5 Protection
5 Protection
• There is ,normally at
generation and
transmission stages, a
back-up protection which
is a completely separate protection scheme which operates if the
main protection fails to operate
• The back-up system should be as independent of the main as
possible i.e. having its own CTs and relays.
Overcurrent protection
• Is applied to generators,
transformers and feeders.
Inverse time
overcurrent
protection
Ifault/Tap setting
Overcurrent protection- summary
•Inverse time relays:
•Slow to trip at low currents.
•Faster to trip at high fault currents.
•Used to co-ordinate over load protection,
which may have a high starting current.
•Generally the most sensitive to operate.
•Instantaneous relays:
•Used when co-ordination is not required.
•Usually the least sensitive of all relays, as the relay must not operate
for any kind of inrush, or operate before any downstream relay.
Overcurrent protection- radial systems
Inverse time relays are normally used in radial systems such that the
breaker closest to the fault opens while the upstream breakers with larger
time delays remain closed. Hence, minimum load interruption is
achieved.
E.g. for the radial system above, the time delay for the breakers are chosen
such that: Td-B3<Td-B2<Td-B1. Thus, for a fault at F,
B3 will operate first i.e. only L3 is interrupted.
If B3 fails, B2 will operate i.e. L3 and L2 are interrupted.
If B2 fails, B1 will operate i.e. L3, L2 and L1 are interrupted.
Directional overcurrent protection
In such cases, Directional Relays, which operate for fault currents in only
one direction, are used!
Directional overcurrent protection
To solve this, relays sensitive to V/I ratio (i.e. impedance) are used!
Distance (impedance) relay
• During a fault, current↑, voltage (close to fault place)↓→ V/I↓↓
• E.g. if I increases 5 times, V reduces by half →V/I reduces by 10
• I.e. V/I is more sensitive than current or voltage alone.
Three zones are normally defined for each impedance relay (e.g. for RA):
• Zone-1 is instantaneous and covers first 80% of the length of feeder (AB)
• Zone-2 has a time delay (0.2-0.3 sec) and covers 100% of the main feeder
(AB) plus 20-30% of the next feeder (BC)
• Zone-3 has a longer time delay and covers 100% of the main feeder (AB)
plus up to 100% (normally 40-50%) of the next feeder (BC)
• Note that each zone also operates as a back-up for the previous zone.
Differential relay are used to protect generators, transformers, and
busbars. Protected zone e.g.
Gen./Trans./ Busbars
We need two identical CTs: CB I1 CT CT I2 CB
2+𝑘 ′
𝐼2′ > 𝐼1
2−𝑘
For I2’<I1’:
2−𝑘 ′
𝐼2′ < 𝐼1
2+𝑘
Using restraining coil and
adjusting k :
• I1=I2 (i.e. normal operation
and faults outside protected
zone): mmfs by I1’ and I2’ (on
restraining coil) are additive >
mmf by I1’-I2’ (on operating Protected zone e.g.
Gen./Trans./ Busbars
coil)→block. CB I1 CT CT I2 CB