Liebert gxt5 Installer User Guide - 01
Liebert gxt5 Installer User Guide - 01
Installer/User Guide
120/208 V Input (L1, L2, N, G), 120/208 V Output (MV)
Vertiv™ Liebert® GXT5 UPS Installer/User Guide
The products covered by this instruction manual are manufactured and/or sold
by Vertiv. This document is the property of Vertiv and contains confidential and
proprietary information owned by Vertiv. Any copying, use, or disclosure of it
without the written permission of Vertiv is strictly prohibited.
TABLE OF CONTENTS
Comply with all warnings and operating instructions in this manual strictly. Save this manual and carefully read the following
instructions before installing the unit. Do not operate this unit before reading all safety information and operating instructions
carefully.
Transportation
Only transport the UPS system in the original packaging to protect against shock and impact.
Preparation
• Condensation may occur if the UPS system is moved directly from a cold to a warm environment. The UPS
system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to
acclimate the environment.
• Do not install the UPS system near water or in moist environments.
• Do not install the UPS system where it would be exposed to direct sunlight or near a heater.
• Do not block ventilation holes in the UPS housing.
Installation
• Do not connect appliances or devices which would overload the UPS system (e.g. laser printers) to the UPS
output sockets.
• Place cables in such a way that no one can step on or trip over them.
• Do not connect domestic appliances such as hair dryers to UPS output sockets.
• Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the
UPS system.
• Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your computer) to connect the UPS
system to the building wiring shockproof outlet.
• Please use only VDE-tested, CE-marked power cables to connect the loads to the UPS system.
• When installing the equipment, ensure that the sum of the leakage current of the UPS and the connected
devices does not exceed 3.5 mA.
Operation
• Do not disconnect the mains cable on the UPS system or the building wiring shockproof outlet during operations
since this would cancel the protective earthing of the UPS system and of all connected loads.
• The UPS system features its own, internal power source (batteries). The UPS output sockets or output terminal
blocks may be electrically live even if the UPS system is not connected to the building wiring outlet.
• In order to fully disconnect the UPS system, first press the OFF/Enter button to disconnect the mains.
• Prevent fluids and foreign objects from entering the inside of the UPS system.
1 Important Safety Instructions Proprietary and Confidential ©2024 Vertiv Group Corp. 1
Vertiv™ Liebert® GXT5 UPS Installer/User Guide
WARNING! Risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet),
components inside the UPS system are still connected to the battery and electrically live and dangerous.
• Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no current is
present and no hazardous voltage exists in the terminals of high energy capacitors such as Bus capacitors.
• Only persons that are adequately familiar with batteries and with the required precautionary measures may
replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries.
WARNING! Risk of electric shock. The battery circuit is not isolated from the input voltage. Hazardous
voltages may occur between the battery terminals and the ground. Before touching, please verify that no
voltage is present!
• Batteries may cause electric shock and have a high short circuit current. Please take the precautionary measures
specified below and any other measures necessary when working with batteries:
• Remove wristwatches, rings, and other metal objects.
• Use only tools with insulated grips and handles.
• When changing batteries, install the same number and same type of batteries.
• Do not attempt to dispose of batteries by burning them. This could cause battery explosion.
• Recycle or dispose of batteries properly according to local regulations.
• Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and eyes. It may be toxic.
• Please replace fuses only with the same type and amperage in order to avoid fire hazards.
• Do not dismantle the UPS system.
2 Proprietary and Confidential ©2024 Vertiv Group Corp. 1 Important Safety Instructions
Vertiv™ Liebert® GXT5 UPS Installer/User Guide
2 Product Description
The Vertiv™ Liebert® GXT5 is a compact, online uninterruptible power system (UPS) that continuously conditions and
regulates its output voltage. The Liebert® GXT5 supplies computers and other sensitive equipment with clean sine-wave
input power.
Upon generation, AC power is clean and stable. However, during transmission and distribution it is subject to voltage sags,
spikes, and complete failure that may interrupt computer operations, cause data loss, and damage equipment.
The Liebert® GXT5 protects equipment from these disturbances. The Liebert® GXT5 continuously charges its batteries from
the mains, enabling it to supply power to connected loads, even when the mains fail.
Item Description
1 Operation/Display panel
2 Upper bezel
Item Description
3 USB port
Item Description
7 Input breaker
10 Output breaker
Item Description
3 USB port
6 EBC connector
7 Output breaker
9 Input breaker
Item Description
2 USB port
6 EBC connector
7 POD breaker
8 Output breaker
9 Input breaker
The 8 kVA and 10 kVA models ship with the standard POD installed. The POD options are shown in Figure 2.6 on page 8, and
Figure 2.7 on page 9.
NOTE: Output power capacity after derating with POD can be found under the About menu at the Efficiency tab.
NOTE: In Figure 2.5 on the facing page, the components on PD5-001 are labeled. The features may be arranged
differently on other PODs.
NOTE: In Figure 2.6 on the next page, the components on PD2-101 are labeled. The features are arranged differently
on other PODs.
Figure 2.7 Additional Power Output Distribution Options for GXT5-8000/10KMVRT6UXLN and GXT5-15K/20KMVR
T11UXLN
3 PD2-109 2x L14-30R
Item Description
1 Handle
2 Connector
Transient Voltage
Surge
Provide surge protection. Filter electromagnetic interference (EMI) and radio frequency interference (RFI). Minimize
1 Suppression
surges or interference present in the utility power and protect devices connected on the same branch as the UPS.
(TVSS) and
EMI/RFI Filters
In normal operation, converts utility AC power to regulate DC power for use by the inverter while ensuring that the wave
shape of the input current used by the UPS is near ideal. Extracting this sine-wave input current ensures efficient use of
Rectifier/Power
utility power and reduces reflected harmonic distortion making cleaner power available to devices that are not
2 factor Correction
protected by the UPS. The DC-to-DC converter raises the DC voltage from the battery to the optimum operating
(PFC) Circuit
voltage for the inverter. This allows the inverter to operate continuously at its optimum efficiency and voltage, thus
increasing reliability.
Regulates input AC power to continuously float charge the batteries. Batteries are changed when the UPS is plugged in,
3 Battery Charger
even when not powered on.
In normal operation, inverts the DC output of the PFC circuit into precise, regulated sine-wave AC power. When utility
5 Inverter power fails, the inverter receives DC power from the DC-to-DC converter. In either operating mode, the UPS inverter
remains on-line, generating clean, precise, regulated AC-output power.
In the unlikely event of UPS failure such as overload or over-temperature, automatically transfers the connected load to
Dynamic Internal bypass.
6
Bypass To manually transfer the connected load from inverter to bypass, see Transferring from Normal to Bypass Mode on
page 34.
Filter electromagnetic interference (EMI) and radio frequency interference (RFI). Minimize interference present in the
7 EMI/RFI Filters
utility power and protect devices connected on the same branch as the UPS.
In the unlikely event of UPS failure, allows replacing the UPS while keeping the connected equipment powered with
Maintenance utility power.
8
Bypass NOTE: The bypass power path does not protect connected equipment from disturbances in the utility supply. 15
kVA and 20 kVA units do not have internal maintenance bypass.
Item Description
2 Rectifier/PFC
3 Inverter
4 Battery charger
5 Battery
7 UPS output
NOTE: If utility power fails or if the utility voltage goes outside of the permissible range during bypass mode
operation, the UPS shuts down and no output is supplied to the load.
Item Description
2 Rectifier/PFC
3 Inverter
4 Battery charger
5 Battery
7 UPS output
Item Description
2 Rectifier/PFC
3 Inverter
4 Battery charger
5 Battery
7 UPS output
NOTE: The batteries are fully charged before shipment. However, transportation and storage inevitably cause some
loss of capacity. to ensure adequate back-up time, it is recommended to charge the batteries for at least 8 hours
before first start-up.
NOTE: If utility power fails and the batteries are charged, you may cold-start the UPS in battery mode and use battery
power to extend system availability for a time.
NOTE: Powering off the UPS when it is in battery mode results in loss of output power to the connected load.
NOTE: The default for all model of the Liebert® GXT5 is Auto Sensing - 50 Hz or 60 Hz - Bypass Enabled.
NOTE: During ECO mode, if a bypass failure or abnormal bypass voltage notification appears when the output is not
overloaded, the UPS will transfer to Normal Mode. However, if a notification showing bypass failure or abnormal
bypass voltage appears when the output is overloaded, the UPS will shut down the bypass and therefore the load will
shut down.
3 Installation
Do not start the UPS until after the installation is finished.
WARNING! Risk of electric shock. Can cause equipment damage, injury and death. Before beginning
installation, verify that all external overcurrent protection devices are open (Off), and that they are locked-
out and tagged appropriately to prevent activation during the installation, verify with a voltmeter that power
is Off and wear appropriate, OSHA approved personal protective equipment (PPE) per NFPA 70E. Failure to
comply can cause serious injury or death. Before proceeding with installation, read all instructions. Follow all
local codes.
• Inspect the UPS for shipping damage. If any shipping damage is found, report it to the carrier and your local
Vertiv representative immediately.
• Check the accessories included against the packing list. If there is any discrepancy, contact your local Vertiv
representative immediately.
CAUTION: The UPS is heavy (see Specification on page 65, for the weight). Take proper precautions when
lifting or moving the unit.
NOTE: Operating the UPS in temperatures above 77°F (25°C) reduces battery life.
After installing the UPS as a tower or in a rack, and before attempting to start-up, you must install the internal batteries. See
Installing the Internal Battery Kits on the next page.
NOTE: When installing the UPS or making input and output connections, comply with all relevant safety codes and
standards.
Item Description
1 Support bases
2. If optional external battery cabinets will be connected, take out the spacers shipped with the battery cabinet.
3. Connect the spacers and the support bases as shown in Figure 3.1 above. Each Vertiv™ Liebert® GXT5 requires 2
support bases, one in the front and one in the rear.
4. Place the Liebert® GXT5 and any battery cabinets on the 2 support bases.
5. See Installing the Internal Battery Kits below, to install the battery packs.
CAUTION: The Liebert® GXT5 is heavy. The UPS must be installed as near the button of a rack as possible. If
placed too high, it can make the rack top-heavy and prone to tipping over. For unit weights, see Specification
on page 65.
1. Loosen and remove the screws on the battery door, see Figure 3.2 on the facing page.
2. Lay the battery door and screws aside for reassembly.
3. Unpack the battery pack.
4. Line up and slowly slide the battery pack in until two-thirds of the length is inserted, then pull up slightly and
continue pushing in firmly until the battery pack is fully inserted.
5. Attach the battery door with the screws. The battery door will cover the batteries if the packs are properly
installed.
6. Attach the front cover to the UPS.
Item Description
1 Front Panel
2 Battery Door
For applications where the number of EBCs exceeds 6 or for legacy applications where EBC auto-detection is not possible,
please contact Vertiv service for assistance.
WARNING! Risk of electric shock. Can cause injury or death. Disconnect all local and remote electric power
supplies before working with the UPS. Ensure that the unit is shut down and power has been disconnected
before beginning any maintenance.
CAUTION: The external battery cabinets are heavy, see Table 8.5 on page 69. Take proper precautions when
lifting them.
1. Inspect the EBC for freight damage. Report damage to the carrier and your local dealer or Vertiv representative.
2. For tower installation:
• An additional set of support-base extensions ships with each EBC.
• See the steps in Tower Installation on the previous page, to connect the support extenders and install the
bases
- or -
NOTE: Optional slide rails and securing hardware are sold separately. Please contact your Vertiv representative for
options and Vertiv Technical Support for assistance.
NOTE: When removing an EBC, turn off the circuit breaker on the rear of the cabinet before disconnecting the cable.
NOTE: If shipping or storing the UPS for an extended time, disconnect the EBCs minimize stand-by current drain on
the batteries and help maintain design life.
Item Description
2 EBC connector
3 UPS
6 EBC-detection port
1. Align the connectors and press the power distribution box onto the UPS.
2. Hold the box firmly against the UPS and tighten the captive screws except the one over the maintenance bypass
breaker cover.
3. Confirm the maintenance bypass breaker Off.
4. Loosen the captive screw over the maintenance bypass breaker cover, pull down the cover and tighten the other
screw on the UPS side of the cover.
5. Turn the output and input breakers On.
6. Start the UPS according to start-up instructions.
WARNING! Risk of electric shock. Can cause injury or death. The UPS must be shut down or the load must be
transferred to an external maintenance bypass before a power distribution box may be added, changed or
removed. If the UPS will be shut down, the connected load must be shut down. If the UPS will be transferred
to maintenance bypass, it must be transferred to an external maintenance bypass. Verify that the GXT5 is
shut down and that all local and remote electric input power has been disconnected before beginning any
work on or in the UPS.
1. With the cover of distribution box removed, connect the UPS and distribution box connectors together. Ensure
that the connectors are fully connected.
2. Align the screw holes and press the power distribution box onto the UPS, making sure that the tabs at the
bottom of the box fit into the slots on the UPS.
3. Attach the box to the UPS by installing screws into the two holes at the top of the box.
4. Tighten the screws.
5. Turn the output and input breakers On.
6. Start the UPS according to start-up instructions.
NOTE: The UPS transfers the connected loads to the internal bypass.
c. Loosen the maintenance captive screw over the maintenance bypass breaker cover, pull up the cover and
tight another screw, ensure the screw is on the ON location.(see the following figure for the breaker's
location).
d. Turn the maintenance bypass breaker On.
NOTE: The load is unprotected from disturbances in the power supply while the UPS is on bypass.
2. Please wait 1 minute if the UPS is operating in battery mode, then confirm the UPS has turned off.
3. Turn the output and input breakers Off.
4. Loosen other captive screws until the power distribution box releases.
5. Remove the power distribution box from the UPS and set it aside.
6. On the rear panel of the new UPS, remove the new power distribution box from the UPS.
7. Mount and connect the new UPS to the old power distribution box.
8. Turn on the UPS input and output breakers and allow the UPS to start up. The load will continue to be powered
through the maintenance bypass breakers. See Figure 3.7 on page 25 for details.
9. Ensure the UPS is operating in Bypass mode.
10. Turn off the maintenance bypass breaker and replace the upper connector cover screw.
11. Use the power button to switch the output to the UPS inverter.
Figure 3.5 Power Distribution Box Removal from GXT5-5000MVRTLN and GXT5-6000MVRT4UXLN
Item Description
1 Output breaker
3 Input breaker
5 Screws
Figure 3.6 Power Distribution Box Removal from GXT5-8000MVRT6UXLN and GXT5-10KMVRT6UXLN Models
Item Description
1 Remove screws
WARNING! Risk of electric shock. Can cause equipment damage, injury and death. Before beginning
installation, verify that all external overcurrent protection devices are open (Off), and that they are locked
out and tagged appropriately to prevent activation during the installation, verify with a voltmeter that power
is Off and wear appropriate, OSHAapproved personal protective equipment (PPE) per NFPA 7OE. Failure to
comply can cause serious injury or death. Before proceeding with installation, read all instructions. Follow all
local codes.
Observe the following guidelines and specifications when making the hard wire input and output connections:
Observe the following guidelines and specifications when making the hard wire input and output connections:
• Provide circuit breaker protection according to local codes. The mains disconnect should be within sight of the
UPS or have an appropriate lock out.
• Maintain service space around the UPS or use flexible conduit.
• Provide output distributions panels, circuit breaker protection, or emergency disconnects according to local
codes.
• Do not install input and output wiring in the same conduit.
Models equipped with a manual bypass breaker pass bypass power directly to the bypass breaker from the input terminal
block. The input circuit breaker on the distribution box does not disconnect power from the manual bypass breaker.
GXT5-8000MVRT6UXLN 60A
GXT5-10KMVRT6UXLN 60A
N/A
GXT5-15KMVRT11UXLN 125A
GXT5-20KMVRT11UXLN 125A
Item Description
3 UPS
4 Mains/Utility
Item Description
6 Input
10 Output-distribution POD
GXT5-5000MVRT4UXLN 10 AWG
40 A
GXT5-6000MVRT4UXLN 8 AWG
4 AWG 20 lb-in (2.26 Nm)
GXT5-8000MVRT6UXLN
60 A 6 AWG
GXT5-10KMVRT6UXLN
GXT5-15KMVRT11UXLN 1 AWG
125 A 1/0 AWG 110 lb-in (5.65 Nm)
GXT5-20KMVRT11UXLN 1/0 AWG
1. Loosen the screws from the cable-entry/conduit-box cover, and pull the cables through the cable-entry
hole/knockout leaving some slack for connection.
NOTE: We are recommended using the knockouts to install input and output wiring in seperate conduit. You must use
a suitable cable gland or risk electric shock.
2. Referring to the appropriate terminal-block connection instructions, connect the cables to the corresponding
input/output terminals and use a torque wrench to turn the screw clockwise until tightened as specified in Table
3.2 above.
3. Re-install the cable-entry/conduit-box cover, and tighten the screws.
Item Description
1 Output
2 Input
NOTE: We recommend that signal-cable lengths be less than 10 ft (3 m), and are kept away from power cabling.
See the appropriate figure for your model in Rear Panels on page 4, for the location of the card port.
1. Remove the screws from the slot cover plate and remove the plate.
2. Insert the card into the slot, and secure with the screws that held the cover plate.
To make connections to the card, refer to the Installer/User Guide for the appropriate lntelliSlot card available at
www.Vertiv.com.
The I/0 dry contact port capacity is 125 VAC, 0.5 A; 30 VDC, 1 A.
NOTE: The emergency power off (EPO) action of the UPS closes the rectifier, inverter and static bypass, but it cannot
disconnect the UPS mains input inside. To completely disconnect the UPS, disconnect the upstream input circuit
breaker when generating the EPO. For details on REPO connection and operation, see Connecting a Remote
Emergency Power Off (REPO) Switch on the facing page.
User configurable dry contact input that can be set to trigger the events below. The user can also
select the dry contact as either NO or NC. (See System Parameter Options on page 45) When NO,
Pins 1 and 2 are shorted to trigger the event. When NC, Pins 1 and 2 are opened to trigger the
event.
Remote Options are:
1 Comms
Shutdown 1 • Disable (default)
1 Input 1
• Battery mode shutdown - If the UPS is running on batteries and this input is
triggered, the UPS shuts down
• Any mode shutdown - If this input is triggered, the UPS shuts down regardless of
current operating mode
Signal
2 Signal Ground
Ground
User configurable dry contact input that can be set to trigger the events below. The user can also
select the dry contact as either NO or NC. (See System Parameter Options on page 45) When NO,
Pins 3 and 4 are shorted to trigger the event. When NC, Pins 3 and 4 are opened to trigger the
event.
Remote Options are:
3 Comms
Shutdown 2 • Disable (default)
2 Input 2
• Battery mode shutdown - If the UPS is running on batteries and this input is
triggered, the UPS shuts down
• Any mode shutdown - If this input is triggered, the UPS shuts down regardless of
current operating mode.
Signal
4 Signal Ground
Ground
Battery EBC Automatically detects number of external battery cabinets when pins 5 and 6 are connected to
3 5, 6
Detection Detection the detection port, see Installing External Battery Cabinets on page 19.
REPO REPO Input 7 +5V REPO power supply, 5 VDC 100 mA.
User configurable dry contact output that can be set to alert the user to the faults below. The user
can also select the dry contact as either NO or NC. (See System Parameter Options on page 45)
When NO, Pins 9 and 10 are shorted when the fault occurs. When NC, Pins 9 and 10 are opened
when the fault occurs.
Remote Options are:
5 Output 5 9,10
Fault Alert 5
• Low battery (default)
• On battery
• On bypass
• UPS fault
User configurable dry contact output that can be set to alert the user to the faults below. The user
can also select the dry contact as either NO or NC. (See System Parameter Options on page 45)
When NO, Pins 11 and 12 are shorted when the fault occurs. When NC, Pins 11 and 12 are opened
when the fault occurs.
Remote Options are:
6 Output 6 11, 12
Fault Alert 6
• Low battery
• On battery
• On bypass
• UPS fault (default)
UPS ships with a REPO jumper installed, allowing the UPS to operate as a normally-closed switch system (failsafe). Opening
the circuit disables the UPS. To connect a REPO switch that opens the circuit to shut down the rectifier and inverter and
power off the UPS, use a cable from the remote switch to plug into the REPO port on the UPS.
In normal conditions, the REPO switch cannot cut off the UPS input power. When the REPO switch trips, the UPS generates an
alarm and immediately cuts-off battery charging and output power. When the emergency condition is resolved, the UPS will
not return to normal operation until you reset the REPO switch and manually power on the UPS.
Figure 3.10 on the next page, shows the cable required to make the connection. We recommend using 18 AWG to 22 AWG
(0.82 mm2 to 0.33 mm2) copper-core cable.
CAUTION: To maintain safety (SELV) barriers and electromagnetic compatibility, signal cables should be
shielded and run separately from power cables.
1. Connect one end of the cable to the remote switch, see Figure 3.10 below.
2. Remove the factory installed jumper from pins 7 and 8 of the dry contact port on the UPS.
3. Connect the plug to pins 7 and 8.
Figure 3.10 Cable/Plug for Connecting REPO switch to UPS REPO port
Item Description
1 Terminal 1
2 Terminal 2
4 REPO switch
The standard, B-type USB port connects to a network server or other computer system. The USB port supports HID/CDC
protocol. The CDC protocol is reserved for service software. To use the HID protocol for monitoring, get Power Assist from
www.vertiv.com/PowerAssist.
Item Description
1 NC
2 NC
3 TXD (out)
4 GND
5 NC
Item Description
6 RXD (in)
7 NC
8 NC
CAUTION: Starting the UPS applies mains/utility power to the output terminals. Make sure that the load
power is safe and ready to accept power. If the load is not ready, isolate the load with the output terminal.
1. If included on your UPS model, make sure the maintenance bypass switch is in the open OFF position and that
the guard is secured in place.
2. Ensure that the REPO connector on the rear of the unit has a jumper between pins 7-8 or that it is properly wired
to an Emergency Power off circuit (normally closed).
3. Make sure the breaker supplying power to the UPS is closed, and if necessary, press the input circuit breaker
reset buttons at the rear of the UPS.
4. Close all output breakers on the rear of the UPS (or in an external panel board, if used).
5. If external battery cabinets are attached, close the breakers on the rear of each cabinet.
6. Power on the UPS by pressing and holding the power button on the operation and display panel until the
confirmation dialog appears. Use the Up/ Down arrows to select YES, then press Enter.
7. If this is the first time start-up of the UPS, the Start-up Guidance wizard opens to set the basic parameters of the
UPS. Follow the prompts.
For detailed description of UPS display functions and settings, see Operation and Display Panel on page 35.
NOTE: Battery back-up run times are listed in Battery Run Times on page 69.
4 Operating the UPS Proprietary and Confidential ©2024 Vertiv Group Corp. 33
Vertiv™ Liebert® GXT5 UPS Installer/User Guide
If the UPS is operating normally, without faults, the option to continue to turn-on or turn-off the UPS displays:
a. Use the arrow buttons to select Turn on UPS or Turn off UPS, and press Enter.
b. Use the arrow buttons to select No or Yes, then press Enter to confirm.
If the bypass power is outside normal operating range, the option turn-off the UPS displays. Use the arrow buttons to select
No or Yes, then press Enter to confirm.
If the UPS is operating normally, without faults, the option to continue to turn-on or turn-off the UPS displays:
a. Use the arrow buttons to select Turn on UPS or Turn off UPS, and press Enter.
b. Use the arrow buttons to select No or Yes, then press Enter to confirm.
NOTE: The UPS automatically switches back to normal mode after an overheated or overloaded fault is cleared and
normal power is restored.
WARNING! Risk of electric shock. Can cause injury or death. Disconnect all local and remote electric power
supplies before working with the UPS. Ensure that the unit is shut down and power has been disconnected
before beginning any maintenance.
Transfer to Bypass mode, see Transferring from Bypass to Normal Mode above. Then, if power to the load is not needed, open
the main-input circuit breaker.
For systems with direct power distribution, isolate the UPS from AC power by disconnecting the external input MCB. If the
main and bypass are independently powered, close the two input MCBs.
To manually power off in an emergency, disconnect the terminal connecting the REPO port on the rear of the UPS.
If mains/utility power is present, the UPS control circuit remains active even though output power is disabled. To remove all
mains/utility power, disconnect the external main-input circuit breaker.
34 Proprietary and Confidential ©2024 Vertiv Group Corp. 4 Operating the UPS
Vertiv™ Liebert® GXT5 UPS Installer/User Guide
Item Description
5 LCD panel.
Escape Go back.
Power Power on the UPS, power off the UPS, transfer to bypass mode.
5 Operation and Display Panel Proprietary and Confidential ©2024 Vertiv Group Corp. 35
Vertiv™ Liebert® GXT5 UPS Installer/User Guide
NOTE: While the UPS is operating, the LCD will dim and display a screen saver if there is no active alarm or user
interaction for two minutes, see Figure 5.2 below. If an alarm or fault occurs or if any button is pressed, the UPS flow
screen displays.
NOTE: Do not rotate display, and follow handling instructions (pick up only from sides, do not use any plastic parts to
support the weight of the UPS).
NOTE: When an alarm is indicated, an alarm message is logged on Table 5.4 on page 52, describes the alarm
messages you may see. When a fault is indicated, front panel display list the fault, which are described in Table 7.2 on
page 64.
36 Proprietary and Confidential ©2024 Vertiv Group Corp. 5 Operation and Display Panel
Vertiv™ Liebert® GXT5 UPS Installer/User Guide
NOTE: Figure 5.3 below is an example flow screen and does not reflect the actual values that you may see on your
unit.
Use the arrow buttons to select the sub-menu options, and press Enter to open the sub menu. Press ESC to return to the flow
screen.
Status Voltage, current, frequency, and parameters for UPS components, see Status Screen on the next page.
Setting Display and system parameter settings, see Settings Submenu on page 41.
Log Current alarms and event history, see Log Screen on page 48.
About Product and network information, see About Screen on page 52.
Maintenance Service only, service password protected page for use only by Vertiv service representatives.
5 Operation and Display Panel Proprietary and Confidential ©2024 Vertiv Group Corp. 37
Vertiv™ Liebert® GXT5 UPS Installer/User Guide
Item Description
3 Ambient temperature and humidity. Only displays when sensors are connected.
1. At the main menu, select the Status icon, and press Enter.
2. Use the arrow buttons to move the cursor left/right and select a tab, then press Enter to display the status
information for the selected tab.
Item Description
NOTE: Multiple phases are shown in multiple columns. For example, a unit with three-phase input will display 3
columns of status data.
Frequency (Hz)
L-L voltage(V)
38 Proprietary and Confidential ©2024 Vertiv Group Corp. 5 Operation and Display Panel
Vertiv™ Liebert® GXT5 UPS Installer/User Guide
Power Factor
Energy (kWh)
Input power.
The number times that the input voltage was lost or dropped below 60 VAC (black out). Resets to 0 when UPS is
powered down.
The number of times that the input voltage was too low to support the load and the UPS was forced to switch to
battery power (brown out). Resets to 0 when the UPS is powered down.
Frequency (Hz)
L-L voltage(V)
Discharge count
5 Operation and Display Panel Proprietary and Confidential ©2024 Vertiv Group Corp. 39
Vertiv™ Liebert® GXT5 UPS Installer/User Guide
Frequency (Hz)
L-L voltage(V)
Energy (kWh)
Output power
Pout (kW)
Power Factor
40 Proprietary and Confidential ©2024 Vertiv Group Corp. 5 Operation and Display Panel
Vertiv™ Liebert® GXT5 UPS Installer/User Guide
• Output
• Battery
• Monitor
• System
NOTE: Do not change parameter settings or reset to factory defaults when powering-off the UPS.
1. At the main menu, select the Settings icon, and press Enter.
Voltage selection
Nominal voltage setting. Set the nominal system voltage to match the input voltage of the UPS.
• 100/173V
• 100/173RVS (L1/L2 reversed)
• 100/200V
• 110/190.5V
• 110/190.5RVS (L1/L2 reversed)
• 110/220V
• 115/199V
• 115/199RVS (L1/L2 reversed)
• 115/230V
• 120/208V (default)
• 120/208RVS (L1/L2 reversed)
• 120/240V
• 125/216.5V
• 125/216.5RVS (L1/L2 reversed)
• 125/250V
• Autodetect (default)
Startup on bypass
5 Operation and Display Panel Proprietary and Confidential ©2024 Vertiv Group Corp. 41
Vertiv™ Liebert® GXT5 UPS Installer/User Guide
Frequency selection
• Auto, Bypass enabled — Automatically detects frequency of utility/mains power and sets the nominal frequency
to match and bypass mode is enabled (default).
• Auto, Bypass disabled — Automatically detects frequency of utility/mains power and sets the nominal frequency
to match and bypass mode is disabled.
• 50 Hz — Bypass mode is disabled and the UPS provides 50-Hz output from any qualified utility/mains power.
• 60 Hz — Bypass mode is disabled and the UPS provides 60-Hz output from any qualified utility/mains power.
Sets the percentage that the input voltage may be above the selected output voltage setting and remain in Bypass mode.
• +10% (default)
• +15%
• +20%
Sets the percentage that the input voltage may be below the selected output voltage setting and remain in Bypass mode.
• -10%
• -15% (default)
• -20%
Run mode
• Normal — Connected load is always powered through the UPS inverter. ECO mode is disabled (default).
• ECO mode — ECO mode is enabled. The UPS inverter is bypassed, and the connected load is powered by
utility/mains power within the selected ECO voltage and frequency tolerances.
(Option only available when Run mode is set to ECO). Sets the percentage that the input voltage may be above or below the
selected output voltage setting and remain in ECO mode.
• ±5%
• ±10% (default)
• ±15%
(Option only available when Run mode is set to ECO). Sets the amount that the input frequency (Hz) may be above or below
the selected frequency setting and remain in ECO mode.
• ±1 Hz
• ±2 Hz
• ±3 Hz (default)
42 Proprietary and Confidential ©2024 Vertiv Group Corp. 5 Operation and Display Panel
Vertiv™ Liebert® GXT5 UPS Installer/User Guide
(Option only available when Run mode is set to ECO). To ensure the stability of the utility/mains power, this is the length of
time that the UPS requires the input voltage and frequency tolerences to be maintained before switching to ECO-mode.
• 1 min (default)
• 5 min
• 15 min
• 30 min
Sounds an alarm when the selected amount of time remaining for the UPS to operate in Battery mode.
• 2 - 30 minutes (default is 2)
• Enable (default)
• Disable
Sets the day of the week that the battery periodic test is performed.
Sets the length of time after the batteries are replaced to generate an alarm to remind the user to replace the batteries.
• Disable (default)
• 1 - 72 months
5 Operation and Display Panel Proprietary and Confidential ©2024 Vertiv Group Corp. 43
Vertiv™ Liebert® GXT5 UPS Installer/User Guide
Sets the maximum discharge time for the UPS. The default setting is the maximum allowing the battery to fully discharge. This
can be set lower to limit the amount of time the UPS will provide battery protection after which it will shut down. If the
discharge time remaining on the battery is lower than the setting value, it will have no effect.
Replace battery
Activates newly installed battery packs after replacement and reset all battery statistics for new battery packs.
Language
Selects the language of the display, see Selecting the Display Language on page 56. Options are:
• English (default)
• French
• Portuguese
• Spanish
• Chinese
• German
• Japanese
• Russian
Date
Selects the current date for the UPS display, YYYY-MM-DD. See Setting the Date and Time on page 56.
Time
Select the current time for the UPS display, HH:MM:SS. See Setting the Date and Time on page 56.
Display orientation
Selects the orientation of the display for use in rack or tower configuration. Options are:
• Auto-rotate — Automatically rotates based on the detected orientation of the UPS. (default)
• Horizontal — Screen rotated for rack use.
• Vertical — Screen rotated for tower use.
Audible alarm
If enabled, the UPS will beep when an alarm is generated. If disabled, it will be silent. See Audible Alarm (Buzzer) on page 63.
• Enable (default)
• Disable
44 Proprietary and Confidential ©2024 Vertiv Group Corp. 5 Operation and Display Panel
Vertiv™ Liebert® GXT5 UPS Installer/User Guide
Opens the dialog to change the password used to access and update the UPS parameter settings, see Changing the
Password on page 55.
Auto restart
Allows the automatic restart of the UPS when input power is restored after a complete shutdown of the UPS due to battery
end of discharge (EOD).
• Enable — The UPS will restart automatically when the input power is restored after EOD (default).
• Disable — The UPS will not restart automatically.
Length of time to elapse before an automatic restart after input power is restored.
Guaranteed shutdown
Forces a continued shutdown of the UPS after the Low Battery alarm threshold is reached, even if input power is restored
during this time. This can be used to ensure connected equipment shuts down completely after receiving a signal to
shutdown from an external monitoring device before power is re-applied. This ensures that once the equipment begins to
shut down, it is brought down completely before power is applied again.
• Enable
• Disable (default)
Allows the UPS to start when the battery is not installed or is not functional due to damage. This can be used to turn on the
UPS and power the attached load without battery protection when utility power is available but battery backup is not.
• Enable
• Disable (default)
Remote control
Allows the UPS to be controlled remotely via the CLI or RDU101 card.
• Enable (default)
• Disable
Automatically restart the UPS after an Any mode shutdown signal is received. When the UPS is shut down via dry contact
inputs 1 or 2, it will restart automatically if this option is enabled.
• Enable
• Disable (default)
5 Operation and Display Panel Proprietary and Confidential ©2024 Vertiv Group Corp. 45
Vertiv™ Liebert® GXT5 UPS Installer/User Guide
• Low battery — The contacts switch when the UPS reaches the amount of time left on battery configurable from
Low battery time. (default)
• On bypass — The contacts switch when the UPS is running in bypass mode
• On battery — The contacts switch when the UPS is running on battery
• UPS fault — The contacts switch when a UPS fault has occurred
• Low battery — The contacts switch when the UPS reaches the amount of time left on battery configurable from
Low battery time.
• On bypass — The contacts switch when the UPS is running in bypass mode
• On battery — The contacts switch when the UPS is running on battery
• UPS fault — The contacts switch when a UPS fault has occurred. (default)
Selects the action taken by the UPS when the input of dry contact 1 is triggered:
• Disable (default)
• Battery mode shutdown — If the UPS is running on batteries and this input is triggered, the UPS shuts down
• Any mode shutdown — If this input is triggered, the UPS shuts down regardless of current operating mode
Selects the action taken by the UPS when the input of dry contact 2 is triggered:
• Disable (default)
• Battery mode shutdown — If the UPS is running on batteries and this input is triggered, the UPS shuts down
• Any mode shutdown — If this input is triggered, the UPS shuts down regardless of current operating mode
46 Proprietary and Confidential ©2024 Vertiv Group Corp. 5 Operation and Display Panel
Vertiv™ Liebert® GXT5 UPS Installer/User Guide
Sleep mode
Allows the UPS to turn off the output on a weekly schedule. For instance, turn on every Monday at 1:00 and off every Friday at
23:00.
• Enable
• Disable (default)
Sets the day of week to turn on the UPS. This option is only shown when sleep mode is enabled.
Power on time
Sets the time of day to power on the UPS on the selected day. This option is only shown when sleep mode is enabled.
Sets the day of week to turn off the UPS. This option is only shown when sleep mode is enabled.
Sets the time of day to power off the UPS on the selected day. This option is only shown when sleep mode is enabled.
IT system compatibility
When this option is enabled, the Input phase reversed and Input ground lost alarms are disabled.
• Enable
• Disable (default)
1. At the main menu, select the Control icon, and press Enter.
2. Use the arrow buttons to move the cursor to the option, then press Enter.
5 Operation and Display Panel Proprietary and Confidential ©2024 Vertiv Group Corp. 47
Vertiv™ Liebert® GXT5 UPS Installer/User Guide
Control Options
Opens the dialog to change operating modes, see Operating the UPS on page 33.
Silences or un-silences the audible alarm, see Silencing the Audible Alarm on page 33.
Starts the battery self test manually. If the manual self test is already running, stop the self test.
Clear faults
Clears displayed faults after the issue causing the fault is resolved, see Table 7.2 on page 64, for a description of the faults.
Resets the values tracked to calculate the Efficiency graph, see About Screen on page 52.
1. At the main menu, select the Log icon, and press Enter.
2. Use the arrow buttons to move the cursor left/right and select a tab, then press Enter to display the log for the
selected tab.
48 Proprietary and Confidential ©2024 Vertiv Group Corp. 5 Operation and Display Panel
Vertiv™ Liebert® GXT5 UPS Installer/User Guide
Aux. power fault UPS internal auxiliary power voltage fault. Contact Vertiv Technical Support.
Battery cabinet More than 6 external battery cabinets are connected to the UPS with the auto-detect feature in use. Contact Vertiv service if using
connect abnormal more than 6 EBCs.
Battery aged The battery is old and at the end of its useful life. Replace the battery.
The battery has reached the end of discharge and mains/utility power is unavailable. Restore the mains power. The UPS will power off
Battery EOD
if it is not restored.
This alarm occurs when the battery approaches the EOD. After the pre-warning, the battery capacity allows two minutes discharge at
Battery low pre-
full load. The user can set the time with the Low Battery Time setting in Battery settings from 2 min - 30 min, (2 min by default). This
warning
allows for any loads to be shut down before the system powers off if utility power cannot be restored.
Battery mode The UPS operating in battery mode. The alarm will clear when utility power is restored.
Battery ambient temperature too high. Ensure that the battery ambient temperature is not higher than setting value 40 ~ 60 °C
Battery overtemp
(default: 50 °C)
Battery
The system time is past the time set for the batteries to be replaced. If you have disabled the Batt. note duration or have no batteries
replacement
installed, the alarm will not occur.
timeout
Battery reversed The battery positive and negative are reversed. Reconnect the battery and check the battery cable connections.
The remaining energy at the end of the periodic or manual self-test was deemed lower than acceptable. Battery replacement is
Battery test fail
recommended.
Battery test
The battery periodic self-test or manual self-test was started. This will display in the log whenever the event occurs.
started
Battery test
The battery periodic self-test or manual self-test has finished. This will display in the log whenever the event occurs.
stopped
Battery to utility
The UPS has transferred the load to the mains power from the battery. This will display in the log whenever the event occurs.
transition
Battery voltage
The battery voltage exceeds the normal range. Check if the battery terminal voltage exceeds the normal range.
abnormal
Battery to utility
The UPS has transffered the load to the mains power from the battery. This will display in the log whenever the event occurs.
transition
Bypass voltage
The battery voltage exceeds the normal range. Check if the battery terminal voltage exceeds the normal range.
abnormal
5 Operation and Display Panel Proprietary and Confidential ©2024 Vertiv Group Corp. 49
Vertiv™ Liebert® GXT5 UPS Installer/User Guide
May be caused by bypass voltage and frequency outside of range, bypass power off and incorrect bypass cables connection. Check
Bypass abnormal that the bypass voltage and frequency are within the setting range.
Check the bypass wiring
Bypass abnormal May be caused by ECO bypass voltage and frequency outside of range, ECO bypass power off, and incorrect ECO bypass cables
in ECO mode connection. Check that the ECO bypass voltage and frequency are within the setting range. Check the bypass cable connection.
Bypass mode The UPS is on bypass. This will clear when the UPS returns to Normal mode.
Bypass over-
The load is drawing more current than the UPS is rated to supply in bypass mode. Reduce the load.
current
Charger fault The charger output voltage is abnormal, and the charger is off. Contact Vertiv Technical Support.
Communication
Internal communication is abnormal. Check that the communication cables are connected correctly.
fail
The inverter is off due to DC bus voltage out of acceptable range. The load will transfer to bypass if the bypass is available because
DC bus abnormal
the bus voltage is outside of the acceptable range.
DC/DC fault The discharger is faulty, because the bus voltage exceeds the range when the discharger starts. Contact Vertiv Technical Support.
EOD turn off The inverter is off due to EOD. Check the mains power off state and recover the mains in time.
Fan fault At least one fan is faulty. Check if the fan is blocked or the cable connection is loose.
Faults cleared The faults have been cleared using Settings > Controls > Clear faults. This will display in the log whenever the event occurs.
Guaranteed The battery has finished discharging, then system shuts down because Guaranteed Shutdown is enabled (see Guaranteed shutdown
shutdown on page 45). This alarm will clear when the UPS is turned on again.
The rectifier and charger are off due to the mains voltage and frequency exceeding normal range. Check if the input voltage and
Input abnormal
frequency are within the normal range or if the mains input has gone down.
Input ground lost Check that the PE line is well connected and that the alarm can be cleared at the display.
Input neutral lost The mains input neutral is not detected. The alarm will clear when the neutral connection has been restored.
Input phase
The mains input line and neutral are reversed. Shut off external input breaker and connect the lines correctly.
reversed
Insufficient The UPS is on bypass and is started with a load greater than 105% of the rated capacity. Reduce the load to the rated capacity or
capacity to start below to start the unit.
The inverter is turned off when the inverter output voltage or current exceed the ranges set. If bypass is available, the UPS will
Inverter fault
transfer to bypass mode, otherwise the system will power off. Contact Vertiv Technical Support.
Inverter load capacity is larger than the rated value, overload delay time is up, inverter shuts down. If bypass is available, the system
Inverter overload will transfer to the bypass mode, otherwise the system will power off. Check the output load. If overloaded, reduce the load, and the
system will transfer to the inverter mode after five seconds with no alarm.
Inverter relay
The inverter relay is shorted. Contact Vertiv Technical Support.
welded
Manual power on The system was turned on via the display panel. This will display in the log whenever the event occurs.
50 Proprietary and Confidential ©2024 Vertiv Group Corp. 5 Operation and Display Panel
Vertiv™ Liebert® GXT5 UPS Installer/User Guide
Manual shutdown The system was shut down via the display panel. This will display in the log whenever the event occurs.
No battery No battery detected. Check the battery and battery cable connections.
On maintenance
The UPS is operating in maintenance bypass mode. This will display in the log whenever the event occurs.
bypass
Operating on
The UPS output is being powered by the inverter. This will display in the log whenever the event occurs.
inverter
Output disabled The system is in standby state, and the dry contact shutdown is enabled. Check if the shutdown dry contact is enabled.
Output off, This occurs when the output is off and the system detects that there is still voltage on the output. Check output equipment for
voltage is not zero backfeeds or contact Vertiv Technical Support.
Output pending Remote shutdown has been initiated, and the system will turn off shortly.
Output short A short has occurred on the output. Check the output cables and for any equipment that may have shorted.
Rectifier fault The rectifier is off because the bus voltage is out of the acceptable range when the rectifier starts. Contact Vertiv Technical Support.
The output power is larger than the rectifier overload point. Check that the input voltage meets the output load, if the mains input
Rectifier overload
falls to 176 V - 100 V, the load is derated linearly from 100% - 50%.
Remote power on The UPS was powered on remotely. This will display in the log whenever the event occurs.
Remote shut-off The UPS was powered off remotely. This will display in the log whenever the event occurs.
Remote shutdown Any mode shutdown was initiated by the dry contact input. This will display in the log whenever the event occurs.
Shutdown caused by the REPO terminal Normally-Closed contact input opening. This will display in the log whenever the event
REPO
occurs.
Restore factory On the Maintenance page, Restore Factory Defaults has been set while the UPS is in the stand-by state. This will return settings to
defaults their factory settings.
During the UPS operation, the system checks if the heat sink temperature exceeds the setting range. If an overtemperature, occurs,
check if:
Shutdown due to
1. The ambient temperature is too high.
over temp
2. Dust is blocking any of the UPS vents.
3. A fan fault has occured.
5 Operation and Display Panel Proprietary and Confidential ©2024 Vertiv Group Corp. 51
Vertiv™ Liebert® GXT5 UPS Installer/User Guide
Internal heat sink temperature is too high, and the inverter is off. The alarm can only be silenced if the heat sink temperature is lower
than the alarm setting. The system can automatically start after overtemperature fault is corrected. If an overtemperature occurs,
check if:
System over temp
1. The ambient temperature is too high.
2. Dust is blocking any of the UPS vents.
3. A fan fault has occured.
The UPS does not start because there is no mains/utility power or it is outside of the range of the voltage required to supply the full
Turn on fail
load. Check the AC input power.
UPS has no Both Inverter and Bypass are not supplying power due to the UPS output being turned off remotely or via the LCD or are unavailable
output due to no input power or input power out of range. Check that UPS is on and input power is available.
• Product tab—shows UPS identification information, firmware versions, and information about the communication
card (when the card is installed).
• Efficiency tab—shows curve of the efficiency of your UPS model vs the load. The efficiency at the current load is
shown to the right of the graph.
• Battery age tab—Shows the curve of the state of health (SOH) percentage of the installed battery over time. The
SOH is measurement of the installed battery's condition and ability to deliver the specified performance
compared to a fresh battery. During the lifetime of a battery, its health will deteriorate gradually due to
irreversible physical and chemical changes which take place with usage and with age until eventually the battery
will no longer usable. The UPS calculates one value per week and plots it on the graph. The value are based on
battery temperature, age, and the total amount of energy discharged from the battery that week. With use over
time, this percentage will decrease until the Battery Aged alarm is generated is at 25% . It is recommended to
replace the battery at or before this time.
1. At the main menu, select the About icon, and press Enter.
2. Use the arrow buttons to move the cursor left/right and select a tab, then press Enter to display the information
for the selected tab.
52 Proprietary and Confidential ©2024 Vertiv Group Corp. 5 Operation and Display Panel
Vertiv™ Liebert® GXT5 UPS Installer/User Guide
Item Description
Product Information
Product Type
Serial number
Boot FW version
Monitor FW version
DSP FW version
MAC address
Shows the MAC address of the RDU101 card. This is only shown when the RDU101 card is installed.
IPv4 address
Shows the IPv4 address of the RDU101 card. This is only shown when the RDU101 card is installed.
Subnet mask
Shows the subnet mask of the RDU101 card. This is only shown when the RDU101 card is installed.
Gateway address
Shows the gateway address of the RDU101 card. This is only shown when the RDU101 card is installed.
Efficiency Tab
Capacity
5 Operation and Display Panel Proprietary and Confidential ©2024 Vertiv Group Corp. 53
Vertiv™ Liebert® GXT5 UPS Installer/User Guide
Cap. (%)
This shows the percentage of the maximum capacity your UPS is currently using.
Eff. (%)
This shows the efficiency the UPS is currently operating at based on the Cap. (%) value.
Battery Age
This page also displays the following values:
This shows the date that it is recommend to replace the battery. It is 5 years from the time the battery was
installed.
SOH (%)
NOTE: We recommend that you change the password to protect your system and equipment and record the new
password and store it in an accessible location for later retrieval. See Changing the Password on the facing page.
1. Press the up-arrow button to change the digit, then press the down-arrow button to move to the next digit.
2. Repeat to select each digit, and press Enter to submit the password.
54 Proprietary and Confidential ©2024 Vertiv Group Corp. 5 Operation and Display Panel
Vertiv™ Liebert® GXT5 UPS Installer/User Guide
Turn on failed, condition is Appears when proper conditions are not met for UPS power on. Applies when using the power button or when execute the
not met command of Turn on/turn off/to Bypass on the LCD panel Control page).
NOTE: We recommend that you change the password from the default to protect your system and equipment. Record
the new password and store it in an accessible location for later retrieval.
1. At the main menu, select the Settings icon, and press Enter.
2. At the password prompt, use the up-arrow to select the first digit, press the down-arrow to move to the next digit,
repeat for each digit, then press Enter to access the settings.
3. Use the arrow buttons to select the Monitor tab, then press Enter.
4. Use the down arrow to highlight Change Settings Password, press Enter, and re-enter the current password. The
Input new password dialog opens, see Figure 5.10 below.
5. Enter the new password, then confirm the new password.
6. A confirmation dialog opens to indicate a successful password change.
7. Press ESC to return to the settings or main men.
5 Operation and Display Panel Proprietary and Confidential ©2024 Vertiv Group Corp. 55
Vertiv™ Liebert® GXT5 UPS Installer/User Guide
1. At the main menu, select the Settings icon, and press Enter.
2. At the password prompt, use the up-arrow to select the first digit, press the down-arrow to move to the next digit,
repeat for each digit, then press Enter to access the settings.
3. Use the arrow buttons to select the Monitor tab, then press Enter.
4. Use the down arrow to highlight Language, then press Enter.
5. Use the up/down arrows to select the language, then press Enter.
6. All the LCD elements display in the selected language.
1. At the main menu, select the Settings icon, and press Enter.
2. At the password prompt, use the up-arrow to select the first digit, press the down-arrow to move to the next digit,
repeat for each digit, then press Enter to access the settings.
3. Use the arrow buttons to select the Monitor tab, then press Enter.
4. Use the down arrow to highlight Date or Time, then press Enter.
5. Use the up/down arrows to select the date/time, then press Enter to confirm.
6. Use the down arrow to select the digit to change and the up arrow to select the correct digit. Repeat as needed
to set each digit.
56 Proprietary and Confidential ©2024 Vertiv Group Corp. 5 Operation and Display Panel
Vertiv™ Liebert® GXT5 UPS Installer/User Guide
6 Maintenance
WARNING! Risk of electric shock. Can cause equipment damage, injury and death. A battery can present a
risk of electrical shock and high short-circuit current.
WARNING! Risk of electric shock. Can cause injury or death. Disconnect all local and remote electric power
supplies before working with the UPS. Ensure that the unit is shut down and power has been disconnected
before beginning any maintenance.
WARNING! Risk of electric shock and explosion. Can cause equipment damage, injury and death. Do not
dispose of the battery in a fire. The battery may explode. Do not open or damage the battery. Released
electrolyte is toxic and is harmful to skin and eyes. If electrolyte comes into contact with the skin, wash the
affected area immediately with plenty of clean water and get medical attention.
WARNING! Risk of electric shock. Can cause equipment damage, injury and death. A battery can present a
risk of electrical shock and high short- circuit current.
WARNING! Risk of explosion. Can cause equipment damage, injury and death. A battery can explode if the
battery is replaced by an incorrect type. Dispose of used batteries according to the instructions included with
the battery-pack.
Read all safety cautions before proceeding. A trained user can replace the internal battery pack when the UPS is in a
restricted access location (such as a rack or server closet). To obtain the appropriate replacement battery packs, refer to
Table 6.1 on the next page, and contact your local dealer or Vertiv representative.
GXT5-5000MVRT4UXLN GXT5-144VBATKIT
GXT5-6000MVRT4UXLN GXT5-144VBATKIT
1
GXT5-8000MVRT6UXLN GXT5-288VBATKIT
GXT5-10KMVRT6UXLN GXT5-288VBATKIT
GXT5-15KMVRT11UXLN GXT5-288VBATKIT
2
GXT5-20KMVRT11UXLN GXT5-288VBATKIT
NOTE: The internal battery pack is hot-swappable. However, you must exercise caution because; during this
procedure, the load is unprotected from disturbances and power outages. Do not replace the battery while the UPS is
operating in Battery Mode. This will result in a loss of output power and will drop the connected load.
1. Press the button on the left-front of the UPS front panel, and pull the panel open, then, loosen and remove the
screw from the battery door, see Figure 6.1 on the facing page.
2. Lay the battery door and screw aside for reassembly.
3. Grasp the battery handle, and pull out the battery pack, see Figure 6.1 on the facing page.
4. Unpack the replacement battery pack, taking care not to damage the packaging to re-use when disposing of the
old battery.
5. Compare the new and old battery pack to make sure they are the same type and model. If so, proceed with step
6. If they are different, stop and contact your Vertiv representative, or Technical Support,
https://www.vertiv.com/en-us/support/.
6. Line-up and slowly push-in each replacement battery pack. The battery is fully inserted if the battery door fits
flush against the UPS.
7. Re-attach the battery door with the screw and replace the front cover.
8. Activate the new battery packs using the operating/display panel.
NOTE: The display menus and functions are described in Operation and Display Panel on page 35.
9. From the main menu, select Settings, then the Monitoring tab and verify that the date and time are correct. If the
date or time need correction, see Setting the Date and Time on page 56.
10. Select the Battery tab, use the arrows to select Replace Battery, and press Enter. The replaced battery packs are
activated.
11. Use ESC to return to the main display.
Item Description
1 Front panel
2 Battery door
If the UPS will be stored for a long time, We recommend connecting the UPS to input power for at least 24 hours every 4 to 6
months to ensure full recharge of the batteries.
We recommend checking the UPS operation once every 6 months. Ensure that output power loss to the connected load will
not cause data loss or other errors before conducting the check.
1. Press the Enter button to check the indicators and display function.
2. Check for alarm or fault indicators on the operation/display panel.
3. Make sure that there are no audible or silenced alarms. Select the Log, and look at the current tab for alarm and
fault history, see Log Screen on page 48.
4. Select the Setting menu, and look at the log for alarm and fault history.
5. Check the operating mode for Normal mode. If the UPS is operating in bypass mode, contact Vertiv Technical
Support.
6. Check to see if batteries are discharging (operating in Battery mode) and utility power is normal. If so, contact
Vertiv Technical Support.
WARNING! Risk of electric shock. Can cause injury or death. Disconnect all local and remote electric power
supplies before working with the UPS. Ensure that the unit is shut down and power has been disconnected
before beginning any maintenance.
The UPS requires no internal cleaning. If the outside of the UPS becomes dusty, wipe with a dry cloth. Do not use liquid or
aerosol cleaners. Do not insert any objects into the ventilation holes or other openings in the UPS.
WARNING! Risk of electric shock. Can cause injury or death. Disconnect all local and remote electric power
supplies before working with the UPS. Ensure that the unit is shut down and power has been disconnected
before beginning any maintenance.
NOTE: Do not operate the UPS with the POD removed. To shut off all power to the POD and to the load, utility input
power must be disconnected.
NOTE: The load is unprotected from disturbances in the power supply while the UPS is on bypass.
NOTE: The captive screws and maintenance bypass breaker cover is similar for all models. Figure 6.2 below, shows an
example on the 5 kVA/6 kVA model.
NOTE: Secure only one captive screw on the maintenance bypass breaker cover; do not attempt to force the second
screw.
Item Description
8. Align the tabs on the bottom of the replacement POD with the slots on the UPS, and press the POD onto the
UPS.
9. Secure the POD to the UPS using two screws.
10. Make sure the maintenance bypass switch is in the open, OFF, position and that the guard is secured in place.
NOTE: The maintenance bypass breaker interlock bracket must be installed behind the captive screw, and the screw
must be tightened for the UPS to operate in Normal mode.
11. Turn ON the input breaker on the rear of the UPS and leave the output breakers OFF. The UPS will begin to
startup.
12. Confirm that the UPS is operating in bypass mode. If not, then manually transfer the connected equipment to
bypass as follows:
a. Press and hold the Power button for two seconds.
b. Select Turn to bypass and press Enter.
13. Turn the output breakers ON.
14. Power on the UPS by pressing and holding the power button on the operation and display panel until the
confirmation dialog appears. Use the Up/Down arrows to select YES, then press Enter.
7 Troubleshooting
This section indicates various UPS symptoms you may encounter and provides a troubleshooting guide in the event the UPS
develops a problem. Use the following information to determine whether external factors caused the problem and how to
remedy the situation.
• The relative indicators illuminate, indicating the UPS has detected a problem.
• An alarm buzzer sounds, alerting the user that the UPS requires attention.
Continuous beep Generated when a UPS fault appears, such as a fuse or hardware failure.
One beep every 0.5 second Generated when a UPS critical alarm appears, such as on inverter overload.
One beep every 1 second Generated when a UPS critical alarm appears, such as on battery low voltage.
One beep every 3.3 seconds Generated when a UPS general alarm appears.
NOTE: When an alarm is indicated, an alarm message is logged. Table 5.4 on page 52, describes the alarm messages
you may see. When a fault is indicated, front panel display list the fault, which are described in Table 7.2 on the next
page.
7.2.1 Faults
When the fault indicator is illuminated, the LCD displays the fault. The faults are described in Table 7.2 on the next page.
Battery test fail The battery is bad or weak. Contact technical support.
When reporting a UPS issue to Vertiv, include the UPS model and serial number. These are located in several places for your
ease of location:
UPS is short-circuited or Ensure UPS is Off. Disconnect all loads and ensure nothing is lodged in output receptacles. Ensure loads
overloaded are not defective or shorted internally.
UPS fails to
start Batteries are not Check to ensure the internal battery is connected. If it is not, make the connection and try to start the unit. If
charged enough or not the battery is connected, leave the UPS connected to input power for 24 hours to recharge batteries, then
connected try to start the unit.
8 Specification
Table 8.1 UPS Specifications, 5 kVA to 10 kVA Models
Model GXT5 5000MVRT4UXLN 6000MVRT4UXLN 8000MVRT6UXLN 10KMVRT6UXLN 15KMVR-T11UXLN 20KMVR-T11UXLN
Unit 16.9 x 25.6 x 6.8 (430 x 650 x 173) 16.9 x 25.6 x 10.2 (430 x 650 x 261) 16.9 x 26.7 x 18.9 (430 x 680 x 482)
Shipping 35 x 25.2 x 29.1 (890 x 640 x 740) 35 x 25.2 x 38.6 (890 x 640 x 980) 27.1 x 48.0 x 46.0 (690 x 1220 x 1169)
Weight, lb.(kg)
Input AC
Operating
Frequency, 50 or 60 Hz (factory-default is 60 Hz)
Nom.
Factory
120/208 VAC at 120 degrees
default VAC
User
100/173V, 100/200, 110/190.5, 110/220. 115/199, 115/199, 115/230, 120/208, 120/240, 125/216.5, 125/250
Configurable
Allowable
Input Phase 120, 180, 240 degrees, auto-sensing on application of alternating current. (Restrictions for L-N voltages other than 120 VAC).
Angle
Input
frequency
without 40-70 Hz
battery
operation
Input Power
Hard-wired terminal terminal block 3W+G (L1-L2-N-G)
connection
L1-N, L2-N,
Maximum
150 VAC
Allowable
VAC
Output AC
Factory-
120/208 VAC at 120 degrees
default VAC
L1-L2
Factory-
default 120 degrees
Output Phase
Angle
Allowable
Output Phase 120, 180, 240 degrees, auto-sensing on initial application of input AC
Angle
Factory
default L1-N, 120 VAC nominal
L2-N VAC
Re-enable
Bypass If input voltage returns to within ±10% nominal output voltage.
Operation
Disable
Bypass When the input frequency prevents synchronous operation.
Operation
Battery Parameters
Quantity x
Voltage x 12 x 12V x 9.0AH 24 x 12V x 9.0AH 48 x 12V x 9.0AH
Rating
Recharge
5 hours to 90% capacity after full-discharge into 100% load.
time
Charger
1.8 A (default), maximum 5A
Current, A
Environment
Operating
Temperature, 32 to 104 (0 to 40) (no derating)
°F (°C)
Extended
Operating
Temperature 32 to 122 (0 to 50) output derated by 1% per 1 °C above 40°C
(derated), °F
(°C)
Storage
Temperature, 5 to 122 (-15 to 50)
°F (°C)
Relative
0 – 95% non-condensing
Humidity
Operating
Up to 10,000 ft (3,000 m) at 77°F (25°C) without derating
Elevation
Agency
Surge
IEEE/ANSI C62.41 Category B
Immunity
Transportat
ISTA Procedure 1A
on
Weight, lb.(kg)
Unit 6 (2.7) 8.8 (4.0) 8.6 (3.9) 9.9 (4.5) 10.6 (4.8) 9.5 (4.3)
Shipping 8.2 (3.7) 11 (5) 10.8 (4.9) 12.1 (5.5) 12.8 (5.8) 11.7 (5.3)
Electrical Specifications
Rating when
installed on 5 Factory default 5000VA/4500W
kVA
Rating when
installed on 6 Factory default 6000VA/5100W
kVA
(4)
5-20R (2) (4) (4) (4) (2)
Output power Hard-wired terminal block 3W + G (1) 5-20R 5-20R L5-20R L5-20R (4) L5-20R
connection (L-L-N-G) L14-30R (2) (2) (2) (2) L6-20R (2)
(1) L6-20R L6-30R L5-30R L6-30R L6-20R
L6-30R
Weight, lb.(kg)
Electrical Specifications
(4) (4)
(2) (4) (4) 5-20R 5-20R (4) (4) (2)
Output power L6-30R L6-20R 5-20R (2) (2) L6-20R L5-20R L6-20R (2)
connection (8) (4) (4) L6-30R L5-30R (4) (4) (2) L14-30R
5-20R 5-20R L6-30R (2) (2) L5-20R 5-15/20R L6-20R
L6-20R L5-20R
Weight, lb.(kg)
Electrical Specifications
Custom Connector
Input power connection
3W+G (L1-L2-N-G) to UPS
Unit (with bezel) 17.5 x 26.5 x 3.5 (430 x 650 x 85) 17.5 x 26.5 x 7.1 (430 x 650 x 173) 16.9 x 26.7 x 13.6 (430 x 680 x 346)
Shipping 35.5 x 25.7 x 19.8 (845 x 630 x 485) 35.5 x 25.7 x 23.2 (845 x 630 x 570) 26.4 x 34.6 x 34.1 (670 x 880 x 867)
Weight, lb.(Kg)
Battery
Environmental Requirements
Agency
% VA W Minutes
10 500 500 87.0 195.0 311.0 427.5 543.5 660.0 776.0 892.5 1009.0 1125.0 1241.5
20 1000 1000 41.5 94.0 149.0 211.0 273.5 335.5 397.5 460.0 522.0 584.5 646.5
30 1500 1500 24.5 61.0 97.0 133.0 175.0 218.0 260.5 303.0 345.5 388.0 430.5
40 2000 2000 16.5 44.0 71.5 99.0 126.5 157.5 190.0 222.5 255.5 288.0 320.5
50 2500 2500 12.5 33.0 55.5 78.0 100.0 122.5 146.5 173.0 199.0 225.5 252.0
60 3000 3000 9.5 25.5 44.5 63.5 82.0 100.5 119.0 138.5 160.5 182.5 204.5
70 3500 3500 7.5 20.5 36.5 53.0 69.0 85.0 101.0 117.0 133.0 151.5 170.5
80 4000 4000 6.5 17.0 30.5 45.0 59.0 73.0 87.0 101.0 115.0 129.0 145.0
90 4500 4500 5.0 14.5 26.0 38.5 51.5 64.0 76.5 89.0 101.5 114.0 126.5
100 5000 5000 4.5 12.5 22.5 33.5 45.0 56.5 68.0 79.0 90.0 101.5 113.0
% VA W Minutes
10 600 600 72.5 160.0 258.5 357.5 456.5 555.0 654.0 752.5 851.5 950.5 1049.0
20 1200 1200 33.0 77.5 122.0 172.0 224.5 277.0 329.5 382.0 434.5 487.0 539.5
30 1800 1800 19.0 49.5 80.0 110.0 142.0 178.0 213.5 249.5 285.5 321.5 357.5
40 2400 2400 13.0 35.0 58.5 81.5 104.5 128.0 154.0 181.5 209.0 236.5 263.5
50 3000 3000 9.5 25.5 44.5 63.5 82.0 100.5 119.0 138.5 160.5 182.5 204.5
60 3600 3600 7.5 20.0 35.5 51.0 66.5 82.0 98.0 113.5 129.0 146.5 165.0
70 4200 4200 6.0 16.0 28.5 42.0 56.0 69.0 82.5 96.0 109.0 122.5 136.5
80 4800 4800 4.5 13.5 24.0 35.5 47.5 59.5 71.0 82.5 94.5 106.0 118.0
90 5400 5400 4.0 11.5 20.0 30.5 41.0 51.5 62.0 72.5 83.0 93.5 104.0
100 6000 6000 3.5 9.5 17.5 26.0 35.5 45.5 55.0 64.5 73.5 83.0 92.5
% VA W Minutes
10 800 800 118 267.5 420 572.5 725 878 1030.5 1183 1335.5 1488 1640.5
20 1600 1600 56.5 124.5 203 283 363 443.5 523.5 603.5 684 764 844
30 2400 2400 35 81.5 128 181.5 236.5 291 346 400.5 455.5 510 565
40 3200 3200 23.5 59 93.5 128.5 169 210.5 251.5 293 334.5 375.5 417
50 4000 4000 17 45 73 101 129 161.5 195 228 261 294.5 327.5
60 4800 4800 13.5 35.5 59.5 82.5 106 129.5 156.5 184.5 212 240 267.5
70 5600 5600 10.5 29 49.5 69.5 89.5 110 130 153 177 201 225
90 7200 7200 7.5 20.5 36 52 67.5 83.5 99 115 130.5 148.5 167.5
100 8000 8000 6.5 17.5 31 45.5 60 74 88 102.5 116.5 131 147
% VA W Minutes
10 1000 1000 94.0 211.0 335.5 460.0 584.5 708.5 833.0 957.5 1082.0 1206.0 1330.5
20 2000 2000 44.0 99.0 157.5 222.5 288.0 353.0 418.0 483.0 548.0 613.5 678.5
30 3000 3000 25.5 63.5 100.5 138.5 182.5 226.5 270.5 314.5 358.5 402.5 446.5
40 4000 4000 17.0 45.0 73.0 101.0 129.0 161.5 195.0 228.0 261.0 294.5 327.5
50 5000 5000 12.5 33.5 56.5 79.0 101.5 124.0 149.0 175.5 202.5 229.0 255.5
60 6000 6000 9.5 26.0 45.5 64.5 83.0 102.0 121.0 140.5 163.0 185.5 207.5
70 7000 7000 7.5 21.0 37.0 54.0 70.0 86.0 102.0 118.5 135.0 154.0 173.0
80 8000 8000 6.5 17.5 31.0 45.5 60.0 74.0 88.0 102.5 116.5 131.0 147.0
90 9000 9000 5.5 15.0 26.5 39.5 52.0 65.0 77.5 90.0 102.5 115.5 128.0
100 10000 10000 4.5 13.0 23.0 34.5 46.0 57.5 69.0 80.5 91.5 103.0 114.5
NOTE: EBCs must be connected in pairs to these models. See Figure 3.4 on page 21 for details.
% VA W Minutes
10 1500 1500 133.0 303.0 473.0 643.5 814.0 984.0 1154.5 1324.5 1495.0 1665.0 1835.5
20 3000 3000 63.5 138.5 226.5 314.5 402.5 491.0 579.0 667.0 755.0 843.0 931.0
30 4500 4500 38.5 89.0 140.0 199.0 258.0 317.5 376.5 435.5 494.5 554.0 613.0
40 6000 6000 26.0 64.5 102.0 140.5 185.5 230.0 274.5 319.0 363.5 408.0 453.0
50 7500 7500 19.0 49.5 79.5 110.0 141.5 177.0 213.0 249.0 284.5 320.5 356.0
60 9000 9000 15.0 39.5 65.0 90.0 115.5 142.0 172.0 202.0 232.0 262.0 291.5
70 10500 10500 12.0 32.0 54.5 76.0 98.0 120.0 143.0 169.0 194.5 220.5 246.5
80 12000 12000 10.0 27.0 46.5 65.5 85.0 104.0 123.5 144.0 167.0 189.5 212.5
90 13500 13500 8.5 23.0 40.0 57.5 74.5 91.5 108.5 125.5 144.0 164.5 184.5
100 15000 15000 7.0 19.5 34.5 50.5 66.0 81.0 96.5 112.0 127.5 144.5 162.5
% VA W Minutes
10 2000 2000 99.0 222.5 353.0 483.0 613.5 743.5 873.5 1004.0 1134.0 1264.5 1394.5
20 4000 4000 45.0 101.0 161.5 228.0 294.5 361.0 427.0 493.5 560.0 626.5 693.0
30 6000 6000 26.0 64.5 102.0 140.5 185.5 230.0 274.5 319.0 363.5 408.0 453.0
40 8000 8000 17.5 45.5 74.0 102.5 131.0 164.0 197.5 231.0 265.0 298.5 332.0
50 10000 10000 13.0 34.5 57.5 80.5 103.0 126.0 151.5 179.0 206.0 233.0 260.0
60 12000 12000 10.0 27.0 46.5 65.5 85.0 104.0 123.5 144.0 167.0 189.5 212.5
70 14000 14000 8.0 21.5 38.0 55.0 71.0 87.5 104.0 120.5 137.5 157.0 176.5
80 16000 16000 6.5 18.0 32.0 46.5 61.0 75.5 89.5 104.0 118.5 133.0 150.0
90 18000 18000 5.5 15.0 27.0 40.0 53.0 66.0 78.5 91.5 104.0 117.0 130.0
100 20000 20000 4.5 13.0 23.0 34.5 46.5 58.0 69.5 81.0 92.5 104.5 116.0
Appendices
1-800-543-2378
1-800-543-2378
1-800-222-5877
1-800-543-2378
A.2 Locations
United States
Vertiv Headquarters
Westerville, OH 43082
Europe
Asia
Hong Kong
©2024 Vertiv Group Corp. All rights reserved. Vertiv™ and the Vertiv logo are trademarks or registered trademarks of Vertiv Group Corp. All other
names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been
taken to ensure accuracy and completeness here, Vertiv Group Corp. assumes no responsibility, and disclaims all liability, for damages resulting
from use of this information or for any errors or omissions.
SL-70524_REV5_05-24