Ad200 Adt Manual
Ad200 Adt Manual
This series of inverter is used to control the variable speed operation of three-phase
motor and cannot be used for single-phase motor or other applications. Otherwise,
inverter failure or fire may be caused.
This series of inverter cannot be simply used in the applications directly related to
the human safety, such as the medical equipment.
This series of inverter is produced under strict quality management system. If the
inverter failure may cause severe accident or loss, safety measures, such as
redundancy or bypass, shall be taken.
Note
If the inverter is found to be damaged or lack parts, the inverter cannot be installed.
Otherwise, accident may be caused.
Installation
Note
When handling and installing the product, please hold the product bottom. Do not
hold the enclosure only. Otherwise, your feet may be injured and the inverter may
be damaged because of dropping.
The inverter shall be mounted on the fire retardant surface, such as metal, and kept
far away from the inflammables and heat source.
The inverter shall be mounted on the fire retardant surface, such as metal, and kept
far away from the inflammables and heat source.Keep the drilling scraps from
falling into the inside of the inverter during the installation; otherwise, inverter
failure may be caused.
When the inverter is installed inside the cabinet, the electricity control cabinet shall
be equipped with fan and ventilation port. And ducts for radiation shall be
constructed in the cabinet.
Wiring
Danger
The wiring must be conducted by qualified electricians. Otherwise, there exists the
risk of electric shock or inverter damage.
Before wiring, confirm that the power supply is disconnected. Otherwise, there
exists the risk of electric shock or fire.
The grounding terminal PE must be reliably grounded, otherwise, the inverter
enclosure may become live.
To ensure the safety, the inverter and the motor must be grounded. Please do not
touch the main circuit terminal. The wires of the inverter main circuit terminals
must not contact the enclosure. Otherwise, there exists the risk of electric shock.
The connecting terminals for the braking resistor are (+)and PB. Please do not
connect terminals other than these two. Otherwise, fire may be caused.
Note
Power supply can only be connected after the wiring is completed and the cover is
installed. It is forbidden to remove the cover in live condition; otherwise, there
exists the risk of electric shock.
When auto failure reset function or restart function is set, isolation measures shall
be taken for the mechanical equipment, otherwise, personal injury may be caused.
When the inverter is powered on, even when it is in the stop state, the terminals of
the inverter are still live. Do not touch the inverter terminals; otherwise electric
shock may be caused.
The failure and alarm signal can only be reset after the running command has been
cut off. Otherwise, personal injury may be caused.
Note
Do not start or shut down the inverter by switching on or off the power supply,
otherwise, the inverter may be damaged.
Before operation, please confirm if the motor and equipment are in the allowable
use range, otherwise, the equipment may be damaged.
The heatsink and the braking resistor have high temperature. Please do not touch
such device; otherwise, you may be burnt.
When it is used on lifting equipment, mechanical contracting brake shall also be
equipped.
Please do not change the inverter parameter randomly. Most of the factory set
parameters of the inverter can meet the operating requirement, and the user only
needs to set some necessary parameters. Any random change of the parameter may
cause the damage of the mechanical equipment.
In the applications with industrial frequency and variable frequency switching, the
two contactors for controlling the industrial frequency and variable frequency
switching shall be interlocked.
Maintenance, Inspection
Danger
In the power-on state, please do not touch the inverter terminals; otherwise, there
exists the risk of electric shock.
If cover is to be removed, the power supply must be disconnected first.
Wait for at least 10 minutes after power off or confirm that the CHARGE LED is off
before maintenance and inspection to prevent the harm caused by the residual
voltage of the main circuit electrolytic capacitor to persons.
The components shall be maintained, inspected or replaced by qualified electricians.
Note
The circuit boards have large scale CMOS IC. Please do not touch the board to
avoid the circuit board damage caused by electro static.
Contents
Charper 1 Introduction to AD200 Series Inverter ............................................... 1
1.1 Product Model Description ...................................................................... 1
1.2 Product Nameplate Description .............................................................. 1
1.3 Product Series ........................................................................................ 2
1.4 Technical Specifications of Product ......................................................... 3
1.5 Product Outline, Mounting Dimension ..................................................... 6
1.6 Operating Panel Outline and Mounting Dimension .................................. 7
1.7 Operating Panel Outline and Mounting Dimension .................................. 7
1.8 Selection Of Braking Resistor ................................................................. 8
Chapter 2 Inverter Installation ............................................................................. 9
2.1 Environment for Product Installation ....................................................... 9
2.2 Mounting Direction and Space ................................................................ 9
Chapter 3 Wiring of Inverter .............................................................................. 10
3.1 Connection of the Product and Peripheral Devices ............................... 10
3.2 Terminal Configuration Of Main Circuit .................................................. 11
3.3 Attention for Main Circuit Wiring ............................................................ 12
3.4 Terminal Wiring ..................................................................................... 14
3.5 Functions of Control Circuit Terminals ................................................... 16
3.6 Control board schematic drawing .......................................................... 20
3.7 code switch function explanation .......................................................... 20
Chapter 4 Operation and Display ...................................................................... 21
4.1 Introduction to Operation and Display Interface .................................... 21
4.3 Display status of keyboard .................................................................... 24
4.4 Password Setting.................................................................................. 25
Chapter 5 List of Parameters ............................................................................. 26
Chapter 6 Parameter description ...................................................................... 49
6.1 Group 0 Basic Function ........................................................................ 49
6.2 Group 1 Start and Stop Control ............................................................. 55
6.3 Group 2 Auxiliary Function .................................................................... 59
6.4 Group 3 Vector Control Parameters ...................................................... 62
6.5 Group 4 V/F Control Parameters .......................................................... 65
6.6 Group 5 Motor Parameters ................................................................... 68
6.7 Group 6 Input Terminal ......................................................................... 70
6.8 Group 7 Output Terminal....................................................................... 78
6.9 Group F8 PID Parameters .................................................................... 83
6.10 Group F9 Multi-step speed and PLC ................................................... 87
6.11 Group FA Swing Frequency Operating ................................................ 91
6.12 Group FC Protection and Fault Parameters ........................................ 93
6.13 Group FD Communication Parameters ............................................... 96
6.14 Group FE Keyboard and Display ........................................................ 97
6.15 Group FF Running History Record ...................................................... 99
6.16 Group FP Protection Parameters ...................................................... 100
Chapter 7 Fault information and solutions ..................................................... 102
7.1 Fault information and solutions. .......................................................... 102
7.2 Warnning information .......................................................................... 104
7.3 The general fault diagnosis and solutions ........................................... 105
Chapter 8 Routine Repair and Maintenance ................................................... 107
8.1 Routine Maintenance .......................................................................... 107
8.2 Periodic Maintenance ......................................................................... 108
8.3 Component Replacement ................................................................... 109
8.4 Warranty ............................................................................................. 110
Apenndix A Modbus Communication Protocol ............................................... 111
AD200 Performance Vector Control /Torque Control Inverter User manual
The digits and letters in the inverter model field on the nameplate indicate such
information as the product series, power supply class, power class and software/hardware
versions.
Open-loop
Closed-loop
Control mode vector V/F control
vector control
control
Startup torque 0.5Hz 1.5Hz
----
Control features
150% 150%
Speed adjustment range ---- 1:100 1:50
Speed stabilization
---- ± 0.2% ± 0.5%
precision
Torque control ---- Yes No
Acceleration/deceleration
functions
0.01~360.0s
time
Inverter of 400V voltage grade: Braking unit
Powered braking action voltage: 650 ~ 750V
capacity Inverter of 200V voltage grade: Braking unit
action voltage: 360 ~ 390V
DC braking initial frequency:0.00~300.0Hz;
DC braking current : Constant torque:0.0 ~
100.0%;Variable torque: 0. 0~80.0%
DC braking capacity
DC braking time:0.0~30.0s;there is no initial
waiting time for the DC braking to realize quick
braking
Magnetic flux braking Ongoing action and no action upon deceleration
function as option, no action upon deceleration at default
The unique multifunctional key is used to set
Multifunctional MFK the frequently used operations: JOG, emergency
key shutdown, running command reference mode
Unique switch
functions The standard operation panel can realize the
parameter upload, download. The user can
Parameter copy
select to forbid the overwriting of the uploaded
parameters.
规格 H W D H1 A B d
AD200-S2 0R4 GB
AD200-S2 R75 GB
AD200-S2 1R5 GB
150 83 120 166 65 153 5
AD200-T4R75GB/1R5PB
AD200-T41R5GB/2R2PB
AD200-T4 2R2 GB -M
AD200-S2 2R2 GB
AD200-T41R5GB/2R2PB-S
200 120 140 215 98 202 5
AD200-T4 2R2 GB / 4R0 PB
AD200-T4 4R0 GB / 5R5 PB
Note:
AD200 inverter support standard slideway installer.
KB-SAL01 is the mounting pallet when the operation panel is to install on the electric
control cabinet. The outline and dimension are as follows:(Unit:mm):
Avoid installing the product in the sites with oil mist, metal powder and dust.
Avoid installing the product in the sites with hazardous gas and liquid, and corrosive,
combustible and explosive gas.
Avoid installing the products in salty sites.
Do not install the product in the sites with direct sunlight.
Do not mount the product on the combustible materials, such as wood.
Keep the drilling scraps from falling into the inside of inverter during the installation.
Mount the product vertically in the electric control cabinet, mount the cooling fan or air
conditioner to prevent the ambient temperature from rising to above 40 ºC.
For the sites with adverse environment, it is recommended to mount the inverter
Radiator heatsink outside the cabinet.
In order not to reduce the inverter cooling effect, the inverter must be mounted vertically,
and certain space must be maintained, as shown in Fig. 2-1
Fig.2-1 Mounting Direction and Space Fig.2-2 Installation Diagram of Upper and Down
Power supply
circuit breaker or
leakage circuit breaker
Contactor
Inverter
Grounding
Braking resistor
Output AC reactor
Motor
Grounding
It is forbidden to connect the power cable to the inverter output terminal, otherwise, the
internal components of the inverter will be damaged.
To facilitate the input side over current protection and power failure maintenance, the
inverter shall connect to the power supply through the circuit breaker or leakage circuit
breaker and contactor.
Please confirm that the power supply phases, rated voltage are consistent with that of the
nameplate, otherwise, the inverter may be damaged.
It is forbidden to short circuit or ground the inverter output terminal, otherwise the
internal components of the inverter will be damaged.
Avoid short circuit the output cable and the inverter enclosure, otherwise there exists the
danger of electric shock.
It is forbidden to connect the output terminal of the inverter to the capacitor or LC/RC
noise filter with phase lead, otherwise, the internal components of the inverter may be
damaged.
When contactor is installed between the inverter and the motor, it is forbidden to switch
on/off the
contactor during the running of the inverter, otherwise, there will be large current
flowing into the inverter, triggering the inverter protection action.
Length of cable between the inverter and motor
If the cable between the inverter and the motor is too long, the higher harmonic leakage
current of the output end will cause adverse impact on the inverter and the peripheral
devices. It is suggested that when the motor cable is longer than 100m, output AC reactor
be installed. Refer to the following table for the carrier frequency setting.
Carrier frequency
Less than 10kHz Less than 6kHz Less than 4kHz
(F0.15)
Terminal
Terminal
Type function Technical specification
symbol
description
Multi-functional
Frequency range:0~200Hz
X1~X5 input terminals
Voltage rang:0~12V
Digital 1~5
input/output Open collector maximum sink current:50mA
Y1
output Output Voltage range:0~24V
GND Grounding
Analog input
open circuit output voltage come to
10V reference
11V. Internal .Maximum load 30mA.
voltage
Analog input Input Voltage range:0~10V
AI1
channel 1 Input impedance:100kΩ
Input Voltage range:0~10V
Analog
Input impedance:100kΩ
input Input current range:0~30mA
Analog input
AI2 Current Input impedance:500Ω
channel 2
0~20mA or 0~10V analog input can
be selected through DIP switch
SW1
GND Grounding
0 ~ 20mA : allowable output
impedance 200~500Ω
0 ~ 10V : allowable output
Analog AO Analog output
impedance ≥10kΩ.
output 0~20mA or 0~10V analog output can
be selected through DIP switch SW2
GND Grounding
TA-TB:Normally closed
Relay TA-TC:Normally open
TA/TB/TC Relay output
output Contact capacity : 250VAC/1A ,
30VDC/1A
Keyboard Interface
Table 3-10 T568B standard
Number Corresponding
1 White/Orange
2 Orange
3 White/Green
4 Blue
5 White/Blue
6 Green
The cables connecting keyboard and control board use standard super-five-class network
cable. RJ-45 Interface uses through-line method, namely both sides are connected according
to EIA/TIA568B standard. You can make the cable by yourself if you need, May also
purchase in the market condition the general mesh wire to use in operating kneading board's
connection.
The keyboard of AD200 series inverters is the main unit of accepting order, displaying
and modificating parameters. The keyboard designed for these series inverters is LED
keyboard. The LED keyboard is the standard fitting, and the LED keyboard is options for
special use. For the convenience of introducing, we just introduce the LED keyboard for the
different dimensions and operation. The keyboard figure described Fig.4-1.
Symbol of
Meanings
Indicator
On: Inverter is running
RUN
Off: Inverter has stopped
On: Inverter is running forward steadily
FWD Off: Inverter is running reverse or stop
Flash: Speed up or speed down forward
Status
Four-digit LED display, able to display setup frequency, output frequency, various
monitoring data and alarm code.
The operation panel of the AD200 inverter adopts three-level menu structure to carry
out operations such as parameter setting.The three-level menu is:
1. function parameter set (level 1 menu)
2. Function code (level 2 menu)
3. Function code setup value (level 3 menu)
Caution: When operating on level 3 menu, press PRG key or ENTER key to return to
level 2 menu. The difference between PRG key and ENTER key is described as follows:
Pressing ENTER KEY will save the setup parameter and return to the level 2 menu and then
automatically shift to the next function code, while pressing PRG key will directly return to
level 2 menu without saving the parameter, and it will return to the current function code.
Example: Modify the function code F9.01 from 10.00Hz to 20.00Hz. (The Bigger-type
work indicates the flashing bit.), refer to Fig.4-2 for the operation procedure.
In level 3 menu, if the parameter has no flashing bit, it indicates that the function code
cannot be modified. The possible reasons include:
1) The function code is an unchangeable parameter, such as actual detection parameter,
running record parameter, etc.
2) The function code cannot be modified in running status. It can be modified only
after the unit is stopped.
The display status of AD200 series inverters are the stopped state parameter display,
the running status parameter display, the function code edition display and the fault warning
condition display respectively.
1. The stop status parameter display
The keyboard displays the stop state parameter display, press “>>” to display
circularly different the stop state parameter when the inverter enters into this state.
2. The running state parameter display
The keyboard displays the running state parameter display, press “>>” to display
circularly different running state parameter when the inverter is running.
3. Fault and warning state
If the inverter has checked out a warning signal, it will come into warning state and
show the warning code flickeringly. If the warning signal disappeared, the warning code
will automatically disappear.
If the inverter has checked out an error, it will come into fault state and show the fault
code steadily. And the indicator TRIP will light up.By depressing the “>>”key, user can
view the parameters value of stop state; If you want to see the details of fault information,
depress the “PRG” key, the keyboard will go to programming state, to see the details, please
see the parameter values of group FF.
To reset the inverter, depress the “STOP” key or control terminals or serial
communication. If the fault signal is still exist, the keyboard will keep the fault code
displaying and the indicator TRIP lighting.
4. the function code edition state
When in the stop, running fault or warning state, depress the “PRG” key, the inverter
will come into programming state. Depress the “ENTER” key, the display menu will be
changed gradually. When in function parameter value menu, depress the “ENTER” key
can save the value of the parameter; Depress the “PRG” key will exit from one menu to
another.
The inverter provides user password protection function. When FP.00 is set to non-zero
value, it indicates the user password, and the password protection turns valid after exiting
the function code editing status. When pressing PRG key again, “0000“ will be displayed,
and common menu cannot be entered until user password is input correctly.
To cancel the password protection function, enter with password and set FP.00 to “0”.
Attention:
“○”means that the parameters can be changed during inverter running and stopping state;
“×”means that the parameters cannot be changed during running;
“*” means that the actually measured value or fixed parameters cannot be changed;
“-” means that the parameter is set by the manufacturer and cannot be changed by the user
Function Factory
Function code name Setting range Property
Code default value
1: Al1
2: Al2
3: PULSE setup
4: Communication setup
F0.04 Frequency setting 2 1 ○
5:MS (Multi-step) Speed
6: Reserved
7: Reserved
8:keyboard potentiometer
0:Frequency setting1
1:Frequency setting2
2: Frequency setting1+ Frequency
setting2
3:Switching between Frequency setting 1
and Frequency setting 2
Frequency setting
F0.05 4: Switching between (Frequency 0 ○
selection
setting1+ Frequency setting2) and
Frequency setting1
5:MIIN(Frequency setting1, Frequency
setting2)
6:MAX(Frequency setting1, Frequency
setting2)
UP/DOWN Preset
F0.06 0~Max frequency 50.00Hz ○
frequency
Terminal UP/DOWN
F0.07 0.01~50.00Hz/s 1.00Hz/s ○
rate
0:Active keyboard and terminal
UP/DOWN keyboard UP/DOWN
F0.08 1 ○
and terminal select 1:Active only in keyboard UP/DOWN
2: Active only in Terminal UP/DOWN
UP/DOWN Power 0: Power failure record
F0.09 failure record 1: Power failure non-record 0 ○
selection 2:Stop non-record
F0.10 Basic frequency 0.10~600.0Hz 50.00Hz ×
MAX[50.00Hz, Frequency upper limit,
F0.11 Max frequency 50.00Hz ×
Reference frequency]~600.0Hz
F0.12 Frequency upper limit Frequency lower limit ~ max frequency 50.00Hz ×
Function Factory
Function code name Setting range Property
Code default value
Carrier frequency
0: adjustment
F0.16 auto-adjustment 0 ○
1: non- adjustment
selection
Keyboard direction 0: Forward
F0.17 0 ○
setting selection 1: Reverse
Wiring direction of 0: Positive sequence
F0.18 0 ×
motor 1: Antitone sequence
F0.19 Acceleration time1 0.01~360.0s 6.00 ○
Function Factory
Function code name Setting range Property
Code default value
Type G: 0.0~100.0% of inverter rated
DC brake current at current
F1.11 0.0% ○
stop Type P: 0.0 ~ 80.0% of inverter rated
current
F1.12 DC brake time at stop 0.0~30.0s 0.0s ○
Energy consumption 0: Disabled
F1.13 0 ○
braking selection 1: Enabled
Energy consumption
380V: 650~750V 380V: 700V
F1.14 braking unit action ○
220V: 360~390V 220V: 380V
voltage
Restart automatically
0: Disable
F1.15 after power resumes 0 ○
1: Enable
normal
Waiting time for
F1.16 0.0~3600s 1.0s ○
restart
Function Factory
Function code name Setting range Property
Code default value
Forward/ Reverse
F2.13 rotation dead-zone 0.0~3600s 0.0s ○
time
Start frequency lower
0: Run with frequency lower limit
F2.14 than frequency lower 0 ×
1: Zero frequency operation
limit action
Running time to 0: Continue running
F2.15 0 ×
action selection 1: Stop
F2.16 Reserved Reserved Reserved -
0: Disabled
F2.17 AVR Function 1: Enabled 2 ×
2: Disabled only at speed-down
Over modulation 0: Enabled
F2.18 1 ×
enabled 1: Disabled
F2.19 Reserved Reserved Reserved -
Function Factory
Function code name Setting range Property
Code default value
Speed loop
F3.03 0.1~9.9 1.0 ○
proportional gain 2
Speed loop integral
F3.04 0.01~10.00s 0.3s ○
time 2
Switching frequency
F3.05 0.0~60.00Hz 10.00Hz ○
2
F3.06 ASR filtering time 0~500ms 1ms ○
Current loop
F3.07 proportional 0~2000 500 ○
coefficient
0:Torque control Disabled
1:Torque digital setting(F3.11)
2:AI1
Current loop integral
F3.08 3:AI2 0 ○
coefficient
4:PULSE
5:serial communication
6:keyboard potentiometer
0:Torque control Disabled
1:Torque digital setting(F3.11)
2:AI1
Slip compensation
F3.09 3:AI2 0 ○
coefficient
4:PULSE
5:serial communication
6:keyboard potentiometer
0:Torque control Disabled
1:Torque digital setting(F3.11)
2:AI1
F3.10 Torque control 3:AI2 0 ○
4:PULSE
5:serial communication
6:keyboard potentiometer
F3.11 Torque digital setting 0.0~200.0% 50.0% ○
0:digital setting(F3.13)
1:AI1
Torque control upper
F3.12 2:AI2 0 ○
speed limit
3:PULSE
4:Serial communication
upper speed limit
F3.13 0.00~600.0Hz 50.00Hz ○
setting
F3.14 Reserved Reserved Reserved -
Function Factory
Function code name Setting range Property
Code default value
F3.15 Reserved Reserved Reserved -
Function Factory
Function code name Setting range Property
Code default value
Cutoff frequency of
F4.08 0.00~60.00Hz 50.00Hz ○
torque boost
Slip compensation
F4.09 0.0~200.0% 0.0% ○
coefficient
V/F voltage
F4.04 0.0~100.0% 50.0% ×
point 2
Slip compensation
F4.10 0.01~2.55s 0.20s ○
filtering time
Function Factory
Function code name Setting range Property
Code default value
30: External stop terminal When it is in
the keyboard control mode, this terminal
can be used to stop, which is similar to
STOP key on the keyboard.
31: Reserved
32: PLC status reset
33: Swing frequency pause
34: Swing frequency status reset
35: PID pause
36: PID parameters switching
37: PID action direction reverse terminal
If this terminal is enabled, PID action
direction is opposite to the direction set in
F8.04.
38: Timing drive input
39: Counter trig signal input
40: Counter clear
Analog Nonlinear 0: none 1: AI1
F6.10 0
Selection 2: AI2
F6.11 AI1 minimum input 0.00~F6.13 0.00V ○
AI1 minimum Input
F6.12 0.0~200.0% 0.0% ○
corresponding setup
F6.13 AI1 maximum input F6.11~10.00V 10.00V ○
AI1 maximum Input
F6.14 0.0~200.0% 100.0% ○
corresponding setup
F6.15 AI1 input filter time 0.01~50.00s 0.05s ○
Function Factory
Function code name Setting range Property
Code default value
F3.24 Reserved Reserved Reserved -
Function Factory
Function code name Setting range Property
Code default value
Frequency arrival
F7.05 0.00~10.00Hz 2.50Hz ○
detection width
Frequency detection
F7.06 0.00~600.0Hz 5.00Hz ○
value 1 (FDT1 level)
Frequency detection
F7.07 hysteresis1(FDT1-hys 0.00~10.00Hz 1.00Hz ○
teresis)
Frequency detection
F7.08 0.00~600.0Hz 25.00Hz ○
value 2 (FDT2 level)
Frequency detection
F7.09 hysteresis1(FDT2-hys 0.00~10.00Hz 1.00Hz ○
teresis)
Up detection
F7.10 0.00~600.0Hz 50.00Hz ○
frequency
Down detection
F7.11 0.00~600.0Hz 0.00Hz ○
frequency
Torque detection
F7.12 0.0~200.0% 100.0% ○
reference
F7.13 Preset Count value 0~9999 0 ○
Function Factory
Function code name Setting range Property
Code default value
9: Output power (0 ~ 2*Inverter rated
power)
10: Bus voltage (0~1000V)
11: 9: AI1 (0~10V)
12: AI2 (0~10V/0~20mA)
13: Pulse input
AO1 output range 0: 0~10V/0~20mA
F7.22 0 ○
selection 1: 2~10V/4~20mA
F7.23 Reserved Reserved Reserved -
Function Factory
Function code name Setting range Property
Code default value
Analog closed loop
F8.03 1.0~999.9 100.0 ○
measuring range
F8.04 PID action direction 0: Positive 1: Negative 0 ○
PID proportional gain
F8.05 0.1~9.9 1.0 ○
1 (KP1)
F8.06 PID integration time 1 0.00~100.0s 10.00s ○
PID differential time
F8.07 0.00~1.00s 0.00s ○
1
PID proportional gain
F8.08 0.1~9.9 1.0 ○
2 (KP2)
F8.09 PID integration time 2 0.00~100.0s 10.00s ○
PID differential time
F8.10 0.00~1.00s 0.00s ○
2
0: No switching, use the first group
PID parameters parameters
F8.11 0 ○
switching 1: switching by terminal
2: auto-switching by deviation
Deviation 1 using PID
F8.12 0.0~999.9 20.0 ○
switching
Deviation 2 using PID
F8.13 0.0~999.9 80.0 ○
switching
PID delay time
F8.14 0.00~100.0s 0.00s ○
constant
F8.15 Deviation limit 0.0~999.9 0.2 ○
PID output positive
F8.16 0.00~600.0Hz 50.00Hz ○
limit
PID output negative
F8.17 0.00~600.0Hz 0.00Hz ○
limit
F8.18 PID preset frequency 0.00~300.0Hz 0.00Hz ×
Hold time of PID
F8.19 0.0~3600s 0.0s ×
preset frequency
F8.20 Enable dormancy 0: Disabled 1: Enabled 0 ×
Function Factory
Function code name Setting range Property
Code default value
Step T1 program
F9.18 1 F/r ~ 4 F/r 1F ○
running setting
Step T2 program
F9.19 1 F/r ~ 4 F/r 1F ○
running setting
Step T3 program
F9.20 1 F/r ~ 4 F/r 1F ○
running setting
Step T4 program
F9.21 1 F/r ~ 4 F/r 1F ○
running setting
Step T5 program
F9.22 1 F/r ~ 4 F/r 1F ○
running setting
Step T6 program
F9.23 1 F/r ~ 4 F/r 1F ○
running setting
Step T7 program
F9.24 1 F/r ~ 4 F/r 1F ○
running setting
F9.25 Record of PLC steps 1~7 0 *
Function Factory
Function code name Setting range Property
Code default value
Over-voltage point at 380V:140.0%
FC.07 110.0~150.0%(Bus voltage) ×
stall 220V:120.0%
Input phase loss
FC.08 1~100% 20% ×
detection level (SPI)
Input phase loss
FC.09 2~255s 10s ×
detection delay time
Output phase loss
FC.10 0~100% 0% ×
detection level (SPO)
Output phase loss
FC.11 0.0~2.0s 0.2s ×
detection delay time
Fault auto reset 0~10,“0” means “auto reset” is disabled.
FC.12 0 ×
times Only 3 faults have auto reset function
Fault auto reset
FC.13 2.0~20.0s 5.0s ×
interval
0: No precession
1: Auto reset after input voltage is
UU1 fault procession recovered
FC.14 0 ○
selection 2: Auto reset and run after input voltage is
recovered (auto running interval relative
to F1.16)
Function Factory
Function code name Setting range Property
Code default value
0.0~100.0s
Communication
Fd.04 0: No timeout Setting 0.0s ○
Timeout time
Others: Detection time
Fd.05 Response delay 0~500ms 5ms ○
Communication
Fd.06 frequency setting 0.0~200.0% 100.0% ○
coefficient
Function Factory
Function code name Setting range Property
Code default value
0: No display
Output frequency 1: Display only on stop
FE.04 0 ○
(Hz) (Actual) 2: Display only on run
3: Display on stop and run
0: No display
Reference frequency 1: Display only on stop
FE.05 1 ○
(Hz, flashes) 2: Display only on run
3: Display on stop and run
0: No display
1: Display only on stop
FE.06 Output current(A) 2 ○
2: Display only on run
3: Display on stop and run
0: No display
1: Display only on stop
FE.07 Bus voltage (V) 0 ○
2: Display only on run
3: Display on stop and run
0: No display
1: Display only on stop
FE.08 Output voltage (V) 0 ○
2: Display only on run
3: Display on stop and run
0: No display
1: Display only on stop
FE.09 Output torque (%) 0 ○
2: Display only on run
3: Display on stop and run
0: No display
Reference torque (Hz, 1: Display only on stop
FE.10 0 ○
flashes) 2: Display only on run
3: Display on stop and run
0: No display
1: Display only on stop
FE.11 Rotate speed (r/min) 0 ○
2: Display only on run
3: Display on stop and run
0: No display
Reference speed 1: Display only on stop
FE.12 0 ○
(r/min flashes) 2: Display only on run
3: Display on stop and run
0: No display
1: Display only on stop
FE.13 Output power (kW) 0 ○
2: Display only on run
3: Display on stop and run
Function Factory
Function code name Setting range Property
Code default value
0: No display
1: Display only on stop
FE.14 AI1 (V) 0 ○
2: Display only on run
3: Display on stop and run
0: No display
1: Display only on stop
FE.15 AI2 (V) 0 ○
2: Display only on run
3: Display on stop and run
0: No display
1: Display only on stop
FE.16 Analog PID feedback 0 ○
2: Display only on run
3: Display on stop and run
0: No display
1: Display only on stop
FE.17 Analog PID setup 0 ○
2: Display only on run
3: Display on stop and run
0: No display
Terminal status (no 1: Display only on stop
FE.18 0 ○
unit) 2: Display only on run
3: Display on stop and run
FE.19 Reserved Reserved Reserved -
Function Factory
Function code name Setting range Property
Code default value
FF.08 Total power on time 0~65530h 0h *
note:
The value in the”【】” indicates the factory default value of the parameter.
7: PID
Select process PID control. In this case, it needs to set Group F8 “PID
Parameters”. The running frequency of the inverter is that after PID functions
8:keyboard potentiometer
Note:
In frequency setting 1, the Multi-step is prior to others’ frequency source.
In the case of the frequency setting 1+ the frequency setting 1, when the
frequency setting 1 source is digital reference, the preset frequency (F0.06)
has no action, and the value (adjusted by through the keys “▲”and “▼” of
the keyboard or UP and DOWN of multifunctional input terminals) is
overlapped at the frequency 2 as the final frequency.
frequency【50.00Hz】
F0.13 Frequency lower limit Range:0.00~Frequency upper limit
【0.00Hz】
F0.14 Max output voltage Range:110~440V【Model dependent】
The basic frequency (Fb) is the min output frequency when the output voltage of
inverter is equal to rated voltage. Usually, the motor rated frequency can be treated as basic
frequency.
The max frequency (Fmax) is the frequency allowed to be maxi output of this series
inverter.
The frequency upper limit (fH ) and frequency lower limit (fL) are the maximum and
minimum operating frequency of the motor set according to the production process
requirement by the user during the use.
The maximum output voltage Vmax is the output voltage when the inverter is in basic
operating frequency.
The basic frequency, the max frequency, the frequency upper limit, the maximum
output voltage and the basic frequency relationship, as shown in Fig.6-1
Output Voltage(V)
Rated Voltage
Output Freq.(Hz)
Basic Max output
Frequency Frequency
increase.
Note:
If the torque boost is set to be too large, the motor may be over heat, and the
inverter may be over current. In
When the inverter drives synchronous motor, torque boost function is
recommended to be used and V/F curve should be adjusted according to the
motor parameters
Freq. after
compensation Compensation Freq. f
Synchronous
speed
Load torque T
R1 jX 1 jX 2
I1 Rm R2
U1 I2
I0 s
Xm
current without load respectively. The setting of F5.07 is the sum of leakage inductance of
stator and leakage inductance of rotor.
The above parameters F5.06~F5.09 settings are all percentage values calculated by the
following formulas:
V: Rated voltage
I: Motor rated current
Formula used for calculating resistance (resistance of stator or rotor):
R
%R
V / 3I 100%
Formula used for calculating inductance (leakage inductance or mutual inductance):
X
%X
V / 3I 100%
If motor parameters are known, please set F5.06~F5.09 to the values calculated
according to the above formulas.
After motor power F5.02) change, the inverter will change F5.03~F5.09 according to
the motor power.
FWD and REV respectively. However, the pulse is enabled through disconnecting the
signal of HLD terminal when the inverter stops. As shown in Fig.6-15
Setting
Function Description
value
The inverter locks the output, and the motor
stop process is beyond the inverter control. It
13 Coast to stop
is the general method adopted when there is
huge load and no requirement for the stop time.
This terminal is enabled, and the inverter directly
DC injection
14 switches to the DC brake status. Intensity of DC brake
braking
refer to DC braking current(F1.11).
Protect the inverter from affecting by the
Acceleration/deceler
15 external signals (except stop command), and maintain
ation inactive
the current frequency.
Once this terminal is enabled, if the inverter is on
Inverter running running status, the inverter will coast to stop
16
prohibit immediately, if the inverter is on stop status, the
inverter can not run.
Multi-step speed
17
terminal 1
It can realize 16S speed through the combination
Multi-step speed
18 of digital status of these four terminals. Refer
terminal 2
attached table 6-3 for the MS speed function
Multi-step speed
19 description. And K1~K4 corresponds 17~20 function
terminal 3
terminal.
Multi-step speed
20
terminal 4
Acceleration/deceler
22 ation time selection
It can select four types of speed-up/speed-down time
terminal 1
through the combination of digital status of these two
Acceleration/deceler
terminals. Refer to table 6-4 for detail.
23 ation time selection
terminal 2
External pause The inverter decelerates to stop, but al l
24
normally open input the running parameters are al l in the
memory status, such as PLC parameter, swing
External pause
frequency parameter and PID parameter. After this
25 normally closed
signal disappears, the inverter restores to the
input
status before stopping.
External fault
26
normally open input
After the external fault signal is sent to the inverter,
External fault
the inverter reports fault and stops.
27 normally closed
input
Setting
Function Description
value
Running command When Run command source (F0.02) is 0 or 2, the
28 switching to run command is switching to terminal via this
terminal terminal.
Running command When Run command source (F0.02) is 1 or 2, the
29 switching to run command is switching to keyboard via this
Keyboard terminal.
External stop
terminal When it is
in the keyboard
External stop terminal When it is in the keyboard
control mode, this
30 control mode, this terminal can be used to stop, which
terminal can be used
is similar to STOP key on the keyboard.
to stop, which is
similar to STOP key
on the keyboard.
31 Reserved Reserved
PLC pauses during the execution process. When it
32 PLC status reset resumes running, it can effectively restore to the initial
status of simple PLC via this terminal.
The inverter maintains the current frequency. When
Swing frequency
33 the terminal is invalid, the inverter continues the
pause
swing frequency status.
Swing frequency
34 The inverter runs on the center frequency.
status reset
PID is inactive temporarily, and the inverter maintains
35 PID pause
the current frequency output.
PID parameters If the terminal is valid, PID parameters are switched
36
switching to second group.
PID action direction If this terminal is enabled, PID action direction is
37
reverse terminal opposite to the direction set in F8.04.
If the terminal is valid, start the timing, otherwise
38 Timing drive input
zero-clear.
Counter trig signal
39 The input terminal of counting pulse.
input
40 Counter clear Clear the counter status.
Corresponding
K4 K3 K2 K1 Frequency Setup
Parameter
OFF OFF OFF OFF F0.06 F0.06
OFF OFF OFF ON Multi-step frequency 1 F9.00
OFF OFF ON OFF Multi-step frequency 2 F9.01
OFF OFF ON ON Multi-step frequency 3 F9.02
OFF ON OFF OFF Multi-step frequency 4 F9.03
OFF ON OFF ON Multi-step frequency 5 F9.04
OFF ON ON OFF Multi-step frequency 6 F9.05
OFF ON ON ON Multi-step frequency 7 F9.06
ON OFF OFF OFF Multi-step frequency 8 F9.27
ON OFF OFF ON Multi-step frequency 9 F9.28
ON OFF ON OFF Multi-step frequency 10 F9.29
ON OFF ON ON Multi-step frequency 11 F9.30
ON ON OFF OFF Multi-step frequency 12 F9.31
ON ON OFF ON Multi-step frequency 13 F9.32
ON ON ON OFF Multi-step frequency 14 F9.33
ON ON ON ON Multi-step frequency 15 F9.34
1: AI1
All the parameters from F6.11 to F6.20 are setting points for the AI1 channel,
as shown in Fig.6-17. The filter time the parameter F6.15.
2: AI2
All the parameters from F6.11 to F6.20are setting points for the AI2 channel,
as shown in Fig.6-17. The filter time the parameter F6.15.
Terminal)
F6.16 AI2 minimum input (AI2
Setting range: 0.00~F6.18【0.00V】
Terminal)
F6.17 AI2 minimum Input corresponding
Setting range:0.0~200.0%【0.0%】
setup
F6.18 AI2 maximum input (AI2) Setting range: F6.16~10.00V【10.00V】
F6.19 AI2 maximum Input corresponding
Setting range: 0.0~200.0%【100.0%】
setup
F6.20 AI2 input filter time 2 (AI2
Setting range: 0.01~50.00s【0.05s】
Terminal)
The above function codes define the relationship between the analog input voltage and
analog input setup value. When the analog input voltage exceeds the setup maximum input
or minimum input range, the excess part will be calculated as maximum input or minimum
input, as shown in Fig.6-18.
minimum input
corresponding setup
maximum input
corresponding setup
Analog Analog
minimum input maximum input
Bit4~bit15---- Reserved
Setup
Function Description
value
When the running time exceeds the preset time
12 Timing arrival
(F7.14), it output ON signal.
counting value The count value is bigger than the value defined in
13
arrival F7.13, it output ON signal.
Preset operating time When the accumulated running time of the inverter
14
arrival exceeds the setup time F7.15, it outputs ON signal.
Torque arriving When motor's torque i exceeds reference value (set
15
detection threshold by P7.12), it outputs ON signal.
16 Inverter fault output When the inverter is faulty, it outputs ON signal.
Under voltage status When the inverter is in under voltage status, it
17
output outputs ON signal.
If the output current is higher than the value defined
Inverter overload pre
18 by FC.02 (Overload detection), it outputs ON
warning
signal..
Fixed-length arrived,
If the actual length exceeds the preset lengt, t it
19 output a high level
outputs ON signal.
signals
20 PID Standby When PID is standby, it outputs ON signal.
When the analog input AI1 value is higher than AI2
21 AI1>AI2
value, it outputs ON signal.
When the analog input AI1 value is lower than
22 AI1<F7.16
F7.16, it outputs ON signal.
When the analog input AI1 value is higher than
23 AI1>F7.16
F7.16, it outputs ON signal.
When the analog input AI1 value is higher than
24 F7.16<AI1<F7.17
F7.16 and is lower than F7.17, it outputs ON signal.
Frequency lower When the running frequency reaches frequency
25
limit arrival lower limit, it outputs ON signal.
Auxiliary pump control signal for constant pressure
Auxiliary pump
26 water supply, refer to the parameter F7.28&F7.29
control signal
instruction for detail.
Output frequency
Frequency Time
Detection Signal
Time
AO can be used as either voltage output of 0V to10V or current input of 0mA to 20mA,
which can be selected by the jumper on the control board. These output selection details
shown as table 6-7:
Table 6-7 analog output terminal
Setup value Function Discription
0 NULL NULL
1 Running frequency 0~maximun frequency
2 setting frequency 0~maximun frequency
3 output current 0~2* inverter rated current
Out prequency
F0.12
F7.11
tmie
Auxiliary
pump
control
signal tmie
0: AI1 terminal
As 0~10V analog voltage input.
1: AI2 terminal
Through the switch SW1, As 0 ~ 10V analog voltage or 0 ~ 20mA current input.
2: Reserved
3: serial communication
The input value should in 0~100.00% (0~10000) , 100.00% correspond the full
scale of PID.
4: AI1-AI2
AI1-AI2 as PID feedback, if the result is negative the feedback value is negative
5: AI1+AI2
AI1+ AI2 as PID feedback , if the result is bigger than the actual physical
quantities(100%) the PID feedback quantity is the 100% full range.
6: MAX(AI1, AI2)
Take the larger between AI1 and AI2 as the PID feedback.
7: MIN(AI1, AI2)
Take the smaller between AI1 and AI2 as the PID feedback.
The swing frequency operating means that the output frequency of the inverter swings
up and down with the setup frequency as the center. The trace of running frequency at the
time axis is shown As in Figure 6-25, of which the swing amplitude is set by FA-00.When
FA-00 is set to 0, indicating the swing amplitude is 0, the swing frequency is disabled.
1 min
Output current
100% 200%
to 0, it means “auto reset” is disabled and the protective function will be activated in case of
fault.
Note:
Only OC, OU can be auto reset.
This function parameters defines the display in the downtime and operation monitoring
condition。
0: No display
1: Display only in stop process
2: Display only during running
3: Display in stop and run
Explanation:
In stop process, if no parameter is set to show in monitor state, reference
frequency will be displayed. Otherwise, during running , the output frequency
(before compensation) will be displayed.
The unit light for analog PID feed and analog PID feedback is “Hz” +” A”, and
if switch to display analog PID feed, the light will lit up and flashing.
The terminal status are shown by four LED units without unit indicator, the
specific meaning shown in figure 6-26.
X1 X2 X3 X4 X5
常亮
Y1 继电器1
TA/TB/TC
In addition to this function code and FP.03, all parameters shows as "0000" and
can not be modified, this can prevent irrelevant person to check .
Fault
type Possible reasons solutions
code
1.Acceleration time is 1. Increase the
Over Voltage in too short acceleration time
Ou1
Acceleration process 2.Uncommon power of 2. Check the input power
the grid source.
1. Increase the
1.Deceleration time is
Over voltage in acceleration time
Ou2 too short
deceleration process 2. Add suitable brake
2.Large load inertia
packages.
1. Check the input power
Over voltage in 1.Uncommon power of
source.
Ou3 constant speed the grid
2. Add suitable brake
Operation 2.Large load inertia
packages.
1.The converter and the 1. Check whether the
motor wiring have short electric motor coil is
SC Load short-circuit circuit short circuit.
2.Damage of the 2. Ask for the services
contravariant module from manufactures.
1.Too high temperature
1. Lower the working
of the environment
temperature.
OH1 Radiator over heat 2.The damage of air fan
2. Change the fan
3.The passage of fan is
3. Clear the ail channel.
blocked
1. Low voltage grid 1.Check the input power
2. Rated current of source.
electrical machine sets 2. Check whether the
wrongly electric motor’s rated
3.The Curve of V/F is current is correctly set up.
not fit 3. Adjust the V/F curve
4.The normal electrical and torque pull-up.
OL1 Motor overload machine always work 4. Choose the special
with a low speed load electric motor.
5.The mutation of load is 5. Check the load and
too high or blocked shift whether the electric
by electronically motor’s rotor is locked.
machine 6. Select Appropriate
6.The motor power is too capacity Motor and
lower inverter
1. Check the input power
1. Low voltage grid source.
2. Too heavy load 2. Select bigger capacity
3. Accelerates inverter.
OL2 Inverter overload
excessively quickly 3. Increase the
4.Restart the turning acceleration time
electronic machine 4. Avoid starting during
the motor rotation.
Fault
type Possible reasons solutions
code
1. Baud rate and parity
1.Check the
checksum is set
communication
uncorrected
EF0 Communication fault parameters is correct.
2. Be breaked for long
2. Check the interface
time when
wiring.
communication
1. Faults comes from 1. Check the input from
EF1 External terminal fault
external control circuit external devices.
Input phase failure or 1. Input R,S,T have
SP1 1. Check input voltage
Unbalance phase loss or imbalance
1.There is lack of U,V,W
1. Check U,V,W input
Output phase failure when output
SPO wire.
or Unbalance 2.There is a big
2. Check the load
unbalance of output
Transmission between
1.Connection cable 1. Check the connection
the inverter and
CCF between keyboard and cable between keyboard
keyboard cannot be
control panel is broken and control panel
established
1.The braking line or 1. Check the brake unit,
braking pipe is brokem change the brake pipe.
bCE Brake unit fault
2.brake resistor is too 2. Choose the suitable
lower braking resistor.
1.There is some
disturbing caused by the
1. Shorten the cable
two long connecting line
length between Keyboard
between Keyboard and
and control board in order
control broad when copy
to reduce interference.
the parameter
PCE Parameter copy Error 2. During download,
2.There is some conflict
make sure the parameters
between the parameter of
in keyboard is matched
keyboard and the
with that of in the
parameter of transducer
frequency converter.
when download the
parameter
1.The galvanoscopy of
IDE Hall current
IDE transducer or the damage 1. Ask for sevice
detection fault
of the cell of hall
Once a fault is detected, the AD200 series of frequency converter would immediately
block PWM output and enter the fault protection state and TRIP on the keyboard would
spark and the digital control area display the fault code, when alarming the frequency
converter can continue to work, once the alarm disappears the converter would
automatically return to the previous display status. Specific warning information is shown in
Table 7-2
Table 7-2 warnning information
Warnning
Type Discription
Code
Warnning of
Uu The bus voltage is below the voltage point
undervoltage
Operating current exceeded the converter
The warn about
OLP2 overload detection level and maintained more
overload of encoder
than overload detection time
Warns caused by the
Temperature in the radiator higher than the
OH2 too high temperature of
OH2 standard
radiator
Setting function code Output terminal DO, Y1, Y2 does not
SF3
unreasonable simultaneously select No.10 function
Please try to analysis according to the following way when you meet some accident
using the encoder.
serial abnormal
Possible reasons Method
number occurrence
1. Whether there is power
supply 1. Check the input power
The
2. The keyboard or the supply
keyboard
connecting cable between 2. Change connecting cable
1 can’t display
keyboard and control board between keyboard and
when power
is damaged. control board
on
3. The inverter is damaged in 3. Ask for service
the internals.
1. replace the electric motor
1.The motor is damaged or
or rule out the mechanical
block up
failure.
2.The conflict of the setting
Motor don’t 2.set up approval of reverse
prevented reverse and the
rotate when or change the operation
2 works direction
the inverter direction.
3. The frequency reference is
is running 3.check the given signal of
zero.
the frequency.
4.The wire of motor maybe
4.check the electric motor
short-cut
wiring.
serial abnormal
Possible reasons Method
number occurrence
the electric 1. alter the sequence of the
1.The connecting lines of
works with a side line in electric motor.
3 electric motor with a wrong
opposite 2.adjust the function code
sequence
direction F0.017
1.mechanical resonance
Electric
2.The leg of motor is not 1. adjust the machine
motor
4 stable 2. adjust the under-classis.
shakes too
3.The balance outputting 3.check the load.
heavy
between the three phase
1. repair or replace the
1.Lubrication is not good or
The noise of electric motor.
bearing wear
5 motor is too 2.Increase the carrier
2.carrier frequency is too
loud frequency of the frequency
low
converter.
The application environment (such as temperature, humidity, dust and powder, wool,
smoke and oscillation), burning and wearing of internal devices and other factors may
increase the possibilities of inverter failure. To reduce the failures and prolong the service
life the inverter, it needs to conduct routine repair and periodic maintenance.
Note:
1. Only the personnel receiving professional training can dismantle and replace the
inverter components.
2. Before inspection and maintenance, please make sure that the power supply to the
inverter has been shut down for at least ten minutes or the CHARGER indictor is OFF,
or there may be risks of electric shock..
3. Do not leave metal components and parts in the inverter, or it may damage the
equipment.
The inverter shall be used under the allowable conditions as recommended in this
manual and its routine maintenance shall be conducted as per the table below.
Item Inspection Contents Inspection
-10 ~ +40ºC Derated at 40 to
50ºC, and the rated output
Temperature Thermometer current shall be decreased by
1% for every temperature
rise of 1ºC.
Humidity Humidiometer 5 ~ 95%, no condensing
There are no dust, oil, water
Operating Dust, oil, water
Visual check and
Environment and drop
drop.
3.5mm,2~9Hz;
Special test
Vibration 10m/s2,9~200Hz;15m/s2,
instrument
200~500Hz
Special test
instrument, smell 3.5mm, 2~ 9Hz; 10m/s2,9~
Gas
check and visual 200Hz; 15m/s2,200~ 500Hz
check
It needs to perform periodic inspection on the inverter once every three to six months
according to the application environment and work conditions.
Different types of components have different service lives. The service lives of the
components are subject to the environment and application conditions. Better working
environment may prolong the service lives of the components. The cooling fan and
electrolytic capacitor are vulnerable components and shall be conducted routine inspection
as per the table below. If any fault occurs, please conduct immediate replacement.
Vulnerabl
Damage Causes Solutions Items for Routine Inspection
omponents
The fan blade has no cracks and
Bearing wear, blade
Fan Change rotates normally. The screws are
aging
tightened.
There are no electrolyte leakage,
Ambient color change, crack and shell
temperature is inflation. The safety valve is
Electrolytic
relatively high and Change normal.
capacitor
electrolyte Static capacity is equal to or
volatilizes. higher than the initial value times
0.85.
Note:
When the inverter is stored for a long period of time, power connection test shall be
conducted once within two years and last at least five hours. It can use voltage regulator to
gradually increase thevalue to the rated value when power connection is performed.
8.4 Warranty
The invertor's warranty period is of 18 months (from date of purchase), during which
the company would offer free repair or replacement if the fault or damage occurred under
normal use.
During the warranty period, the maintenance will be charged a reasonable cost due to
fault caused by the following reasons.
①fault caused by no following the operating manual or exceeding the operating
standards.
②fault caused by without permission to repair or modify the convertor.
③fault caused by using the convertor for non-normal function, such as the wiring
errors.
④fault caused by fire, salt corrosion, gas corrosion, earthquakes, storms, floods,
lightning, abnormal voltage, or other force majeure causes damage to the machine.
The inverter support Modbus protocol, RTU format, Broadcast address 0, slave address
“1-247”. Interface mode: RS485: Asynchronous, half duplex.
1.Protocal Format
Start The initial space of frame is 3.5 characters or above
Slave address 1~247
03: Read parameters from slave
Function Code 06: Write parameters to slave
08: Loopback Test
Data(N)
2×N data, this is the main content of modbus
………
communication.
Data(0)
Error check CRC check
End The End space of frame is 3.5 characters or above
Function Code 06H: Write parameters and status words of one parameters of the
inverter. Example:write parameter(F0.19 register address: 0113H) to the slave 1, the
format is as follows:
The Master Request
Slave address 01H
Function code 06H
Register address Hi 01H
Register address Lo 13H
Data Hi 00H
Data Lo 64H
CRC Hi 78H
CRC Lo 18H
Function Code 10H: Write parameters and status words of one parameters of the
inverter.
Example:write parameter(F0.19 register address: 0113H) to the slave 1, the format is
as follows:
The Master Request
Slave address 01H
Function code 10H
Register address Hi 01H
Register address Lo 13H
Number of registers Hi 00H
Number of registers Lo 01H
Byte Count 02H
Data Hi 00H
Data Lo 64H
CRC Hi B5H
CRC Lo D8H
If the operation request is rejected, the response will be error code and abnormal
function code. Error function code equals to function code +0x80, abnormal code shows the
error cause in detail. The format is as follows:
The slave response for the rejected request
Slave address 01H
Function code 83H
Error Code 02H
CRC Hi C0H
CRC Lo F1H
Name of Register
Content R/W
Parameters Address
Range(-10000~10000)
Note: Communication Setting is percentage.
(-100.00 ~100.00%)。When it ‘s used to
frequency setting, it’s relative to the
Communication
0002H maximum frequency. When it’s used to W/R
Setting
torque setting, it’s relative to the 2*rated
torque. When it’s used to PID setting or
feedback, it’s relatived to the analog input
corresponding setup
0003H
Reserved ~ Reserved Reserved
001FH
Bit0--1:Run 0: Stop
Bit1--1:Reverse rotation 0:Forward rotation
Inverter Status 0020H Bit2--1:Fault 0:No Fault R
Bit3--1:Warning 0:No warning
Bit4--1:On fault reset 0:no on fault reset
0: NULL
1: Uu1 bus Under voltage fault
2: OC1 over current in acceleration
3: OC2 over current in deceleration
4: OC3 over current in constant speed
5: Ou1 over voltage in acceleration
6: Ou2 over voltage in deceleration
7: Ou3 over voltage in constant speed
8: GF Ground Fault
9: SC Load Short-Circuit
10: OH1 Radiator over heat
11: OL1 Motor overload
Fault Content 0021H R
12: OL2 Inverter overload
13: EF0 communication fault
14: EF1 external terminal fault
15: SP1 Input phase failure or Unbalance
16: SPO Output phase failure or Unbalance
17: EEP EEPROM Fault
18: CCF Transmission between the inverter
and keyboard cannot be established
19: bCE Brake unit fault
20: PCE Parameter copy Error
21: IDE Hall current detection fault
22: ECE PG fault
0:No warning
1:uu Bus under voltage warning
Warning 2:OLP2Inverter overload warning
0022H
Content 3:OH2Inverter overheat warning
4:SF3Output Terminal function selection 10
not reach to 3
Name of Register
Content R/W
Parameters Address
0023H Output frequency R
0024H Frequency reference R
0025H Bus voltage R
0026H Output voltage R
0027H Output current R
0028H Rotate speed of motor R
0029H Output power R
002AH Output torque R
002BH PID reference R
4.CRC16 Function
unsigned int CRC16(unsigned char *data,unsigned char length)
{
int i,crc_result=0xffff;
while(length--)
{
crc_result^=*data++;
for(i=0;i<8;i++)
{
if(crc_result&0x01)
crc_result=(crc_result>>1)^0xa001;
else
crc_result=crc_result>>1;
}
}
return (crc_result=(
(crc_result&0xff)<<8)|(crc_result>>8)
);
}