Vibgyor: 590Wp Solar Module Mcb/Mccb/Acb Sungrow Inverter Four Pole Current Transformer Earth Fault Relay

The document provides detailed specifications for a 335.71 kWp rooftop solar PV project at BHRC Phase-II, Vrindaban, U.P. It includes information on system components such as solar modules, inverters, and electrical parameters like supply voltage and frequency. The document is intended for internal use and requires written permission for any disclosure.

Uploaded by

Ankit Kushwaha
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
41 views1 page

Vibgyor: 590Wp Solar Module Mcb/Mccb/Acb Sungrow Inverter Four Pole Current Transformer Earth Fault Relay

The document provides detailed specifications for a 335.71 kWp rooftop solar PV project at BHRC Phase-II, Vrindaban, U.P. It includes information on system components such as solar modules, inverters, and electrical parameters like supply voltage and frequency. The document is intended for internal use and requires written permission for any disclosure.

Uploaded by

Ankit Kushwaha
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

3 4 5 6 7 8

S. NO. PARAMETER DETAILS DEVELOPER/CLIENT:


LEGEND SYSTEM INFO SOLAR LT PANEL BHRC PLANT:
SUPPLY VOLTAGE 415 V BHRC PHASE-II, VRINDABAN, U.P
1.
590Wp SOLAR MODULE 1. RENEWSYS MODULE 590Wp = 569
2. SUPPLY FREQUENCY 50 HZ
2. TOTAL SYSTEM CAPACITY = 335.71 kWp POWER PURCHASER:
MCB/MCCB/ACB AS PER SUPPLY CODE OF
A 3. INVERTER CAPACITY = 250 kW BHRC PHASE-II, VRINDABAN, U.P A
3. VOLTAGE VARIATION DISCOM (INVERTER SHALL BE
- ~ SUNGROW INVERTER 4. DC / AC RATIO = 1.34 RATED FOR 400 V + / - 20 %)
PROJECT:
4P FOUR POLE 4. PROPOSED CONNECTION 335.71 kWp ROOFTOP
LT, 415V
TYPE, RATING & DETAILS SOLAR PV PROJECT
CT CURRENT TRANSFORMER LOCATION:

B EFR EARTH FAULT RELAY 27.566517°, 77.686754° B


MFM
MULTIFUNCTION METER SHEET TITLE:
SLD
SURGE PROTECTION CONNECTED TO THE SPARE
DEVICE FEEDER AT MAIN L.T. PANEL
DRAWING NO:
OF BHRC
VE-PP-595-SLD
2Rx3.5Cx185 SQ.MM
EQUIPMENT EARTHING
AL 1.1 KV XLPE ARMOURED CABLE
STAMP: ORIGINAL : "420X297"
C Solar LT C
Panel
500A, 4P, MCCB
WITH EFR A4 A3 A2 A1 A0

SPD 415V,
18 kA, TYPE II THIS INFORMATION IS CONFIDENTIAL AND IS
6A NO PART IS TO BE DISCLOSED TO OTHERS
MCB WITHOUT WRITTEN PERMISSION FROM
CTS: 500/5A CONCERN PERSON
MFM
D CL:0.5, 10VA D
V = 415 V, I = 500A
4P, AL, BUSBAR
250A, 4P, 250A, 4P, DATE : 28-08-2024
MCCB MCCB
6A R 6A R PREPARED BY : HARJINDER
MCB MCB
1Rx3.5Cx185 SQ.MM
CHECKED BY : HARJINDER
AL 1.1 KV XLPE ARMOURED CABLE
E CHECKED BY : GAUTAM
E

SUNGROW APPROVED BY : S. SHAHNAZ


INVERTER INVERTER 1 INVERTER 2
~ ~
SG125CX-P2,
415V, 181.1A
1 2 3 4 5 6 7 8 9 10
- 11 12 1 2 3 4 5 6 7 8 9 10
- 11 12
APPROVED BY :

NO. REVISION DATE


2R x 1C x 4 SQ.MM
CU SOLAR DC CABLE
F F
Isc = 13.97A/ STRING
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
RENEWSYS 590 Wp
PV MODULE
Vmp-43.93V,
Imp-13.44A 16 16 16 16 16 16 17 17 17 15 15 15 14 17 17 17 17 17 16 16 16 16 16 16 15 15 15 15 14 14 14
TYPICAL OF ALL
G MODULES 2 STRINGS OF 16 MODULES IN MPPT-1 to 4 1 STRINGS OF 17 MODULES IN MPPT-1 to 5 G
1 STRINGS OF 16 MODULES IN MPPT- 5 to 7 2 STRINGS OF 16 MODULES IN MPPT- 6 to 8 SCALE : NTS
2 STRINGS OF 17 MODULES IN MPPT- 8 2 STRINGS OF 15 MODULES IN MPPT- 9 to 10
1 STRINGS OF 17 MODULES IN MPPT-9 2 STRINGS OF 14 MODULES IN MPPT-11 SHEET NO :
2 STRINGS OF 15 MODULES IN MPPT-10 1 STRINGS OF 14 MODULES IN MPPT-12
1 STRINGS OF 15 MODULES IN MPPT-11
1 STRINGS OF 14 MODULES IN MPPT-12

H H
A - ISSUED FOR INFORMATION

B - ISSUED FOR APPROVAL


VIBGYOR
ENERGY
C - ISSUED FOR CONSTRUCTION

D - AS BUILT