Chapter4 Insulation-Coordination
Chapter4 Insulation-Coordination
Insulation Coordination
BG
TU-IOE
1/10/2024 BG 1
The term Insulation Co-ordination was originally introduced to arrange the insulation
levels of the several components in the transmission system in such a manner that an
insulation failure, if it did occur, would be confined to the place on the system where it
would result in the least damage, be the least expensive to repair, and cause the least
disturbance to the continuity of the supply.
The present usage of the term is broader. Insulation co-ordination now comprises the
selection of the electric strength of equipment in relation to the voltages which can appear
on the system for which the equipment is intended. The overall aim is to reduce to an
economically and operationally acceptable level the cost and disturbance caused by
insulation failure and resulting system outages.
To keep interruptions to a minimum, the insulation of the various parts of the system must
be so graded that flashovers only occur at intended points. With increasing system voltage,
the need to reduce the amount of insulation in the system, by proper co-ordination of the
insulating levels become more critical. So Insulation coordination means the correlation of
the insulation of the various equipment in a power system to the insulation of the protective
devices used for the protection of those equipment against overvoltages.
1/10/2024 BG 2
Terminology
Nominal System Voltage: It is the r.m.s. phase-to-phase (line) voltage by which a system is
designated.
Maximum System Voltage: It is the maximum rise of the r.m.s. phase-to-phase system
voltage.
Rated Short Duration Power Frequency Withstand Voltage: This is the prescribed r.m.s.
value of sinusoidal power frequency voltage that the equipment shall withstand during tests
made under specified conditions and for a specific time, usually not exceeding one minute.
Protective Level of Protective Device: These are the highest peak voltage value which should
not be exceeded at the terminals of a protective device when switching impulses and lightning
impulses of standard shape and rate values are applied under specific conditions.
1/10/2024 BG 3
Basic Lightning Impulse Insulation Level (BIL): The crest value of a standard
lightning impulse for which the insulation exhibits a 90% probability of withstand (10%
probability of failure) under specified conditions.
Basic Switching Impulse Insulation Level (BSL):The crest value of a standard
switching impulse for which the insulation exhibits a 90% probability of withstand (10%
probability of failure) under specified conditions.
Lightning impulse wave shape
American Standard : 1.5/40 μs
Indian Standard : 1.2/50 μs Impulse Wave Shape
An 1.2/50 μs impulse wave
represents a unidirectional wave
which rises to its peak value from
zero in 1.2 microseconds and then
falls to 50% of peak value in 50
microseconds.
Switching impulse wave shapes: 100/2500 μs, 250/2500 μs, 500/2500 μs
1/10/2024 BG 4
1/10/2024 BG 5
Factor of Earthing: This is the ratio of the highest r.m.s. phase-to-earth power
frequency voltage on a sound phase during an earth fault to the r.m.s. phase-to-phase
power frequency voltage which would be obtained at the selected location without
the fault. This ratio characterizes, in general terms, the earthing conditions of a system
as viewed from the selected fault location.
1/10/2024 BG 6
Volt-Time Curve
The breakdown voltage for a particular insulation or flashover voltage for a gap is a function of
both the magnitude of voltage and the time of application of the voltage.
The volt-time curve is a graph showing the relation between the crest flashover voltages
and the time to flashover for a series of impulse applications of a given wave shape.
For the construction of volt-time curve, waves of the same shape but of different peak values
are applied to the insulation whose volt-time curve is required.
1/10/2024 BG 7
In a power system, various equipment like
transformers, circuit breakers, bus supports etc. have
different breakdown voltages and the volt-time
characteristics. For the proper protection of all the
equipment, it is desired that the insulation of the
various devices must be properly coordinated.
The basic concept of insulation coordination is
illustrated in the Fig. Curve A is the volt-time curve of
the protective device and B the volt-time curve of the
equipment to be protected.
This figure shows the desired positions of the volt-
time curves of the protecting device and the equipment
to be protected. Thus, any insulation having a Volt-time curve A (protective
withstand voltage strength in excess of the insulation device) and volt-time curve B
strength of curve B is protected by the protective (device to be protected)
device of curve A.
1/10/2024 BG 8
A lightning arrester (surge diverter) protects the transformer insulation in the entire time
region. The rod gap protects the transformer insulation, only if the rate of rise of surge is
less than the critical slope (curve X). Thus, if the surge voltage rise is as shown by curve 1,
rod gap flashes and protects the transformer. If the surge voltage rise follows curve 2, only
the surge diverter can protect the transformer insulation.
1/10/2024 BG 9
Significance of v-t curve
v-t curve gives an idea of FOV at
different values of time of application of
various voltages. So it gives an idea of
protection level of various equipment.
Useful in making proper insulation
coordination by determining the relative
margin in protection level of various
sub-station equipment.
1/10/2024 BG 11
Surge Protection
An overhead earth wire provides considerable protection against direct strikes. They also
reduce induced overvoltages. However, they do not provide protection against surges that
may still reach the terminal equipment. Such protection may either be done by diverting
the major part of the energy of the surge to earth (surge diverters), or by modifying the
waveform to make it less harmful (surge modifiers). The insertion of a short length of
cable between an overhead line and a terminal equipment is the commonest form of surge
modifier.
1/10/2024 BG 12
Rod gaps are simple and cheap devices but do not meet all the requirements of a
protective device. Moreover, their flashover characteristics depend on the
atmospheric conditions, polarity of the wave, and waveshape.
Also, it may give rise to very steep impulse waves on the transformer windings as
chopped waves, because no current limiting resistance is used. Chopped impulse
waves may lead to the destruction of the transformer turn to turn insulation.
But still, rod gaps provide reasonable protection where lightning surge levels are
low, and steep fronted surges are controlled by overhead ground wires.
1/10/2024 BG 13
Surge Diverters
Surge diverters (or surge arrestors) generally consist of spark gaps in series, together with one
or more non-linear resistors in series. Silicon Carbide (SiC) was the material most often used
in these nonlinear resistor surge diverters. However, Zinc Oxide (ZnO) is being used in most
modern day surge diverters on account of its superior volt-ampere characteristic. In fact the
ZnO arrestor is often used gapless, as its normal follow on current is negligibly small.
1/10/2024 BG 16
The discharge voltage of the selected arrestor should be below the BIL of the protected
equipment by a suitable margin (generally selected between 15% and 25%).
The discharge voltage of an arrestor at nominal discharge current is not a constant, but also
depends on the rate of rise of the current and the wave shape. Typically, an increase of the
rate of rise from 1 kA/µs to 5 kA/µs would increase the discharge voltage by only about 35
%.
The dependence of the discharge voltage on the discharge current is also small. Typically,
an increase of discharge current from 5 kA to 10 kA would increase the discharge voltage by
about 15% for Silicon Carbide arrestors and by about 2% for Zinc Oxide arrestors. [The
discharge voltage is more often referred to as the residual discharge voltage].
(d) Power frequency spark over voltage
The power frequency spark over voltage is the r.m.s. value of the lowest power frequency
voltage, applied between the line and earth terminals of a surge diverter, which causes
spark-over of all the series gaps. The power frequency spark over voltage should generally
be greater than about 1.5 times the rated voltage of the arrestor, to prevent unnecessary
sparkover during normal switching operations.
1/10/2024 BG 17
(e) Impulse spark over voltage
The impulse spark over voltage is the highest value of voltage attained during an impulse of
a given wave shape and polarity, applied between the line and earth terminals of a surge
diverter prior to the flow of discharge current.
The impulse spark over voltage is not a constant but is dependant on the duration of
application. Thus it is common to define a wavefront impulse sparkover voltage in addition
to the impulse spark-over voltage.
Good designs aim to keep (i) the peak discharge residual voltage, (ii) the impulse sparkover
voltage and (iii) the wavefront impulse sparkover voltage reasonably close to each other.
1/10/2024 BG 18
1/10/2024 BG 19
Protection of Lines by Insulators
In a transmission line, an insulator serves two purposes;
i) Mechanical support to the conductor, and
ii) Electrical separation between the line and the supporting structure (pole, tower)
Insulators are required to withstand not only the normal power frequency overvoltage but
are required to withstand other high voltages too. Besides, they are required to operate in
the worst conditions.
Transmission insulators come in various shapes and types, including individual or strings
of disks, line posts or long rods. They are made of ceramic (glass and porcelain) or
polymers- each with different densities, tensile strengths and performing properties in
adverse conditions.
Porcelain insulators: Strings of discs, post type, bushing
Polymer insulators: longrod, post type, bushing
1/10/2024 BG 20
Use of Insulators in Tr. Line
1/10/2024 BG 22
Arcing horns:
‘Arcing horns’ or ‘arc horns’ are projecting conductors
used to protect insulators on high voltage lines from
damage during flashovers. Flashover along the insulator
can cause degradation of the insulator surface. The arc
horns encourage the flashover to occur between
themselves rather than across the insulators.
Horns are paired on the either side of the insulator.
Horns are frequently seen in HV O/H lines and
transformer bushing
Horn gap is calculated according to the dielectric
strength of air in the surrounding.
Altitude is also considered while determining the
horn gap. Normally, same value is used up to 1,000
m. above sea level. An increase of 1% per 100 m. is
made after this altitude.
1/10/2024 BG 23
Grading Rings:
Grading ring is a large metal ring surrounding the bottom unit of the
insulator string and connected to the line. This introduces new
capacitances between different metallic joints of the insulator string
and the line. The overall effect is the improved string efficiency.
1/10/2024 BG 24
Voltage across Equipment Protected by Arrester
In ideal case, the arrester must be located adjacent to the transformer or shunt reactor. In
practice, however, there may be length of the line between the two extending to 20 to 40 m.
This results in a slightly higher voltage across the equipment due to repeated reflections.
The high inductance of a transformer or reactor represents nearly an open-circuit to a surge.
The excess voltage experienced is given by an empirical equation and depends on the line
length and the rate of rise of the voltage.
ΔV = (dVw/dt) . (l/150) kV
where,
l = length of the line (between LA and equipment) in m
dVw/dt = steepness of wave front in kV/µS of the incoming wave. This can be taken as
approximately 500 kV/µS for lines with overhead ground wires and 1,000 kV/µS when a
line conductor is hit.
1/10/2024 BG 25
Calculations of Lightning Arrester
The volt-ampere characteristics of the resistance element inside a lightning arrester is given by,
I=kVa
where; I = discharge current
V = applied voltage across the element
k, a = constants depending on material and dimensions
When a surge voltage Vw is applied to the surge arrester, it breaks down giving the discharge
current Ia and maintains a voltage Vp across it.
Vw Iw Vp
Ia
1/10/2024 BG 26
Initial surge current through the line,
Iw = Vw/Z
With the arrester connected, the current through it is given by,
Ia = (2Vw-Vp)/Z
1/10/2024 BG 27
Equipment Insulation Level and Insulation Coordination of Sub-stations
For steep fronted lightning waves at sub-stations and at different points on lines, the voltages
at sub-stations may exceed the protective level depending on the distances involved and the
diverter locations. Hence, it is necessary to decide the number of locations for diverters to
optimize the overall cost. For high voltage sub-stations, it is usual to install surge diverters
between a transformer and its circuit breaker, in order to protect the transformer from current
chopping and the overvoltage due to it. Further, nearness of the diverter to the transformer
offers better protection.
The basic insulation level is often determined by giving a margin of 30% to the protective
level of surge diverter and selecting the next nearest standard BIL.
When a surge diverter is used to give switching surge protection also, the margin allowed
is only 15%.
The insulation level for lines and other equipment is to be chosen separately. The selection
of this level for lines depends on the atmospheric conditions, the lightning activity,
insulation pollution present and the acceptable outrage or failure rate of the line.
1/10/2024 BG 28
The protective level of the sub-station insulation depends on the station location, the
protective level of the diverter, and the line shielding used. The line insulation in the
end spans near the sub-station is normally reduced to limit the lightning overvoltages
reaching the sub-station.
In a sub-station, the busbar insulation level is the highest to ensure continuity of supply.
The circuit breakers, isolators, instrument and relay transformers, etc. are given the
next lower level. Since the power transformer is the costly and sensitive device, the
insulation level for it is the lowest.
1/10/2024 BG 29
The standard values of BIL for system voltages from 145 to 765 are given in Tables below.
Insulation Levels (BIL) for Various System Voltages
1/10/2024 BG 30
Standard Insulation Levels for Equipment (> 300 kV)
1/10/2024 BG 31
Example:
(1) Insulation co-ordination of a 132-kV sub-station
1/10/2024 BG 32
(2) Insulation co-ordination of a 220-kV sub-station
Nominal system voltage = 220 kV
Highest system voltage = 245 kV
Highest system voltage to ground = 244 (√2/√3) = 200 kV
Expected switching surge voltage ≈ 3.0 p.u. = 600 kV
Lightning arrester of 196 kV (as available) is chosen.
Front of wave impulse spark overvoltage ≈ 760 kV
Discharge voltage for 5 kA lightning surge current ≈ 690 kV
Discharge voltage for 2 kA switching surge current ≈ 615 kV
BIL for 220 kV system = 1050 kV
SIL for 220 kV System = 1050/1.24 ≈ 850 kV (The ratio of 1.24 is as per the design practice)
Protective margin for lightning impulses = (1050-690)/1050 = 360/1050 = 34.3%
Protective margin for switching surges = (850-615)/850 = 27.6%
The margin when the lightning just sparks over = (1050-760)/1050 = 27.5%
The protective level is adequate (more than 25%)/
(The lightning arrester data is as provided by the manufacturer.)
1/10/2024 BG 33
Numerical examples
1) A lightning arrester with BIL rating of 1600 kV is located at the end of the line having
surge impedance of 300 Ω receives a travelling wave of 4200 kV. Determine the
following;
(i) Arrester discharge current
(ii) Resistance offered by the arrester
(iii) Reflected current
(iv) Reflected voltage
1/10/2024 BG 34
2) The arrester discharge voltage is 320 kV. A surge having steepness of 800 kV/μS on the
front reaches the arrester. Calculate the voltage across the terminal of a transformer
located at a distance of 30 m from the arrester.
800 kV/μS 30 m
Vw
Vp
Ia
R
1/10/2024 BG 35
3) A transformer is protected by an arrester at the incoming line. The BIL withstand
voltage of the transformer is chosen to be 500 kV. The protective ratio required for
transformer protection is 1.2. A lightning strike at the arrester causes an arrester discharge
current of 24 kA. Check whether the transformer is properly coordinated.
Assume arrester residual voltage to be given by 200Id0.25.
1/10/2024 BG 36
4) A 132 kV transmission line is terminated by a transformer at a substation. The
transformer is protected by arrester of rating 400 kV located at the incoming line. The
BIL withstand voltage of the transformer is chosen to be 500 kV and the protective ratio
(PR) required for transformer protection is 1.2.
Check whether the transformer is properly coordinated with the arrester if a lightning
stroke of 8000 kV is incident at the arrester.
The relationship between the discharge current and the residual voltage is given by
Vd = kIdβ.
1/10/2024 BG 37
5) For a 750 kV line, take Vw = 3000 kV and BIL of LA (Vp) = 1700 kV. The line surge
impedance is Z = 300 Ω. Calculate:
(i) the current flowing in the line before reaching the arrester.
(ii) the current through the arrester.
(iii) the value of arrester resistance for this condition
(iv) reflection and refraction coefficients.
1/10/2024 BG 38