3-V&F Control
3-V&F Control
So the change of
frequency in steady state
can be describe using the
following equation in
terms of change in load
power. This equation is
called “droop” and m (in
Hz/MW) is droop gain: f-f0=-m(P-P0)
Frequency control
• The gain m is set such that the frequency deviation for maximum power
generation is within the grid’s code (usually 2%). f-f0=-m(P-P0)
• The droop control is also called Primary Control.
If two generators have the same gain m, any change in load will be shared by
them equally.
Cost/hour = f(P)≈a+bP+cP2
P=output power
Incremental cost Ic (cost/MWh) is
defined as: df ( P)
Ic = b + 2cP
dP
Economic dispatch
df ( P)
Ic = b + 2cP
dP
The economic dispatch problem is to find the values of unit outputs P1,
P2,…,Pn that minimize F, subject to the equality constraint.
To solve this problem let’s consider two units (for sake of simplicity):
Economic dispatch
F = f ( P1 ) + f ( P2 )
P1 + P2 = PL
P is constant
⎯⎯
L
⎯ ⎯ ⎯⎯→ dP1 + dP2 = 0 (1)
Using (1) :
I c1dP1 = I c 2 dP2 → I c1 = I c 2
Economic dispatch
df ( P1 ) df ( P2 ) df ( Pn )
= = ... =
dP1 dP2 dPn
I c1 = I c 2 = ... = I cn
Example
Consider two generators operating on economic dispatch with Ic1=0.004P1+4
(£/MWh) and Ic2=0.006P2+3.2 (£/MWh). If each machine is limited between
100-600MW, for PL varies from 200 to 1200MW, draw the output power of
each machine vs PL (on one graph).
Ic1=Ic2→0.004P1+4 =0.006P2+3.2
P2=PL-P1
0.004P1+4 =0.006(PL-P1)+3.2→P1 =0.6PL-80 MW
P2 =0.4PL+80 MW
Economic dispatch
It says that for each load how much generation from each machine is the
most economical value.
Not that, for some load, economic generation of machine 1 is more/less
than its maximum/minimum limits i.e. economical operation is not
possible.
Voltage control
V = IR cos + IX cos(90 − ) = IR cos + IX sin
V
V → V = V (IR cos + IX sin ) PR + QX
⎯⎯⎯ =
V V
Since δ is usually small: ΔV=Ecosδ-V≈E-V , hence:
PR + QX R 0 QX
E −V = ⎯⎯⎯→ E − V =
V V
257 /132
kV
much reactive power is needed to restore
its nominal voltage
Q = − I sc V
~
V = −5kV = −5 / 132 = −0.0379 pu
V ( pu ) 1
I sc ( pu ) = = = 2 pu
X eq ( pu ) 0.5
Q( pu ) = − I sc ( pu ) V ( pu ) = 2 0.0379 = 0.0758 pu
Q = 0.0758 500 = 37.9 MVAr
Method of Voltage control
There are two main methods to control voltage:
• Tap-changing Transformers
• and injection / absorption of reactive power.
Tap-changing Transformers
A simple schematic diagram of a single-
phase tap changing transformer is shown.
The taps are usually located on the H.V.
side as it is larger than the L.V. side and
more taps can be applied on it.
V = IR cos + IX sin
X = jX L − 2 jX C
Injection/absorption of reactive power: