typical configuration scenario 3.

Issue 01 (2017-09-25)
This issue is the first official release.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. iii


FusionModule800 Smart Small Data Center
Product Description (Latin America) Contents

Contents

About This Document .................................................................................................................... ii


1 Overview......................................................................................................................................... 1
1.1 Positioning .................................................................................................................................................................... 1
1.2 Features ......................................................................................................................................................................... 3

2 Typical Application Scenarios and Configurations ............................................................... 6


2.1 Typical Application Scenarios ...................................................................................................................................... 6
2.2 Typical Configuration for a Single-Row Cold Aisle Containment ............................................................................... 7

3 System Architecture ...................................................................................................................... 8


3.1 Structure System ........................................................................................................................................................... 8
3.1.1 Cabinet ....................................................................................................................................................................... 8
3.1.2 Converged Cabinet .................................................................................................................................................. 12
3.1.3 Components of the Single-Row Aisle Containment ................................................................................................ 13
3.2 Power Supply and Distribution System ...................................................................................................................... 17
3.2.1 Overview ................................................................................................................................................................. 22
3.2.2 Power Distribution Module ..................................................................................................................................... 23
3.2.3 UPS .......................................................................................................................................................................... 27
3.2.4 Transformer ............................................................................................................................................................. 29
3.2.5 Battery Cabinet ........................................................................................................................................................ 30
3.2.6 PDU2000 ................................................................................................................................................................. 31
3.3 Cooling System ........................................................................................................................................................... 32
3.3.1 Features .................................................................................................................................................................... 32
3.3.2 Product Composition ............................................................................................................................................... 34
3.3.2.1 Indoor Unit............................................................................................................................................................ 34
3.3.2.2 Outdoor Unit ......................................................................................................................................................... 36
3.3.3 Smart Cooling Product Control Unit ....................................................................................................................... 37
3.3.4 Application Conditions ............................................................................................................................................ 37
3.3.5 Technical Specifications .......................................................................................................................................... 39
3.3.6 (Optional) Emergency Fan Assembly ...................................................................................................................... 41
3.4 Monitoring System ..................................................................................................................................................... 42
3.4.1 Overview ................................................................................................................................................................. 42
3.4.2 ECC800 Core Controller ......................................................................................................................................... 44
3.4.3 AI/DI module ........................................................................................................................................................... 47

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. iv


FusionModule800 Smart Small Data Center
Product Description (Latin America) Contents

3.4.4 Smart ETH Gateway ................................................................................................................................................ 48


3.4.5 Intelligent Battery Monitoring System .................................................................................................................... 50
3.4.5.1 iBOX..................................................................................................................................................................... 51
3.4.5.2 iBAT...................................................................................................................................................................... 61
3.4.6 (Optional) Video System.......................................................................................................................................... 63
3.4.6.1 Network Camera ................................................................................................................................................... 63
3.4.6.2 VCN500 ................................................................................................................................................................ 64
3.4.6.3 VCN540 ................................................................................................................................................................ 65
3.4.7 Water Sensor ............................................................................................................................................................ 66
3.4.8 (Optional) Access System ........................................................................................................................................ 68
3.4.8.1 Access Actuator .................................................................................................................................................... 68
3.4.8.2 Room-Level Access Control ................................................................................................................................. 71
3.4.9 Smoke Detector ....................................................................................................................................................... 77
3.4.10 WiFi Module .......................................................................................................................................................... 78
3.4.11 PAD ........................................................................................................................................................................ 79
3.5 Surge Protection and Grounding System .................................................................................................................... 80
3.5.1 Surge Protection Solution ........................................................................................................................................ 80
3.5.2 Grounding Solution ................................................................................................................................................. 81
3.6 Fire Extinguishing System .......................................................................................................................................... 82
3.7 Integrated Cabling System .......................................................................................................................................... 82
3.7.1 Integrated Cabling ................................................................................................................................................... 82
3.7.2 Cables ...................................................................................................................................................................... 83

4 Technical Specifications ............................................................................................................ 84


A Equipment Derating Coefficients ........................................................................................... 86
B Acronyms and Abbreviations .................................................................................................. 87

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. v


FusionModule800 Smart Small Data Center
Product Description (Latin America) 1 Overview

1 Overview

1.1 Positioning
The FusionModule800 is a small-sized data center solution applied to air cooled scenarios
where the equipment room area is less than 30 m2. This solution mainly applies to city-,
district-, and county-level data centers of the government vertical industry, small-sized
second-level branches and large-sized offices in the financial industry, and equipment rooms
of small- and medium-sized enterprises. The following figure shows the position of the
FusionModule800 in its product family.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 1


FusionModule800 Smart Small Data Center
Product Description (Latin America) 1 Overview

Figure 1-1 Position of the FusionModule800 in the financial industry

(1) FusionModule5000 (2) FusionModule2000


(3) FusionModule800 (4) FusionModule500

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 2


FusionModule800 Smart Small Data Center
Product Description (Latin America) 1 Overview

Figure 1-2 Position of the FusionModule800 in the government vertical industry

(1) FusionModule5000 (2) FusionModule2000


(3) FusionModule800 (4) FusionModule500

1.2 Features
The FusionModule800 features integration, safety, reliability, small footprint, energy
conservation, easy and quick installation, compatible structure, rapid and flexible deployment,
and comprehensive monitoring. The FusionModule800 represents a new-generation smart
module data center.

Integration
 The smart module integrates the cabinets, power supply and distribution system, smart
cooling products, monitoring system, surge protection and grounding system, fire
extinguishing system, and integrated cabling system to provide a comprehensive
solution.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 3


FusionModule800 Smart Small Data Center
Product Description (Latin America) 1 Overview

 The Converged Cabinet integrates the power distribution, uninterruptible power system
(UPS) power distribution, smart cooling product, and monitoring system.

Security and Reliability


 Single power input is used.
 Each UPS is configured with a manual maintenance bypass switch. When the smart
module is working properly, the switch is turned off to prevent electrical accidents
caused by misoperations.
 UPSs work in N+1 redundancy mode to improve the system reliability.
 Strong-current and weak-current cables are separately routed to minimize the
electromagnetic interference.

Small Footprint and Energy Conservation


 The equipment room can be renovated from an office building room.
 The smart module can be directly installed on a concrete floor in a building, which
simplifies external engineering.
 Equipment room area ≤ 30 m2.
 The smart module features a short delivery period and quick installation. It takes five
person-days at most to complete the installation and commissioning (of the typical 7.5
kW/R3 module scenario), which is really time efficient.

Easy and Quick Installation


 Standard solutions and engineering designs are adopted.
 The prefabricated 250 mm aisle containment saves both space and time.
 The rack-mounted smart cooling product indoor units are prefabricated, facilitating the
redundancy.

Architecture Compatibility
 T1 environments are supported.
 Modular power distribution and smart cooling products facilitate flexible expansion.
 Cold aisle containments are supported and noise is low.
 If PUE is enabled on the monitoring page, the PUE value will not be displayed.

Fast and Flexible Deployment


 The integrated design supports the relocation of primary equipment with offices.
 Flexible deployment based on the dimensions of the equipment room and the power
consumption of each cabinet is supported to meet the requirements of capacity
expansion.
 IT cabinets are flexibly configured with servers and storage and network devices to meet
enterprise requirements for web application and internal services and provide users with
more space.

Comprehensive Monitoring
 Various sensors monitor the functional modules in the equipment room in real time.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 4


FusionModule800 Smart Small Data Center
Product Description (Latin America) 1 Overview

 The smart module provides a module-level pad to easily manage the functional modules
locally.
 A maximum of four smart module cameras and in-room cameras can be monitored.
(Smart module cameras are installed in the smart module and the in-room cameras are
installed in the room.)
 In-room access controllers can be monitored.
 ECC800s in two smart modules can be cascaded.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 5


FusionModule800 Smart Small Data Center
Product Description (Latin America) 2 Typical Application Scenarios and Configurations

2 Typical Application Scenarios and


Configurations

2.1 Typical Application Scenarios


This product is mainly applied in government, education, medical, traffic, energy, and
financial organizations, small- and medium-sized enterprises, and branches of large
enterprises. It is primarily sold in Latin American regions that support 208 V, 3-phase, 60 Hz
power systems.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 6


FusionModule800 Smart Small Data Center
Product Description (Latin America) 2 Typical Application Scenarios and Configurations

2.2 Typical Configuration for a Single-Row Cold Aisle


Containment
Figure 2-1 Single-row cold aisle containment

Figure 2-2 Layout of a single-row cold aisle containment

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 7


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

3 System Architecture

3.1 Structure System


3.1.1 Cabinet
Cabinets are categorized into the IT cabinet, battery cabinet, Converged Cabinet, and network
cabinet.
Cabinets used in the data center comply with the International Electrotechnical Commission
(IEC) 60297-1 standard and provide stable installation space for servers, thereby ensuring the
safe operation of servers.
Cabinets are of uniform dimensions and provide front and rear ventilation channels.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 8


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Figure 3-1 Cabinet

The cabinets provide the following features:


 The ventilation rate of the cabinet perforated door is at least 70%.
 Two PDU2000s can be vertically installed at the rear of each cabinet.
 The position of each U is marked on the vertical mounting bars.
 The front and rear doors are locked and can be unlocked only with dedicated keys.
 The cabinets can be installed on bases.

Table 3-1 Cabinet technical specifications

Item Technical Specifications


Dimensions (H x W x D)  IT cabinet: 2000 mm x 600 mm x 1350 mm
 Converged Cabinet: 2000 mm x 600 mm x 1350 mm
 Battery cabinet (deployed inside the aisle
containment): 2000 mm x 600 mm x 1350 mm
 Battery cabinet (deployed outside the aisle
containment): 2000 mm x 600 mm x 1100 mm/1200
mm
 Network cabinet: 2000 mm x 600 mm x 1350 mm

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 9


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Item Technical Specifications


Color Black
Material High-intensity class A carbon cold rolled steel plate and
zinc-coated steel plate
Ventilation channel Front and rear ventilation channels
Space for installing the IT  Each cabinet provides 42 U available space.
cabinet and network cabinet  The distance between the front and rear mounting bars
can be adjusted by the step of 25 mm.
 The maximum depth for installing devices inside the
cabinet is 700 mm and can be extended to 750 mm by
adjusting the mounting bars.
 Positions for vertically installing two PDU2000s are
provided at the rear of the cabinet.
Installation mode Installed on a concrete or raised floor
Static load 1500 kg
Dynamic load 1000 kg
Protection level IP20

Cabinets and contained aisles are assembled for delivery. The cabinet depth is 1350 mm.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 10


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Figure 3-2 Mounting hole positions at the cabinet bottom

Table 3-2 Technical specifications of mounting holes at the cabinet bottom

Cabinet Model Mounting Hole (L x W)


2000 mm x 600 mm x 1350 mm 980 mm x 400 mm
2000 mm x 800 mm x 1350 mm 980 mm x 600 mm

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 11


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Figure 3-3 Method of adjusting a mounting bar

3.1.2 Converged Cabinet


The Converged Cabinet consists of the input and output power distribution module,
monitoring module, UPS, transformer, rack-mounted smart cooling product, and smart
cooling product power distribution control unit.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 12


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Figure 3-4 Converged Cabinet

3.1.3 Components of the Single-Row Aisle Containment


Overview
Components of the single-row aisle containment include the sealing frame, door assembly,
and binding plate or M-shaped cable trough.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 13


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Figure 3-5 Single-row cold aisle containment

(1) IT cabinet (2) Sealing frame (3) Converged Cabinet


(4) Camera mounting bracket (5) Emergency fan assembly (6) Binding plate

Sealing Frame
The sealing frame applies to the 250 mm single-row aisle containment. It has two adjustable
feet at the bottom for adjusting its height. There are 600 mm and 800 mm wide sealing frames
which apply to 600 mm and 800 mm wide cabinets respectively. Different steel plates can be
installed on the two sides of the aisle based on the cabinet position to meet the requirements
of sealing cold aisles.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 14


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Figure 3-6 Exterior of a sealing frame

Table 3-3 Technical specifications of a sealing frame

Model Specifications (H x W x D)

600 mm wide sealing frame 2000 mm x 600 mm x 250 mm


800 mm wide sealing frame 2000 mm x 800 mm x 250 mm

Door
For the cold aisle containment, a single-swing tempered sealing door is configured in the front,
and double sheet metal perforated doors are configured in the rear.
The door assembly is configured with a mechanical lock by default.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 15


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Figure 3-7 Tempered sealing door

Cable Trough (Optional)


Signal cables and power cables are routed in different cable troughs to isolate strong-current
cables and weak-current cables.
Cable troughs are clamped one by one to form a whole. A cable trough is assembled by
clamping two side panels, one pallet, and one baffle (used to separate weak-current optical
fibers from weak-current network cables and strong-current route A from strong-current route
B).

Figure 3-8 Cable trough

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 16


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

3.2 Power Supply and Distribution System


The Converged Cabinet integrates the rack-mounted UPS, power distribution module,
transformer, smart cooling product indoor unit, and ECC800, and supports single power
supply.
 The Converged Cabinet integrates the UPS input and output, IT load, smart cooling
product power distribution, and monitoring system power distribution, and supports
single power supply.
 The power distribution module, which is rack-mounted, includes the surge protective
device (SPD), UPS input, output, and maintenance bypass as well as the power supply to
IT loads and smart cooling products.
 N and N+1 UPS systems are supported, and 10 kVA and 20 kVA UPSs can be selected to
adapt to the actual load power. The power distribution module for IT loads can power a
maximum of six IT cabinets.
 The air cooled smart cooling product consists of the indoor unit and outdoor unit and is
supplied with mains power.
 The monitoring system consists of the ECC800, video cloud node 500 (VCN500),
camera, door status sensor, temperature sensor, temperature and humidity sensor (T/H
sensor), smoke detector, iBOX (CIM), and water sensor. They are powered by the power
supply and distribution system.
 The power supply and distribution system powers the battery cabinet that houses the
battery tray, battery input switch, and intelligent battery monitoring system including the
iBAT (BIM) and iBOX (CIM) and is compatible with 26 Ah, 40 Ah, 65 Ah, and 100 Ah
batteries.
 The iBattery (optional) can be used for battery management.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 17


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Figure 3-9 Typical configuration scenario 1

(1) Indicator module (2) 3 U power distribution unit (3) 6 U power distribution unit
(4) 10 kVA (5) Transformer (6) ECC800
UPS2000-G
(7) Filler panel (8) Smart cooling product (9) Smart cooling product
control unit indoor unit

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 18


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Figure 3-10 Typical configuration scenario 2

(1) Indicator module (2) 3 U power distribution unit (3) 6 U power distribution unit
(4) 10 kVA (5) Transformer (6) Filler panel
UPS2000-G
(7) ECC800 (8) Smart cooling product (9) Smart cooling product
control unit indoor unit

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 19


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Figure 3-11 Typical configuration scenario 3

(1) Indicator module (2) 3 U power distribution unit (3) 6 U power distribution unit
(4) 20 kVA (5) Transformer (6) Filler panel
UPS2000-G
(7) ECC800 (8) Smart cooling product (9) Smart cooling product
control unit indoor unit

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 20


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Figure 3-12 Typical configuration scenario 4

The third smart cooling product and smart cooling product control unit need to be installed onsite.

(1) Indicator module (2) 3 U power distribution (3) 6 U power distribution


unit unit
(4) 20 kVA UPS2000-G (5) Transformer (6) ECC800
(7) Smart cooling product (8) Smart cooling product (9) Filler panel
control unit indoor unit

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 21


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

3.2.1 Overview
Conceptual Diagram for the N Power Distribution System

Figure 3-13 Conceptual diagram for the N power distribution system

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 22


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Conceptual Diagram for the N+1 Power Distribution System

Figure 3-14 Conceptual diagram for the N+1 power distribution system

 The 10 kVA UPSs in a parallel system cannot share battery strings or battery packs.
 The 20 kVA UPSs in a parallel system can share battery strings or battery packs.

3.2.2 Power Distribution Module


Table 3-4 Power distribution module specifications

Item Power Power Distribution Power Indicator Module


Distribution Module 2 Distribution
Module 1 Module 3
System IT load output This power This power It is a three-phase power
parameters module with eight distribution module is distribution indicator and works with
208 V outputs and used in the scenario in module is used in the power distribution
eight 120 V outputs. which a single input is the scenario in module when there is only
The external ports of provided, the IT load which a single one input.
the module are all power is less than or input is provided,
connected by using a equal to 7.5 kW, UPS the IT load power

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 23


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Item Power Power Distribution Power Indicator Module


Distribution Module 2 Distribution
Module 1 Module 3
terminal block. The N/N+1 architecture is is greater than or
module can be supported, and a equal to 7.5 kW
operated from the maximum of two 10 and less than or
front and maintained kVA UPSs and two equal to 15 kW,
from the front and smart cooling UPS N/N+1
rear. products are architecture is
configured. This supported, and a
module can be maximum of two
operated from the 20 kVA UPSs and
front and maintained three smart
from the rear and cooling products
front. (can be two smart
cooling products
with heating and
humidification and
one cooling only
smart cooling
product) are
configured. The
module can be
operated from the
front and
maintained from
the front and rear.
Dimension 130 mm x 442 mm x 263 mm x 442 mm x 263 mm x 442 mm 43.6 mm x 442 mm x
s (H x W x 450 mm 450 mm x 450 mm 44.5 mm
D)
General 125 A power 125 A M8 input 180 A M8 input -
input terminal copper bar copper bar
208 V IT 8 x C40A/2P MCB - - -
power
distribution
120 V IT 8 x C40A/1P MCB - - -
power
distribution
UPS input - 2 x D63A/2P MCB 2 x D125A/2P -
MCB
UPS output - 2 x C63A/2P MCB 2 x C125A/2P -
MCB
UPS - 1 x C63A/2P MCB 1 x C125A/2P -
bypass MCB
Power - 1 x C63A/2P MCB 1 x C63A/2P -
distribution MCB
for
transforme

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 24


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Item Power Power Distribution Power Indicator Module


Distribution Module 2 Distribution
Module 1 Module 3
rs
Power - 3 x C40A/2P MCB 3 x C40A/2P -
distribution MCB
for smart
cooling
products
Power - 1 x C16A/2P MCB 1 x C16A/2P -
distribution MCB
for
monitoring
devices
SPD - 1 x C32A/4P MCB 1 x C32A/4P -
switch MCB

10 kVA and 20 kVA UPS power distribution modules use UPS N+1 architecture by default. If
only one UPS is configured, the N architecture is supported.

Figure 3-15 Power distribution module 1

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 25


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Figure 3-16 Power distribution module 2

Figure 3-17 Power distribution module 3

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 26


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Figure 3-18 Indicator module

Table 3-5 Power distribution specifications

Item Specifications
Rated operating 208 V AC
voltage
Rated insulation 440 V
voltage
Rated frequency 50 Hz/60 Hz
Operating current < 200 A
Surge protection Level C SPD
level
Cable routing Routed in and out from the top or bottom

3.2.3 UPS
The UPS2000-G works under the 208 V power system and features adequate protection, high
reliability, intelligent operation, flexible expansion, high energy efficiency, and environmental
protection.

Figure 3-19 UPS2000-G

Table 3-6 UPS2000-G specifications

Category Item 10 kVA 20 kVA

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 27


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Category Item 10 kVA 20 kVA


Input Input voltage range 80–280 V AC, dual-live wire 80–280 V AC, dual-live wire
(When the voltage is 80–176 V (When the voltage is 80–176 V
AC, the load power is linearly AC, the load power is linearly
derated to 40%–100%.) derated to 40%–100%.)
Input power factor > 0.99, single-phase input > 0.99
(100% load) > 0.95, three-phase input
Rated input voltage 208 V AC dual-live wire
Input frequency 40–70 Hz
range
Output Rated capacity 10 kVA 20 kVA
Rated voltage 208 V AC dual-live wire
Power factor 0.9
Derating coefficient 0.9
Total harmonic < 4% (non-linear load)
distortion of output
voltage (THDv) < 2% (resistive load)

Output voltage ±1%


precision
Dynamic voltage ±5%
transient
Crest factor A maximum of 3:1
Overload capability  In normal mode, when the UPS is overloaded to a range between
105% and 125%, the UPS transfers to bypass mode in 5 min if
the bypass mode is normal, or disconnects the power output if the
bypass mode is abnormal.
 In normal mode, when the UPS is overloaded to a range between
125% and 150%, the UPS transfers to bypass mode in 1 min if
the bypass mode is normal, or disconnects the power output if the
bypass mode is abnormal.
 In normal mode, when the UPS is overloaded to more than 150%
(150% included), the UPS transfers to the bypass mode in 0.1s if
the bypass mode is normal, or disconnects the power output if the
bypass mode is abnormal.
Structure Dimensions (H x W 430 mm x 86 mm x 615 mm 430 mm x 130 mm x 757 mm
x D)
Installation mode Rack-mounted
Surge protection IEC/EN60240-2
IEC/EN61000-4-5
YD/T1095-2000 YD/T944-2007
The AC input side meets class D surge protection (differential mode

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 28


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Category Item 10 kVA 20 kVA


and common mode: 5 kA, 8/20 μs).
Environment Operating 0–40°C
temperature
Relative humidity 0%–95% RH (non-condensing)
Maximum altitude < 1000 m (For 1000–4000 m, refer to the derating data of
IEC62040-3.)
Storage and –40°C to +70°C (battery pack: –20°C to +40°C)
transportation
temperatures

3.2.4 Transformer
Figure 3-20 Transformer appearance

Table 3-7 Transformer technical specifications

Item Specifications

Rated capacity 10 kVA


Rated input current 48 A
Rated input voltage Dual-live wire 208 V
input frequency 60 Hz
Output voltage Single-phase 120 V
Output frequency 60 Hz
Efficiency (full load) 96%

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 29


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Item Specifications
Dimensions (H x W x D) 430 mm x 650 mm x 130 mm
Weight 65 kg

3.2.5 Battery Cabinet


A battery cabinet provides space for installing batteries and routing battery cables. The battery
cabinet can be deployed inside or outside the Smart Module. A maximum of two battery
cabinets are allowed when deployed inside the Smart Module.
Battery cabinets are classified into main battery cabinets and auxiliary battery cabinets.
Conversion copper bars are required for the input and output circuit breakers in the main
battery cabinet.
Required battery backup time: 15 min or 30 min

Table 3-8 Battery cabinet technical specifications

Item Specifications
Dimensions (H x W x D)  Deployed inside: 2000 mm x 600 mm x 1350 mm
 Deployed outside: 2000 mm x 600 mm x 1100 mm/1200
mm
Color Black
Material High-intensity class A carbon cold rolled steel sheets and
zinc-coated steel sheets
Ventilation channel Front and rear ventilation channels
Installation space A space of 42 U is available
Installation mode Installed on a concrete floor or ESD floor
Weight (excluding  Deployed inside: 160 kg
batteries)  Deployed outside: 140 kg
Static load 1500 kg
Dynamic load 1000 kg
Protection level IP20

Table 3-9 Battery specifications

Battery Battery Vendor Battery Battery Dimensions (H x W Number of Batteries


Capacity and Model Weight x D) in One Battery
Cabinet

26 Ah Shoto 6-GFM-26 10.0 kg 172 mm x 125 mm x 165 mm 40

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 30


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Battery Battery Vendor Battery Battery Dimensions (H x W Number of Batteries


Capacity and Model Weight x D) in One Battery
Cabinet

Enersys NP24-12 9.1 kg 125 mm x 175 mm x 166 mm


40 Ah Shoto 6-GFM-26 14.0 kg 172 mm x 165 mm x 197 mm
Enersys NP38-12 14.6 kg 172 mm x 165 mm x 197 mm
65 Ah Shoto 6-GFM-65 22.0 kg 214 mm x 168 mm x 258 mm 20
Enersys NP65-12 23.6 kg 174 mm x 166 mm x 350 mm
100 Ah Shoto 6-GFM-100 30.0 kg 222 mm x 174 mm x 330 mm
Enersys NP100-12 32.9 kg 214 mm x 174 mm x 329 mm

Figure 3-21 Battery pack

Table 3-10 Battery pack specifications

Battery Pack Dimensions (L x W x H) Weight


Specifications
9 Ah 685 mm x 430 mm x 130 mm 69 kg

3.2.6 PDU2000

Figures provided in this document are for reference only.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 31


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Figure 3-22 Vertical PDU2000

Figure 3-23 Horizontal PDU2000

Table 3-11 PDU2000 specifications

Item Specifications
Input current 16 A 32 A 40 A
Input voltage 100 V AC-240 V AC
range
Input wiring Ph + N + PE/2Ph + PE Ph + N + PE 2Ph + PE
Output power 120V: 8 x C13 or 120V: 20 x C13 + 4 x 208V: 20 x C13 + 4 x
distribution 208V: 8 x C13 C19 C19
specifications
Install type Horizontal Vertical Vertical
Dimensions 484 mm x 44.5 mm x 1865 mm x 55 mm x 1865 mm x 55 mm x
(L x W x D) 44.5 mm 44.5 mm 44.5 mm
Net weight 1.6 kg 2.49 kg 2.49 kg

3.3 Cooling System


3.3.1 Features
The NetCol5000-A features high energy efficiency, high reliability, high compatibility,
multiple power systems, intelligent monitoring, and easy installation and maintenance.

High Energy Efficiency


 The name-brand efficient DC variable-frequency compressor allows the cooling capacity
of a normal-temperature smart cooling product to be adjusted steplessly in a range of
20% to 100%. This ensures that cooling capacity is delivered as required, greatly
reducing energy consumption.
− Six EC fans that use the horizontal air supply mode achieve in-cabinet cooling and
support 20%–100% stepless speed adjustment. Precise control can be implemented

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 32


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

over the supply air temperature and direction, thereby reducing energy
consumption.
 Optimal system configurations and efficient refrigeration coil pipes ensure efficient heat
exchange.
 The variable-frequency temperature control algorithm enables quick response to load
changes and precise temperature control to conserve energy. The variable-frequency
smart cooling product consumes 30% less energy when compared with a
constant-frequency one.
 Fans support variable-frequency start, which lowers the start current and prevents shock
on the power grid and other equipment connecting to the power grid.
 A wet film humidifier consumes at least 90% less energy when compared with a
conventional humidifier because energy consumption of a wet film humidifier comes
only from the water pump.
 The smart cooling products are connected over the FE port and networked through the
MAC protocol bus to achieve teamwork control, which effectively saves energy.

High Reliability
 The DC variable-frequency smart cooling product greatly reduces the number of startup
and shutdown times, reducing component failures and extending the lifespan of key
components.
 The electronic expansion valve is used, allowing rapid and precise adjustment of the
refrigerant volume based on the temperature and humidity requirements and improving
system stability. A backup power module is provided to close the electronic expansion
valve when the system experiences a power failure.
 The Positive Temperature Coefficient (PTC) electric heater provides dual protection
functions: automatic reset and auto-recovery disabling.
 The smart cooling product provides the dehumidification function to maintain the
humidity in cold aisles in the range of 20%–80% at low loads (10% load at least) in a
high humidity environment.
 The smart cooling product features 6 kV surge protection design, providing high surge
protection reliability.

High Compatibility
 The smart cooling product can be rack-mounted, significantly reducing the footprint
required for the cooling system. Only 11 U height space in the Converged Cabinet is
occupied.
 Both the refrigerant pipes and water pipes can be routed from the top or bottom.
 Heating and humidification functions are optional.

Multiple Power Systems


The smart cooling product is compatible with the 208–240 V AC, 2PH+PE, and 50 Hz/60 Hz
power systems. It supports a voltage range of 187–264 V AC and a frequency range of 47–53
Hz or 57–63 Hz, which enables the smart cooling product to be applied in various countries
and regions.

Intelligent Monitoring
 Users can monitor and configure parameters for the cooling system on the monitoring
unit.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 33


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

 T/H sensors are cascaded using RJ12 ports, connected to the smart cooling product
control unit, and detect temperature and humidity in real time over Modbus.

Easy Installation and Maintenance


 The smart cooling product can be easily inserted into a cabinet, facilitating installation.
 Sealing stop valves are reserved for the end faces of the indoor and outdoor units. The
welding-free design achieves fast maintenance and requires no open flame.
 The outdoor unit is delivered with refrigerant for 30 m long pipes. The prefilled
refrigerant oil can be used for 60 m long pipes.
 Remote parameter setting and remote inspection are supported, reducing service costs.
 Key components support front and rear maintenance. The entire smart cooling product
can be easily replaced without extra maintenance space. During the maintenance and
replacement of a smart cooling product, other smart cooling products are not affected.
 The control unit adopts drawer-type maintenance. The power module, auxiliary module,
and main control module embedded in the control unit can be quickly removed and
inserted for maintenance, greatly reducing O&M time and difficulty.

3.3.2 Product Composition


3.3.2.1 Indoor Unit

Exterior

Figure 3-24 Indoor unit

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 34


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Components
The indoor unit consists of the EC(Electronic Commutation) fan, evaporator, electronic
expansion valve, electric heater (optional), wet film humidifier (optional), light load
dehumidifier, and condensate pump.
 EC fan
EC fans that support stepless speed adjustment are used, reducing energy consumption of
loads in overtemperature scenarios.
 Evaporator
The highly efficient V-shaped evaporator together with the light load dehumidification
design are used. After entering the light load dehumidification mode, the smart cooling
product automatically closes the dehumidification solenoid valve to lower the
evaporating temperature and increase the dehumidification capacity. This mode
addresses the requirements for effectively controlling the equipment room temperature
and humidity in low load and high humidity application scenarios.
 Electronic expansion valve
The throttling equipment is a name brand electronic expansion valve. The system
controls the electronic expansion valve to quickly and accurately adjust the refrigerant
volume based on the temperature and humidity requirements. In this way, system
stability and reliability can be ensured, and balanced temperature and humidity can be
achieved in the equipment room.
 Electric heater
The PTC electric heater features quick start, large heating capacity, and balanced heat
dissipation. It automatically adjusts heating capacity and provides two protection
mechanisms to ensure the secure and stable running of the equipment.
 Wet film humidifier
The wet film evaporation cooling technology is used for cooling to reduce energy
consumption and maintenance costs. Cyclic humidification can save water.
 Light load dehumidifier
The smart cooling product provides the dehumidification function to maintain the
humidity in cold aisles in the range of 20%–80% at low loads (10% load at least) in a
high humidity environment.
 Condensate pump
The condensate pump uses materials with high temperature resistance to ensure that
condensate water can be drained smoothly in various application scenarios. The water
pump has a lift of 4 meters and uses double liquid level detectors, providing high
reliability. Alarms indicating abnormal water drainage can be uploaded to the monitoring
unit, and audible and visual alarms can be generated.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 35


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

3.3.2.2 Outdoor Unit

Exterior

Figure 3-25 Exterior of the outdoor unit of a normal-temperature model

Components
The outdoor unit consists of the DC variable-frequency compressor, oil separator,
vapor-liquid separator, filter dryer, and DC fan.
 Compressor
DC variable-frequency compressors which provide 20%–100% stepless cooling capacity
adjustments for common–temperature models respectively.
 Oil separator
Separates the lubricant brought out due to exhaustion of the compressor and brings back
the separated lubricant to the compressor.
 Gas-liquid separator
A vapor-liquid separator is installed at the upper end of a compressor to ensure the
compressor reliability.
 Filter dryer
The filter dryer drains the water in the refrigerant pipes and filters out foreign matter,
which reduces the probability of damage to the components and ensures the efficient and
reliable operating. It is installed in the outdoor unit and easy to maintain.
 Fan
The DC axial fan is used, which supports stepless speed adjustment.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 36


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

3.3.3 Smart Cooling Product Control Unit


The smart cooling product control unit mainly includes the main control board. The display
unit is integrated in the Converged Cabinet. The controller implements functions such as logic
control, data collection, control signal sending, alarm reporting, data storage, and teamwork
control. The smart cooling product connects to the ECC over the FE port using the MAC
protocol, and the ECC connects to the NMS to realize remote management.

Main Functions
 Single unit control: When only one unit is running, the controller provides logic control
over components in the unit to meet the indoor temperature and humidity requirements.
 Teamwork control: When multiple smart cooling products work cooperatively, the
controller optimally distributes the heat load, greatly lowering the power consumption.
Multiple smart cooling products provide backup for higher reliability.
 Remote management: You can monitor, manage, and upgrade one or more smart cooling
products using the remote management function provided by Huawei.
 Configuration synchronization: You can synchronize parameters between smart cooling
products on the touchscreen (optional) of the Converged Cabinet, ECC800 WebUI, or
ECC800 app.
 One-click export: You can export the alarms and logs of a smart cooling product on the
ECC800 WebUI.
 Software upgrade: You can perform a remote upgrade on the touchscreen of the
Converged Cabinet, ECC800 WebUI, or ECC800 app.
 Alarm details query: You can view the possible causes of alarms and handling
suggestions on the ECC800 WebUI.

Features
 The controller is highly precise and responsive.
 Automatically stores operation logs, 1500 historical alarms, and 30-day temperature and
humidity curves and displays these data on the touchscreen of the Converged Cabinet.
 Provides protection functions such as automatic recovery after power failure and
shutdown for protection in the case of abnormal drainage, improving the system
reliability.
 Displays the following information on the touchscreen of the Converged Cabinet in real
time: operating status of the smart cooling product components and the corresponding
time points.
 Provides RS485 and FE ports that support the MAC-Modbus protocol.
 Uses FE ports for teamwork control networking using the MAC protocol, offering a
higher transmission rate.

3.3.4 Application Conditions


Operating Environment

Table 3-12 Operating environment

Item Specifications

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 37


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Item Specifications
Indoor unit 0–45°C
operating
temperature
Indoor unit 5%–95% RH (non-condensing)
operating humidity
Outdoor unit For normal-temperature outdoor units: –20°C to +45°C
operating
temperature
Storage temperature Without refrigerant: –40°C to +70°C
With refrigerant: –40°C to +55°C
Storage humidity 5%–95% RH (non-condensing)
Application Class B (uncontrollable environment)
environment NOTE
Indoor environments in which the ambient temperature and humidity are not
controllable, or outdoor environments (with simple shielding measures)
where humidity can reach 100% occasionally.

Altitude 0–4000 m. The smart cooling product performance is derated when


the altituderanges from 1000 m to 4000 m. The maximum outdoor
operating temperature decreases by 1°C and the nominal cooling
capacity decreases by 1% for each additional 200 m.

Installation Requirements

Table 3-13 Installation requirements

Installation Mode Rack-mounted

Vertical Difference  Outdoor unit placed higher than the indoor unit: ≤ 20 m
Between the Indoor and  Indoor unit placed higher than the indoor unit: ≤ 5 m
Outdoor Units

Maximum Equivalent 60 m. If the length exceeds 60 m, contact Huawei technical


Length of One-way Pipe support.

Thermal Insulation ≥ 13 mm
Foam Thickness

Water Supply The inlet water pressure should be in the range of 0.1–0.7
Requirements MPa, and the temperature should be in the range of
1°C–40°C.
The wet film humidifier should use tap water that meets the
following requirements:
 Non-freezing and nephelometric turbidity units (NTU) <
3
 No visible substances

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 38


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

 6.5 ≤ pH value ≤ 8.5


 Total hardness (in CaCO3) ≤ 450 mg/L
For details, refer to the GB 5749-2006 Standards for
Drinking Water Quality.

Drainage Requirements The distance between the upper drainage of the water pump
and the cabinet installation floor should not exceed 4 m.
(BSPT 1/2 inch drainpipe connectors with external threads
are provided in standard configuration. Drainpipes and BSPP
1/2 inch connectors with internal threads should be prepared
by the customer.)

Ports

Table 3-14 Ports

Item Specifications
Refrigerant gas pipe Reserved port: 5/8 inch (15.9 mm); thread connection
Refrigerant liquid Reserved port: 3/8 inch (9.52 mm); thread connection
pipe
Humidifier water Reserved port: G 1/2 inch, thread connection
inlet pipe
Condensate pump Reserved port: BSPP 1/2 inch, thread connection
drainpipe
Pipe and cable Top or bottom routing
routing

3.3.5 Technical Specifications


Table 3-15 Indoor unit technical specifications

Item NetCol5000-A011 (Including NetCol5000-A011 (Excluding


Heater and Humidifier) Heater and Humidifier)

Power system 208–240 V AC, 50 Hz/60 Hz, 2PH+PE


Voltage If upstream voltage fluctuation exceeds the rated voltage±10%, you are
tolerance advised to add a voltage regulator.Otherwise, the smart cooling product
may generate alarms frequently andfail to work properly.
Frequency ±3 Hz
tolerance
Certification Normal-temperature models: REACH, RoHS, CB
Maximum 17.3 A 3.3 A

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 39


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Item NetCol5000-A011 (Including NetCol5000-A011 (Excluding


Heater and Humidifier) Heater and Humidifier)
current
Cooling mode Air cooled Air cooled
Refrigerant R410A R410A
Cooling 11 kWa 11 kWa
capacity
Humidification Yes No
function
Humidification 1.0 kg/h -
capacity
Heating Yes No
function
Heating 3 kW -
capacity
Air supply Horizontal air supply Horizontal air supply
mode
Maximum 2600 m3/h 2600 m3/h
airflow
Condensate Yes Yes
pump
Power supply Single power supply Single power supply
mode
Dimensions (H 486 mm x 442 mm x 800 mm 486 mm x 442 mm x 800 mm
x W x D)b
Package 710 mm x 610 mm x 1000 mm 710 mm x 610 mm x 1000 mm
dimensions (H
x W x D)
Net 57 kg/74 kg 54 kg/70 kg
weight/Gross
weightb
Protection IP20 IP20
level
a: The cooling capacity of thesmart cooling product is obtained when the indoor dry bulb
temperature is 37.8°C, the indoor wet bulb temperature is 20.8°C, and the outdoor dry bulb
temperature is 35°C. The actual cooling capacity varies depending on the indoor and
outdoor ambient temperatures and relative humidity.
b: The outdoor unit dimensions include the dimensions of the control unit. The net weight
and gross weight also include the weight of the control unit.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 40


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Table 3-16 Technical specifications of normal-temperature outdoor units

Item NetCol500-A018
Maximum operating current 24 A
Number of fans One
Dimensions (H x W x D) 966 mm x 1057 mm x 339 mm
Package dimensions (H x W x D) 1210 mm x 1105 mm x 435 mm
Net weight/Gross weight 83 kg/99 kg
Certification REACH, RoHS, CB
Protection level IPX4

3.3.6 (Optional) Emergency Fan Assembly


One emergency fan assembly can be on the top of the aisle containment for every cabinet.
 The fans are powered and controlled by the ECC800. The fan status detection is not
required.
 Upon detecting a power failure or a smart cooling product fault which makes the cooling
requirements unmet, theECC800 starts the fan to circulate air inside the equipment
room.This helps avoid partial hot spots.
 When the fan is installed in a cold aisle, it supplies air for the aisle.

Figure 3-26 Fan

Table 3-17 Fan specifications

Item Specifications
Operating voltage 48 V DC
Operating current 0.42 A
Power consumption 20.16 W

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 41


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Item Specifications
Speed 5300 rpm
Air volume 180 CFM
Dimensions (L x W x H) 120 mm x 120 mm x 25.4 mm

3.4 Monitoring System


3.4.1 Overview
The smart module monitoring solution consists of the collector and monitoring components.
The ECC800 functions as the collector.
The smart module provides a module-level pad for local intelligent management in terms of
real-time monitoring, status browsing, alarm management, and system configuration.
The NetEco can manage the infrastructures of a single data center or of data centers in various
areas in a centralized manner. The BIN4.0/SNMP protocol used for the northbound interface
is opened, so that the third-party NMS can be connected.
The ECC800 manages the real-time status, alarms, and configuration information about the
devices inside the smart module. It also provides a graphical user interface (GUI) for ease of
operating and maintaining devices inside the smart module.

Figure 3-27 Management system network diagram

In the figure, RF_Z represents wireless networking, and the iBAT and iBOX communicate with each
other in wireless mode.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 42


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Table 3-18 Network diagram description

Device Maximum Quantity Port


Camera 4 FE
The total number of room-level cameras
and smart module–level cameras cannot
exceed 4.
VCN 1 FE
Smart ETH gateway 3 FE
Access actuator 2 FE
One access actuator connects to at most
one magnetic lock, one access control
device, one exit button, and one
emergency door release button.
NetCol5000-A011 smart 3 FE
cooling product
CIM (iBattery system) 2 FE
UPS2000-G 2 RS485
AI/DI module 1 RS485
One AI/DI module can connect to a
maximum of eight cabinet door status
sensors.
Smoke detector 1 DI
Temperature sensor 1 DI
Water sensor 1 DI
Cabinet door status sensor 8 DI
WiFi converter 1 USB

The management system provides a GUI to implement comprehensive management functions


based on requirements. The system can monitor the following equipment:
 Power equipment: suchas the smart cooling product and UPS
 Environment equipment: such as the smoke detector and water sensor
 Video equipment: camera and VCN500. Room-level cameras and smart module-level
cameras can be monitored at the same time.
 Access control equipment: A standard room-level access management system is
integrated to manage and monitor key information such as door status, card swiping, and
permission setting.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 43


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Figure 3-28 Layout of the access control system

The access actuator should be installed near the door, have a maximum of 3.5 m cabling distance away
from the magnetic lock, and have a maximum of 5 m cabling distance away from other switches and the
access control device.

3.4.2 ECC800 Core Controller


The ECC800 is the core component for local management. It is intelligent, flexible to deploy,
easy to maintain, and reliable. It adopts the PoE bus for expansion, and allows all intelligent
monitoring devices to be flexibly laid out so that it can manage the devices.

Figure 3-29 ECC800 (front view)

(1) PSU (optional) (2) PSU (optional) (3) Status (4) 3G/4G

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 44


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

indicator antenna port


(5) FE ports (WAN_1–WAN_2 (6) AI/DI_1–6 sensor (7) RF_Z (8) SW
and LAN_1–LAN_2) input ports antenna port button
(9) DO_1–2 dry contact outputs (10) RS485 port (11) Default (12) USB
(COM1–4/12 V) button port
(13) ECC800 main control
module

Figure 3-30 ECC800 controller (rear view)

(1) 53.5V DC_OUT1 (2) 53.5V DC_OUT2 (3) AC_INPUT1


(4) AC_INPUT2

Figure 3-31 ECC800 main control module (side view)

(1) SIM card slot (2) Micro-SD card slot

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 45


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

ECC800 Specifications

Table 3-19 ECC800 environmental specifications

Item Specifications
Operating temperature –20°C to +50°C
Storage temperature –40°C to +70°C
Humidity 5%–95% RH (non-condensing)
Altitude 0-4000 m (When the altitude is between 3000 m and 4000 m,
the temperature decreases by 1°C for each additional 200 m.)

Table 3-20 ECC800 structural specifications

Item Specifications
Dimensions (H x W x D) 43.6 mm x 442 mm x 330 mm
Color Black
Installation requirements  Installed in a standard 1 U cabinet
 Installed in a 19-inch rack
Environmental protection requirements RoHS5

Table 3-21 ECC800 technical specifications

Item Specifications

Power input  Two AC inputs


 Rated operating voltage: 200–240 V AC or 100–120 V AC
 Rated operating frequency: 50/60 Hz
Power output  Output voltage: 42–58 V DC (rated voltage: 53.5 V DC)
 Output power of two power supplies: 2000 W (176–300 V AC);
940 W (linear derating at 85-175 V AC)
 Output power of a single power supply: 1000 W (176–300 V
AC); 470 W (linear derating at 85–175 V AC)
FE port expansion Supports two WAN ports and two LAN ports with the 10/100M
communications rate.
RS485 serial port  Four RS485 ports with the default communications rate of 9600
expansion bit/s
 Each port provides 12 V DC power with the rated current of 450
mA.
AI/DI expansion  Supports six AI/DI ports to connect to sensors such as smoke,
(RJ45) water, and temperature sensors.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 46


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Item Specifications
 Each port provides 12 V DC power with the rated current of 85
mA.
DO expansion Two DO ports both supporting active and passive DO
(RJ45)  Supports passive (dry contact) DO port with contact point
capacity of 20 W, maximum withstand voltage of 60 V DC, and
rated current of 500 mA.
 Supports the active DO port with an output voltage of 12 V DC
and output current of 450 mA.
Wireless Wireless communication that complies with IEEE802.15.4
communication
3G (optional) Supports 3G (WCDMA) communication and is compatible with 2G
(GSM) communication. A standard SIM card slot is provided.
NOTE
The prerequisite for using a SIM card is that the site has signal coverage.

USB  After installing the WiFi module, connect the WiFi module to
the ECC800 using the app on the mobile phone or tablet
computer to view the basic information about the smart module,
such as layout, resources, energy efficiency, environment, and
alarms.
 Insert a USB flash drive to export historical data, device data,
fault information, and configuration files, and import or export
the device configuration data and historical data.
Button  SW: wireless network pairing button
 Default: button for restoring the default IP address

3.4.3 AI/DI module


An AI/DI module provides a maximum of eight AI/DI inputs to collect AI/DI signals. It can
be mounted on a 19-inch rack.

Figure 3-32 AI/DI module

Table 3-22 Description of ports on the front panel of the AI/DI module

Silk Screen Port Description


COM_IN Cascading ports. COM_IN connects to an RS485 expansion card,

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 47


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Silk Screen Port Description


COM_OUT and COM_OUT connects to another AI/DI module.
Pin definitions of the ports are the same as those of the COM4 port
on the communications card.
AI/DI_1–AI/DI_8 Provides 12 V DC outputs for sensors and are compatible with
4–20 mA current signals, signals from current-based smoke sensors
and water sensors, dry contact signals, and NTC signals.
Pin definitions:
 3: 12 V DC, 54 mA
 6: D-
 7: D+
 8: GND

3.4.4 Smart ETH Gateway


A smart ETH gateway allows the extension of the 53.5 V DC power supply and FE
communication for the ECC800 and can be flexibly deployed in a smart module.

Figure 3-33 Smart ETH gateway

(1) PWR_IN (2) FE_1 cascading (3) POE_1–2 (4) POE_3–4 ports
cascading power port signal port ports
(5) 48V_OUT1 (6) 48V_OUT2 (7) FE_2 (8) PWR_OUT
power output port power output port cascading signal cascading power port
port
(9) BLINK button (10) Status indicator

Specifications

Table 3-23 Technical specifications for a smart ETH gateway

Item Specifications

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 48


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Item Specifications
Power input PWR_IN D-type power input terminal, for power cascading, input voltage
range: 45–55 V DC
Power of a single smart ETH gateway: max (2.7 A, 48 V DC); power of
cascaded smart ETH gateways: max (25 A, 48 V DC)
Power output  PWR_OUT D-type power output terminal, for power cascading, output
voltage range: 45–55 V DC
 48V_OUT1 and 48V_OUT2, terminal (1 A,48 V DC), output voltage
range: 45–55 V DC
FE port Two FE ports, RJ45 terminal with an indicator, 10/100M communication
rate, for the cascading between smart ETH gateways and the
communication with the upper computer
POE port Four POE ports, RJ45 terminal with an indicator, 10/100M
communications rate, complying with IEEE802.3, IEEE802.3u,
IEEE802.3af/at
BLINK If you press the BLINK button, the RUN indicator blinks intermittently at
button super short intervals (blinking at super short intervals for 0.5s and then off
for 0.5s) for 5 seconds.

Indicators

Table 3-24 Indicators on a smart ETH gateway

Indicator Color Name Status Description


PWR Green Power input Steady on The power input is normal.
status indicator
Off There is no power input.
RUN Green Module Off The power supply is
running status abnormal.
indicator
Blinking at The smart ETH gateway
long successfully registers with
intervals the ECC800 and the software
runs properly (the indicator
blinks at 0.5 Hz, on for 1s
and then off for 1s).
Blinking at The smart ETH gateway does
short not register with the ECC800
intervals (the indicator blinks at 4 Hz,
on for 0.125s and then off for
0.125s).
Blinking The indicator blinks at super
short intervals for 0.5s
(blinking at 10 Hz, on for
0.05s and then off for 0.05s)

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 49


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Indicator Color Name Status Description


and then turns off for 0.5s.
The cycle lasts for 10s.
ALM Red Alarm Steady on A system failure alarm is
indicator generated.
Off No system alarm is
generated.

3.4.5 Intelligent Battery Monitoring System


The intelligent battery monitoring system consists of the iBOX (CIM) and iBAT (BIM).
The iBOX is an intelligent battery management module that collects wireless communication
data from the downstream iBAT groups, collects and analyzes the operating data of battery
strings, calculates state of charge (SOC) and state of health (SOH) of batteries and battery
strings and estimates the battery health status accordingly, supports battery tripping
management, and uploads data to the management unit through COM or POE ports.
The iBAT is a battery monitoring module that monitors the voltages, internal resistances, and
pole temperatures of batteries.
In the scenario with battery cabinets, the iBOX is installed inside a smart module battery
cabinet and the iBOX communications cable connects to a smart ETH gateway.
(Optional) When a battery system needs to be managed by multiple iBOXs, the iBOXs can be
connected to northbound devices using straight-through cables (the ECC800 supports four
iBOXs in parallel through the smart ETH gateway) without cascading.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 50


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Figure 3-34 Connecting the iBOX signal cable

3.4.5.1 iBOX
iBOX is a battery information collection module. It collects battery status data from the
downstream iBAT groups through wireless communication, and sends the data to the ECC,
UPS, and the third-party network management system (NMS) through COM or POE ports.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 51


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Appearance

Figure 3-35 iBOX front view

(1) –48 V 0.5 A port (2) POE port (3) COM_IN port (RS485
(power input) communication input)
(4) COM_OUT port (5) DI and DO ports (6) HALL_1–HALL_8
(RS485 communication current monitoring ports
output)
(7) RF_Z antenna port (8) BCB_1–BCB_4 ports (9) BCB_OUT and BCB_IN
(BCB_2–BCB_4 reserved) ports
(10) Networking switch (11) PWR indicator (12) RUN indicator
(13) ALM indicator (14) RF_Z indicator (15) Delivered antenna

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 52


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Figure 3-36 iBOX bottom view

(1) Fastener (2) Micro SD card slot


(3) Default button (IP (4) ADDR dual in-line package (DIP) switch (RS485
reset) communications address)
(5) 12 V 2 A port (power
input)

Power Port

Figure 3-37 Power port pins

Table 3-25 12 V, 2 A port pin definitions

Pin Definition Description

1 – In this scenario, an external


power module is adopted to
2 + supply 12 V DC operating
voltage.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 53


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Table 3-26 –48 V, 0.5 A port pin definitions

Pin Definition Description


1 + The system provides 48 V
DC operating voltage in this
2 – scenario.

POE Port

Figure 3-38 POE port pins

Table 3-27 POE port pin definitions

Pin Definition Description


1 TX+ Supports power supply
through the POE port. The
2 TX– terminal is an RJ45 terminal
with an indicator.
3 RX+
4, 5 P45_P1
6 RX–
7, 8 P78_P1

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 54


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

COM Port

Figure 3-39 COM port pins

Table 3-28 COM port pin definitions

Pin Signal Description


1 RS485+ Two cascaded RS485
communication ports
2 RS485–
3 NC
4 RS485+
5 RS485–
6 GND
7 NC
8 NC

DI and DO Ports

Table 3-29 DI and DO port pin definitions

Pin Definition Signal Status Initial Remarks


Description Description Status
1 + Dry contact  Open: The Open Dry contact
input signal dry input and
2 – contact output signal
input is
open.
 Closed:
The dry
contact

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 55


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Pin Definition Signal Status Initial Remarks


Description Description Status
input is
closed.
3 NO Dry contract  Open: The Open
output signal dry
4 COM contact
output is
open.
 Closed:
The dry
contact
output is
closed.

HALL Current Monitoring Port

Figure 3-40 HALL current monitoring port pins

Table 3-30 HALL current monitoring port pin definitions

Pin Definition Description

1 +12 V Detect the charge and discharge currents of four battery strings
or eight battery routes.
2 –12 V
3 AI
4 GND

 If the battery string is configured with the neutral wire, measure the currents of the positive and
negative battery string cables. If the battery string is not configured with the neutral wire, measure
the current of either the positive or negative battery string cable. The following uses the scenario
where the battery string is configured with the neutral wire as an example.
 When an iBOX manages multiple battery strings, first connect the Hall effect sensors on the positive
and negative cables of battery string 1 respectively to the corresponding ports on the iBOX. Then
connect the Hall effect sensors on battery string 2 to the iBOX in the same way, and so on.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 56


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

 If the positive or negative battery string cable is too thick to be routed through the Hall effect sensor,
or the measurement range of the Hall effect sensor is not enough, use multiple Hall effect sensors to
monitor the current of one battery string. The iBOX supports the sum of the monitoring results of
multiple Hall effect sensors, which is set through Multi-Hall cur. setting.
 The value of Multi-Hall cur. setting equals the number of positive or negative Hall effect sensors in
a single battery string and should be greater than or equal to 1.

BCB Port

Figure 3-41 BCB port pins

Table 3-31 BCB_1–BCB_4 port pin definitions

Pin Definition Signal Status Initial Remarks


Description Description Status

1 OL Monitors  Grounded: Disconnected The four BCBs can


whether the BCB separately manage
BCB box is connected. tripping of four battery
connected  Disconnected: routes.
BCB not
connected.
2 STA Monitors the  Grounded: Disconnected
battery circuit The battery
breaker circuit breaker
is ON.
 Disconnected:
The battery
circuit breaker
is OFF.
3 DRV Controls battery  0 V: There is 0V
circuit breaker no driving
trip and outputs signal for
12 V driving BCB tripping.
signals  12 V: There is
4 GND Secondary side a driving
ground signal for
BCB tripping.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 57


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Table 3-32 BCB_IN and BCB_OUT cascading port pin definitions

Pin Definition BCB_IN BCB_OUT Status Description Initial Description


Signal Signal Status
Description Description

1 OL Specifies Specifies  Grounded: BCB Disconnected Receives


whether the whether the connected. BCB
BCB connects cascaded  Disconnected: commands
to the signal BCBs connect BCB not sent by the
output port. to the signal connected. UPS and
input port. supports
BCB port
2 STA Signal output Monitors  Grounded: The Disconnected cascading
port for the whether the battery circuit management.
battery circuit cascaded breaker is ON.
breaker status BCBs are  Disconnected:
connected to The battery
the input. circuit breaker is
OFF.
3 DRV Controls battery circuit breaker  0 V: There is no 0V
trip and receives 12 V driving driving signal for
signals BCB tripping.
 12 V: There is a
4 GND Secondary side ground
driving signal for
BCB tripping.

DIP Switch

Table 3-33 DIP switch description

No. Definition Description


1 ADDR_1 RS485 communications
address setting
2 ADDR_2
3 ADDR_3
4 ADDR_4

Indicators

Table 3-34 Indicator description

Indicator Color Meaning Status Description Measure


RF_Z Green Wireless Steady on No network Requires no
communica parameters exist. handling.
(A network is to be

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 58


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Indicator Color Meaning Status Description Measure


tion status created.)
Blinking at A network is being
super short created (new nodes
intervals allowed).
Blinking at Data is being
long transmitted (new
intervals nodes not
allowed).
RUN Green Northbound Blinking at The Requires no
communica long communication is handling.
tion status intervals normal.
Blinking Blinking, lasting Requires no
intermittent for 10s. handling.
ly at super
short
intervals
Blinking at Communication 1. Check
short fails. (No whether the
intervals legitimate communicati
northbound data on cable is
has been received loose.
for 3 minutes.)  If yes,
reconnect
the
communi
cation
cable.
 If no, go
to the
next step.
2. Check
whether the
device is
malfunctioni
ng.
 If yes,
replace
the
device.
 If no,
contact
Huawei
technical
support.
ALM Red Alarm Steady on The actual number Check the value
indicator of online devices is of iBAT
less than the value number, the

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 59


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Indicator Color Meaning Status Description Measure


of iBAT number. iBAT cable
connection, and
the iBAT
indicators.
Off The actual number Requires no
of online devices handling.
equals the value of
iBAT number.
PWR Green Power Steady on Board power Requires no
indicator indicator. handling.

 If an indicator blinks at long intervals, it is blinking at 0.5 Hz, that is, on for 1s and then off for 1s.
 If an indicator blinks at short intervals, it is blinking at 4 Hz, that is, on for 0.125s and then off for
0.125s.
 If an indicator blinks at super short intervals, it is blinking at 10 Hz, that is, on for 0.05s and then off
for 0.05s.
 Blinking intermittently at super short intervals means an indicator blinks at super short intervals for
0.5s and then remains off for 0.5s.

Networking Switch

Table 3-35 Networking switch description

Name Definition Function


Button pressing Press the button for less iBOX blinking function
than 1s.
Button pressing Press and hold the button Creates a network if no network has
for more than 1s but less been created. Switches between network
than 5s. organization and data transmission if a
network has been created.
Button holding Press and hold the button Clears the current network (including
down for more than 10s but less the network parameters of all the online
than 20s. iBATs).

Default Button

Table 3-36 Default button description

Name Definition Function


Default button Hold down the button Reset to the default IP address
for more than 10 (192.168.0.10)
seconds.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 60


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

3.4.5.2 iBAT
The iBAT is a battery monitoring module that monitors the voltages, internal resistances, and
pole temperatures of batteries and supports 12 V power.

Features
 Monitors the voltages, internal resistances, and pole temperatures of 12 V batteries.
 Supports the hibernation function. (When it detects that the battery voltage is low, it will
enter the low-power mode.)
 Communicates with the iBOX wirelessly.

iBAT Appearance

Figure 3-42 iBAT2.0

Figure 3-43 iBAT3.0

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 61


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Indicators

Table 3-37 Indicator description

Indicator Color Silk Status Description


Screen

Running Green RUN Off Power consumption is low or the


iBAT is not powered on.
Blinking at The networking has started but not
super short completed.
intervals
Blinking at The networking succeeds.
long intervals
Alarm Red ALM Off The iBAT is not faulty.
Steady on  The iBAT is faulty.
 Communication with the iBOX
times out.
 No network is connected. (The
iBAT is waiting to connect to a
network.)
Blinking at  Network parameters are being
super short cleared.
intervals  The iBAT is blinking.
(iBattery 2.0)
Blinking at
short intervals
(iBattery 3.0)

 If an indicator blinks at long intervals, it is blinking on for 1s and then off for 1s.
 If an indicator blinks at super short intervals, it is blinking at 10 Hz, that is, on for 0.05s and then off
for 0.05s.
 If an indicator blinks at super short intervals, it is blinking at 4 Hz, that is, on for 0.125s and then off
for 0.125s.

Networking Switch

Table 3-38 Networking switch description

Name Definition Function


Button pressing Press the button for less Searches for and joins a network if there is no
than 5 seconds. network. Initializes the network parameters if
there is a network.
Button holding Hold down the button Clears the current network and resets the

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 62


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Name Definition Function


down for more than 5 wireless module; disconnects the network.
seconds.

3.4.6 (Optional) Video System


The video system consists of the camera and VCN (a network video recorder) and implements
real-time monitoring, video storage, and video playback.

3.4.6.1 Network Camera


The IPC6325-WD-VR network camera (IPC6325 camera for short) is a two-megapixel wide
dynamic infrared zoom dome camera that can be wall-mounted or ceiling-mounted.

Figure 3-44 IPC6325 network camera

Table 3-39 IPC6325 camera technical specifications

Item Specifications
Image sensor 1/2.8'' two-megapixel progressive scan CMOS
Lowest illuminance Color: 0.01 lux (F1.4, AGC ON)
Black and white: 0.004 lux (F1.4, AGC ON)
0 lux (infrared enabled)
Wide dynamic range 120 dB
Focal length 2.8–12 mm manual zoom, 4.3x optical zoom
Video coding format H.265/H.264/MJPEG
Maximum resolution 1920 x 1080
Intelligent video Supports tripwire detection, loitering detection, intrusion
detection, abandoned object detection, removed object detection,

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 63


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Item Specifications
analysis target color recognition, classifications of people and vehicles,
and metadata backhaul.
Power supply PoE (802.3at/af), 24 V AC±25%, 24 V DC±25%, 12 V
DC±25% (polarity-insensitive DC power supply), applicable to
DC/AC adapter and PoE hot backup
Protection level IP66; complying with IEC 60529
Vandal-proof class IK10; complying with IEC 62262

3.4.6.2 VCN500

Figure 3-45 VCN500

Table 3-40 VCN500 performance specifications

Item Specifications
Video access A single VCN500 supports the access from a maximum of 32
cameras and the maximum access bandwidth of 160 Mbit/s.
Video forwarding A single VCN500 supports the video forwarding from 32 cameras
or of 160 Mbit/s.
Storage performance A single VCN500 supports the storage access from a maximum of
32 cameras and the maximum storage access bandwidth of 160
Mbit/s.
Video playback and A single VCN500 supports the video playback and download of 32
download cameras or 160 Mbit/s.

Table 3-41 VCN500 hardware specifications

Item Specifications

Hard disk slot Twelve 3.5 inch hard disk slots


Hard disk type and Twelve 3 TB or 4 TB SATA hard disks
quantity NOTE
 The VCN500 supports hard disks at enterprise and monitoring
levels.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 64


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Item Specifications
 It is recommended that you use the SD card in the camera to view
the data stored within 7 days and that you use the VCN500 to
view the data stored within 7 to 30 days.

RAID control card The VCN500 does not have a RAID control card on its
mainboard.
The VCN500-R has a RAID control card on its mainboard.
CPU type and quantity One CPU with the primary frequency of 1 GHz, maximum 10
MB cache
Memory capacity 2 GB
I/O port Two service network ports, with RJ45 connectors and
LNK/ACT indicators
Power parameters Maximum ATX PSU power: 250 W
Maximum gold PSU power: 460 W
AC input voltage range: 100–240 V
AC power frequency range: 47–63 Hz
Weight (full ≤ 20 kg
configuration)
Typical power 40 W
consumption (excluding
hard disks)
Maximum power 70 W
consumption (excluding
hard disks)
Dimensions (H x W x D) 86.1 mm x 482 mm x 488 mm (including mounting ears)

3.4.6.3 VCN540

Figure 3-46 VCN540

Table 3-42 VCN540 performance specifications

Item Description

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 65


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Item Description
Device access and video storage Supports a maximum of 64 video access
channels or 320 Mbit/s video access
bandwidth.
Video forwarding Supports a maximum of 128 video
forwarding channels or 320 Mbit/s video
forwarding bandwidth.
Video playback and download Supports a maximum of 32 video playback
and download channels or 320 Mbit/s video
playback and download bandwidth.

Table 3-43 VCN540 hardware specifications

Item Specifications
Number of disks 8
Whether the hard disk supports hot swap Yes
Supported hard disk type 3 TB, 4 TB, 6 TB, or 8 TB SATA disks
CPU type and maximum number of 1 x ARM Cortex A17 Quad-core @Max.
supported CPUs 1.4 GHz
Memory capacity 2 GB
Network port Two GE network ports
Power parameters  One power module
 AC power (100 V AC to 240 V AC; 50
or 60 Hz)
Weight in full configuration (including hard ≤ 14 kg
disks)
Maximum power consumption (including < 150 W
hard disks)
Dimensions (H x W x D) 86.1 mm (2 U) x 442 mm x 420 mm
(excluding the panel)
86.1 mm (2 U) x 442 mm x 450 mm
(including the panel)

3.4.7 Water Sensor


The WLDS900 water sensor with the BOM number of 33010352 consists of a water detection
cable, a water detector, and a conversion cable.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 66


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Figure 3-47 WLDS900 water sensor

(1) Water detector (2) Conversion cable end A, connected (3) Conversion cable
to the water detector
(4) Conversion cable (5) Water detection cable end A, (6) Water detection
end B, connected to connected to the conversion cable cable
the water detection
cable

Table 3-44 WLDS900 water sensor specifications

Item Specification
Operating 12 V DC (9–16 V DC)
voltage
Operating –20°C to +70°C
temperature
Storage –40°C to +85°C
temperature
Humidity 10%–80% RH (non-condensing)

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 67


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

3.4.8 (Optional) Access System


3.4.8.1 Access Actuator
The access actuator is the control component for the aisle door in a smart module. It connects
to the ECC800 controller over FE port, wireless networking (802.15.4). It opens the magnetic
lock by detecting the card swiping information of the card reader, door open button
information, and fire linkage information. It has access right management, access event record,
and alarm record functions.

Figure 3-48 Access actuator

(1) 48 V power port (2) POE port (3) RS485 port COM2
(4) RS485 port COM1 (5) Address DIP switch (6) Status indicator
(7) BLINK button (8) WG_2 Wiegand (9) WG_1 Wiegand interface
interface
(10) AI/DI_2 dry (11) AI/DI_1 dry (12) LOCK/GND/GATE/COM door
contact (Reserved port contact (Reserved port status or magnetic lock port
for linkage control or for exit button)
third-party fire
extinguishing system
dry contacts)

Specifications

Table 3-45 Access actuator technical specifications

Item Specifications

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 68


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Item Specifications
Power input  DC input: Terminal, with input voltage of 36–60 V DC
 POE input: One POE port that complies with IEEE802.3at.
POE port FE communication, 10/100M communications rate
Wireless One wireless communication port that complies with IEEE802.15.4,
communicatio mutual backup with FE communication
n
AI/DI port Two AI/DI ports, can connect to the fire alarm and exit button
DO/DI port  One 12 V DC power output that controls magnetic locks, terminal
 One DI input port for connecting to the door status switch
RS485 serial Two RS485 ports (one route) with the default communications rate of
port expansion 9600 bit/s, physical port cascading supported (reserved function)
Wiegand Two Wiegand interfaces, 12 V DC card reader operating power output;
interface two routes of card readers (non-fingerprint readers) can operate at the
same time.
BLINK button  Press the button for less than 1 second to start blinking.
 Hold down the button for 1–5 seconds to search for a network and
start networking.
 Hold down the button for more than 10 seconds to clear network
parameters.
Address DIP 4-pin address DIP switch
switch
E-label Supported

Indicators

Table 3-46 Access actuator indicator description

Indicator Color Name Status


PWR Green Power input status  Steady on: The power
indicator input is normal.
 Off: There is no
power input.
RUN Green Communication status  Off: The power is
indicator abnormal or the
board program is
loading.
 Blinking at long
intervals: The access
actuator successfully
registers with the

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 69


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Indicator Color Name Status


ECC800 and the
software runs
properly (the
indicator blinks at 0.5
Hz, on for 1s and
then off for 1s).
 Blinking at short
intervals: The
communication is
disconnected or the
access actuator fails
to register with the
ECC800 (the
indicator blinks at 4
Hz, on for 0.125s and
then off for 0.125s).
 Blinking: The
indicator blinks at
super short intervals
for 0.5s (blinking at
10 Hz, on for 0.05s
and then off for
0.05s) and then turns
off for 0.5s. The
cycle lasts for 5s.
ALM Red Alarm indicator  Steady on: A system
failure alarm is
generated.
 Off: No system alarm
is generated.
RF_Z Green Wireless  Steady on: No
communication status network parameters
indicator exist, or a network is
to be created.
 Blinking at long
intervals: A network
is set up, and no node
access is allowed (the
indicator blinks at 0.5
Hz, on for 1s and
then off for 1s).
 Blinking at super
short intervals: A
network is set up, and
node access is
allowed (the indicator
blinks at 10 Hz, on
for 0.05s and then off
for 0.05s).
 Blinking

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 70


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Indicator Color Name Status


intermittently at super
short intervals: The
access actuator is
searching for a
network (the
indicator blinks at
super short intervals
for 0.5s and then
turns off for 0.5s).

Communications Ports
The access actuator provides one DO port (LOCK/GND) and one DI port (GATE/COM).
Table 3-47 lists the LOCK/GND/GATE/COM port pin definitions.

Table 3-47 LOCK/GND/GATE/COM port pin definitions

Item Description
LOCK/GND LOCK 12V_OUT
(control
magnetic GND GND
locks) pin
sequence
GATE/COM GATE DI1
(door status)
pin sequence COM COM

3.4.8.2 Room-Level Access Control


The access control system collects and monitors data about the access of devices and
personnel to ensure access security.
Diverse access control devices such as the fingerprint and card reader with a keypad,
fingerprint and card reader, and card reader with a keypad are supported.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 71


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Fingerprint and Card Reader with a Keypad

Figure 3-49 Fingerprint and card reader with a keypad

(1) Fingerprint reader (2) LED indicator

Table 3-48 Specifications for the fingerprint and card reader with a keypad

Item Specifications
Dimensions (L x W x H) 156 mm x 53 mm x 38 mm
Rated operating voltage 12 V DC ±15%
Rated operating current 300 mA ±15%
Card type supported IC card
Authorized storage A maximum of 3000 authorized users, with a maximum
of 6000 fingerprints
Communications mode RS485 and Wiegand communications ports

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 72


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Table 3-49 Access control device operating status

Item New Version


Standby LED indicator The indicator is steady blue.
Fingerprint reader The indicator is off.
Unauthorized fingerprint LED indicator The indicator blinks blue,
collection red, blue, red, and blue in
order.
Fingerprint reader The indicator turns on
(white).
Buzzer sounds The buzzer sounds three.
Authorized fingerprint LED indicator The indicator blinks blue,
collection red, and blue in order.
Fingerprint reader The indicator turns on
(white).
Buzzer sounds The buzzer sounds once.
Card swiping LED indicator The indicator blinks blue,
red, and blue in order.
Buzzer sounds The buzzer sounds once.

Fingerprint and card reader

Figure 3-50 Fingerprint and card reader

(1) Fingerprint reader (2) LED indicator

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 73


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Table 3-50 Fingerprint and card reader

Item Specifications
Dimensions (L x W x H) 156 mm x 53 mm x 38 mm
Rated operating voltage 12 V DC ±5%
Rated operating current 300 mA ±5%
Card type supported IC card
Authorized storage A maximum of 3000 authorized users, with a maximum
of 6000 fingerprints
Communications mode RS485 and Wiegand communications ports

Table 3-51 Access control device operating status

Item New Version


Standby LED indicator The indicator is steady blue.
Fingerprint reader The indicator is off.
Unauthorized fingerprint LED indicator The indicator blinks blue,
collection red, blue, red, and blue in
order.
Fingerprint reader The indicator turns on
(white).
Buzzer sounds The buzzer sounds three.
Authorized fingerprint LED indicator The indicator blinks blue,
collection red, and blue in order.
Fingerprint reader The indicator turns on
(white).
Buzzer sounds The buzzer sounds once.
Card swiping LED indicator The indicator blinks blue,
red, and blue in order.
Buzzer sounds The buzzer sounds once.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 74


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Card Reader with a Keypad

Figure 3-51 Card reader with a keypad

Table 3-52 Specifications of a card reader with a keypad


Item Specifications

Dimensions (L x W x H) 114 mm x 63 mm x 25 mm
Operating voltage Operating voltage range: 10.8–13.2 V DC; rated voltage:
12 V DC
Operating current Static standby current 80 mA, dynamic operating current
(card swiping, key pressing) 150 mA, minimum input
current 12 V DC/300 mA
Communications mode Wiegand communications port

Dual-door Magnetic Lock

Figure 3-52 Dual-door magnetic lock

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 75


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Single-door Magnetic Lock

Figure 3-53 Single-door magnetic lock

Exit Button

Figure 3-54 Exit button

Emergency Door Release Button


In case of emergency, break the glass of the emergency door release button to disconnect the
power supply to the lock and therefore unlock the door.

Figure 3-55 Emergency door release button

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 76


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

3.4.9 Smoke Detector


Figure 3-56 Smoke detector

Table 3-53 Smoke detector technical specifications

Item Specifications
Operating voltage 9–16 V
Quiescent current < 8 mA
Alarm current < 35 mA
Output mode Relay output
Output contact capacity 3 A/120 V AC or 3 A/24 V AC
Operating temperature –10°C to +50°C
Ambient humidity ≤ 95% RH
Dimensions Diameter: 112 mm; height: 41 mm

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 77


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

3.4.10 WiFi Module


The WiFi module provides WiFi signals for equipment for the data interaction with the host
computer.

Figure 3-57 WiFi module

Table 3-54 WiFi module technical specifications

Item Specifications

Standard IEEE 802.11n, IEEE 802.11g, IEEE 802.11b


Wireless speed  11n: Up to 150 Mbps
 11g: Up to 54 Mbps
 11b: Up to 11 Mbps
Frequency range 2.4–2.4835 GHz
Wireless transmit 20 dBm (MAX EIRP)
power
Supported Windows 2000/XP/Vista/Linux/Win 7
operating system
Dimensions (L x 20 mm x 14 mm x 6 mm
W x H)
Interface USB 2.0 Hi-Speed connector
Voltage range DC 5.0 V ±5%
Operating –20°C to +70°C
temperature
Storage –40°C to +90°C
temperature
Humidity 10%–90% RH, non-condensation
Storage humidity 5%–90% RH, non-condensation

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 78


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Item Specifications
Power < 0.8 W
consumption

3.4.11 PAD
The PADallows wireless access to the data center management systemproductn monitor the
equipment in the data center and environmental parameters in real time over the app.
Subsystems of the FusionModule800 are well integrated. All facility running parameters of
the module, including the video device, smart cooling productr, UPS, temperature and
humidity sensor, smoke sensor, water sensor, and intelligent battery monitoring system, can
be monitored over one interface.

Figure 3-58 PAD

The PAD provides a capacitive multi-touch screen.

Table 3-55 PAD structural specifications

Item Specifications
Dimensions (L x W x 229.8 mm x 159.8 mm x 7.95 mm
H)
Weight About 460 g (including batteries)

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 79


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Table 3-56 PAD technical specifications

Item Specifications
Touchscreen 9.6-inch, 1280x800 HD resolution, IPS screen, and capacitive
10-point touch
CPU model Qualcomm SnapDragon 425
Number of CPU cores Quad-core
WLAN 802.11a/b/g/[email protected] GHz & 5 GHz
Storage  ROM: 16 GB
 RAM: 2 GB
 Expansion card: micro SD, up to 128 GB (non-standard
configuration)
Button/Port  Power and volume buttons
 3.5 mm stereo headphone port
 Micro SD card port
 Micro-USB 2.0 B type port that supports charging and
synchronization with PC data
Battery  Material: Li-polymer
 Capacity: 4800 mAh
 Standby time: about 500 hours
 Power adapter charge time: about less than 4.5 hours
Operating system Android 7.0

3.5 Surge Protection and Grounding System


3.5.1 Surge Protection Solution
The Smart Module is mainly used for building equipment rooms. Its power distribution
system is a subsystem of the building power distribution system. Class I surge protective
devices (SPDs) of the power system are provided by the general low-voltage power
distribution room or cabinet of the building.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 80


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Figure 3-59 Surge protection solution

 The Smart Module provides class C SPDs in standard configuration, and 32 A SPDs are
configured on the upstream side.
 If the power cable to the smart cooling product outdoor unit needs to be routed through
the rooftop, it is recommended that the cable be routed through metal pipes or metal
cable troughs. The metal pipes or metal cable troughs should have good electrical contact
and be grounded at both ends.
 The SPD connection conductors should be short (within 0.15 m) and straight. The SPD
power cable uses copper wires with the minimum cross-sectional area of 10 mm2. The
SPD ground cable uses copper wires with the cross-sectional area of at least 16 mm2.

3.5.2 Grounding Solution


Equipotential Grounding for Cabinets in the Module
A general ground bar is configured in the Converged Cabinet. The ground terminals in other
cabinets are connected to the general ground bar by cables with a cross-sectional area no less
than 16 mm2. The general ground bar is connected to the floor ground bar (FEB) or collective
ground bar (25 mm x 3 mm copper bar laid along cable trays or walls) of the equipment room
by ground cables with a cross-sectional area no less than 35 mm2.

The AC input power is from the upstream power distribution system. The cross-sectional areas of
ground cables are determined according to IEC 60364-5-54.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 81


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Figure 3-60 Equipotential bonding for cabinets

(1) General ground bar

Cabinet Grounding
 Metal components and parts of cabinets are properly connected. A structural connection
area is protected and applied with antioxidants. An area protected with painting should
ensure proper metal surface contact for two connected components. The DC resistance is
within 0.1 ohm between any two connected metal components. Use a ground cable to
connect two metal components that cannot be directly connected, such as cabinets and
cabinet doors. A cable for connecting these two metal components has a minimum
cross-sectional area of 6 mm2.
 A ground bar or general ground point is provided in each cabinet for equipment
grounding. These ground bars are not insulated.
 A ground terminal is larger than or equal to M8 in dimensions. A yellow ground label

is attached close to the general ground terminal for cabinets.


 Connect equipotential cables to metal components without carrying currents in the
module, such as metal doors and windows, cable trays, and ESD floor supports. Each
equipotential cable has a minimum cross-sectional area of 6 mm2.

3.6 Fire Extinguishing System


Huawei provides only sensors for the fire extinguishing system in the Smart Module. Other
components should be prepared by the customer.

3.7 Integrated Cabling System


3.7.1 Integrated Cabling
Cable troughs are installed on the top of cabinets for routing cables. There are two types of
cable troughs: signal cable troughs and power cable troughs.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 82


FusionModule800 Smart Small Data Center
Product Description (Latin America) 3 System Architecture

Figure 3-61 Cables routes through binding plates

(1) Signal cable (2) Power cable

3.7.2 Cables
Power Cable
Power cables include the input power cables for the converged cabinet, power cables from the
UPSto the battery switch, battery cabinet power cables, smart cooling productpower cables,
PDU2000 power cables, AC power cables (such as the ECC800 power cables and VCN power
cables).

Ground Cable
Ground cables include thosefor the converged cabinet, battery cabinet, IT cabinet, and smart
cooling product.

Monitoring Cable
Monitoring cables include thosefor the T/H sensor, smart cooling product, converged cabinet,
UPS, water sensor, smoke detector, video system, and door status sensor.

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 83


FusionModule800 Smart Small Data Center
Product Description (Latin America) 4 Technical Specifications

4 Technical Specifications

Table 4-1 Key technical specifications

Item Normal-Temperature Version


Module dimensions (H x W x D) Cold aisle containment: 2000 mm x L x 1350 mm, L ≤
(mm) 4800 mm (for a 600 mm wide network cabinet) or
5000 mm (for an 800 mm wide network cabinet)
Number of IT cabinets ≤ 6 (including the network cabinet), a maximum of two
battery cabinets deployed inside the aisle containment
Number of cabinets ≤ 8, a maximum of two battery cabinets deployed
inside the aisle containment
Power system 208 V, 3-phase, 60 Hz
Voltage range 187.2–228.8 V
Frequency range 57–63 Hz
Total IT equipment power  120 V only: maximum 9 kW
 208 V only: maximum 15 kW
 208 V and 120 V: maximum 15 kW
Maximum power of a single ≤ 6 kW
cabinet
Protection level IP20
Altitude 0-4000 m (derated when the altitude exceeds 1000 m)
Installation mode Installed on a concrete or raised floor
Cable and pipe routing Cables and pipes routed from the top or bottom
Operating temperature Indoor: 0–40°C
Outdoor: –20°C to +45°C
Operating humidity 5%–95% RH (non-condensing)
Storage temperature Without refrigerant: –40°C to +70°C
With refrigerant: –40°C to +55°C

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 84


FusionModule800 Smart Small Data Center
Product Description (Latin America) 4 Technical Specifications

Item Normal-Temperature Version


Storage humidity 5%–95% RH (non-condensing)

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 85


FusionModule800 Smart Small Data Center
Product Description (Latin America) A Equipment Derating Coefficients

A Equipment Derating Coefficients

The coefficients listed in the Table A-1 are based on the dry air density being 1.225 kg/m3 (sea level
+15ºC).

Table A-1 Derating coefficients of the UPS2000-G

Altitude (Unit: m) Derating Coefficients


1000 1.0
1500 0.95
2000 0.91
2500 0.86
3000 0.82
3500 0.78
4000 0.74
4500 0.7
5000 0.67

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 86


FusionModule800 Smart Small Data Center
Product Description (Latin America) B Acronyms and Abbreviations

B Acronyms and Abbreviations

A
AC alternating current

B
BIM battery interface module

C
CIM communication interface module

D
DC direct current

I
IEC International Electrotechnical Commission

M
MCB miniature circuit breaker

S
SNMP Simple Network Management Protocol
SPD surge protective device
SOC state of charge
SOH state of health

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 87


FusionModule800 Smart Small Data Center
Product Description (Latin America) B Acronyms and Abbreviations

U
UPS uninterruptible power system

Issue 06 (2020-03-20) Copyright © Huawei Technologies Co., Ltd. 88