The document outlines the technical specifications for a diesel generator, detailing the requirements for the diesel engine, alternator, and associated systems. Key features include engine performance parameters, fuel and lubrication systems, and electrical components such as the automatic voltage regulator and control panel. The specifications ensure the generator operates efficiently and meets safety and environmental standards.

Uploaded by

ahmed7737758
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
7 views14 pages

Technichal Specifications

The document outlines the technical specifications for a diesel generator, detailing the requirements for the diesel engine, alternator, and associated systems. Key features include engine performance parameters, fuel and lubrication systems, and electrical components such as the automatic voltage regulator and control panel. The specifications ensure the generator operates efficiently and meets safety and environmental standards.

Uploaded by

ahmed7737758
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 14

Technical Specifications

1. Diesel Generator Technical Specifications


1.1. Generator Unit (Set):
1.1.1. Diesel Engine
1.1.1.1. General
- The diesel engine shall be of the turbocharger, after cooled type with the
following characteristics:
- The engine shall be of the vertical, four strokes, cold starting.
- The engine shall be capable of running satisfactorily with fuel oil and
lubricating oil of grades and standards used in Sana’a City – Yemen.
- The engine speed regulation shall not exceed ± 10% for the momentary
and ± 6% for the permanent change when the full load on the engine is
suddenly thrown off or put on, respectively.
- Provision shall be made for varying the engine speed within 6% above or
below the normal speed at all loads.
- The engine shall be provided with a control panel as mentioned hereafter.
1.1.1.2. Engine Rating
- The engine when running at 90% of its continuous rated output at site
shall be capable of driving the alternator when delivering its full load
output, i.e., the power of the engine shall be nearly 10% in excess of the
power of the alternator.
- The engine shall be capable of supporting 10% overload for a period of
two hrs. Running without sustaining any mechanical trouble or under
heating, after 24 hours continuously running.
1.1.1.3. Rated Speed of the Engine and Piston Speed
- The speed of the engine shall not exceed 1500 RPM and the mean piston
speed shall not exceed 10 m/sec.
1.1.1.4. Mean Effective Pressure
- The mean effective pressure inside the engine cylinder should not exceed
14 kg/cm2.
1.1.1.5. Stroke-Bore Ratio
- The average value of the stroke bore ratio will vary between 1.2 to 1.5.
1.1.1.6. Supercharging
- The supercharging of the diesel engine shall be achieved by means of
charging blowers utilizing the energy of exhaust gases. An after cooler
must be fitted in the air manifold for cooling air before entering the
engine cylinders.
1.1.1.7. Piston Cooling
- The pistons may be oil cooled by means of an independent system using
lubricating oil as coolant
Technical Specifications

1.1.1.8. Cylinders, Liners and Cylinder Cover


- The engine shall be multi-cylinder type provided with removable cylinder
covers and renewable liners, furnished with water jacket of ample size,
avoiding any pockets, which may cause accumulation of deposits from
the cooling water.
- Each cylinder cover shall be fitted with a safety valve and a test cook for
measuring the compression pressures inside the cylinder
1.1.1.9. Duplex Fuel Oil Strainer and Filter
- Fuel-flow strainers shall be provided ahead of the engine fuel pump. The
fuel-flow filters shall be provided after the engine fuel pump. Strainers
shall be of the metal edge or screen type as recommended by the engine
manufacturer. The filter case shall have inlet and outlet connections
plainly marked. The case shall be mounted in an accessible location,
which will permit changing strainers and filter elements without
disconnecting the piping or other engine-mounted equipment.
1.1.1.10. Engine Fuel Pumps
- Engine fuel pumps shall be of the positive-displacement, engine-driven
type and capable of sullying the necessary quantity of fuel under all
conditions of operation. Relief valves shall be provided to prevent
equipment damage due to buildup of excessive pressures, which might
result from restrictions in the discharge lines. In addition, a hand-
operated fuel oil priming pump shall be provided.
1.1.1.11. Fuel Oil Drip
- Nozzle drip lines, overflow, … etc., shall not drain on the floor. Means
shall be provided for collecting these lines and return of excess fuel to the
day tank automatically.
1.1.1.12. Fuel Oil Lines
- Fuel oil lines shall be provided with solid connections between fuel piping
and engine.
1.1.1.13. Lubricating System
- The engine lubricating system shall operate and be maintained at a
predetermined constant pressure by means of an engine-driven positive-
displacement lubricating oil pump. Relief valves, a pressure gauge, and
automatic safety feature, to sound an alarm and shut down the engine at
a predetermined lubrication oil pressure by closing contact, shall be
supplied. To maintain proper oil temperature, if deemed necessary,
lubrication system shall be provided with water cooler.
1.1.1.14. Oil Cooler
- One shell type or plate type cooler arranged to utilize engine-cooling
water as the oil-cooling medium, shall be furnished with the engine. The
capacity and construction of the unit shall be as recommended by the
engine manufacturer. Suitable connections shall be furnished for
connections between the engine, radiator, and oil cooler as required.

Page 2 of 14
Technical Specifications

1.1.1.15. Lubrication Oil Strainers and Filters


- Duplex full-flow filters shall be provided in the lubrication. Oil line. The
filters shall be of the cartridge type.
1.1.1.16. Lubrication Oil Priming Pump
- An electrically operated priming pump shall be provided for priming the
engine lubricating system prior to starting. The pump shall be of suitable
capacity. The pump shall be mounted on the engine and shall be factory
completed. A manual pump shall also be provided as stand-by. Starting of
engine without priming can be accept if the engines' manufacturer
recommends it.
1.1.1.17. Exhaust System
- The exhaust system shall include a flexible section, condensate drain,
muffler-silencer, weather cap and all necessary accessories.
- Exhaust piping shall be of the diameter recommended by the diesel
manufacturer. The flexible exhaust connection shall be stainless steel. The
exhaust silencer shall be of heavy duty, side inlet and end outlet,
designed for vertical installation. It shall be of size and design that will
ensure durability, prevent backpressure, and provide medium degree
silencing. Flanged connections shall be provided at each end of the
silencer. All companion flanges shall be furnished, installed, and securely
attached to the housing. Exhaust system components shall be painted
with high temperature aluminized paint. Each flanged joint shall be
provided with 1/16" asbestos, full-face gaskets.
1.1.1.18. Air Intake System
- The engine shall be equipped with heavy-duty oil bath or dry type air
cleaner (S) of sufficient capacity to protect working parts of the engine
from dirt or grit. The air-cleaner shall be equipped with a pre-cleaner and
a restriction indication. A crankcase breather shall be included. In-line air
inlet silencer shall be provided between the turbocharger and air inlet.
1.1.1.19. Speed Control Governor
- The engine shall be equipped with a full hydraulic isochroous governor,
which shall be mechanically driven by the engine, and which shall hold
engine speed to within ± 5% of any selected speed at any constant load
form no-load to full load.
- The governor shall control speed smoothly but positively and shall be
fitted with stabilizing or compensating device to preclude hunting or over
travel. The governor shall prevent variation in speed of the sustained
periodic type (Hunting) and shall limit variation in speed of
1.1.1.20. Flywheel
- The flywheel shall be adequately protected by means of removable
guards. An appropriate means shall be provided for barring.

Page 3 of 14
Technical Specifications

1.1.1.21. Emissions standers


- The engine shall be meet Tire 4 final emission standers.

1.2. Alternator
1.2.1. Design Data
- The alternator shall be directly connected to the engine flywheel through
a coupling designed and supplied in accordance with alternator
manufacturer requirements.
- The alternator shall be of three phase, synchronous, drip proof, self-
excited with built in exciter machine and voltage setting rheostat,
provided with special windings for reduced harmonics and arranged for
parallel operation with similar unit.
- Insulation shall be of tropical and moisture proof type, class (H).
- The alternator shall be of the following technical data:
Power As mentioned in B.O.Q

Power factor 0.8 – 0.85


Efficiency Minimum 92%
Voltage 400 V
Frequency 50 Hz
Speed does not exceed 1500 RPM
Voltage dip at starting not to exceed
15 %
Overload rating 10 % for one hour each 12 hours
Short circuit rating 300% of alternator capacity
symmetrical for 10 seconds
Temperature rises over ambient 65 °C
temperature
Maximum harmonic content 1.10
Ambient temperature 45 °C

1.2.2. Exciter
- The exciter shall be brush less and its armature shall be directly connected
to the alternator shaft. It shall be of the alternator type and have a solid-
state, hermetically sealed rectifiers mounted directly on its armature. The
rectified exciter output shall be directly connected to the revolving
alternator field windings without brushes, slip ring or communicators. The

Page 4 of 14
Technical Specifications

excitation system shall be equipped with a series of boots transformers or


permanent magnet generator for field forcing capabilities.

1.2.3. Automatic Voltage Regulator


- Alternator and regulator manufacturers must use solid electronic state
technology with no electron tubes or electrolytic capacitors and must use
the voltage regulator's recommended type and size.
- It shall be designed to provide an overall alternator performance as
follows:
o Steady State
▪ With any constant load between no load and full load and
at any power factor from 0.8 to 1.0, and ambient
temperature, specified voltage regulation shall be 1%.
▪ With constant load and ambient temperature, voltage dip
shall not exceed 1% during any one-hour period.
o Transient
▪ 12% maximum voltage drop when applying of 50% rated
load, with two second maximum recovery time to steady
state, when operating at 50% load.
▪ 12% maximum voltage rise when removing of 50% rated
load, with two second maximum recovery time to steady
state, when operating at 100% load.
o Voltage Adjusting Rheostat
▪ The voltage regulator shall be designed for adjusting
alternator output within ± 10%. A manual voltage-adjusting
rheostat with operating knob shall be supplied and
mounted on the switchboard.
▪ The voltage regulator shall contain a limiting circuit to
prevent output voltage surges in excess of 110% of rated
voltage during generator set operation. On a loss of the
sensing signal, the voltage regulator shall shutdown to
prevent an overvoltage condition from occurring. A voltage
regulator that can go into a full field condition is
unacceptable. LED indication will be provided on the
regulator to monitor the sensing (yellow), excitation
(green), and output circuit (red). A rheostat shall provide a
minimum of plus or minus 10% voltage adjustment from
the rated value.

Page 5 of 14
Technical Specifications

1.3. Main Line Circuit Breaker, Control and Instrument Panel:


- The main line circuit breaker shall be mounted and connected in a
guarded drip-proof enclosure meeting IP 23 and IEC 144.
- For generating unit, a main line circuit breaker with shunt trip to protect
generator set from accidental faults and to disconnect it from its load
shall be supplied. (It shall be with min. rating Amps and sized to the
output of the generator at 50 Hz as specified at BOQs).
- The control and instrument panel shall be provided. This panel shall be
mounted on to the alternator and shall be provided with vibration
isolators of adequate size to protect the instruments and control from
vibrations.
- It shall operate both manually for normal switching functions and
automatically during the above-mentioned failure events. The breaker
shall also include ground fault sensing that will trip the breaker on ground
fault conditions.
- The following minimum instruments and control shall be provided.
● Cooling water to engine.

● Cooling water from engine.

● Lubrication Oil from engine.

● Cylinder and combined exhaust (using thermo-couples).

● Cooling water after turbocharger.

● Alternator bearing temperature, high.

● Charging air to cylinders.

● Lubrication Oil to filter.

● Engine water temperature, high-shut down of the engine.

● Engine, over speed and visual alarm.

● Engine control, on.

● Radiator fan, on.

● Low fuel level in the daily fuel tank

Page 6 of 14
Technical Specifications

1.4. Starting of the Generating Units


1.4.1. Electric Starting System
- The engine shall be equipped with a 12/24 VDC solenoid shift electric
starter capable of withstanding four, 30 second consecutive cranking
periods.
- The starting battery shall be Nickel-Cadmium, Alkaline, especially
designed for diesel engine cranking service and of a capacity as
recommended by the battery manufacturer for cranking the engine being
furnished, for the necessary break-away current as required and spinning
current for four consecutive starts of thirty seconds of cranking on each
start, or for 60 seconds of continuous cranking without being recharged
and with the ambient temperature of both the engine and battery of 45°C.
Steel battery rack shall be secured to the mounting skid and the battery
shall be secured to this rack.
- A complete automatic battery charger shall be furnished for charging the
Nickel-Cadmium, Alkaline battery being supplied. The charger shall be the
static type, magnetic amplifier control with direct current voltmeter, direct
current ammeter and potentiometer for voltage adjustment and shall have
float and high charge rate, with a 0-to-24-hour high-rate charge timer.
Charge rate shall be automatically determined by the state of the battery
and reducing to milliamp. Current to fully charged battery. Charger shall be
for 220-volt, single phase, and 50 Hz alternating current input, with an
output of not less than 6 percent of the nominal ampere-hour rating of the
battery. A time delay under voltage relay shall be provided within the
charger for remote alarms. The charger shall be for the correct voltage for
the battery. The charger shall be mounted inside the pump housing.
- Required battery cables shall be installed for connecting the battery to
electric starter.

1.5. Fuel System:


1.5.1. Fuel Transfer Pumps
- Fuel oil shall be transferred to and from the main fuel tanks by electrically
driven pumping units.
- The electrically driven pumps shall be of the self-primed, rotary type,
having a discharge of 1 Ltr/sec. directly driven and mounted on a
common bedplate with its A.C., single phase, 50 cycles/sec, 220 volt,
electric motor.
- The pump shall be provided with dry running protection in conjunction
with the fuel level in the main storage tanks.

Page 7 of 14
Technical Specifications

- The pump shall be complete with all piping and valves which shall be
arranged to transfer the fuel oil from tankers to the main storage tanks
and from main tanks to the daily fuel service tanks inside generating
building.
- The fuel piping shall be of black steel. Piping outside the generating units
buildings shall be laid down in trenches. Piping indoor shall be laid inside
concrete ducts with Chaucer plate covers. Pipes shall be properly
protected against corrosion. The joints shall be of the flanged and/or of
the sleeve type with union couplings wherever necessary for easy
dismantling.

1.5.2. Daily Fuel Tank


An integral skid type fuel tank shall be provided with the generator set , a
daily fuel tank made of welded black steel sheets of heavy construction
according to manufacturer, specification and with capacity to cover 10-12
hours consumption of the engine when running at full load, Including all
required accessories (interconnecting fuel piping, heavy duty filter
incorporating a water trap shall be fitted between the day tank and the
engine mounted fuel feed pump). Isolating valves shall be provided on both
sides of the filter.

1.5.3. Fuel Storage Tanks


Fuel oil storage tanks, outdoor type, over ground, CYLINDRICAL, the fuel tank
capacity as per drawing and B.O.Q and should be suitable liters powered by
electric driven pump (s), fuel flow meter complete with bypass pipe work,
valves and fittings to connect to engine, The unit rate include materials,
workmanship, foundations and all civil works, epoxy painting, finishing, and
any others required to complete the work as per drawing and engineer
instruction

The tank shall be complete with steel platform and stand and shall be
equipped with the following:
- Level indicator.
- Fuel filter.
- Air vent, overflow pipe and drain pipe with cock.
- Strainer on outlet.
- Inspection opening with cover.
- Turbine type flow meter on the outlet pipeline.

Page 8 of 14
Technical Specifications

- The tanks shall be painted externally with aluminum paint.


- The contractor should submit shop drawings for the tank and fuel
pipe distribution, location of fittings and accessories with specific
dimensions, for approval by UNOPS engineer.

1.5.4. Hand Pump


A hand operated pump with the delivery permanently connected to the day
tank and with a flexible suction pipe to facilitate the filling of the day tank
from drums of diesel shall be provided will used for emergency situations.

1.5.5. Surface Preparation and Painting


The entire works shall be painted or treated with protective coatings such as
galvanizing.

For outdoor environments, paint and protective coatings shall provide for
long-term protection suitable for severe atmospheric classification.

All carbon steel pipe work, equipment and fittings to be insulated shall be as
a minimum painted with a primer prior to cladding. Non stainless-steel
engine exhaust pipe work shall be painted with inorganic zinc primer.

Paints shall be free of any isocyanides and shall comply with the paint
manufacturer’s instructions for the specified environmental conditions. Paint
systems shall be of the self- leveling type.

1.6. Cooling System


- The engine shall be water-cooled of a closed type of system, with liquid to
air radiator supplied with blower fan(s) to maintain desired operation
conditions. The radiator unit shall be of the indoor or outdoor type
designed for operating 10% continuous overload at 50 °C ambient
temperature.
- All connections to the engine and its mounted accessories shall be solid.
The radiator shall have an engine driven fan of adequate size.
- The system shall not be susceptible to the formation of deposit of rust and
scale within the engine and shall circulate the coolant through the engine
at a regulated temperature and flow rate as recommended by the
manufacturer.

Page 9 of 14
Technical Specifications

- A jacket water temperature control valve shall be provided. It shall be of


thermostatic type with 3-way body and flanged connections. The
thermostatic element shall be designed to maintain the jacket water
temperature within the requirements at stated by the engine
manufacturer.
- The system shall also include a separate path of lubrication Oil cooling.
- Similar approved type can be taken into consideration.
- Gen sets shall be equipped with a cooling system having sufficient capacity
to effectively cool the engine when delivering full rated horsepower at the
conditions stated above. A radiator and engine-driven fan of a type and
capacity recommended by the engine manufacturer shall be included.
- The radiator shall be sized in accordance with the engine manufacturer’s
recommendation for use with 50 percent aqueous ethylene glycol. Air flow
shall be controlled by a power inlet damper and a gravity discharge
damper, Design ambient air temperature shall be 50 degrees C at sea
level.
- Gen sets shall have an engine-driven, gear driven centrifugal type water
circulating pump for circulating water through the cooling system.

1.7. Control panel


- The following minimum instruments and control shall be providing for
the generating unit power supply and one for transformer power supply:
- AC automatic transfer switch suitable for Existing DG & New DG will be
install.
- AC voltage 3 phase (L – L & L – N).
- AC amps 3 PH & total.
- KW total & per phase.
- KVA total.
- K VAR total.
- KWh total.
- KVARh total.
- Power factor average & total.
- Percentage of rated (total).
- Frequency.
- DC voltage.
- Coolant temperature.
- Oil pressure.
- RPM.

Page 10 of 14
Technical Specifications

- Hours run.
- System diagnostic.
- CONTROLS
o Automatic transfer switch.
o Auto start / stop and Emergency stop.
o Lamp test.
o Cycle crank.
o Voltage control.
o Cool down timer.
o Phase selector switch.
o Load demand relay.
- INDICATING LIGHTS
o Low oil pressure.
o High coolant temperature.
o Over speed.
o Emergency stop.
o Fault shutdown and Fault alarms.
o 3 spare lights / 4 spare inputs, customer programmable
(shutdown or alarm) to spare alarm or fault Leeds and Over crank.
- PROTECTIVE RELAYING
o Programmable relays.
o Over / under voltage.
o Reverse power relay.
o Over / under frequency and over current.
- LOW VOLTAGE CIRCUIT BREAKERS
o Low voltage circuit breakers shall be metal clad and shall be of the
air break, horizontal draw out pattern 400 volts and rupturing
capacity as mentioned in the drawing. Circuit breakers shall
comply with VDE or BS 4752 & IEC 60439 and shall be complete
with the auxiliary equipment described for high voltage circuit
breakers. The circuit breakers closing mechanism shall be of the
trip-free type and shall incorporate a mechanical "ON/OFF"
indicator and mechanical interlock in order to prevent withdrawal,
plugging or access to the breaker in the closed position.
o Contactors shall be robust in design and shall be capable of
carrying full load for an indefinite period, and shall be provide
with an arc-quenching device. Contacts shall have readily
renewable tips. The live fixed contacts shall be fully shroud.

Page 11 of 14
Technical Specifications

- LOW VOLTAGE FUSED SWITCHES / ISOLATORS


o Fused switches shall be of the heavy duty type complying with
VDE No.0670 part 1/1.64 and shall be equipped with detachable
neutral links and class Q1HRC fuses to VDE No.0670 part 4/3.67.
o Fused switches shall be of the triple pole and neutral type or
heavy-duty composites unit of the air break switch type and have
not more than one fuse in any one pole, the fuse being contained
in or mounted on the moving member or the switch. The neutral
shall be either switch or taken through a removable link. A
separate brass earth terminal shall be providing.
o Isolators shall be identical to fuse switches but the fuse links shall
be replace by high conductivity copper link.

1.8. Earthing System:


- The Contractor shall Supply and deliver an earthing system in accordance
design of the system and all items shall be according to BS 7430, with the IEE
Wiring regulations BS 7671. The system of PVC conduits and trunking,
metallic sheaths of cables, cases and enclosures of switchgear and electrical
apparatus shall be connect to the earth point, according to the current rules
and regulations. The Contractor is reminded that the resistance of the earth
conductor from the earth-electrode to any point in the earthing system shall
not exceed one ohm as per ANSI IEEE Standard 80.
- Codes of practice and highest prevailing engineering standards for the
following main system component:
a. Extendible copper electrodes, (suggested length: 1.6~2.4 m),
b. Main earthling cable: copper bared as per BOQ, and the length as
required. And earthling cables for Gen. sets, hanger frame, fuel tank
and any other equipment: insulated copper as per BOQ, Cupper
earthling bar, Earth pit with manhole cast iron cover plate complete as
per standard, the cover of the manhole is preferred to be clearly
stamped with grounding sign.
c. Ground Enhancement Material (Bentonite / (Salt & Coal).
d. Earthing busbar shall be protected fixed inside sealed box.

Page 12 of 14
Technical Specifications

1.9. Cables
- Cables shall be supplied by an approved manufacturer and where possible
the same manufacturer shall be used for all cables and according to IEC
60228, IEC 61537, ISO, IEC 60227/IS 694, IEC 60502/151554 standards. In
addition, the Calculations of the current rating of the cables should be
according to IEC 60287.
i. Rating:
▪ The Contractor shall ensure that each cable is adequately rate for its
duty under normal and possible fault conditions.
▪ The rated voltage of the cable shall not less than the operating
voltage and when assessing the rating and cross section of each cable
the following factors shall be taken into account:
● Maximum voltage drops permissible.

● Type and magnitude of load.

● Fault level and duration related to circuit protection relays and


fuse gear.
● Over current setting of relays and circuit breakers.

● Route length and disposition of cables.

● Ambient temperature.

● Method of laying.
ii. Type:
▪ Cables complying with VDE or approve equivalent standards will be
accepted provided all cables, which are supplied for a specified
operating voltage, are to the same national standard. Standards
specified in the following clauses indicated the type of cables used in
the design: if the contractor wishes to use cables to alternative
standard, then details of current carrying capacity, de-rating factors
etc., shall be submitted to the Engineer for approval.
i. XLPE/SWA/PVC:
▪ Power cables specified as cross-linked polyethylene insulated steel
wire armored and PVC sheathed are hereafter refer to as
XLPE/SWA/PVC.

Page 13 of 14
Technical Specifications

▪ All such cables shall be terminated with mechanical glands, which shall
be of a type as to provide adequate mechanical support by positively
locking on the armor and shall at the same time give a high level of
earth continuity.
i. PVC/SWA/PVC:
▪ Power and control cables specified as PVC insulated and sheathed,
galvanized single wire armored cable with an overall PVC sheath are
hereinafter referred to as PVC/SWA/PVC.
i. MICC/PVC:
▪ Certain control and miscellaneous circuits shall be carried out in
mineral insulated copper clad cable with an overall extruded PVC
sheath, hereinafter referred to as MICC/PVC cable.
▪ For the purposes of core phase identification colored PVC core sleeves
or colored PVC extension sleeves shall be use. Core sleeves and
extension sleeves to be use on the core sizes for which they are
intend.

Page 14 of 14