0% found this document useful (0 votes)
38 views12 pages

Attachment 4 - Performance Test Run Protocol

The document outlines the Engineering Specification Performance Test Run Protocol for the H2 Unit 09 at MIDOR in Alexandria, Egypt. It details the procedures, terms, and responsibilities for conducting performance test runs to evaluate the unit's performance against specified guarantees. Key sections include definitions, performance guarantee conditions, and measurement protocols necessary for the successful execution of the tests.

Uploaded by

Hazem Mohamed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
38 views12 pages

Attachment 4 - Performance Test Run Protocol

The document outlines the Engineering Specification Performance Test Run Protocol for the H2 Unit 09 at MIDOR in Alexandria, Egypt. It details the procedures, terms, and responsibilities for conducting performance test runs to evaluate the unit's performance against specified guarantees. Key sections include definitions, performance guarantee conditions, and measurement protocols necessary for the successful execution of the tests.

Uploaded by

Hazem Mohamed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

Project n° - Unit Material code Serial N° Rev.

Page

202812C 001 JSD 0000 0010 00 1 / 12

Client : MIDOR
Location : Alexandria, Egypt
Plant : H2 Unit 09

Engineering Specification
Performance Test Run Protocol

Pages modified under this revision:

00 19/12/22 FOR PROPOSAL JNOO MSWA PKRI/OMEH


Date WRITTEN BY CHECKED BY APPROVED BY
Rev STATUS
DD/MM/YY (name & visa) (name & visa) (name & visa)

DOCUMENT REVISIONS

Sections changed in last revision are identified by a vertical line in the margin

T.EN NETHERLANDS B.V. (TEN-NL)

This document or drawing is the property of T.EN NETHERLANDS B.V. and shall not, under any circumstances, be totally or partially, directly or indirectly,
transferred, reproduced, copied, disclosed or used without T.EN NETHERLANDS B.V.'s prior written consent.
Project n° - Unit Material code Serial N° Rev. Page

202812C 001 JSD 0000 0010 00 2 / 12

Engineering Specification Performance Test Run Protocol

TABLE OF CONTENTS

1. Introduction................................................................................................................ 3

2. Performance Test Run Terms ................................................................................... 3


2.1 Guarantee Conditions ....................................................................................... 3
2.2 Performance Guarantee.................................................................................... 4
2.3 Performance Test Run ...................................................................................... 4

3. Process Design .......................................................................................................... 7

4. Measurements............................................................................................................ 7

5. Worksheets ................................................................................................................ 8
5.1 Correction Factors for Flow Meter Readings ..................................................... 8
5.2 Measurement Accuracy and Calibration Requirements for Instruments .......... 10
5.3 Test Report ..................................................................................................... 10
Project n° - Unit Material code Serial N° Rev. Page

202812C 001 JSD 0000 0010 00 3 / 12

Engineering Specification Performance Test Run Protocol

1. Introduction
This Performance Test Run Protocol (“Protocol”) intends to describe in more detail the
activities to be carried out and the organizational approach to be applied to the execution of
the Performance Test Run(s).

This detailed procedure set out below shall be complementary to the relevant provisions of
the Contract

The capitalized terms used in this Protocol shall have the same meaning as defined in the
Contract, unless defined otherwise below:

“Contract” means the Letter of Acceptance related to the Proposal including their annexes as
applicable, signed by the Parties.

“Performance Guarantee” means the process performance guarantee set forth in Section 2.2
– Performance Guarantee of this Protocol.

“Performance Test Run” means the test or tests during the designated period of operation of
the Unit conducted in accordance with this Protocol for the purpose of collecting operating
data to evaluate the performance of the Unit relative to the Performance Guarantee.

“Performance Test Run Period” means the period ending on the date falling on one hundred
(100) weeks from the signature by both parties of the LOA, whereby the first Performance
Test Run shall need to occur not later than six (6) months after delivery to MIDOR of the
final Equipment item in accordance with the Contract.

“Unit“ means HPU (Hydrogen Production Unit) 9 in relation to which the Engineering
Services and Equipment are being supplied and the Performance Test Run is being
undertaken, located at Middle East Oil Refinery, Alexandria, Egypt.

2. Performance Test Run Terms


2.1 Guarantee Conditions
The Performance Guarantee is valid if each of the following conditions are met:

i. the conditions having been met as set out in the Contract and the Unit is
maintained by experienced personnel of MIDOR,

ii. the Equipment is installed in the Unit in strict accordance with the specifications,
drawings, installation instructions and other instructions issued by TEN-NL in
accordance with the Contract,

iii. the Unit’s pre-commissioning and commissioning is executed in strict accordance


with the original procedures provided during the Unit’s original commissioning
which are presumed to be in line with TEN-NL specifications and guidelines, as
well as with TEN-NL’s written instructions as applicable,
Project n° - Unit Material code Serial N° Rev. Page

202812C 001 JSD 0000 0010 00 4 / 12

Engineering Specification Performance Test Run Protocol

iv. the Performance Test Run, or as applicable Performance Test Runs, is/are
executed within the Performance Test Run Period in accordance with this Protocol
and is being witnessed by TEN-NL, and

v. all equipment and components thereof, in the Unit perform as per original design
(in general, and not limited to main items as listed: Reformer Catalyst, HT Shift
catalyst, PSA unit, convection section coils, flue gas fans and combustion air
fans).

2.2 Performance Guarantee


2.2.1 Provided the obligations have been satisfied as set forth herein, including but not limited to
the conditions set forth in Section 2.1 above, and MIDOR has satisfied its obligations set out
in the Contract, TEN-NL provides Performance Guarantee in accordance as set out in the
table below.

Unit Guarantee
H2 net capacity Nm3/h 64,000

2.3 Performance Test Run


General

2.3.1 Operation of the Unit shall be at all times under the control and responsibility of MIDOR (or
its designated Unit plant manager). MIDOR shall execute the Performance Test Run and
be the coordinator for all operations to be performed during the Performance Test Run.

2.3.2 Within the constraints of the above responsibility, the Performance Test Run will be
monitored by TEN-NL's (technical) representatives (subject to the terms of and the
reimbursable rates as specified in the Contract). MIDOR may adjust the Unit conditions as
suggested by TEN-NL’s technical representatives for the purpose of optimizing the Unit
performance in so far as such adjustments do not jeopardize safe and stable operations.
TEN-NL's recommendations during the Performance Test Run will be advisory only.

2.3.3 During the Performance Test Run phase, meetings shall be held daily between MIDOR’s
operations staff and TEN-NL’s personnel attending the Performance Test Run. During a
Performance Test Run, the instructions or as applicable, recommendations, of either Party,
the progress in the performance of the Performance Test Run, any result and any other
data relevant to evaluate the Performance Test Run, shall be recorded in a logbook which
shall be the official reference regarding logging of activities during the Performance Test
Run. The logbook shall be written by MIDOR in the presence of TEN-NL. In case there is a
difference in opinion or interpretation, the representatives of the Parties shall state so in the
logbook.
Project n° - Unit Material code Serial N° Rev. Page

202812C 001 JSD 0000 0010 00 5 / 12

Engineering Specification Performance Test Run Protocol

Pre-Performance Test Run Period

2.3.4 With the Unit at Performance Test Run capacity, MIDOR shall carry out a 24 hour
pre-Performance Test Run. Prior to the start of this pre-Performance Test Run period, an
instrument zero check and calibration shall be carried out on the feedstock, steam, product
flow and all other meters that are relevant to the process guarantee (calibration shall be in
accordance to ISA Standards or Instrument Vendor instructions.) All temperature indicators
and pressure indicators/manometers that affect process guarantee shall be zero checked
and calibrated.

2.3.5 All flow, temperatures and pressures should be recorded at two hourly intervals during this
pre-Performance Test Run period and all orifice corrections; if required, made to ensure
that the process guarantee can be met.

Performance Test Run

2.3.6 The Performance Test Run will be performed based on the REFERENCE CASE (which is
defined as the original 100% NG case Heat and Material Balance).

2.3.7 Performance test will be performed meeting safety requirements, under steady state, for a
consecutive period of 24 hour.

2.3.8 MIDOR shall prepare the Unit for the Performance Test Run as soon as possible after
normal and stable operation has been established and all instruments for measurement of
guaranteed parameter have been checked, calibrated by MIDOR representatives. TEN-NL
and MIDOR will mutually agree when the Performance Test Run can commence.

2.3.9 MIDOR shall provide at battery limits all necessary utilities within specification, such as:
electricity, cooling water, nitrogen, instrument air, and drinking water.

2.3.10 MIDOR shall provide at battery limits all necessary feedstocks within specification for the
production of Hydrogen, such as: Natural Gas and Boiler Feed Water.

2.3.11 MIDOR shall be responsible to provide sufficient number of operation and analysis
personnel of adequate technical level and experience for the pre-Performance Test Run
operation and the Performance Test Run, which will be conducted in the presence of TEN-
NL in accordance with Section 2.3.2. TEN-NL shall consult with MIDOR on a continuous
basis during the Performance Test Run.

2.3.12 The results obtained from automatic DCS data, manual field data, instruments and sample
analysis shall be averaged over the entire Performance Test Run period and the average
values obtained shall be the basis for interpreting the Performance Test Run. Questionable
results will be excluded, as long as there is proof that the results are evidently erroneous.
On the Performance Test Run data measurements a tolerance shall apply as set out in 6.2.

2.3.13 All analysis required will be performed by MIDOR in accordance with the standards as
given in the Design and Operating Manual provided during the unit’s original project which
are presumed to be in line with TEN-NL specifications and guidelines, as well as with TEN-
NL’s written instructions as applicable.
Project n° - Unit Material code Serial N° Rev. Page

202812C 001 JSD 0000 0010 00 6 / 12

Engineering Specification Performance Test Run Protocol

2.3.14 Based on Performance Test Run information and analytical data to be furnished to TEN-NL
by MIDOR, TEN-NL will evaluate the Performance Test Run to determine conformance
with the Performance Guarantee. This evaluation, and data reconciliation if any, will be
performed by TEN-NL at its established offices. TEN-NL will issue a report to MIDOR
which indicates either, that the Performance Test Run was successful and the Performance
Guarantee has been met, or that the Performance Test Run was not successful, outlining
noted deficiencies in the performance of the Unit. Such report will be issued after receipt of
the required analytical data. The Performance Guarantee shall be deemed to have been
satisfied if TEN-NL certifies that the Performance Test Run was successful and if MIDOR,
within ten (10) business days thereafter, has not furnished TEN-NL with a written a
substantiated report setting out the grounds based on which MIDOR contests that the
Performance Guarantee has been satisfied.

2.3.15 Any terms relating to the Performance Test Run process in amendment or in addition to the
terms set out in this Protocol shall need to be agreed and confirmed in writing by both
Parties.
Project n° - Unit Material code Serial N° Rev. Page

202812C 001 JSD 0000 0010 00 7 / 12

Engineering Specification Performance Test Run Protocol

3. Process Design

Original design was based on the following Natural Gas composition

Description Design

Composition (%mol)
C1 87.02
C2 7.85
C3 0.86
i-C4 0.02
n-C4 0.02
C5 0.00
CO2 2.86
N2 1.37
H2S,wtppm 8

Molecular weight g/mol 18.37

Reformer inlet temperature = 560 °C @ 25.9 barg.


Reformer outlet temperature = 875 °C @ 23.4 barg.

PSA unit 09-PK-01 should have a minimum hydrogen recovery of 88.5 %

Original Hydrogen Product specification is as follows:

Description Units Target

Hydrogen Purity %Vol. 99.9 (min)

Impurities (CO+CO2) ppmVol. 10 (max)

Intended Hydrogen product flowrate = 64732 Nm3/h

4. Measurements

4.1.1 The mean of the measured/recorded values as per Section 5.3.2, will represent the
measured performances of the plant. These will be compared to the values taking into
account the accuracy of measurement.

4.1.2 Other main parameters: flow, temperature and pressure, though not used for guarantee,
should also be recorded two hourly.

4.1.3 Correction factors for flow meter readings can be calculated according the formulas given
in Section 5.1.
Project n° - Unit Material code Serial N° Rev. Page

202812C 001 JSD 0000 0010 00 8 / 12

Engineering Specification Performance Test Run Protocol

5. Worksheets

5.1 Correction Factors for Flow Meter Readings

The flow rate indicated in DCS is normally calculated from an actual measured value, like
pressure drop over an orifice plate, using the density of the gas or liquid. The density is
affected by changes in pressure, temperature, as well as composition of the medium
passing through the orifice flow meter. Not all corrections for density are included in DCS
and additional corrections by the operator may be required. The overall required correction
for density is dependent on the flow meter type and are listed below.
Correction factors for flow meters based on differential pressure requiring a square root
correction for density (orifice plate, annubar, Pitot, venturi):

• Meter reads in mass units, (for instance kg/h) for liquids:


D
W = WD
DD

• Meter reads in mass units, (for instance kg/h), for gases:


P TD M
W = WD
PD T M D

• Meter reads in volume units, (for instance liquid meters)


DD
Q = QD
D

• Meter reads in standard volume units, (for instance gas meters in Nm3/h)
P TD M D
N = ND
PD T M

Correction factors for flow meters based on volumetric flow requiring a linear correction
for density (Vortex):

• Meter reads in mass units, (for instance kg/h) for liquids:


D
W = WD
DD

• Meter reads in mass units, (for instance kg/h), for gases:


P TD M
W = WD
PD T M D

• Meter reads in volume units, (for example liquid, reading actual volume rate)
Project n° - Unit Material code Serial N° Rev. Page

202812C 001 JSD 0000 0010 00 9 / 12

Engineering Specification Performance Test Run Protocol

No correction required

• Meter reads in standard volume units, (for gas meters with conversion into in Nm3/h)
P TD
N = ND
PD T

Correction factors for flow meters based on mass flow requiring a linear correction for
density (corriolis):

The measurement principle results in a direct measurement of the mass flow. When DCS
indication is in volumetric units, it is generally based on a density derived from the meter
that may be in accurate. The reported density or molecular weight from DCS should be
used for additional flow meter correction for the actual calculated density from the
laboratory data.

• Meter reads in mass units, (for instance kg/h) for liquid and gases

No correction required

• Meter reads in volume units, (for instance liquid meters)

DD
Q = QD
D

• Meter reads in standard volume units, (for instance gas meters in Nm3/h)

MD
N = ND
M
Where:
W = Actual mass flow in kg/h
WD = Mass flow indicated by meter, (equal to meter reading * meter factor), (kg/h)
P = Actual absolute pressure (upstream flow meter)
PD = Design absolute pressure (upstream flow meter)
T = Actual absolute temperature, (°C + 273.15)
TD = Design absolute temperature, (°C + 273.15)
M = Actual molecular weight from analysis
MD = Design molecular weight
Q = Actual volume flow, in m3/h
QD = Volume flow at conditions indicated by meter, (equal to meter reading * meter
factor), in m3/h
N = Actual volume flow at standard condition, in Nm3/h
ND = Volume flow at standard conditions indicated by meter,
(equal to meter reading * meter factor), in Nm3/h
D = Actual density, in kg/m3
DD = Density for which the meter was designed, in kg/m3
Project n° - Unit Material code Serial N° Rev. Page

202812C 001 JSD 0000 0010 00 10 / 12

Engineering Specification Performance Test Run Protocol

5.2 Measurement Accuracy and Calibration Requirements for Instruments

Table 1 indicates the measurement accuracy and calibration and installation requirements
for the indicated instruments.

Table 1
Measurement accuracy, calibration and installation requirements of unit
instrumentation for determining performance standards
MEASURING FLUID MEASUREMENT INSTALLATION/-
INSTRUMENT ACCURACY CALIBRATION
(NOTE 1) REQUIREMENT
Orifice Plate Liquid ± 2% of Full Scale (FS) ISO 5167
Gas ± 3% of FS ISO 5167
Vortex Liquid ± 1% of R Manufacturer’s
standards
Gas ± 2% of R “ “
Coriolis (mass flow) Liquid ± 0.3% of R “ “
Gas ± 0.4% of R “ “
Thermal (mass flow) Gas ± 1.0% of FS “ “
Gas chromatography Gas / ± 1% of R “ “
Liquid
NOTES:
1. Measurement accuracy will be as stated in this column or as specified by the
manufacturer whichever is greater.

5.3 Test Report

The following data shall be collected during the test run:

1. Analyses of natural gas and hydrogen product


2. Hourly readings.
3. Additional samples and analyses to be taken.

5.3.1 Analyses of Feed, Fuel, (Intermediate) Products

Full composition analysis of natural gas and hydrogen product shall be made every 8
hours. The results shall be tabulated in excel format.
Project n° - Unit Material code Serial N° Rev. Page

202812C 001 JSD 0000 0010 00 11 / 12

Engineering Specification Performance Test Run Protocol

5.3.2 Hourly readings

For DCS readings hourly average shall be collected throughout the test run and stored
electronically for the following items as a minimum:

Reading Parameters Tagnumber Units REFERENCE Actual


(1)

Flow, FI055 Nm3/h 26910


Natural Gas Flow
Temperature, TI095 °C 27
from B.L.
Pressure PI082 barg 29
Recycle hydrogen Flow, FIC002 Nm3/h 667
Temperature, TI002 °C 38
Coil /E-06 out Temperature TI105 °C 338
Desulphurized feed Flow, FIC007 kg/h 18290
to mixing tee Temperature, TI017 °C 370
Opening FV007 % 50

Steam to mixing tee Flow FI010 kg/h 56573


Coil /E-03 feed Temperature TI019 °C 343
Reformer feed Temperature TI106 °C 560
Reformer outlet Temperature TI024 & -025 °C 875
X-over Temperature TI036 & -044 °C 1000
CH4 at PGB outlet AI008 mol% 4.2
(dry)
HTS Reactor Temperature TIC046 °C 350
inlet/outlet Pressure in PI030 barg 23.2
TIO051 °C 422

Process gas to PSA Flow FI028 Nm3/h 97733

Hydrogen product to Flow, FI030A Nm3/h 64732


B.L. Pressure PI092 barg 20
Make-up fuel Flow FI038 Nm3/h 4663

Purge gas Flow, FI041-042 Nm3/h 33000


Opening PV044 % 0
APH Flue gas in Temperature TI040 °C 338
APH Flue gas out Temperature TIC042 °C 150
Combustion Air APH Flow FI043 – 044 Nm3/h 123233
In Temperature TI076 °C 30
Out Temperature TI041 °C 300
Excess Oxygen AIC002 %v 1.52
ID Fan in Pressure PI025 mm WC -282
Note 1: The values above represent REFERENCE CASE values and are not guaranteed
values. If any of the values deviate not attributable to equipment supplied by TEN-NL, TEN-
NL can reconcile the Test Run results as stated in section 2.3.14.

These readings shall be retrieved from DCS/Field and supplied in excel format.

When additional DCS data is required based on test data reconciliation results, client shall
provide the additional data promptly on TEN-NL's request.
Project n° - Unit Material code Serial N° Rev. Page

202812C 001 JSD 0000 0010 00 12 / 12

Engineering Specification Performance Test Run Protocol

5.3.3 Additional Samples, Readings and Analyses to be taken

Item Number 1) Unit

Hydrogen Product -
PSA 01 Feed composition % dry
PSA 01 Purge Gas % dry
composition
Relative humidity %

Note: 1) To be taken every 8 hours.

The results shall be tabulated in excel format.

You might also like