Module 3
Power Measurement
Numericals
1. Three identical coils each having a reactance of 20 Ohms and resistance 10 Ohms are connected in star
across a 440V three phase line. Calculate :
a. Line Current and Phase Current
b. Active, reactive and apparent power
c. Reading of each wattmeter connected to measure power
May 2018 (8 Marks)
Ans: Iph = 11.36A, Q = 7.7436KVAR, S = 8.658 KVA, W1 = 4.1717 KW, W2 = -0.299 KW
1. Two wattmeters connected to measure the input to balanced three phase circuit indicates 1250W and
20 W, respectively. Find the total power supplied, and the power factor of the circuit.
(i) When both readings are positive and
(ii) When the latter reading is obtained after reversing the connections to the pressure coil.
May 2017 (8 Marks)
[Ans.: (i) P = 1270W; pf = 0.5120 lag; (ii) P = 1230W; pf = 0.6957 Lag]