NFS2-3030 Programming Manual
NFS2-3030 Programming Manual
NFS2-3030
Programming Manual
N3
Document 52545
09/08/2015 Rev:
P/N 52545:N3 ECN 15-0230
Fire Alarm & Emergency Communication System Limitations
While a life safety system may lower insurance rates, it is not a substitute for life and property insurance!
An automatic fire alarm system—typically made up of smoke (caused by escaping gas, improper storage of flammable materi-
detectors, heat detectors, manual pull stations, audible warning als, etc.).
devices, and a fire alarm control panel (FACP) with remote notifi- Heat detectors do not sense particles of combustion and alarm
cation capability—can provide early warning of a developing fire. only when heat on their sensors increases at a predetermined
Such a system, however, does not assure protection against rate or reaches a predetermined level. Rate-of-rise heat detec-
property damage or loss of life resulting from a fire. tors may be subject to reduced sensitivity over time. For this
An emergency communication system—typically made up of reason, the rate-of-rise feature of each detector should be tested
an automatic fire alarm system (as described above) and a life at least once per year by a qualified fire protection specialist.
safety communication system that may include an autonomous Heat detectors are designed to protect property, not life.
control unit (ACU), local operating console (LOC), voice commu- IMPORTANT! Smoke detectors must be installed in the same
nication, and other various interoperable communication meth- room as the control panel and in rooms used by the system for
ods—can broadcast a mass notification message. Such a the connection of alarm transmission wiring, communications,
system, however, does not assure protection against property signaling, and/or power. If detectors are not so located, a devel-
damage or loss of life resulting from a fire or life safety event. oping fire may damage the alarm system, compromising its abil-
The Manufacturer recommends that smoke and/or heat ity to report a fire.
detectors be located throughout a protected premises following Audible warning devices such as bells, horns, strobes,
the recommendations of the current edition of the National Fire speakers and displays may not alert people if these devices
Protection Association Standard 72 (NFPA 72), manufacturer's are located on the other side of closed or partly open doors or
recommendations, State and local codes, and the are located on another floor of a building. Any warning device
recommendations contained in the Guide for Proper Use of may fail to alert people with a disability or those who have
System Smoke Detectors, which is made available at no charge recently consumed drugs, alcohol, or medication. Please note
to all installing dealers. This document can be found at http:// that:
www.systemsensor.com/appguides/. A study by the Federal • An emergency communication system may take priority over
Emergency Management Agency (an agency of the United a fire alarm system in the event of a life safety emergency.
States government) indicated that smoke detectors may not go
off in as many as 35% of all fires. While fire alarm systems are • Voice messaging systems must be designed to meet intelligi-
designed to provide early warning against fire, they do not bility requirements as defined by NFPA, local codes, and
guarantee warning or protection against fire. A fire alarm system Authorities Having Jurisdiction (AHJ).
may not provide timely or adequate warning, or simply may not • Language and instructional requirements must be clearly dis-
function, for a variety of reasons: seminated on any local displays.
Smoke detectors may not sense fire where smoke cannot • Strobes can, under certain circumstances, cause seizures in
reach the detectors such as in chimneys, in or behind walls, on people with conditions such as epilepsy.
roofs, or on the other side of closed doors. Smoke detectors • Studies have shown that certain people, even when they hear
also may not sense a fire on another level or floor of a building. a fire alarm signal, do not respond to or comprehend the
A second-floor detector, for example, may not sense a first-floor meaning of the signal. Audible devices, such as horns and
or basement fire. bells, can have different tonal patterns and frequencies. It is
Particles of combustion or “smoke” from a developing fire the property owner's responsibility to conduct fire drills and
may not reach the sensing chambers of smoke detectors other training exercises to make people aware of fire alarm
because: signals and instruct them on the proper reaction to alarm sig-
• Barriers such as closed or partially closed doors, walls, chim- nals.
neys, even wet or humid areas may inhibit particle or smoke • In rare instances, the sounding of a warning device can cause
flow. temporary or permanent hearing loss.
• Smoke particles may become “cold,” stratify, and not reach A life safety system will not operate without any electrical
the ceiling or upper walls where detectors are located. power. If AC power fails, the system will operate from standby
• Smoke particles may be blown away from detectors by air batteries only for a specified time and only if the batteries have
outlets, such as air conditioning vents. been properly maintained and replaced regularly.
• Smoke particles may be drawn into air returns before reach- Equipment used in the system may not be technically compat-
ing the detector. ible with the control panel. It is essential to use only equipment
listed for service with your control panel.
The amount of “smoke” present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at var- Telephone lines needed to transmit alarm signals from a prem-
ious levels of smoke density. If such density levels are not cre- ises to a central monitoring station may be out of service or tem-
ated by a developing fire at the location of detectors, the porarily disabled. For added protection against telephone line
detectors will not go into alarm. failure, backup radio transmission systems are recommended.
Smoke detectors, even when working properly, have sensing The most common cause of life safety system malfunction is
limitations. Detectors that have photoelectronic sensing cham- inadequate maintenance. To keep the entire life safety system in
bers tend to detect smoldering fires better than flaming fires, excellent working order, ongoing maintenance is required per the
which have little visible smoke. Detectors that have ionizing-type manufacturer's recommendations, and UL and NFPA stan-
sensing chambers tend to detect fast-flaming fires better than dards. At a minimum, the requirements of NFPA 72 shall be fol-
smoldering fires. Because fires develop in different ways and lowed. Environments with large amounts of dust, dirt, or high air
are often unpredictable in their growth, neither type of detector is velocity require more frequent maintenance. A maintenance
necessarily best and a given type of detector may not provide agreement should be arranged through the local manufacturer's
adequate warning of a fire. representative. Maintenance should be scheduled monthly or as
required by National and/or local fire codes and should be per-
Smoke detectors cannot be expected to provide adequate warn- formed by authorized professional life safety system installers
ing of fires caused by arson, children playing with matches only. Adequate written records of all inspections should be kept.
(especially in bedrooms), smoking in bed, and violent explosions Limit-D-1-2013
This system meets NFPA requirements for operation at 0-49º This system contains static-sensitive components.
C/32-120º F and at a relative humidity 93% ± 2% RH (non- Always ground yourself with a proper wrist strap before han-
condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful dling any circuits so that static charges are removed from the
life of the system's standby batteries and the electronic com- body. Use static suppressive packaging to protect electronic
ponents may be adversely affected by extreme temperature assemblies removed from the unit.
ranges and humidity. Therefore, it is recommended that this Follow the instructions in the installation, operating, and pro-
system and its peripherals be installed in an environment with gramming manuals. These instructions must be followed to
a normal room temperature of 15-27º C/60-80º F. avoid damage to the control panel and associated equipment.
Verify that wire sizes are adequate for all initiating and indi- FACP operation and reliability depend upon proper installation.
cating device loops. Most devices cannot tolerate more than a Precau-D1-9-2005
10% I.R. drop from the specified device voltage.
FCC Warning
WARNING: This equipment generates, uses, and can Canadian Requirements
radiate radio frequency energy and if not installed and This digital apparatus does not exceed the Class A limits
used in accordance with the instruction manual may for radiation noise emissions from digital apparatus set
cause interference to radio communications. It has been out in the Radio Interference Regulations of the Cana-
tested and found to comply with the limits for class A dian Department of Communications.
computing devices pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable Le present appareil numerique n'emet pas de bruits radi-
protection against such interference when devices are oelectriques depassant les limites applicables aux appa-
operated in a commercial environment. Operation of this reils numeriques de la classe A prescrites dans le
equipment in a residential area is likely to cause interfer- Reglement sur le brouillage radioelectrique edicte par le
ence, in which case the user will be required to correct ministere des Communications du Canada.
the interference at his or her own expense.
HARSH™, NIS™, and NOTI•FIRE•NET™ are all trademarks; and Acclimate® Plus, FlashScan®, NION®, NOTIFIER®, ONYX®, ONYXWorks®, UniNet®,
VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc. Echelon® is a registered trademark and LonWorks™ is a trademark of
Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation. Microsoft® and Windows® are registered trademarks of the Microsoft
Corporation.
©Friday, October 16, 2015 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our
online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct/improve documentation
Send email messages to:
[email protected]
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical
Services.
Table of Contents
Section 1: General Information................................................................................................ 8
1.1: About This Manual ........................................................................................................................................8
1.2: UL 864 Compliance.......................................................................................................................................8
1.2.1: Products Subject to AHJ Approval......................................................................................................8
1.2.2: Programming Features Subject to AHJ Approval ...............................................................................8
1.3: Related Documents ........................................................................................................................................9
1.4: Introduction to the Control Panel ................................................................................................................12
1.4.1: Features..............................................................................................................................................12
1.5: Navigating Menu and Programming Screens ..............................................................................................12
1.6: Basic Procedure ...........................................................................................................................................13
1.7: Getting Started .............................................................................................................................................13
1.7.1: Password Change...............................................................................................................................13
Section 2: Main Menu ............................................................................................................. 16
2.1: Event Counts Display ..................................................................................................................................16
2.2: Multiple Event List ......................................................................................................................................16
2.3: History Display (History Select Screen)......................................................................................................16
2.4: Read Status ..................................................................................................................................................17
2.5: Program/Alter Status....................................................................................................................................17
2.6: Printer Functions..........................................................................................................................................17
Section 3: Program ................................................................................................................. 18
3.1: General Information.....................................................................................................................................18
3.2: Panel Program..............................................................................................................................................19
3.2.1: Panel Program Menu (1)....................................................................................................................19
3.2.2: Network Parameters ..........................................................................................................................19
3.2.3: Network Mapping..............................................................................................................................21
3.2.4: Panel Settings ....................................................................................................................................22
3.2.5: Panel Timers (Menu 1) ......................................................................................................................30
3.2.6: Panel Timers (Menu 2) ......................................................................................................................32
3.2.7: LCD Programming ............................................................................................................................33
3.2.8: ACS Programming ............................................................................................................................34
3.2.9: Supervision ........................................................................................................................................40
3.3: Panel Program Menu (2)..............................................................................................................................42
3.3.1: Password Change...............................................................................................................................42
3.3.2: Weekly Occupancy Schedule ............................................................................................................42
3.3.3: Remote Display Menu .......................................................................................................................43
3.3.4: Loop Configuration ...........................................................................................................................44
3.3.5: Custom Action Message....................................................................................................................46
3.3.6: Event Logging ...................................................................................................................................47
3.3.7: Holiday Menu ....................................................................................................................................47
3.4: Point Program ..............................................................................................................................................48
3.4.1: Detector Point ....................................................................................................................................49
3.4.2: Module Point .....................................................................................................................................58
3.4.3: General Zone .....................................................................................................................................64
3.4.4: Releasing Zone ..................................................................................................................................65
3.4.5: Logic Zone.........................................................................................................................................65
3.4.6: Trouble Zone .....................................................................................................................................69
3.4.7: Annunciator Board Label ..................................................................................................................70
3.4.8: Audio Point Programming.................................................................................................................72
3.5: Delete Program ............................................................................................................................................72
3.6: Autoprogram Menu .....................................................................................................................................74
3.6.1: To Create a New Program .................................................................................................................74
3.6.2: To Add/Delete Devices from the Program ........................................................................................74
3.6.3: Confirmation Screens ........................................................................................................................76
WARNING:
! INFORMATION ABOUT PROCEDURES THAT COULD CAUSE IRREVERSIBLE DAMAGE TO
THE CONTROL PANEL, IRREVERSIBLE LOSS OF PROGRAMMING DATA OR PERSONAL
INJURY.
CAUTION:
! INFORMATION ABOUT PROCEDURES THAT COULD CAUSE PROGRAMMING ERRORS,
RUNTIME ERRORS, OR EQUIPMENT DAMAGE.
NOTE: Information that highlights an important part of the preceding or subsequent text or
illustration.
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control
Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not
used at all as indicated below.
Program Feature or Option Permitted in UL 864? (Y/N) Possible Settings Settings Permitted in UL 864
IP downloads over a local area network No Yes No
(LAN) or the internet (Wide Area Network - No
WAN) Timed
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control
Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not
used at all as indicated below.
Program Feature or Option Permitted in UL 864? (Y/N) Possible Settings Settings Permitted in UL 864
AC Fail Delay Timer Yes None, or 1-12 hours 1-3 hours
1.4.1 Features
Programming features include the following:
• Ease of use - Field program the control panel without special software skills.
• Local programming - program directly from the control panel keypad to reduce installation
time.
• PC programming - input long data entry programming information on a PC; transfer
programming data between a PC and the control panel.
• Autoprogram option - automatically detect newly installed, addressable devices, allowing
quicker installation.
• Security - use passwords to control access to the control panel and protect programming.
• Large display option - 640 character screen, 16 lines x 40 characters
Pressing an ACCEPT soft key will save the information entered on the screen. It may also return to
the previous screen and/or perform other functions as described in the soft key section for each
screen.
When the FACP can not read an address (that is, if the point entered on the screen for processing
does not exist) it will display an error screen for several seconds, then return to the screen where the
address was entered. The user must check his input and investigate the state of the point.
CHANGE PASSWORD
MASTER PASSWORD
USER PASSWORD
BACK
Soft Keys
MASTER PASSWORD - Press to change the master password
USER PASSWORD - Press to change the user password.
Master Password
Press the MASTER PASSWORD Soft Key to display the following screen. Enter a new password
that will replace the factory default password: there can be up to eight alphanumeric characters.
Press the enter key on the keyboard. RE-ENTER PASSWORD will appear. Reenter the password for
verification. Press enter to save the new password.
BACK
User Password
Press the USER PASSWORD soft key to display the following screen.
USER:1 REFERENCE:JOHN
BACK
Soft Keys
USER: Press this soft key to scroll through the nine user password numbers. When this key is
pressed, the rest of the display will update to reflect information for each new record. Stop at the
password number that requires entering.
MODE: Press this soft key to select the user’s level of access. Levels are as follows:
• PROGRAM/ALTER STATUS Gives access to the Program Change Menu and Alter Status
Menu.
• ALTER STATUS Gives access to the Alter Status Menu
• NONE Gives no access.
REFERENCE: Press this key to enter a maximum 20-character alphanumeric label that identifies the
user. Press the enter key on the display/keyboard to enter the information.
ENTER PASSWORD - Press to enter a new password. Enter up to eight alphanumeric characters,
then press enter. RE-ENTER PASSWORD will appear. Retype the password for verification.
ACCEPT: After entering all password information and retyping the password at the prompt, press this
soft key to save all the password information.
Incorrect or Forgotten Password
If a password is entered incorrectly, the panel will respond by displaying an INVALID
PASSWORD message and a code. The programmer may hit the escape key and re-enter the
password correctly. However, if the password has been forgotten, record the code and contact
NOTIFIER. After proper authentication, the master password can be determined by deciphering the
code. An example of the message that would appear on the display follows:
INVALID PASSWORD:
9066-21FS-7D78-5FA4-6163
Code
PROGRAM/ALTER STATUS
Soft Keys
Pressing the soft keys brings the user to the screens described below.
NOTE: All events except troubles are annunciated during programming. When an annunciated
event occurs, the panel will automatically exit the programming screen and the Event Counts
menu screen will appear.
To access the Program level, press the Program/Alter Status soft key on the Main Menu and at the
prompt enter a master password, or a user password that allows access to the Program level. The
following screen will display.
NOTE: No program menus will display if a user password is entered that has access to Alter
Status level only: the Alter Status menu will be the sole menu choice.
AUTOPROGRAM MENU
Press a soft key with the word “program” in its menu to bring up the associated program menu.
When programming the panel for the first time, press the DELETE PROGRAM MENU soft key,
which brings up the Delete Program Menu screen (Refer to Figure 3.61). Press the CLEAR ALL
PROGRAMMING button, then ACCEPT, to ensure that the panel is set to defaults and clear of
programs.
NOTE: Clearing all programs is not necessary when initial programming with a database
downloaded from VeriFire™ Tools.
The logical sequence for initial programming is to program the panel parameters first, then to
program the individual points through autoprogramming and/or point programming.
BACK
NETWORK PROGRAMMING
NODE LABEL:
LAKEVIEW GENERAL HOSPITAL
Soft Keys
NODE NUMBER: Enter the network node number of this panel. For standalone NFS2-3030, the
network node number will be 000. A valid network node number range is 1-240. Once the soft key
has been pressed, the number may be typed in from the keypad, or the Next/Previous Selection spe-
cial function key on the keypad may be used to toggle through online node numbers. The network
node number may be viewed by pressing the Lamp Test special function key longer than five sec-
onds. (Refer to Section 5.1, “Version Information”, on page 102.) Default: 000
NODE LABEL: Enter the network node label for this panel. This is the label that appears in the
System Normal message. Default: <blank>
STYLE: Select the wiring style as 4 or 7. Default: style 4
CHANNEL A THRESHOLD, CHANNEL B THRESHOLD: Enter HIGH or LOW, for high or low
threshold setting for channel A or B on the network communications module. Default: HIGH
IP ACCESS: Press this soft key to bring up the IP ACCESS screen.
ACCEPT: Press this soft key to save the information entered on this screen.
IP ACCESS Screen
NOTE: Use of the IP ACCESS feature is subject to the approval of the local AHJ.
This screen allows the programmer to set the IP Access. This setting allows the disabling/enabling
of commands, downloads and programming from the Wide Area Network (WAN).
IP ACCESS
IP ACCESS: ON
ACCEPT
BACK
NOTE: Enabling IP ACCESS allows downloads over a local area network (LAN) or the internet
(Wide Area Network - WAN) using VeriFire™ Tools through the Noti•Fire•Net™ Web Server
(NWS), or a wide-area enabled NCS through a PC version of Noti•Fire•Net™ Gateway.
Always verify system operation after programming changes are made in this manner.
NOTE: The NFS2-3030 can be programmed to monitor events and initiate drill on one (1)
additional fire panel or gateway and up to four (4) DVCs.
NEXT navigates to the next screen in the sequence. The last screen will not have a NEXT key.
BACK will go to the preceding screen in the sequence or to the Node Programming menu if the
current screen is the first one in the 15-screen sequence. ACCEPT implements any changes that
have been made up to this point and returns the user to the Node Programming menu. AUTO
PROGRAM will consult the internal map of which nodes are on the network and automatically set
all 240 Nodes according to the map, regardless of which screen is being shown. The results will not
be saved to flash until the ACCEPT key is pressed.
Main menu
Program/alter status menu
Panel program menu
Network mapping
NETWORK MAPPING
SCREEN 01 OF 15
001:OFFLINE / 002:OFFLINE /
003:ONLINE /MAPPED 004:OFFLINE /
005:OFFLINE / 006:OFFLINE /
007:OFFLINE / 008:OFFLINE /
009:ONLINE /MAPPED 010:OFFLINE /
011:OFFLINE / 012:OFFLINE /
013:OFFLINE / 014:OFFLINE /
015:OFFLINE / 016:OFFLINE /
NEXT BACK
PANEL SETTINGS
PIEZO: ON MORE
NOTE: ACS devices programmed for acknowledge, signal silence, system reset and drill are not affected
by this setting: these commands will still function at the devices if LOCAL CONTROL is set to NO.
PIEZO:Press this soft key to toggle between OFF and ON. This option enables (ON) or disables
(OFF) the panel piezo from sounding when alarms or troubles occur. A setting of ON is overridden
if LOCAL CONTROL is set to NO. Default: ON
PROPRIETARY SUPERVISING STATION:Press this soft key to enable (YES) or disable (NO)
Local Receive mode. When enabled, events and the clearing of events must be handled one at a
time: each must be acknowledged. Latching events require a system reset. The panel will override a
setting of YES if the Node Number is greater than zero. Default: NO
NOTE: Proprietary Supervising Station does not support standalone mode (direct connect) with a
Digital Voice Command.
EVENT ORDERING: Press this soft key to toggle between USA and CANADA ordering priorities.
This order is applied to events shown in the Multiple Events List screen. Default: USA
With Fire as the highest priority: With MNS as the highest priority:
USA Event Order Canada Event Order USA Event Order Canada Event Order
Security — Security —
Note: Fire/MNS priority dependent on fire panel programming. Refer to page 28 for priority programming.
PANEL SETTINGS
Soft Keys
LCM LOCAL MODE: Press this soft key to toggle between YES and NO. Enter YES to enable all
SLCs to participate in local mode. When enabled, all LCMs will operate together in a limited
fashion when communication is lost with the NFS2-3030 CPU. Inputs on LCM loops (and
associated LEM loops, if installed) will activate outputs on all loops
• for those inputs and outputs that have been set with point programming to participate in local
mode, and
• when type codes are the same point type: that is, an input with a fire type code will activate an
output with a fire type code. (Refer to Appendix G, “Type Codes”, on page 158 for point types).
Default: NO
POWER MANAGEMENT MODE: Select ON to invoke the power management mode to conserve
power consumption. In this mode, the number of LEDs that can be turned ON on a particular loop
will be limited. A maximum of 30 input device (monitor modules and detectors) LEDs will be
allowed ON at a time. No output module LEDs will turn ON. When the limit of 30 LEDs is
reached, every time a new LED is turned ON, the oldest LED activation will turn OFF and will poll
in red rather than the usual green. Default:OFF
DCC PARTICIPATION: Press this key to program the panel for DCC (Display and Control Center)
participation. This network function ensures that one location at a time is in command of the
Acknowledge, System Reset, Signal Silence and Drill functions. Default: NO
CAUTION:
! ON FIRE SYSTEMS UTILIZING THE DCC FUNCTION, ALL LOCATIONS THAT CAN
PARTICIPATE IN DCC SHOULD BE SET TO YES.
FOR MASS NOTIFICATION APPLICATIONS, THE DCC FUNCTION SHOULD SET TO NO FOR ALL
LOCATIONS.
RAPID ALL CALL: Set YES to invoke Rapid All Call for XP Series transponder modules. For use
when retrofitting an AM-2020/AFP-1010 system that has XPP modules used for audio operation.
This setting causes these modules to activate more quickly. Rapid All Call is used with the
“Speaker” type code. Default:NO
DEFAULT SETTINGS: Press this soft key to activate default settings for the following:
REGIONAL SETTINGS: Press this soft key to proceed to the Regional Settings screen.
SCS SETTINGS: Press this soft key to proceed to the SCS Settings screen.
MORE: Press this key to progress to the third Panel Settings screen.
REGIONAL SETTINGS
REGIONAL SETTINGS:DEFAULT
ACCEPT
BACK
REGIONAL SETTINGS: Press the soft key to scroll through the selections. Choices are
CHICAGO, SINGAPORE, AUSTRALIA, CHINA or DEFAULT. The default is that there are no
special regional settings.
SCS SETTINGS
SCS MODE:A
ACCEPT
BACK
SCS MODE: Press to select mode A or mode B for SCS applications. Default: A
Note: For use with local SCS installations. Refer to the Smoke and HVAC Control Station SCS
Series Manual for additional information.
PANEL SETTINGS
BACK
PULSE ON TIME:0.5
PERIOD:1.0
NUMBER OF PULSES:03
BACK
Period
Number of Pulses
P U L S E O N T I M E : The Pulse On time is the amount of time that the tone will be ON within a
Period. Press this softkey to enter the amount of time in second and fraction of a second increments.
P E R I O D : A Period is the length of time designated for a pulse, including Pulse On time and
Pulse Off time. The pulse off time is designated by the amount of time left in a Period after the
Pulse On time has expired. Press this softkey to enter the amount of time in second and fraction of
a second increments.
N U M B E R O F P U L S E S : Press this softkey to enter the number of pulses that will occur before
the Tone Off Period.
T O N E O F F P E R I O D : The Tone Off Period is the amount of time that the tone will be silent
before running the pulse pattern again. Press this softkey to enter the amount of time in seconds and
fraction of a second increments.
For more information on programming the Intelligent Sounder Base, refer to “Detector Point” on
page 49.
Pressing the MORE soft key on this Panel Settings screen will display this screen:
PANEL SETTINGS
SILENCEABLE WATERFLOW: NO
PANEL SETTINGS
ACCEPT
BACK
REMINDER MENU
ACCEPT
BACK
Soft Keys
TROUBLE REMINDER: Press this soft key to toggle between the two possibilities:
YES: Choose this to initiate a daily 11:00AM reminder that there are uncleared troubles in the
system. The reminder will appear on the screen and will sound a piezo (if the piezo is enabled).
NO: Choose this if no reminder is desired. Default: YES
TROUBLE REMINDER DURATION: Press this soft key to toggle between 4 Hours and 24 Hours
to select the duration of time between trouble reminders.
4 HOURS: Choose to initiate a reminder every four hours until all troubles are clear. This
option should be selected if the fire panel is connected to a wireless network via the FWSG.
24 HOURS: Choose to initiate a trouble reminder every 24 hours until all troubles are clear.
Default: 24 HOURS
ACCEPT: Press this soft key to save the information entered on this screen.
PANEL TIMERS
Soft Keys
VERIFY TIME: Press this soft key to set the Alarm Verification timer. Type in a value of 0-240
(seconds), which will delay initiating devices set for Alarm Verification from signaling for the
amount of time entered. If a second alarm occurs while the alarm verification timer is counting, the
timer will stop and the alarm will signal immediately. Default: 30
MAXIMUM VERIFICATION COUNT: Press and enter a value from 0-20 for a maximum
verification count threshold value that applies to detectors set to participate in Alarm Verification.
A value of zero produces no verification trouble. When the counter exceeds the threshold value
entered, a trouble is generated to the panel. Default: 20
AC FAIL DELAY: Press this soft key to set the timing for the time delay from AC failure to when
the trouble is reported. Type in a value of 1-12 (hours), or select NONE. A value of NONE will
cause immediate notification. Default: 8
NOTE: AC FAIL DELAY settings other than 1-3 hours for off-premises notification require the
approval of the local Authority Having Jurisdiction.
The onboard trouble relay (TB3 on the CPU2-3030) will activate and TM-4s will report according
to this setting.
UDACTs and UDACT-2s are notified immediately of AC failure by the panel, regardless of the
panel’s delay setting. Once the UDACT or UDACT-2 receives notification, it operates according to
its own programmed AC Fail Delay reporting schedule.
Example: AC Failure occurs at 1:00 p.m. on a panel with an AC FAIL DELAY setting of 8
hours. The UDACT/UDACT-2 is set for notification after 6 hours
Time Event
1:00 p.m. AC Failure. Panel notifies UDACT/UDACT-2. Panel and UDACT/UDACT-2 timers begin
countdown to report time.
7:00 p.m. UDACT/UDACT-2 reports.
9:00 p.m. TM-4 reports, TB3 trouble relay activates.
The AMPS-24, ACPS-610, and ACPS-2406 power supplies must be set to an AC FAIL DELAY
value of 0 (zero) when used with this panel.
SILENCE INHIBIT: Press to enter a value from 0 (disabled) to 5 minutes. This software timer
disables the SIGNAL SILENCE key function for the time entered when a fire alarm occurs. The
timer starts at the first alarm only; it does not restart with each new alarm. Default: 0
AUTO SILENCE: Press to enter a value of OFF (no Auto Silence Timer), or a value of 10, 15 or
20 minutes. This global software timer functions like pressing the SIGNAL SILENCE key. For
example, if a value of 10 is entered, the control panel will silence all active outputs programmed as
silenceable after ten minutes. Default: 0FF
VERIFY=PREALARM: Press this soft key to enter Yes or No for displaying Prealarm during alarm
verification. Default: NO
PANEL TIMERS
PAS: OFF
DEFAULT TIMERS
ACCEPT
BACK
Soft Keys
PAS: Press to toggle between the choices of OFF or ON for PAS (Positive Alarm Sequence). Refer
to Appendix C, “Special Zone Outputs” for an explanation of this option. Default: OFF
PRESIGNAL DELAY: Press to enter a value of 00:00 (OFF) or a value of 1:00 to 3:00 minutes
(in the format MM:SS, where MM= minutes, SS=seconds). This feature initially causes alarm
signals to sound only in specific areas, monitored by qualified personnel. This allows delay of the
alarm for up to 3 minutes after the start of alarm processing. Refer to Appendix C, “Special Zone
Outputs” for further explanation of this option. Default: 3:00
DEFAULT TIMERS: Press this soft key to activate default settings for the following:
ACCEPT: Press this soft key to save the information entered on this screen and return to the
previous screen.
LCD PROGRAMMING
BRIGHTER DEFAULT
DARKER CURRENT
Soft Keys
BRIGHTER: Press this soft key to increase contrast. The intensity will increase by approximately
5% with each press of the key.
DARKER: Press this soft key to decrease contrast. The intensity will decrease by approximately
5% with each press of the key.
LANGUAGE: Press this soft to choose the language that will display on the LCD. Menu choices are
ENGLISH, HEBREW, PORTUGUESE and SPANISH.
To change the language display on an LCD-160, refer to Section 5.3.1, “LCD-160 Download
Menu”, on page 104.
BACKLIGHT: Press this soft key to select one of the following backlighting options: ON EXCEPT
AC FAIL, OFF, or ON. When ON EXCEPT AC FAIL is selected, the backlight will turn off when
the power supply experiences AC failure.
Default: ON
DEFAULT: Press to select the factory default setting (40%).
CURRENT: Press to select the intensity that was in effect when the screen was accessed.
ACCEPT: Line 5 (which displays LCD INTENSITY: 50% in the figure above) will change
value when the INTENSITY soft keys are pressed. Press ACCEPT to save the desired setting.
NOTE: Smoke Control devices must be set as FSCS or HVAC annunciator types. In addition to
its 64 smoke control points, when an SCS device is operating in FSCS (Firefighters Smoke
Control Station) mode, there are 32 additional points which function as alarm points. They can be
mapped to a zone or point to send the SCS device into a fire alarm state when any of the
additional 32 points is activated. Any of the 32 alarm points that are used must be set to
MONITOR mode from the panel. Any of these points that are not used can be set to NONE. Refer
to the SCS manual for further information on Smoke Control devices.
UDACT/UDACT-2 and TM-4 communicators, as well as the UZC Zone Coder, are installed on the
same EIA-485 ACS circuit as annunciators, and so are included with annunciator programming.
The TM-4 occupies one of the 32 annunciator addresses, and the UDACT or UDACT-2 can occupy
one or more of these addresses. The UZC can occupy up to four annunciator addresses, each with
64 points. When the UDACT/UDACT-2 or UZC expand beyond one annunciator address, 64PT
should be used for the subsequent address types, and the annunciator addresses should be
sequential. Other than address assignment, there is no ACS point programming for these devices.
Refer to the specific device manual for more information.
Press the ACS Programming soft key at the Panel Program screen to invoke the following screen.
Press the up and down arrow keys on the keypad to navigate through the annunciator addresses.
There will be a cursor highlighted at the current annunciator address position.
ACS PROGRAMMING
Soft Keys
ANNUNCIATOR TYPE: When the cursor is placed at the desired address, press this soft key to
scroll through the following list of types. Stop at the appropriate type.
* Two Level Bypass: When an ACS board is programmed as a 64SVC or 96SVC type,
the operator must enter the Program/Alter Status mode of operation before pressing any
push buttons to control points on these boards. If a push button is pressed while not in
the Program/Alter Status screen, and no unacknowledged events exist, the password
screen will automatically be displayed so the operator can enter the Program/Alter
Status mode.
† AMG Addressing: When using an AMG, the address it occupies (an address of 25
through 32, typically address 32) must be set to annunciator type AMG, and address one
must be set to annunciator type 64PT.
POINT PROGRAMMING: Press this soft key to proceed to the ACS Point Programming screen.
ACCEPT: Press this soft key to save all the changes made and return to the previous screen (Panel
Program).
NOTE: SLC output modules with releasing Type IDs may not be listed in the annunciator source
fields.
NOTE: The NFS2-3030 supports ACM-24AT/ACM-48A annunciators and their expanders with
either 64 or 96 points at an address, as well as ACM-16AT/ACM-32A/LDM-32 annunciators with
64 points at an address.
POINT: A27P04
MODE: MONITOR
NEXT ACCEPT
PREVIOUS BACK
Soft Keys
POINT: Press this soft key to enter the ACS point number. The format is AxxPyy, where A is the two-
digit device address, P is the two-digit point number. Enter a leading zero for one-digit numbers.
MODE: Press this soft key to enter the ACS mapping mode. Table 3.5 shows the possible mode
choices and descriptions of their functions.
NONE … is not programmed. No messages are sent from or received at this point.
LEDs at this point do not light.
CONTROL … will change the state of up to eight control modules The Point Active LED is lit if a corresponding mapped
OR (for NFS2-3030 only) up to eight general zones to off point is active. The Status (trouble) LED is on when a
or on when its button is pushed. point or zone is in trouble.
Selecting this point mode will bring up the Control Point
Select screen (refer to Figure 3.22).
MONITOR … will show the current status of a specified point or The Point Active LED is lit if the corresponding mapped
zone. point or zone is active. The Status (trouble) LED is on if
that point or zone is in trouble. If the point has a button, it
has no effect when pushed.
CO MONITOR … will show the current state of the CO element for the The Point Active LED is lit if a corresponding mapped
specified point entered. point is active. The Status (trouble) LED is on when a
point is in trouble. This point is specifically used to
annunciate the CO element of the PHOTO/CO detector.
TELEPHONE … supports telephone functionality when mapped to a Both the Point Active LED and the Status (trouble) LED will
telephone point. Press the button to connect the mapped flash if a telephone has been placed in the jack at the mapped
point with the telephone station. telephone point. Otherwise, the Point Active LED is lit if the
corresponding point or zone is active. The Status (trouble) LED
is lit if that point or zone is in trouble.
DISABLE … will change the state of a point, zone, or DAL device The Point Active LED is lit if the corresponding mapped
speaker circuit(s) specified through mapping from point or zone is active. The Status (trouble) LED is lit only
enabled to disabled, or from disabled to enabled, when if that point or zone is disabled.
its button is pushed.
See Caution below this table.
ACKNOWLEDGE … will act like an Acknowledge soft key or button on the The Point Active LED is lit when there are any fire alarms
panel, acknowledging an event when its button is in the system. The Status (trouble) LED is lit when there
pushed. are troubles in the system.
SILENCE … will act like the Signal Silence button on the panel, The Point Active LED is lit if all silenceable outputs have
silencing all silenceable outputs when its button is been silenced. The Status (trouble) LED is lit if not all
pushed. silenceable outputs have been silenced after the button
is pushed.
RESET … will act like the System Reset button on the panel, No LED will ever light at this point.
resetting the panel when its button is pushed.
DRILL … will act like the Drill button on the panel, initiating a fire The Point Active LED lights when the button is pushed
drill when its button is pushed. and the system has entered the drill state. The Status
(trouble) LED will never light.
ALL CALL This point will activate ALL CALL. (Speaker Circuits will The Point Active LED is lit if a corresponding mapped
turn on according to programming) to a DVC only. point is active. The Status (trouble) LED is on when a
Mapping must be to a DVC node. point or zone is in trouble.
If an AMG is connected to this panel, ALL CALL can be
activated ONLY by the ALL CALL switch on the AMG. Do
not program any other annunciators for ALL CALL.
PAGE EVAC ...will, when pressed after a Page Enable, allow Page The Point Active LED is lit if a corresponding mapped
Evac paging from that source. The Special Paging point is active. The Status (trouble) LED is on when a
Function map programming at the DVC will receive the point or zone is in trouble.
page function.
PAGE ...will, when pressed after a Page Enable, allow PAGE The Point Active LED is lit if a corresponding mapped
INACTIVE INACTIVE paging from that source. The Special Paging point is active. The Status (trouble) LED is on when a
Function map programming at the DVC will receive the point or zone is in trouble.
page function.
PAGE ALERT ...will, when pressed after a Page Enable, allow Page The Point Active LED is lit if a corresponding mapped
Alert paging from that source. The Special Paging point is active. The Status (trouble) LED is on when a
Function map programming at the DVC will receive the point or zone is in trouble.
page function.
ENABLE PAGE ...will cause the associated input to become an active The Point Active LED is lit if a corresponding mapped
audio source on Noti•Fire•Net. The user may then point is active. The Status (trouble) LED is on when a
choose to activate specific PAM points on remote Digital point or zone is in trouble.
Voice Commands to use this network input, or to perform
a paging function such as ALL CALL from this input.
FFT-NFN ....will, when pressed: The Point Active LED is lit if a corresponding mapped
• Notify a DVC in the map format point is active. The Status (trouble) LED is on when a
Nxxx,Nxxx,NxxxLyyMzzz or Nxxx,Nxxx,NxxxAyyT to point or zone is in trouble.
open the FFT-NFN link and turn on the mapped FFT
point or riser. A second press will notify the DVC to
turn off that FFT point or riser and determine whether
the FFT-NFN link should be closed or remain open.
• Notify a DVC in the map format Nxxx,Nxxx to close
or open the FFT-NFN link between two DVCs.
CAUTION:
! WHEN A DISABLED OUTPUT IS ENABLED, IT WILL BE AFFECTED BY CONDITIONS EXISTING
IN THE SYSTEM THAT WOULD NORMALLY AFFECT IT. FOR EXAMPLE, WHEN A CONDITION
EXISTS IN THE SYSTEM THAT WOULD NORMALLY TURN THE OUTPUT ON, THE OUTPUT
WILL TURN ON WHEN IT IS ENABLED.
SOURCE: Pressing this soft key will select the SOURCE field and also toggle between display
formats if a point value is allowed. Enter a point or zone, or the panel’s node number if the mode
type is a system function such as acknowledge or reset.
Up to eight sources are allowed when CONTROL mode is chosen.
For ALL CALL, PAGE INACTIVE, PAGE EVAC, and PAGE ALERT modes, enter the node number
of the DVC where the source is connected.
For TELEPHONE mode, enter the address of the telephone module point using the format
NxxXLyyMzzz. Use the format NxxxAyyT (where xxx=the node number and yy = the digital audio
amplifier address) for FFTs on risers that have no FTM modules installed.
FFT-NFN mode sources:
• format Nxxx,Nxxx,NxxxLyyMzzz: Telephone control module (NxxxLyyMzzz) preceded by
the node numbers of the two DVCs (Nxxx,Nxxx) that will communicate over the FFT-NFN
link.
• format Nxxx, Nxxx: numbers of the two DVCs that will communicate over the FFT-NFN link.
• format NxxxAyyT: Use this address (N = the DVC node number and A = the DAL device
address on the digital audio loop) when no telephone control modules are installed on a
DAL device’s FFT riser.
Refer to the FFT-NFN section of the DVC manual for programming and application examples.
ACCEPT: Press this soft key to save the changes to the point displayed.
BACK: Press this soft key to exit the screen without saving, and return to the ACS Programming
Screen.
N000I0001A00S1 XXX
XXX XXX
XXX XXX
XXX XXX
ACCEPT
NOTE: A zone with a node number of zero (0) will be a local zone.
• Panel circuit modules in the format NxxxPyy.z. xxx = FACP node number, yy = panel
circuit module number, z = panel circuit push button number.
• Prioritized Audio Matrix (PAM) speaker points, in the format NxxxIyyyyAzzSn. xxx = the
DVC node number, yyyy = the input number in the PAM, zz = the DAA address on the
Digital Audio Loop (01 through 32), and n = the DAA speaker circuit (1 through 4).
CAUTION: DO NOT MIX GENERAL ZONES WITH OTHER SOURCE TYPES FOR AN ACS
! CONTROL POINT. PROGRAM UP TO EIGHT GENERAL ZONES OR UP TO EIGHT OTHER
CONTROL POINT TYPES.
Soft Keys
All soft keys function like they do on the ACS Point Programming Screen.
3.2.9 Supervision
From the Panel Program Menu (1), select SUPERVISION to display the following screen.
SUPERVISION
PRINTER: 80-COLUMN
Soft Keys
MAIN POWER SUPPLY AC FAIL ADDRESS: Press to enter the “Monitor AC Fail” (base plus one)
address of the main power supply. Refer to the main power supply manual for complete addressing
information. Enter the power supply address and press ACCEPT.
The LCD backlight will turn off when this power supply experiences AC failure (see BACKLIGHT
in Section 3.2.7, “LCD Programming”, on page 33).
PRINTER: Press to scroll through the types of printer supervision: NONE, 40-COLUMN,
40-COLUMN SUPERVISED, 80-COLUMN, 80-COLUMN SUPERVISED. The printer will not be
active if NONE is selected. If a SUPERVISED selection is made, the printer will be supervised.
Default: NONE
CRT BAUD RATE: Press to scroll through CRT baud rates. “SUP” after the rate indicates
supervised. Select from: 4800, 4800 SUPERVISED, 9600, 9600 SUPERVISED, 19200,
19200 SUPERVISED, 38400, 38400 SUPERVISED, 57600, 57600 SUPERVISED. Default:
NONE
NOTE: When LCD-80 Terminal Supervision is on (LCD-80 is selected at the MORE Supervision
screen, see Figure 3.24 on page 41), CRT baud rate selections of 19200 and 57600 are disallowed.
AUXILIARY TROUBLE REPORTING: Press to toggle between Yes and No. Choose Yes if a
trouble bus cable has been attached at J5 of the CPU2-3030. Default: NO
TAMPER INPUT: Press the soft key to toggle between YES, NO, and AKS-1.
YES/NO reports (YES) or does not report (NO) a tamper situation at the panel cabinet door (as
determined by an STS-1 tamper switch connected as shown in this panel’s installation
manual).
AKS-1 should be selected when there is an AKS-1 key switch connected to the panel cabinet
door (which allows the operator to use Signal Silence, Reset, Drill and Acknowledge functions
when a key turns the lock to “Enable”). Default: NO
MORE: Press to bring up the second supervision screen.
ACCEPT: Press to save changes and return to previous menu.
Supervision Screen (MORE)
This screen appears when MORE is selected at the supervision screen.
SUPERVISION
TERMINAL:LCD-80 ACCEPT
BACK
TERMINAL: Select NONE or LCD-80. (Default: NONE.) When LCD-80 is selected, LCD-160
programming is not allowed.
NOTE: When LCD-80 Terminal Supervision is on, CRT baud rate selections of 19200 and 57600
are disallowed.
LOOP CONFIGURATION
Soft Keys
Press a soft key to bring up the associated menu.
BACK
Use the arrow keys on the keyboard to navigate between occupancy time fields: use the keypad to
type in the time values.
Soft Keys
WEEKLY OCCUPANCY SCHEDULE: Press this soft key to toggle between schedules 1 - 10. A
value of zero indicates no schedule.
ACCEPT: Press this to save changes made on the screen.
NOTE: To change the language of the remote display, or to program the panel banner to appear in
the remote display, refer to Section 5.3.1, “LCD-160 Download Menu”, on page 104.
Soft Keys
INSTALL REMOTE DISPLAY: To install a remote display, press the arrow keys to place the
cursor on the line next to the remote display address to be installed. Press this soft key until YES
displays. Default:NO
POINT PROGRAMMING: Once a display has been installed, press this soft key to program the
display point.
POINT LABEL
EAST WING HALLWAY
LOCAL CONTROL:YES
Soft Keys
DISPLAY POINT: Press this soft key to bring the cursor to the underlined field. Use the keypad to
type in the desired display address.
POINT LABEL: Press this soft key to bring the cursor to the underlined label field. Type in a label
of up to 40 characters that will appear in trouble messages.
LOCAL CONTROL: Press to toggle between YES and NO. A setting of YES enables local control at
the remote display.
LOOP CONFIGURATION
LOOP SELECTION
Lyy (LOOP)
Soft Keys
LOOP SELECTION: Pressing this soft key will invoke the cursor at the underlined field. Enter the
loop number desired (01 through 10) in the yy of the Lyy format.
NEXT/PREVIOUS SELECTION: Press either key to go forward or back through the loop
selections.
ACCEPT: Press to proceed to the Loop Point Programming screen.
Loop Programming
LOOP CONFIGURATION
Soft Keys
INSTALLED: Press this soft key to choose YES or NO, depending on whether an SLC is installed
at this address.
DETECTOR POLL: Press to select loop-polling mode. (See note below.)
MODULE POLL: Press to select loop-polling mode. (See note below.)
Most FlashScan devices can be programmed to run in either CLIP or FlashScan mode. The types
cannot be mixed on a loop: for example, if Loop 1 is programmed with a FlashScan module poll,
CLIP modules may not be used on that loop.
A detector’s LEDs will light a steady green for several seconds while it is subjected to a detector test
during FlashScan polling. Each detector is tested this way on a regular basis. During the short time
the LEDs are on steady, the detector is not providing fire protection.
RAPID POLL: For CLIP mode only - enable or disable Rapid Poll for CLIP. This feature will poll
the first 20 modules more often to speed response on manual pull stations.
WIRING STYLE: Press to select the NFPA wiring style (4 or 6) of the loop. If Style 6 is entered
when the wiring is Style 4, a trouble message will be generated at the panel.
BLINK MODE: Press to enable (ON) or disable (OFF) detector LED blinking for this loop. If the
Loop is configured in FlashScan mode with Blink Mode enabled, all detector and module LEDs
will remain OFF. If the loop is configured in CLIP mode with Blink Mode enabled, the LEDs for
detectors and monitor modules will remain OFF while the control modules operate normally.
MESSAGE
Edit
Custom
Action
Message here.
ACCEPT
VIEW BACK
CUSTOM ACTION MESSAGE:Enter a number with a value of 001 to 100 to display the
corresponding Custom Action Message, or to add or edit a message.
MESSAGE: This soft key appears after VIEW is pressed.Press to enter/edit a custom message in the
four lines indicated. The message may be up to 160 characters.
VIEW: Press this soft key to view the message that corresponds to the number entered in the
underlined field.
ACCEPT: Press to save any change made to the message and return to the previous screen.
NOTE: A printout of all the messages may be obtained by entering the PRINT PROGRAMMING MENU
(2) and pressing the CUSTOM ACTION MESSAGES soft key.
EVENT LOGGING
ACCEPT
BACK
Press the appropriate softkey to choose event logging (YES) and no event logging (NO). When YES
is chosen, the activations are logged into history and printed.
HOLIDAY MENU
MM/DD/YY
01 01/01/**
02 05/28/14
03 07/04/**
04 12/03/14
ANY YEAR 05 12/25/**
The cursor will appear in the date fields, and may be moved using the keyboard arrow keys. Type to
add/edit any holiday dates.
Soft Keys
ANY YEAR: Press to place asterisks in the YY section of the field. An asterisk denotes any year.
NEXT/PREVIOUS SELECTION: Press to view the next or previous group of five holidays.
ACCEPT: Press to save changes to the date fields and to return to the Panel Program Menu.
POINT SELECT:
LyyDzzz (DETECTOR)
Soft Keys
POINT SELECT: Press until the desired point type appears. The types - DETECTOR, MODULE,
GENERAL ZONE, LOGIC ZONE, TROUBLE ZONE, ACS BOARD, or DAA or DVC - appear in the
parenthesis after the point formats. Enter the desired point address in the format field. Formats are
illustrated in Table 3.6.
ACCEPT: Press to progress to the appropriate screen, based on the type of point selected.
NEXT/PREVIOUS SELECTION: Press to scroll backward or forward to the next or previously
installed point.
POINT LABEL:
MORE
EXTENDED LABEL:
ACCEPT
ZONE MAP:
Z003, Z104, Z105, Z106, Z107,
Z110, Z114, Z115, Z116, Z117 BACK
The point address is displayed in line 3 of this screen. Existing point information is displayed in the
fields.
Soft Keys
TYPE: Press this soft key to scroll through the point type choices: stop at the appropriate selection.
If a new point is being added, no other field will be displayed until TYPE: is entered and the
ACCEPT soft key is pressed. At this point, the rest of the fields will appear.
FLASHSCAN CODE LABEL: Press to scroll through a list of FlashScan Codes. Stop when the
appropriate label appears (Table G.4 on page 163 for codes and descriptions). If the detector is not a
FlashScan type, choose NONE.
POINT LABEL: Press this soft key to place the cursor at this field. Type in a 20-character
maximum point label that will appear in message formats. If no entry is made, the field will default
to the point address.
EXTENDED LABEL: Press to place the cursor at this field. Type in a 12-character maximum
extended label to further define the location or nature of the point.
ZONE MAP: Displays the zones mapped to this point. During initial programming, zone map
position one for each detector is set to Z0YY, where YY represents the loop number where the
detector resides. In Figure 3.35 above, zone position one has a value of Z003 (YY = 03). The
detector in the example resides on loop 3.
To add or delete zones for this point, press this soft key to progress to the Detector Zone Map
screen.
MORE: Press this soft key to progress to the next detector point programming screen.
ACCEPT: Press to accept changes. If the user is adding a point, pressing this soft key after entering
the TYPE field will display all the other fields.
Zone Map
The Detector Zone Map screen will display when the ZONE MAP soft key is pressed at the Detector
Point Programming screen.
Zone Map
Position
1
DETECTOR ZONE MAP
2 L03D123
ZONE SELECTION
3 Z003, (ZONE)
Z187, (ZONE)
4 Z234, (ZONE)
ZXXX (UNMAPPED)
5 ZXXX (UNMAPPED)
ZXXX (UNMAPPED)
6 ZXXX (UNMAPPED)
ZXXX (UNMAPPED)
7 ZXXX (UNMAPPED) ACCEPT
ZXXX (UNMAPPED)
8
BACK
9
10
When programming Zone Map for detectors, certain zone map positions are used for specific
functions:
1 Use to link zone label to detector and for group zone disable.
Soft Keys
CUSTOM ACTION MESSAGE: Displays the custom action message number (a value of one
through 100). The default value is 0 (no message). Press this soft key to progress to the Custom
Action Message screen (Figure 3.38) to view the message or to choose a different message for
viewing when this point activates. (To create a new custom action message, refer to Section 3.3.5,
“Custom Action Message”, on page 46.)
ALARM VERIFICATION: Press this key to determine the device’s participation in Alarm
Verification. Choosing Yes will set the device participation to the values entered at the Panel
Timers screen (Figure 3.17).
LOCAL MODE: Press to toggle between Local Mode (ON) or no Local Mode (OFF). When there is
a communication loss between the panel and its LCM/LEMs, SLC devices that have been selected
for Local Mode participation (ON) will continue to function across all the panel’s SLCs in a limited
manner as follows: input points will activate output points of the same Type Code point type
designations. For example, SLC inputs with “fire” point types will activate SLC outputs with “fire”
point types. Refer to Appendix G, “Type Codes”, on page 158 for type code point types. All SLC
detector types can participate in local mode.
NOTE: The panel setting LCM LOCAL MODE must be set to YES for local mode to work at the
device level.
MORE: Press this soft key to progress to the next detector point programming screen. (Note: The
third detector point programming screen may display different programming options depending on
the type ID selected.)
Custom Action Message
Press the Custom Action Message soft key on the Detector Point Programming screen to display
this screen. The user may choose a Custom Action Message at this screen.
Custom
Action
Message
Displayed here.
ACCEPT
VIEW BACK
Soft Keys
CUSTOM ACTION MESSAGE: Enter the number of the Custom Action Message to be displayed
during alarm conditions for this point (refer to Figure 3.31 on page 46 for an example).
VIEW: Press this soft key to view the message associated with the number entered.
ACCEPT: Press to save the entries made on this screen.
Sensitivity
Detector sensitivity levels for alarm and prealarm are set at this screen, which displays when the
SENSITIVITY soft key is pressed at the Detector Point Programming (2) screen.
DETECTOR SENSITIVITY
L03D123
OCCUPIED UNOCCUPIED
SENSITIVITY SENSITIVITY
ALARM - 7 ALARM = 3
OCCUPIED UNOCCUPIED
SENSITIVITY SENSITIVITY
PREALARM - 5 PREALARM = 3
The control panel provides nine levels of Prealarm and Alarm in percent per foot obscuration, with
the following exceptions:
• for heat detectors, the settings are in degrees Centigrade.
• for beam detectors, there are only six levels of Alarm. There is no Prealarm for beam detectors
in CLIP mode.
• for IntelliQuad FSC-851 and IntelliQuad Plus FCO-851 detectors, there are only six levels of
Alarm and Prealarm for FlashScan mode, The sixth level is a fixed 135oF, and it is not
available in CLIP mode.
Alarm sensitivity settings range from one to nine, with one representing the most sensitive alarm
level and nine the least sensitive.
Prealarm sensitivity settings range from zero to nine. Zero indicates no prealarm. A value of one
can be a self-optimizing setting where the control panel selects a suitable prealarm level for the
detector. Values one or two through nine represent decreasing sensitivity, with nine being the least
sensitive.
Refer to the section “Detector Sensitivity Settings” in Appendix D, “Intelligent Sensing
Applications” for a full description and a table of the nine sensitivity levels by detector type.
Soft Keys
OCCUPIED SENSITIVITY ALARM:
Press the soft key next to
OCCUPIED SENSITIVITY PREALARM: these setting categories to
enter values as described
UNOCCUPIED SENSITIVITY ALARM:
above.
UNOCCUPIED SENSITIVITY PREALARM:
ALARM SENSITIVITY TABLE: This table will toggle from ALARM to PREALARM based on
which sensitivity value is being entered. The table will display the values for this type of detector.
BACK
Soft Keys
WEEKLY OCCUPANCY SCHEDULE: Press this soft key to place the cursor at the underlined
field. There can be up to ten Weekly Occupancy Schedules. Enter a value of zero through ten. Zero
indicates no schedule is applied, and occupied detector sensitivity values are used.
ACCEPT: Press this key to accept the change made and return to the previous screen.
SILENCEABLE:NO
Soft Keys
LOW TEMP ENABLE: Press this softkey to select YES or NO to enable the Low Temperature
Warning for the PHOTO/CO detector. This field is only available when programming a
PHOTO/CO smoke detector.
PREALARM: Press this softkey to select ALERT or ACTION for the Prealarm function. Refer to
the section on Prealarm in Appendix D, “Intelligent Sensing Applications” for a description of
Alert and Action.
SILENCEABLE: This field determines whether the user can manually silence a detector’s
activated sounder/relay base. Values are as follows:
YES - RESOUND FIRE Silenceable, resound on fire alarm events Network and Local Resound
YES - RESOUND SUPERV Silenceable, resound on supervisory events Network and Local Resound
NOTE: In network applications, specific nodes can be excluded from having the ability to initiate a
resound on the local fire alarm panel. This is programmable via VeriFire Tools. Refer to the VeriFire Tools
help file.
INTELLIGENT SOUNDER: Press this softkey to select YES if an Intelligent Sounder Base is
installed for this detector.
SOUNDER BASE SETUP: Press this softkey to proceed to the Sounder Base Setup screen. This
option will only be available if the INTELLIGENT SOUNDER is set to YES.
CO PRE-ALARM: Press this softkey to select YES or NO to enable the CO Prealarm function for
the PHOTO/CO smoke detector. This field is only available when programming the PHOTO/CO
smoke detector.
VOLUME:HIGH BACK
A U X T O N E 1 C O N T R O L : Press this softkey to enter the Logic, General or Trouble Zone that
will control the activation of the first auxiliary tone of the intelligent sounder base.
A U X T O N E 2 : Press this softkey to select C O N T I N U O U S , T E M P - 3 , T E M P - 4 , M A R C H or
C U S T O M for the second auxiliary tone of the intelligent sounder base.
A U X T O N E 2 C O N T R O L : Press this softkey to enter the Logic, General or Trouble Zone that
will control the activation of the second auxiliary tone of the intelligent sounder base.
V O L U M E : Press this softkey to select L O W or H I G H for the intelligent sounder base volume level.
For CUSTOM TONE SETUP, refer to “Custom Tone Setup Screen” on page 27.
SILENCEABLE:NO
BACK
FLOW FAULT THRESHOLD: Set the percentage change from the baseline value when a Flow
Fault is detected. Range: 0-45%
DEFAULT: 21%
FLOW FAULT DELAY: Set the amount of time before the panel indicates the Flow Fault. Range 0-
255 seconds. DEFAULT: 200s
SILENCEABLE: Determines whether a user can manually silence an activated sounder/relay base.
NO: Not manually silenceable.
YES - RESOUND FIRE: Silenceable, resound on fire events (Network and Local resound)
YES - RESOUND SUPERV: Silenceable, resound on supervisory events (Network and Local
resound)
YES - NO RESOUND: Silenceable, no resound
NOTE: Specific nodes can be excluded from having the ability to initiate a resound on the local
fire panel. This option is programmable via VeriFire Tools.
REFERENCE DETECTOR ADDRESS: Set a detector to be used as a reference for air flow for
other FAAST detectors. All 5 detectors of each FAAST device using this detector as a reference
must be set with the same reference detector address, have the same Threshold value (set via
PipeIQ), and must be on the same loop as the reference detector. Range: 0, 1-159
DEFAULT: 0 (No reference detector programmed)
POINT LABEL:
MONITOR L03M123 ACCEPT
EXTENDED LABEL:
BACK
NOTE: If the point is not installed, MODULE TYPE:, TYPE CODE LABEL:, and FLASHSCAN
CODE LABEL: must be entered before any entries can be saved using the ACCEPT key.
POINT LABEL: Press this soft key to place the cursor at this field. Type in a 20-character
maximum point label that will appear in message formats. If no entry is made, the field will default
to the point address.
EXTENDED LABEL: Press to place the cursor at this field. Type in a 12-character maximum
extended label to further define the location or nature of the point.
MORE: Press to proceed to the next screen for more point programming.
ACCEPT: Press to save entries made on this screen.
ZONE MAP:
Z003 , Z104 , Z105 , Z106 , Z107
Z110 , Z114 , Z115 , Z116 , Z117
This menu selection will appear when 4-20MA has been entered as the module’s Type Code Label.
Zone Map Position 1 - Use for group zone disable participation.
Soft Keys
CUSTOM ACTION MESSAGE: Displays the custom action message number (a value of one
through 100). The default value is 0 (no message). Press this soft key to progress to the Custom
Action Message screen (shown in Figure 3.38) to view the message or to choose a different
message for viewing when this point activates. To create a new custom action message, refer to
Section 3.3.5, “Custom Action Message”, on page 46.
ZONE MAP: Displays the zones mapped to this point. During initial programming, zone map
position one for each monitor module is set to Z0YY, where YY represents the loop number where
the module resides. In Figure 3.45 above, zone position one has a value of Z003 (YY = 03). The
module in the example resides on loop 3.
To add or delete zones, press this soft key to proceed to the Module Zone Map screen. Refer to
“Zone Map” on page 50 for an illustration and explanation of the Detector Zone Map screen. The
Module Zone Map screen is the same except that Module replaces Detector in the title and the
module address appears instead of the detector address. Up to ten general, releasing or special
zones may be mapped to a monitor module: none of the zone map positions are fixed. Positions 1
and 3 - 7 have additional functionality.
Position 1 - This position is checked when a group zone disable command is issued. If the zone
number in the group zone disable command matches the zone number in the first position of
the zone map, the module point will be disabled.
Positions 3 - 7 - For the FMM-4-20 module only. These positions are assigned to FMM-4-20
threshold levels 1 - 5 respectively. (Threshold levels are user-programmed. Refer to “FMM-4-
20 Monitor Module Programming” on page 60.) Each will activate only if the device is
currently at that threshold level. Once the device leaves that threshold level, the zone in its
corresponding CBE position will remain active or deactivate according to whether its threshold
is programmed for latching or tracking.
ALARM VERIFICATION: Press this key to determine participation in Alarm Verification.
Choosing Yes will set the device participation to the value entered at the Panel Timers screen
(Figure 3.17). The only module type that can participate in alarm verification is the FZM-1.
LOCAL MODE: Press to toggle between Local Mode (ON) or no Local Mode (OFF). When there is
a communication loss between the panel and its LCM/LEMs, SLC devices that have been selected
for Local Mode participation (ON) will continue to function across all the panel’s SLCs in a limited
manner as follows: input points will activate output points of the same Type Code point type
designations. For example, SLC inputs with “fire” point types will activate SLC outputs with “fire”
point types. Refer to Appendix G.3, “Type Codes for Input Devices”, on page 158 for Type Code
point types. This setting is fixed at OFF for the FMM-4-20 module. Default: OFF
NOTE: The panel setting LCM LOCAL MODE must be set to YES for local mode to work at the
device level.
UNITS: PPM
Soft Keys
4 M A S C A L E V A L U E : Enter the 4 mA value.
Pressing the THRESHOLD SETUP soft key at the Module Point Programming screen will display
this screen.
Soft Keys
T H R E S H O L D N U M B E R : Enter the threshold number (1 - 5) that will be described in this screen.
T H R E S H O L D V A L U E : Enter the value for this threshold. (Threshold value is represented in the unit
type specified on the FMM-4-20 Device Setup Screen)
E V E N T : Select the event type that will generate when this threshold is reached. Selections are NO
EVENT,TROUBLE, FIRE, SUPERVISORY, SECURITY, NONFIRE, CRITICAL PROCESS.
T R O U B L E T Y P E : Select a trouble type for this threshold: TROUBLE 1, TROUBLE 2 or DEVICE
INHIBIT. Device Inhibit will generate a trouble when the FMM-4-20 is in a self-calibration state.
E V E N T T R I G G E R : Select LOWER LEVEL (values are falling), UPPER LEVEL (levels are rising), or
SAME LEVEL.
T R A C K I N G / L A T C H I N G : Select TRACKING or LATCHING for the threshold trouble. If more than
one threshold has been programmed as latching, the first threshold reached will be the one that is latched.
A C C E P T : Press to save screen entries.
Pressing the MORE soft key on this Module Point Programming screen will display this screen:
ACCEPT
BACK
ZONE MAP:
Z000 , Z104 , Z105 , Z106 , Z107
Z110 , Z114 , Z115 , Z116 , Z117
SILENCEABLE:NO BACK
Soft Keys
LOCAL MODE: Press to toggle between Local Mode (ON) or no Local Mode (OFF). When there is
a communication loss between the panel and its LCM/LEMs, SLC devices that have been selected
for Local Mode participation (ON) will continue to function across all the panel’s SLCs in a limited
manner as follows: input points will activate output points of the same Type Code point type
designations. For example, SLC inputs with “fire” point types will activate SLC outputs with “fire”
point types. Refer to Appendix G.3, “Type Codes for Input Devices”, on page 158 for Type Code
point types. Default: OFF
NOTE: The panel setting LCM LOCAL MODE must be set to Yes for local mode to work at the
device level.
ZONE MAP: Displays the zones mapped to this point. The default value assigned to control modules
during initial programming is Z000 at Position 1 (refer to Figure 3.49), with the exception of control modules
with the following Type IDs: TELEPHONE, GEN ALARM, GEN SUPERVIS, GEN TROUBLE, and
TROUBLE PEND.
To add or delete zones, press this soft key to proceed to the Module Zone Map screen. Refer to
“Zone Map” on page 50 for an illustration and explanation of the Detector Zone Map screen. The
Module Zone Map screen is the same except that Module replaces Detector in the title and the
module address appears instead of the detector address. Up to ten general, logic, release, special or
trouble zones may be mapped to a control module. Position 1 has additional functionality.
Position 1 - This position is checked when a group zone disable command is issued. If the zone
number in the group zone disable command matches the zone number in the first position of
the zone map, the module point will be disabled.
Note that the group zone disable command has no effect on general alarm zone Z000.
WALK TEST: This field determines if the output will activate during Walk Test. Values are ON
(the output will activate) and OFF (the output will not activate). Default: OFF.
NOTE: The following Type ID codes do not participate in Walk Test, and the WALK TEST soft key
will not appear when the screen displays: REL END BELL, RELEASE CKT, REL CKT ULC, REL.
FORM C, REL AUDIBLE, INST RELEASE, NONRESET CTL, TELEPHONE, and FORM-C RESET.
The FMM-1 module with SMOKE CONV, HEAT DETECT, or SMOKE DETECT does not participate
in Walk Test.
SWITCH INHIBIT: This field determines whether a user can manually activate an output.
Values are YES (can not be activated manually) or NO (can be activated manually). Default: NO
SILENCEABLE: This field determines whether the user can manually silence an activated output.
Values are as follows:
YES - RESOUND FIRE Silenceable, resound on fire alarm events Network and Local Resound
YES - RESOUND SUPERV Silenceable, resound on supervisory events Network and Local Resound
YES - RESOUND SECURITY Silenceable, resound on security events Network and Local Resound
NOTE: This soft key will not appear for modules with Type ID codes where silence is not optional.
NOTE: In network applications, specific nodes can be excluded from having the ability to initiate a
resound on the local fire alarm panel. This is programmable via VeriFire Tools. Refer to the VeriFire Tools
help file.
NON-RESETTABLE CONTROL:NO
SILENCEABLE: NO
BACK
Soft Keys
ZONE LABEL: Press to type in a 20-character maximum zone description that will appear in the
zone’s display messages.
NON-RESETTABLE CONTROL: Select YES to designate the zone as non-resettable (not affected
by System Reset), or NO to designate the zone as resettable (zone will turn off when System Reset
occurs.). Default: NO
SILENCEABLE ZONE: This option will designate the general zone as silenceable. When a
general zone is programmed as silenceable, a signal silence local to the panel or over the network
will deactivate the zone and any devices mapped to it, unless those devices are programmed with
another active zone that is not silenceable. Default:NO
PRECEDENCE PARTICIPATION: Must be set to YES if the zone is programmed as a control
zone to an ACM or SCS device. Default: NO
ACCEPT: Press to save the message and return to the previous screen.
DELAY TIME: 00
Refer to Appendix B, “Releasing Applications” for a full explanation of the fields below.
Soft Keys
DELAY TIME: Press this soft key to type a value from 0 to 60 (seconds). Default 00
NOTE: The FCM-1-REL has an inherent two second delay, which must be factored into the DELAY
TIME entry.
ABORT SWITCH: Press this soft key to scroll through the selection list of ULI, IRI, NYC, or
AHJ. Default:ULI
CROSS ZONE: Press to scroll through the selection list of YES, NO, ZONE, HEAT. Default: NO.
SOAK TIME: Press to type a value from 0 to 9999 (seconds). Default: 0000
NOTE: The FCM-1-REL has an inherent two second delay, which must be factored into the SOAK
TIME entry.
AND(Z20,OR(L2D159,L2D14))
EDIT EQUATION
Soft Keys
EDIT EQUATION: Press to proceed to the edit screen to add or edit a logic equation.
NEXT/PREVIOUS EQUATION: Press to view the next or previous logic equation.
Edit Logic Equation
This screen displays when the EDIT EQUATION soft key is pressed on the Logic Zone
Programming Menu
AND(Z20,OR(L2D159,L2D14))
INSERT UC
The cursor will be present in the equation, and can be moved by pressing the left/right arrow keys
on the keyboard. To add or delete information, use the INS/OVR soft key function described
below. Use the keypad to type in an equation. The ADD POINT/ZONE and ADD LOGIC
FUNCTION soft keys may be used to facilitate creating a logic equation; however, commas must be
added by using the keypad.
Soft Keys
INS/OVR: Press to toggle between insert and overwrite. Stop at the appropriate mode, which
displays in line 8 of the screen. Insert will add information to the equation, overwrite will write
over information already in the equation.
ADD POINT/ZONE: Press to proceed to the Add Point/Zone screen. This screen is an alternative
to typing in the information at this screen; it provides point and zone formats that make it less likely
for typographical errors to occur.
ADD LOGIC FUNCTION: Press to proceed to the Add Logic Function screen. This screen is an
alternative to typing in the information at this screen; it provides logic function formats that make it
less likely for typographical errors to occur.
ADD TIME/DATE: Press to proceed to the Add Time/Date screen.
DELETE EQUATION: Press to delete the entire equation.
ACCEPT: Press to save changes made on this screen and return to the previous screen.
NOTE: When the ACCEPT soft key is pressed to save an equation, the panel checks the
equation for errors. If there is an error in the equation, the previous screen will not appear, and the
cursor will appear at the error point. Correct the equation, and re-press the ACCEPT soft key.
AND(Z20,OR(L2D159,L2D14))
UC
POINT SELECT:
L01D043 (DETECTOR)
The cursor will be present in the logic equation. Place it, using the arrow keys on the keyboard, at
the place where the additional point should be inserted.
Soft Keys
POINT SELECT: Press to scroll through the list of possible formats (detector, module, etc.). Stop
at the desired format. Type in the address for the additional point.
ACCEPT: Press to insert the point into the equation where the cursor is blinking, and to return to
the previous screen.
NEXT/PREVIOUS POINT: Press these soft keys to scroll forward or backward from the
displayed point to the next installed point.
AND(Z20,OR(L2D159,L2D14))
OVERWRITE UC
BACK
The cursor will be present in the logic equation. Place it, using the arrow keys on the keyboard, at
the place where the logic function should be inserted.
Soft Keys
LOGIC FUNCTION: Press to scroll through the list of possible logic functions.
ACCEPT: Press to insert the logic function into the equation where the cursor is blinking, and to
return to the previous screen.
Add Time/Date
This screen appears when the ADD TIME/DATE soft key is pressed at the Logic Zone
Programming Menu screen
DEL
OVERWRITE UC
BACK
Soft Keys
ENTER TIME: _ _:_ _:_ _ Press this soft key to toggle between the time/date formats. Choose one
based on the type of time-based function used.
DEL, SDEL, TIM ENTER TIME:_ _:_ _:_ _ HH:MM:SS, entered as military time (22:30:00 = 10:30 P.M.)
TIM ENTER DAY: MO (Use the TOGGLE DAY soft key that appears to scroll through
and choose a day of the week.
PAIRING: X MORE
BACK
Soft Keys
A C S L A B E L : Type a label for the selected annunciator. The label can have up to 40 characters.
TROUBLE REPORTING DELAY: Smoke Control Systems only: Adjustable trouble timer for
FSCS. Programmable range is 0 to 180 seconds. Default: 90
NOTE: This value may not exceed 90 seconds for ULC installations.
PAIRING: Smoke Control Systems only: Select group 1, 2 or 3 to pair up to eight (8) FSCS
boards so that multiple smoke control modules can act as a single unit. If enabled, each FSCS
address can only be assigned to one group and each group can be assigned up to eight (8) FSCS
addresses, Default: X
PAIRED FSCS: Smoke Control Systems only: Displays any FSCS boards that have been paired
to this annunciator.
ACCEPT: Press to insert the logic function into the equation where the cursor is blinking, and to
return to the previous screen.
Press the MORE softkey to display the second ACS label screen.
SG1
SG2 DOWN
SG3
SG4
SG5 MORE
SG6
SG7
SG8 ACCEPT
VIEW BACK
Soft Keys
ZONE SELECTION: Press to assign the zone label that is to be displayed for the switch group
selected.
VIEW: Press to view the associated zone label for the switch group selected.
UP/DOWN: Press to move between switch group selections.
Press the MORE softkey to display the third ACS label screen.
SG9
SG10 DOWN
SG11
SG12
SG13
SG14
SG15
SG16 ACCEPT
VIEW BACK
Soft Keys
ZONE SELECTION: Press to assign the zone label that is to be displayed for the switch group
selected.
VIEW: Press to view the associated zone label for the switch group selected.
UP/DOWN: Press to move between switch group selections.
MASTER VOLUME: 9
AUXILIARY VOLUME:12
ACCEPT
BACK
Soft Keys
MASTER VOLUME: - This field can set the volume for all audio outputs at the DVC node. When
the audio amplifier point is set to 00, as it is in Figure 3.60, the setting affects all audio outputs on
the DVC node (this includes all outputs on its DAL devices). When a specific DAL device point is
entered at the point program menu (for example, N078AA01) the MASTER VOLUME setting will
apply to the audio outputs at that digital audio amplifier (the digital audio address with its address
set to 01). Set this field to any volume setting from 0 (off) to 15 (high). Default: 15
AUXILIARY VOLUME: - This field sets the volume for DVC inputs AUXA (background music
from various sources or a telephone paging source) and AUXB (AMG-1 input). The field does not
appear if a specific DAL device address has been entered. The DAL devices have onboard volume
control for AUX A and AUXB inputs. Set this field to any volume setting from 0 (off) to 15 (high).
Default: 15.
ACCEPT - Press to program the displayed volume.
CLEAR ACS
Soft Keys
CLEAR ALL PROGRAMMING: Press to remove all panel, loop, point and ACS programming
information, as well as logic and trouble zone equations. Pressing this key removes everything
except passwords. A confirmation screen will display asking the user to confirm the deletion
command. Pressing this key causes a reboot.
CLEAR:PANEL Press to remove all programmed panel setting information from control panel
memory. This does not remove ACS programming. A confirmation screen will display asking the
user to confirm the deletion command. Pressing this key causes a reboot.
CLEAR LOOPS Press to scroll through the options: ALL, LOOP 1, LOOP 2, …, LOOP 10. Stop at
the desired option. Press ACCEPT to delete all loop programming for the selected option. Pressing
this key causes a reboot.
DELETE POINT To delete a point, press this soft key to display the Delete Point screen.
CLEAR ACS: Press to remove all ACS programming from panel memory. A confirmation screen
will display asking the user to confirm the deletion command. Pressing this key causes a reboot.
ACCEPT: Press to clear all programming for the selected loop option for CLEAR LOOPS. A
confirmation screen will display asking the user to confirm the deletion command.
DELETE POINT
POINT SELECT:
LyyDzzz (DETECTOR)
POINT SELECT: Press to scroll through the options: detector or module. Stop at the desired
option. Press the DELETE soft key to delete the point from programming. A confirmation screen
will display asking the user to confirm the deletion command.
NOTE: Deleting points that are active or in trouble will cause a reboot.
AUTOPROGRAM
ACCEPT
BACK
Soft Keys
A U T O P R O G R A M L O O P S : Press to scroll through the options: ALL, 1+2, 3+4, 5+6, 7+8,
9+10. Stop at the desired option to select it.
ACCEPT: Press to autoprogram the selection. A confirmation screen will display asking the
programmer to confirm the autoprogram choice made (press the YES soft key to confirm). A screen
with the message AUTOPROGRAM IN PROGRESS will display until autoprogramming is complete.
AUTOPROGRAM CONFIRMATION
REVIEW BACK
AUTOPROGRAM CONFIRMATION
ADD POINT?
YES NO
EDIT BACK
Soft Keys
YES: Press this soft key to install the new point into the panel’s database.
EDIT: Press this soft key to advance to the point programming menu for the new point.
NO: Press if the point will not be installed.
Error and Discrepancy Resolution
Pressing the REVIEW soft key will bring up screens that provide the means to resolve any errors or
discrepancies found during autoprogram.
AUTOPROGRAM CONFIRMATION
DELETE POINT?
YES NO
BACK
Soft Keys
YES: Press to delete the point information from the panel’s database.
NO: Press to leave the point information in the panel’s database.
AUTOPROGRAM CONFIRMATION
OLD:CONTROL
NEW:MONITOR
ACCEPT CHANGES?
YES NO
EDIT BACK
AUTOPROGRAM CONFIRMATION
ACCEPT
BACK
Soft Keys
ACCEPT: Pressing this soft key acknowledges that the programmer has been informed of the
double address. Autoprogram will not make a modification to the database for this point. The
installer must correct this problem.
TROUBLE
PROGRAM MODE ACTIVATED
TROUBLE
PROGRAM MODE ACTIVATED
CONTROL ON/OFF
MO
RE
WIRELESS BACK
TROUBLE
PROGRAM MODE ACTIVATED
BACK
Soft Keys
All soft key selections (except BACK) are menu selections. Press to display the desired menu.
TROUBLE
PROGRAM MODE ACTIVATED
POINT SELECT:
N104LyyDzzz DETECTOR)
Soft Keys
POINT: Press this soft key to identify the type of point to disable/enable: the choices that will
appear in parentheses next to the point format are DETECTOR, MODULE, LOGIC ZONE,
GENERAL ZONE, or DAA SPEAKER CIRCUIT. Enter the address of the point using the keyboard.
If there is an event in the display area, that address will be the default. If no event is present, the
default format will be that of a detector.
4.2 Disable/Enable
A point can be disabled or enabled using this screen. Press the DISABLE/ENABLE soft key at the
Alter Status screen to display the following.
TROUBLE
PROGRAM MODE ACTIVATED
DISABLE BACK
Soft Keys
DISABLE/ENABLE Only the applicable command will display. Press to disable an installed,
programmed point, or to enable a disabled one.
CAUTION:
! WHEN A DISABLED OUTPUT IS ENABLED, IT WILL BE AFFECTED BY CONDITIONS EXISTING
IN THE SYSTEM THAT WOULD NORMALLY AFFECT IT. THAT IS, IF A CONDITION EXISTS
THAT WOULD HAVE TURNED THE OUTPUT ON WERE IT ENABLED, IT WILL TURN ON WHEN
IT IS ENABLED.
NOTE: When an input or output point associated with releasing functions is disabled, a single
supervisory trouble will be generated.
Group Zone Disable - This term refers to the disabling (or enabling) of a general zone. If the
first position in a device’s zone map matches the general zone number entered at this screen,
that device will be disabled (or enabled).
WARNING:
! DO NOT RELY ON DISABLE TO DISABLE RELEASING POINTS DURING TESTING. RELEASING
POINTS MUST BE PHYSICALLY DISCONNECTED.
TROUBLE
PROGRAM MODE ACTIVATED
POINT SELECT:
LyyDzzz (DETECTOR)
Soft Keys
POINT: Press to place the cursor in the format field. Type the address using the keyboard.
NEXT/PREVIOUS SELECTION: Press these soft keys to scroll sequentially through the detector
addresses on the loop. The screen will display the next loop when the last device on this loop is
passed.
ACCEPT: Press to proceed to the Detector Sensitivity screen.
The current sensitivity values displayed are described in Detector Point Programming (Refer to the
paragraph “Sensitivity” on page 53) and in Appendix D, “Intelligent Sensing Applications”.
TROUBLE
PROGRAM MODE ACTIVATED
BACK
Soft Keys
OCCUPIED ALARM SENSITIVITY:
Press the soft key next to one of
OCCUPIED PREALARM SENSITIVITY: these setting categories to proceed
to the next screen, where the
UNOCCUPIED ALARM SENSITIVITY:
setting value may be changed.
UNOCCUPIED PREALARM SENSITIVITY:
Change Alarm/Prealarm Sensitivity
This screen displays when any of the soft keys is pressed on the Detector Sensitivity Select screen.
The user can change detector sensitivity values using this screen.
The settings (1-9) displayed below the soft key are unique to the type of detector.
TROUBLE
PROGRAM MODE ACTIVATED
Soft Keys
OCCUPIED ALARM: The type of alarm/prealarm will display based on which soft key was
pressed in the previous screen. For example, in the screen above, OCCUPIED ALARM displays
because the OCCUPIED ALARM SENSITIVITY: soft key was pressed.
The detector sensitivity values display below the soft key. Select a value by pressing the soft key
until the desired value appears in the underlined field.
ACCEPT: Press to accept the change made on this screen, and to return to the previous screen.
TROUBLE
PROGRAM MODE ACTIVATED
CLEAR COUNTERS
BACK
Soft Keys
CLEAR COUNTERS: Press this soft key to clear all verification counters.
TROUBLE
PROGRAM MODE ACTIVATED
LOCAL HISTORY
BACK
Soft Keys
LOCAL HISTORY: Press to access the Local History Menu screen.
TROUBLE
PROGRAM MODE ACTIVATED
ALARM HISTORY
EVENT HISTORY
ALL HISTORY
BACK
Walk Test results are sent to the printer and to Event History as “Test”. In Network applications,
specific nodes can be excluded from having the ability to force the fire panel out of Walk Test. This
is programmable via VeriFire Tools. Refer to the VeriFire Tools help file.
WARNING:
! PHYSICALLY DISCONNECT ALL RELEASING DEVICES BEFORE STARTING WALK TEST. IT IS
NOT SUFFICIENT TO DISABLE IN ANY OTHER MANNER.
WARNING:
! WALK TEST MODE CAN DEACTIVATE FIRE PROTECTION. OBSERVE THE FOLLOWING
IMPORTANT PRECAUTIONS.
IMPORTANT!
• Prior to Walk Test, secure all protected buildings, and notify the building owner/operator,
fire department, and other pertinent personnel that testing is in progress.
• Immediately after Walk Test is completed, notify the same people that testing is complete
and the system is restored to normal operation. Reconnect releasing devices.
• Walk Test will “time out” and return to normal operation after one hour when no Walk Test
activations have occurred during that time.
• Walk Test may be exited at any time by pressing the ABORT soft key on the screen.
NOTE: Walk Test will not start if any devices are active (i.e., fire alarms, security, supervisories
or pre-alarms). To perform a walk test while a device is active, disable the device and press the
System Reset button.
NOTE: In network applications, specific nodes can be excluded from having the ability to force the
fire panel out of Walk Test due to an alarm condition. This is programmable via VeriFire Tools. Refer
to the VeriFire Tools help file.
Basic Walk Test - The basic test allows a single operator to run audible tests on the panel. All logic
equation automation is suspended during the test. All ACS devices will default to Disable. They
may be enabled by selecting NO at the DISABLE ACS BOARDS soft key on the Walk Test Menu
screen (Figure 4.12).
Advanced Walk Test - The advanced test allows field-supplied output point programming that will
react to input stimuli such as CBE and logic equations. When points are activated in advanced
testing, each initiating event will latch the input. Release of the latch and subsequent activation of
the next point is controlled through use of the NEXT TEST soft key. All ACS devices default to
disable. They may be enabled by selecting NO at the DISABLE ACS BOARDS soft key on the
Walk Test Menu screen (Figure 4.12). An advanced test is audible.
An audible test is intended for pull station verification, magnet-activated tests on input devices,
input and output device and wiring operation/verification. Only devices previously configured to
participate and designated as part of the test through the following screens will make sound.
NOTE: During local or network Walk Test, activating a Mass Notification device will activate
associated special function zones according to CBE programming and simulate a Mass
Notification event. Any network nodes, zones, or devices not participating in Walk Test will not
participate in the simulated Mass Notification event.
FlashScan poll mode - Once the START TEST soft key has been pressed:
• Each intelligent addressable input device will blink its address in red, and each intelligent
addressable output device will blink its address in green. Pattern examples are given below.
Address Blink Pattern
37 3 blinks, stop, 7 blinks, long stop, 3 blinks, stop, 7 blinks, long stop, …
152 15 blinks, stop, 2 blinks, long stop, 15 blinks, stop, 2 blinks, long stop, …
• An input device activated in Walk Test latches on steady green for the duration of the test. If
the device is put in trouble (for instance, the detector head is removed, then replaced), the LED
will be latched on for the duration of the test.
• An output device activated in Basic Walk Test will remain active and the LED will glow steady
green for
– 4 seconds for alarms
– 8 seconds for troubles.
• An output device activated in Advanced Walk Test will remain active and the LED will glow
steady green until the NEXT TEST soft key is pressed.
CLIP poll mode - Once the START TEST soft key has been pressed:
• Intelligent addressable input and output devices continue to blink red as usual until activated.
• An input device activated in Walk Test latches on steady red during activation. If the device is
put in trouble (for instance, the detector head is removed, then replaced), the LED will be
latched on for the duration of the test.
• An output device activated during Basic Walk Test will remain active and the LED will glow
steady green (if a FlashScan module) or steady red (if a CLIP module) for
– 4 seconds for alarms
– 8 seconds for troubles.
• An output device activated in Advanced Walk Test will remain active and the LED will glow
steady green (if a FlashScan module) or steady red (if a CLIP module) until the NEXT TEST
soft key is pressed.
Conventional Devices - Monitor modules with the Type Codes SMOKE CONV, HEAT DETECT, and
SMOKE DETECT, and outputs with the Type Code FORM C RESET do not participate in Walk Test other
than blinking their addresses if they are polled in FlashScan mode unless they are used with a
FlashScan zone module. To prevent the occurrence of false alarms for conventional devices, 24 volt
power will be interrupted for up to a minute after Walk Test has been exited.
TROUBLE
PROGRAM MODE ACTIVATED
BASIC/ADVANCED: BASIC
SILENT/AUDIBLE: AUDIBLE
Soft Keys
BASIC/ADVANCED: Press to toggle between the two choices. Stop at the desired test.
SILENT/AUDIBLE: This soft key is for future use. Walk test is audible.
PARAMETER: Press to scroll through the choices. Stop at the desired parameter. Choosing the
loops parameter will bring up the Walk Test loops programming screen. (Refer to Figure 4.13.)
Choosing the Zone parameter will bring up the Zone Walk Test screen. (Refer to Figure 4.16.)
Choosing the Devices parameter will bring up the Devices Walk Test screen (Refer to Figure 4.14.
If this
The participating devices/points in Basic The participating devices/points in
parameter is
Test will be… Advanced Test will be…
chosen…
LOOPS All devices/points on all the FACP SLCs All devices/points on all the FACP SLCs
that are set to participate in Walk Test with that are set to participate in Walk Test.
the exception of logic equations, whose When an input test is initiated, outputs
activation is suspended. When an input test mapped on all loops will activate.
is initiated, only the outputs on the
corresponding loop will activate.
PANEL The entire panel - all devices/points set to The entire panel - all devices/points set
participate in Walk Test - will participate with to participate in Walk Test - will
the exception of logic equations, whose participate. When an input test is
activation is suspended. When an input test initiated, outputs mapped on all loops
is initiated, only the outputs on the will activate.
corresponding loop will activate.
ZONE For BASIC Walk test only. When the zone n/a
entered in the parameter field is present in a
device’s first (primary) CBE location, that
device will go into Walk Test when the
parameter zone is put into Walk Test. When
an input test is initiated, outputs mapped to
the corresponding zone on all loops will
activate.
DISABLE ACS BOARDS: This soft key allows the operator to disable ACS devices during Walk
Test. Press to toggle between the two choices, YES (disable) and NO (enable). Default: YES
TROUBLE
PROGRAM MODE ACTIVATED
START TEST
BACK
Once the START TEST soft key has been pressed and the
test begun, the BACK option changes to ABORT
The chosen settings are displayed (BASIC, AUDIBLE in Figure 4.13), and installed loops will
display with a participation field. The up and down arrow keys on the keypad navigate through the
fields. Choose YES for participation, NO for no participation, using the
NEXT SELECTION(+)/PREVIOUS SELECTION(-) keys on the keypad.
Soft Keys
START TEST: Press to begin Walk Test using the chosen parameters. Once Walk Test has begun,
this soft key becomes ABORT, and can be pressed at any time to exit Walk Test.
NEXT TEST: This key appears for Advanced Walk Tests when the panel parameter is chosen at the
Walk Test Menu Screen. Refer to Figure 4.17 for the location of this key. Press it to progress from
one activation to the next, latching the new point and releasing the latch on the previous point.
TROUBLE
PROGRAM MODE ACTIVATED
DEVICE:L01D005
This screen appears when DEVICES is chosen as a parameter at the Walk Test Menu. The chosen
settings are displayed (BASIC, AUDIBLE in Figure 4.14).
Soft Keys
DEVICE:Press this key to type the desired detector address into the underlined field.
NEXT POINT: Press this key to bring up the next installed address for an addressable detector into
the DEVICE field.
PREVIOUS POINT: Press this key to bring up the previous installed address of an addressable
detector into the DEVICE field.
ACCEPT: Press this key to begin Walk Test, and to proceed to the Devices Test Selection screen
(Figure 4.15).
TROUBLE
PROGRAM MODE ACTIVATED
This field will appear only for a beam detector with an integral sensitivity test feature.
Soft Keys
START TROUBLE TEST:Press this key to generate a Trouble on the selected detector.
START ALARM TEST: Press to generate an Alarm on the selected detector.
START OBSCURATION TEST: Press to perform an Obscuration Test on the selected Beam
detector. (Beam detectors only.)
START PREALARM TEST: Press to perform a Prealarm Test on the selected device.
ABORT: Press to stop the Walk Test.
NOTE: The Trouble, Alarm and Obscuration tests described above are additional tools provided to
ascertain the functionality of a detector. They are not a substitute for periodic maintenance and
sensitivity verification per NFPA 72.
TROUBLE
PROGRAM MODE ACTIVATED
POINT SELECT:
Z001 (ZONE)
START TEST
POINT SELECT: Press to enter a zone number that will be put into Walk Test. When the panel
finds that zone in the first position of a device’s CBE map, that device will be put in Walk Test
mode.
START TEST: Press to begin Walk Test using the chosen parameters. Once Walk Test has begun,
this soft key becomes ABORT, and can be pressed at any time to exit Walk Test.
Walk Test In Progress Screen
TROUBLE
PROGRAM MODE ACTIVATED
Once the START TEST soft key has Once the START TEST soft key has
been pressed, this soft key appears. been pressed and the test begun,
Appears in Advanced walk test only. the message changes to ABORT
YES NO
Soft Keys
YES: Press this key to exit Walk Test with the devices remaining active. Once Walk Test is exited,
the fire panel will act as if the devices are newly activated and respond accordingly.
NO: Press this key to remain in Walk Test. This will provide the opportunity to clear the active
devices.
TROUBLE
PROGRAM MODE ACTIVATED
Soft Keys
TIME/DATE: Press to bring the cursor to the time/date field. The current time and date will be
displayed using the current format. Change the values using the keypad.
TIME FORMAT: Press to scroll through a list of formats as follows; HH:MM AM/PM; H:MM
AM/PM; HH:MM; and H:MM. Stop at the desired format.
DATE FORMAT: Press to toggle between MM/DD/YY and DD/MM/YY formats. Stop at the
desired format.
TIME ZONE: Press to scroll through a list of 34 time zone selections. Stop at the appropriate zone.
ACCEPT: Press to save changes made on this screen and to return to the previous screen.
TROUBLE
PROGRAM MODE ACTIVATED
POINT SELECT:
NxxxLyyMzzz (MODULE)
Soft Keys
POINT: Press this soft key to enter the point address or general zone number (except Z000) to be
forced on or off.
NEXT/PREVIOUS SELECTION: Press to progress to the next or previous point on the loop, or
the next or previous general zone.
ACCEPT: Press to continue to the Control On or Control Off screen.
TROUBLE
PROGRAM MODE ACTIVATED
Soft Keys
FORCE OFF: Press this soft key to change the state of the control module or general zone from
A U T O M A T I C A C T I V E to A U T O M A T I C I N A C T I V E .
4.8.2 Control On
If the selected point or zone is inactive, the Control On screen will appear:
TROUBLE
PROGRAM MODE ACTIVATED
FORCE ON
BACK
Soft Keys
FORCE ON: Press this soft key to change the state of the control module or zone from
A U T O M A T I C I N A C T I V E to A U T O M A T I C A C T I V E .
4.9 Wireless
The NFS2-3030 can communicate with a wireless network via the FWSG. Refer to the SWIFT™
Network Manual for additional information on wireless programming.
NOTE: The FWSG as part of the wireless network has been tested for compliance with the
Federal Communications Commission (FCC) requirements of the United States Government.
This product has not been evaluated for use outside the USA. Use of this system outside the
USA is subject to local laws and rules to which this product may not conform. It is the sole
responsibility of the user to determine if this product may be legally used outside the USA.
The following screen is displayed when WIRELESS is selected on the second Alter Status screen:
.
TROUBLE
PROGRAM MODE ACTIVATED
Soft Keys
MESH FORMATION: Press this soft key to display the Mesh Formation screen.
SWITCH DISABLE: Press to display the Switch Disable screen
SHUTDOWN WIRELESS DEVICES: Press to display the Shutdown Wireless Devices screen.
TROUBLE
PROGRAM MODE ACTIVATED
LOOP NUMBER: 01
MESH FORMATION: ON
ACCEPT
BACK
Soft Keys
LOOP NUMBER: Press to select the loop to enable or disable wireless mesh formation.
MESH FORMATION: Press to form a wireless communication mesh surrounding the FWSG. This
is required to establish communication with the wireless devices to the fire panel. Settings are ON
and OFF. If ON, when accepted, a command to start mesh formation is sent to all FWSG units on
the selected loop. If OFF, when accepted, a command to stop mesh formation is sent to all FWSG
units on the selected loop.
TROUBLE
PROGRAM MODE ACTIVATED
LOOP NUMBER: 01
SWITCH DISABLE: ON
ACCEPT
BACK
Soft Keys
LOOP NUMBER: Press to select the loop to enable or disable magnetic switches.
SWITCH DISABLE: Press to disable the magnetic sensor on the FWSG. Once disabled, a
password is required for access to the FWSG using SWIFT™ Tools. Settings are ON and OFF. If
ON, the magnetic sensor switches for the FWSG are disabled and a password is required to access
wireless commands. If OFF, The magnetic sensor switches for the FWSG are enabled and no
password is needed to access the wireless commands.
TROUBLE
PROGRAM MODE ACTIVATED
LOOP NUMBER: 01
ACCEPT
BACK
Soft Keys
LOOP NUMBER: Press to select the loop containing the wireless devices that are to be shutdown.
SHUTDOWN WIRELESS DEVICES: Select the duration of time in which the wireless devices on
the selected loop will be shutdown. The range is from 30 minutes to 24 hours. The wireless devices
on the selected loop will be shutdown for the duration of the time selected.
When in wireless shutdown, fire protection is compromised. All wireless devices will not
communicate with the FWSG until the time specified expires.
TROUBLE
PROGRAM MODE ACTIVATED
POINT SELECT:
N 0 0 0 L y y D z z z (D E T E C T O R )
Soft Keys
POINT: Press this soft key to select the aspiration detector that will be placed in Service Mode.
NEXT/PREVIOUS POINT: Press to progress to the next or previous point on the loop.
ACCEPT: Press to continue to the second Service Mode screen.
TROUBLE
PROGRAM MODE ACTIVATED
BACK
NOTE: If the detector selected is not an aspiration detector, the fire panel will display the
message NOT A FAAST DETECTOR.
Soft Keys
TURN ON SERVICE MODE: Press this soft key to turn on Service Mode for the aspiration
detector displayed. All 5 addresses associated with the FAAST detector will be placed in Service
Mode.When maintenance is complete and the device is ready to return to service, return to this
screen to turn off Service Mode.
TROUBLE
PROGRAM MODE ACTIVATED
POINT SELECT:
N 0 0 0 L y y D z z z (D E T E C T O R )
Soft Keys
POINT: Press this soft key to select the aspiration detector that will be reset.
NEXT/PREVIOUS POINT: Press to progress to the next or previous point on the loop.
ACCEPT: Press to continue to the second Reset Baseline screen.
TROUBLE
PROGRAM MODE ACTIVATED
RESET BASELINE
BACK
NOTE: If the detector selected is not an aspiration detector, the fire panel will display the
message NOT A FAAST DETECTOR.
Soft Keys
RESET BASELINE: Press this soft key to reset the baseline threshold for the aspiration detector
displayed. The VALUES display will show 000% OF ALARM.
TROUBLE
PROGRAM MODE ACTIVATED
POINT SELECT:
N 0 0 0 L y y D z z z (D E T E C T O R )
Soft Keys
POINT: Press this soft key to select the aspiration detector that will be reset.
NEXT/PREVIOUS POINT: Press to progress to the next or previous point on the loop.
ACCEPT: Press to continue to the second Reset Baseline screen.
TROUBLE
PROGRAM MODE ACTIVATED
RESET IP
BACK
NOTE: If the detector selected is not an aspiration detector, the fire panel will display the
message NOT A FAAST DETECTOR.
Soft Keys
RESET IP ADDRESS FAAST DETECTOR: Press to reset the IP Address of a FAAST
Intelligent Aspiration detector to its default address.
PANEL:
SVC PACK: 010.000.042 MAY 25, 2015
BOOT: 010.000.025 MAY 17 2015
APP: 010.000.041 MAY 2 2015
LCM IMAGE:
NCM: (NODE:134)
APP: 003.000.004 MAY 25 2015
DATABASE:
LANGUAGE: ENGLISH
023.010.008
SERIAL NUMBER:
SELF TEST
NOTE: “LCM” refers to the code resident in the CPU2-3030, not the code that is programmed
into the LCM-320.
NOTE: “LCD-160” refers to the code resident in the CPU2-3030, not the code that is
programmed into the LCD-160.
TROUBLE
LOADING..NO SERVICE
LAKEVIEW GENERAL HOSPITAL
BOOTLOADER
REBOOT
LCD-160 DOWNLOAD:Press this soft key to display the LCD-160 Download menu screen.
REBOOT:Press this soft key to reboot the panel, and exit the bootloader screen.
LOOP DOWNLOAD:Press this soft key to display the Loop Download Menu screen.
TROUBLE
LOADING..NO SERVICE
LAKEVIEW GENERAL HOSPITAL
N001
BOOTLOADER
ADDRESS: Press this soft key to scroll through to the desired LCD-160 address. “All” means all
addresses. Default: ADDRESS 001.
Shortcut: Type 1 on the keyboard, which jumps to address 10, or type 2 for twenty, 3 for thirty,
0 to reset back to 1. Type an asterisk (*) to select all addresses.
DOWNLOAD TYPE: Press this soft key to scroll through the languages (LANGUAGE-ENGLISH,
LANGUAGE-HEBREW, LANGUAGE-PORTUGUESE, LANGUAGE-SPANISH), BANNER, APP
and BOOT. Stop at the desired selection.
Choose a language to change LCD-160s selected at the ADDRESS field to display in that
language.
Choose BANNER to add the panel banner to those LCD-160 displays selected at the ADDRESS
field.
Select APP to download an application file to the selected LCD-160(s).
Select BOOT to download a boot file to the selected LCD-160(s).
AUTO:Press this soft key to automatically download to the LCD-160 the most up-to-date language,
bootloader, and application from the panel.
START:Press this soft key to begin the download.
TROUBLE
LOADING..NO SERVICE
LAKEVIEW GENERAL HOSPITAL
BOOTLOADER
LOOP ADDRESS: Press this soft key to scroll through the Loops. Stop at the appropriate pair, or
select ALL.
DOWNLOAD TYPE: Press this soft key to scroll through the download types. Stop at the
appropriate type. Selections are: APP, BOOT, or APP/BOOT.
Select APP to download an application file to the selected loops.
Select BOOT to download a boot file to the selected loops.
Select APP/BOOT to select both for downloading.
AUTO:Press this soft key to automatically download to the selected loop(s) the most up-to-date
applications or boot programming from the panel.
START:Press this soft key to begin the download.
TROUBLE
LOADING..NO SERVICE
LAKEVIEW GENERAL HOSPITAL
BOOTLOADER
PERFORM DOWNLOAD
76%
TROUBLE
EPROM ERROR
LAKEVIEW GENERAL HOSPITAL
BOOTLOADER
PERFORM DOWNLOAD
MAIN MENU
Event Counts Display
More Information
Multiple Event List
History Select
All Events
Alarms Only
Troubles Only
Supervisory Only
Security/Other
Time/Date Interval
Time & Date Range Select
Point Range
Point Range Select
Read Status
Detector
Module
Panel Circuit
Bell Circuit
Zone
Logic Zone
ACS Point
PAM Point
Release Zone
Special Zone
Trouble Zone
DAA Speaker Circuit
Program/Alter Status
Panel Program
Network Parameters
Node Number
Node Label
Style
Ch. A Threshold
Ch. B Threshold
IP Access
Network Mapping
Autoprogram
Panel Settings (Panel Settings (1) Screen
Local Control
Piezo
Proprietary Supervising Station
Event Ordering
Display Address
Reminder Menu
Trouble Reminder
More (Panel Settings (2) Screen
LCM Local Mode
Power Management Mode
DCC Participation
Point Programming
Display Point
Point Label
Local control
Loop Configuration
Loop Point Programming
Loop Selection
Installed
Detector Poll
Module Poll
Rapid Poll
Wiring Style
Blink Mode
Custom Action Message
Custom Action Message
Message
Event Logging
Non-Fire Activations
Output Activations
Holiday Menu
Point Program
Detector Point Programming (1)
Type
FlashScan Type
Point Label
Extended Label
Zone Map
More (Detector Point Programming (2))
Custom Action Message
Alarm Verification
Local Mode
Weekly Occupancy Schedule
Multi-Detector
Sensitivity
Occupied Sensitivity Alarm
Occupied Sensitivity Prealarm
Unoccupied Sensitivity Alarm
Unoccupied Sensitivity Prealarm
More (Detector Point Programming (3))
Low Temp Enable
Prealarm
Silenceable
Intelligent Sounder
Sounder Base Setup
AUX Tone 1
AUX Tone 1 Control
AUX Tone 2
AUX Tone 2 Control
Volume
CO Pre-Alarm
Module Point Programming
Module Type
Type Code Label
FlashScan Code Label
Point label
Extended Label
More (for a Monitor Type)
Clear ACS
Autoprogram Menu
Confirmation Screens
Alter Status
Disable/Enable
Point Select
Detector Sensitivity
Sensitivity Select
Change Alarm/Prealarm Sensitivity
Clear Verify Counters
Clear Counters
Clear History
Alarm History
Event History
All History
Walk Test
Basic/Advanced
Silent/Audible
Parameter
Disable ACS Boards
Change Time/Date
Time Format
Date format
Time Zone
More
Control On/Off Point Select
Point
Force On/Off
Wireless
Mesh Formation
Switch Disable
Shutdown Wireless Devices
More
Service Mode FAAST Detector
Reset Baseline FAAST Detector
Reset IP Address FAAST Detector
Printer Functions
Programming
Print Programming Menu
Print Programming Menu (2)
Active Points
Active Points Menu
Walk Test
Detector Maintenance Report
Installed Points
Installed Points Menu
Installed Points Menu (Range)
Function/Field Explanation
Delay Time Delay Time is the time that elapses between activation of an initiating device and activation
of all outputs mapped to the initiating device through a releasing zone.
Delay Time can have a value of 0 to 60 (seconds). A value of 0 will result in immediate
output activation upon activation of the initiating device.
Following is a graphic representation of what happens when a delay timer is set to 15
seconds for releasing zone ZR02.
All outputs with
Initiating device with Delay Time = 15 (seconds) applicable releasing
releasing zone type codes and with
ZR02 in its zone 15 ZR02 in their zone
0 sec.
map activates sec. maps activate at 15
seconds
NOTE: If cross-zoning is in effect, the delay time will not begin until the cross-
zoning conditions are met. Refer to Appendix B.3.5, “Cross Zones”, on page 120 for
more information.
Abort Switch Selection of a 3-letter abort switch type code (ULI, IRI, NYC, or AHJ) defines the operation
of an Abort Switch in that releasing zone. Refer to the specific abort switch type code
heading in this appendix for details on how each functions.
Cross Zone Select one of three Cross Zone types (Yes, Zone, or Heat), or No (not used). A Cross Zone
requires tripping two or more initiating devices to activate the outputs mapped to a
releasing zone. Refer to the Section B.3.5 on page 120 section of this appendix for details
and examples.
Soak Time (NFPA Soak Time specifies the length of time to dump releasing agents when a releasing zone
16 Applications activates. When the Soak Time expires, the control panel automatically shuts the releasing
only) solenoids for the active releasing zone. Soak Time can have a value of 0 to 9999 seconds.
If Soak Time is set to 0, the releasing solenoids will remain active until system reset.
Following is a graphic representation of what happens when soak time is set to 300
seconds for releasing zone ZR02.
Initiating device
with releasing Soak Time = 300 (seconds) At 300
zone ZR02 in its seconds, the
zone map control panel
activates. All 0 300 sec. shuts releasing
outputs with ZR02 sec. solenoids for
in their zone maps outputs with
activate. ZR02 in their
zone maps
Abort Switch
Manual Agent
Release lever
Monitor
Module with
Detector Detector
ABORT SWITCH
Type Code
ZR05
Example: If you program these three output modules Example: If you program a
as shown, these outputs activate at release. fourth module as shown,
this output activates when
the release is finished.
5 sec 15 sec
Alarm
10 sec
Press and hold the
Abort Switch for 15
seconds Release the Abort
Switch; the 10-second
ULI timer begins
When the 10-seconds
ULI timer expires, the
control panel activates
Releasing Zone outputs
WARNING:
! THE IRI ABORT SWITCH WILL ONLY WORK IF IT IS PUSHED BEFORE THE SECOND ALARM
OCCURS. IF IT IS PUSHED AFTER THE SECOND ALARM, THE RELEASING ZONE WILL
ALREADY HAVE BEEN ACTIVATED, AND THE SWITCH WILL HAVE NO EFFECT.
5 sec
Alarm 1 5 sec
10 sec
Press and hold
the Abort
Switch for 15
10 sec
seconds
Alarm 2
(Cross-zone Release the abort
conditions met) switch; a 10-second
Total time from when Abort Switch IRI timer begins
is pressed to output activation: At the end of the 10
15 + 10 = 25 seconds seconds, the
control panel
Total time from when Abort Switch activates releasing
is released to output activation: 10 seconds zone outputs
When an alarm initiates in the programmed releasing zone, pressing and holding the abort switch
stops the delay timer countdown. The delay timer restarts at the beginning of its countdown when
the abort switch is released. When the Delay Time expires, the 90-second NYC timer starts
counting down. When both timers expire, the control panel activates releasing zone outputs.
NOTE: 120 seconds is the maximum delay after the abort switch is released. If the Delay Time
plus the NYC delay time of 90 seconds exceeds 120 seconds, the releasing zone outputs will still
be activated at 120 seconds after the abort switch is released.
0 sec. 105 sec. (15 + 90). Does not exceed 120 seconds.
10 sec.
30 sec.
Alarm
Press and hold
the Abort Switch
Release Abort Switch---
At this point, the delay time When all timers are expired (in this
becomes the programmed example, 145 seconds after alarm
delay (15 sec.) plus 90 initiation, 105 seconds after the
seconds (105 sec.) OR 120 Abort switch has been released)
seconds, whichever is smaller the control panel activates
Releasing Zone outputs
expire at 150 seconds: however, this time exceeds the maximum of 120 seconds, so the releasing
zone outputs will begin releasing at 120 seconds, not at 150. Following is a graphic example of an
NYC Abort Switch and a delay timer programmed to a releasing zone.
Program selections for this releasing zone
Delay Time: 60 seconds
Abort Switch: NYC
Cross Zone: N
Soak Time: 0
Delay Time =60 sec. Total time from alarm initiation to release:
Pressing and releasing abort 10 + 30 + 60 + 60 = 160 seconds
switch restarts Delay Time = 60
countdown after 40 seconds
have elapsed. Delay=60 sec. NYC Delay=90 sec.
10 sec.
30 sec.
Alarm
Press and hold
the Abort Switch
120 sec. to release
When an alarm initiates in the programmed releasing zone, the programmed Delay Time starts.
Pressing and holding the abort switch suspends the delay timer. When the abort switch is released,
the control panel restores the value of the programmed Delay Time and the delay timer counts
down. When the Delay Time expires, the control panel activates releasing zone outputs.
Program selections for this releasing zone
Delay Time: 60 seconds
Abort Switch: AHJ
Cross Zone: N Total time from alarm initiation to
Soak Time: 0 release:
Delay=60 sec. 45 + 30 + 60 = 135 seconds
45 sec.
30 sec.
Alarm
60 sec.
NOTE: The FACP considers only the Primary Zone (the first zone in a point’s zone map) to
determine whether conditions have been met for Cross Zone type Zone.
CAUTION: MAPPING OF ANY INPUTS THAT ARE NOT ASSOCIATED WITH A PRIMARY
! ZONE COULD CAUSE IMPROPER OPERATION OF CROSS ZONE TYPE ZONE.
A summary of the types of Cross Zones and the conditions for activating a releasing zone:
General
Zone
Z001 *
*
Zone map = Z002 , ZR01
*
Zone map = Z001 , ZR01 *
Zone map = Z001 , ZR01
Releasing
Zone ZR01
* indicates a
Primary Zone
REL Zone Map = ZR01
L02M107
Each Cross Zone option and the conditions required to activate releasing zone ZR01 are shown in
the table below, according to the example in Figure B.8.
Cross Zone Selection
Condition(s) Required to Activate the Releasing zone
(Cross=)
Cross=No An alarm from any initiating device activates the releasing zone.
Cross=Yes An alarm from any two initiating devices activates the releasing zone.
Cross=Zone An alarm from two initiating devices mapped to different primary general zones, but
mapped to the same releasing zone.
For example: • An alarm from L02D101 and L02D103
• An alarm from L02D102 and L02D104
• An alarm from L02D101 and L02D104
• An alarm from L02D102 and L02D103
The two detectors listed in each set above are each mapped to different primary
general zones, but both list ZR01 in their zone maps.
Cross=Heat Activation of heat detector L02D104 and one smoke detector (L02D101, L02D102,
or L02D103).
ABORT SWITCH Provides an abort function through a “How to Program an Abort Switch” on
(tracking) monitor module (connected to a UL-listed page 122
abort station) for a releasing zone.
MAN. RELEASE Provides a manual release through a “How to Program a Manual Release
(latching) monitor module (connected to a UL-listed Switch” on page 123
pull station) for a releasing zone.
MAN REL DELAY Provides a manual release with a “How to Program a Manual Release Delay
(latching) 10-second delay through a monitor module Switch” on page 124
(connected to a UL-listed pull station) for a
releasing zone.
SECOND SHOT Provides a second manual release through “How to Program a Second Shot Switch”
(latching) a monitor module (connected to a UL-listed on page 125
pull station) for a releasing zone.
Type Codes designed for releasing zone outputs (SLC control modules).
Type Code What the Type Code does Refer to
REL END BELL Activates an NAC audio or visual device “How to Program a Release End Bell
when releasing circuits shut off. Circuit” on page 126
REL CKT ULC Directs outputs to perform a release “How to Program a ULC Release Circuit”
function as required by ULC. on page 127
RELEASE CKT Directs outputs to perform a releasing “How to Program a Release Circuit” on
function. page 128
REL. FORM C Directs relay outputs to perform a releasing “How to Program a Release Form-C
function. Circuit” on page 129
REL AUDIBLE Activates audio or visual devices steady “How to Program a Release Audible
when releasing starts. Circuit” on page 130
INST RELEASE Activates non-releasing output (SLC “How to Program an Instant Release
modules) with no delay time. Circuit” on page 131
Monitor
Detector
Module
Type Code
ABORT SWITCH
NBG-12LRA
station with
Abort Switch
R05
SLC SLC
output output
module module
Monitor
Detector
Module
Type Code
MAN. RELEASE
ZR05
SLC SLC
output output
module module
Monitor
Detector
Module
Type Code
MAN REL DELAY
ZR05
NBG-12LRA
station with
Manual Release SLC SLC
Lever output output
module module
For example, program releasing zone ZR05 with a Manual Release Delay switch for the following
releasing selections: Delay Time = 15, Abort Switch = ULI, Cross Zone = NO, Soak Time = 30.
When the Manual Release Delay Switch activates, the control panel replaces the remainder of the
15-second Delay Time, if running, with a 10-second timer.
Examples:
1. The FACP programmed Delay Time begins its 15 second countdown. The Manual Release
Delay switch is pulled when the FACP delay timer has counted down to 12 seconds. The 12
seconds remaining in the countdown are overridden by the 10-second delay initiated by the
Manual Delay switch. In this example, the total time elapsing from FACP countdown initiation
to agent release is 13 seconds, less than the original 15 second FACP Delay Timer countdown.
2. The FACP programmed Delay Time begins its 15 second countdown. The Manual Release
Delay switch is pulled when the FACP Delay Timer has counted down to 8 seconds. The 8
seconds remaining in the countdown are overridden by the 10-second delay initiated by the
Manual Delay switch. In this example, the total time elapsing from FACP countdown initiation
to agent release is 17 seconds, more than the original 15 second FACP Delay Timer
countdown.
3. The FACP programmed Delay Time is not running (as would happen if the releasing station
were pulled before an alarm registered). The Manual Release Delay Switch is activated by the
pull station. Agent release will occur in 10 seconds.
NOTE: The Second Shot switch can only be used with the MAN REL DELAY Type Code.
The following contains information needed to program a Second Shot switch for a monitor module
Description A monitor module—connected to a UL-listed manual station (such as the
NBG-12LRA)—used as for a second release of agents. A Second Shot switch overrides a Delay
Timer programmed to the same Releasing Zone.
Program Select a monitor module for the manual release function. While programming the
module (refer to Section 3.4.2, “Module Point”, on page 58 for instructions)
1. Select the SECOND SHOT Type Code.
2. Enter the number of the desired releasing zone into the module’s zone map. The releasing zone
must be fully programmed (refer to Section 3.4.4, “Releasing Zone”, on page 65).
Example A programming example of a monitor module programmed as a MAN REL DELAY
switch for the first shot and a SECOND SHOT switch for the second shot.
NBG-12LRA station with
Manual Release lever Second
Shot
Switch
Monitor Monitor
Module Detector Module
SLC SLC
output output
module module
With two monitor modules configured as shown above, program releasing zone ZR05 for the
following releasing selections:
Delay Time = 15, Abort Switch = ULI, Cross Zone = Y, Soak Time = 30
ZR05 can be activated in one of two ways, as described in the examples given below.
Example 1: If the detector initiates the alarm, ZR05 activates. Releasing begins after the delay
timer has expired (15 seconds). Releasing will continue for the soak timer duration (30 seconds).
The Second Shot switch can then be activated, and will remain activated for the soak timer
duration. Once the soak timer expires, the Second Shot switch can then be activated to initiate an
additional soak cycle.
Example 2: If the NBG-12LRA (Type Code MAN REL DELAY) lever is pulled, the manual release
delay timer begins its 10 second countdown. Releasing will begin after the manual release delay
timer has expired, and will continue for the soak timer duration (30 seconds). The Second Shot
switch can then be activated, and will remain activated for the soak timer duration. Once the soak
timer expires, the Second Shot switch can then be activated to initiate an additional soak cycle.
NOTE: A releasing circuit with this Type Code requires the following selections: a Releasing
Zone; an output circuit mapped to the same Releasing Zone; Switch Inhibit; Non-Silenceable;
No Walk Test.
The following contains information needed to program a Release End Bell circuit for an SLC
output module.
Description An SLC output module to activate an audible or visual device when releasing
devices shut off when soak time is complete. Multiple outputs with the REL END BELL Type Code
can be mapped to the same Releasing Zone. When the soak timer has expired, all outputs with the
REL END BELL Type Code activate at the same time. A REL END BELL circuit remains on until the
system is reset.
Program Select an SLC output module to use as a Release End Bell circuit. While programming
the point (refer to the Point Programming section of this manual for instructions),
1. Select the REL END BELL Type Code,
2. Enter the number of the desired releasing zone into the module’s zone map. The releasing zone
must be fully programmed (refer to Section 3.4.2, “Module Point”, on page 58).
Example A programming example of a control module programmed as a Release End Bell for
Releasing Zone ZR05.
Monitor
Module Detector Detector Detector
ZR05
SLC SLC
Output output output Output
module module module module
NOTE: A ULC Release Circuit with this Type Code requires the following selections: a Releasing
Zone; an output circuit mapped to the same Releasing Zone; Switch Inhibit; Non-Silenceable; No Walk
Test.
The following contains information needed to program a ULC Release Circuit for an SLC output
module.
Description An SLC output module used to activate a releasing solenoid or other releasing
device. Multiple outputs with the REL CKT ULC Type Code can also be mapped to the same
Releasing Zone. When the Releasing Zone activates, all outputs with the REL CKT ULC Type Code
also activate at the same time. A ULC Release Circuit activates when:
• An initiating device programmed to the same Releasing Zone activates (two devices if using
the Cross Zone option)
• The Delay Timer for the Releasing Zone (if used) expires
• No Abort Switch for the Releasing Zone (if used) is active
A ULC Release Circuit —and all wiring to the release device—is fully supervised and usable with
power-limited energy cable.
Program Select an SLC output module to use for a ULC Release Circuit. While programming the
point (refer to the Point Programming section of this manual for instructions),
1. Select the REL CKT ULC Type Code,
2. Enter the number of the desired Releasing Zone into the module’s zone map. The releasing
zone must be fully programmed (refer to Section 3.4.4, “Releasing Zone”, on page 65).
Example A programming example of a control module programmed as a ULC Release Circuit
for Releasing Zone ZR05.
Monitor
Module Detector Detector Detector
ZR05
NOTE: A Release Circuit with this Type Code requires the following selections: a Releasing
Zone; an output circuit mapped to the same Releasing Zone; Switch Inhibit; Non-Silenceable; No
Walk Test.
NOTE: Do not use a Release Circuit for the following: An application requiring ULC Listing; An
application requiring power-limited energy cable.
The following contains information needed to program a Release Circuit for an SLC output circuit
module.
Description An SLC output module used to activate a releasing solenoid or other releasing
device. Multiple outputs with the RELEASE CKT Type Code can be mapped to the same Releasing
Zone. When the Releasing Zone activates, all outputs associated with the releasing zone and with
the RELEASE CKT Type Code also activate at the same time. A Release Circuit activates when:
• An initiating device programmed to the same Releasing Zone activates (two devices if using
the Cross Zone option)
• The Delay Timer for the releasing zone (if used) expires
• The Abort Switch for the releasing zone (if used) is not active
Program Select an SLC output module to use as a Release Circuit. While programming the point
(refer to the Point Programming section of this manual for instructions),
1. Select the RELEASE CKT Type Code
2. Enter the number of the desired Releasing Zone into the module’s zone map. The releasing
zone must be fully programmed (refer to Section 3.4.4, “Releasing Zone”, on page 65).
Example A programming example of a control module programmed as a Release Circuit for
Releasing Zone ZR05.
Monitor
Module Detector Detector Detector
ZR05
NOTE: An output with a REL. FORM C Type Code requires the following selections: a Releasing
Zone; an output circuit mapped to the same Releasing Zone; Switch Inhibit; Non-Silenceable; No
Walk Test.
The following contains information needed to program a Release Form-C circuit for an SLC
Form-C relay output module.
Description An SLC output module, configured as a relay, programmed to activate an output by
opening or closing a switch. Typical applications include closing doors and air handlers.
Program Select an SLC output module to use as a Releasing Form-C Circuit. While
programming the point (refer to the Point Programming section of this manual for instructions),
1. Select the REL. FORM C Type Code,
2. Enter the number of the desired Releasing Zone into the module’s zone map. The releasing
zone must be fully programmed (refer to Section 3.4.4, “Releasing Zone”, on page 65).
Example A programming example of a control module programmed as a Release Form-C circuit
for Releasing Zone ZR05.
Monitor
Module Detector Detector Detector
ZR05
NOTE: An output with a REL AUDIBLE Type Code requires the following selections: a Releasing
Zone; an output circuit mapped to the same Releasing Zone; Switch Inhibit.
The following contains information needed to program a Release Audible circuit for an SLC output
module.
Description An output module programmed to activate an audio or visual device when all
releasing outputs, programmed to the same Releasing Zone, turn on. Multiple outputs with the
REL AUDIBLE Type Code can be mapped to the same Releasing Zone. When the Releasing Zone
activates, all outputs with the REL AUDIBLE Type Code activate at the same time.
Program Select a control module to use as a releasing circuit. While programming the point
(refer to the Point Programming section of this manual for instructions),
1. Select the REL AUDIBLE Type Code,
2. Enter the number of the desired Releasing Zone into the module’s zone map. The releasing
zone must be fully programmed (refer to Section 3.4.4, “Releasing Zone”, on page 65).
Example A programming example of a control module programmed as a Release Audible circuit
for Releasing ZoneZR05.
Monitor
Module Detector Detector Detector
ZR05
SLC SLC
Output output output Output
module module module module
A B
Type Code Type Code Type Code Type Code
REL AUDIBLE RELEASE CKT RELEASE CKT REL AUDIBLE
NOTE: An output with an INST RELEASE Type Code requires the following selections: a zone
selection (a releasing zone may be used, but is not required); an output circuit mapped to the
same zone; Switch Inhibit; Non-Silenceable; No Walk Test.
The following contains information needed to program an Instant Release circuit for an SLC output
module.
Description An SLC output circuit module programmed to activate non-releasing devices, such
as door openers or warning sounders, without counting down delay timers. A device programmed
with the INST RELEASE Type Code device is supervised for open circuits and ground faults.
Program Select an SLC output module to use with a releasing circuit. While programming the
point (refer to the Point Programming section of this manual for instructions),
1. Select the INST RELEASE Type Code,
2. Enter the number of the desired Releasing Zone into the module’s zone map. The releasing
zone must be fully programmed (refer to Section 3.4.4, “Releasing Zone”, on page 65).
Example A programming example of a control module programmed as an Instant Release circuit
for Releasing Zone ZR05.
Monitor
Module Detector Detector Detector
ZR05
SLC SLC
SLC SLC
output output
output output
module module
module module
A B
The outputs are each set to a code appropriate for one of the three releasing phases: for example,
one code for the first alarm, a faster code when the Delay Timer activates, and a continuous tone
during releasing.
Program Program releasing zone ZR1 as follows:
ZR1 = Delay Time:15, Abort Switch:ULI, Cross Zone:YES, Soak Time:120
Map ZR1 to all inputs and outputs shown in this example.
Program logic zones as follows:
ZL1 = AND(OR(L1D1,L1D2,L1D3,L1D4,L1D5,L1D6),NOT(L1M30))
When conditions are met for ZL1, a first alarm has occurred in the releasing zone, but the
Delay Timer has not yet started. Map ZL1 to an output set to the code chosen for a first alarm
(L1M31 in this example).
ZL2 = AND(L1M30,NOT(L1M20))
When conditions are met for ZL2, the Delay Timer has started, but releasing has not begun.
Map ZL2 to the output set to the code chosen for when the Delay Timer activates (L1M32 in
this example).
ZL3 = OR(L1M20)
When conditions are met for ZL3, the 120 second releasing operation has begun. Map ZL3 to
the output that produces a continuous tone (L1M33 in this example).
Program output Type Codes as follows:
L1M20 = RELEASE CKT, L1M30 = INST RELEASE, L1M31 = CONTROL, L1M32 = CONTROL, L1M33 = CONTROL
Illustration
ZR01
Type Code Type Code Type Code Type Code Type Code
RELEASE CKT INST RELEASE control control control
ZL1 ZL2 ZL3
B.4 Miscellaneous
B.4.1 Initiating Devices
Releasing zone initiating devices include the following:
• FST-851/751 intelligent heat detectors
• FSI-851/751, FSP-851/751, FAPT-851/751, FSL-751intelligent smoke detectors
• Conventional detection UL-listed devices connected to monitor modules
Multiple zone initiating devices can be used for the same releasing hazard. Map zone initiating
devices to the same Releasing Zone. Factory Mutual and certain Local Authorities Having
Jurisdiction require using redundant wiring (NFPA 72 Style 6 or Style D) for initiating devices in
releasing applications.
When the Delay Timer starts, when the Map the SLC to a releasing hazard zone (R0-R9).
releasing device activates, or both
Immediately when one of the initiating Map the SLC output to a separate zone (not R0-R9) that is also
devices activate mapped to all initiating devices of the hazard.
A releasing application requires control Use control modules set for dry contact operation. Program the
relays control relays for different functions by following the instructions
in “To activate a sounder” above.
Providing control functions Use an ACM-8R remote relay module mapped to the software
zones of the control panel.
PAS (15 s)
The control panel delays activation of outputs containing ZF0 in their zone maps for all alarm
initiating devices that contain ZF0 in their CBE list. A subsequent alarm will abort the Presignal
Delay Timer and execute CBE lists.
Notes on using ZF0
• NFPA 72 requires installation of a PAS Inhibit switch, that can be used to turn off the PAS
delay timer when the control panel is unattended. Do so by programming a monitor module
with the Type Code, PAS INHIBIT.
• The Presignal Delay timer countdown can be stopped by pressing the SYSTEM RESET key
before the timer expires.
• Program zone ZF0 to participating inputs and outputs.
Restrictions on using ZF0
• Do not include ZF0 in the CBE list for a releasing device.
• Do not include ZF0 in the CBE list for any monitor module that connects to a device other
than an automatic fire detector.
NOTE: During local or network Walk Test, activating a Mass Notification device will activate
associated special function zones according to CBE programming and simulate a Mass
Notification event. Any network nodes, zones, or devices not participating in Walk Test will not
participate in the simulated Mass Notification event.
ZF20 - MN Alarm
When an MN Alarm condition exists on the fire panel:
• ZF20 will activate and any CBE activations will be initiated.
• ZF20 activation is sent over the network.
• The OTHER LED will flash. (on steady after Acknowledged)
• The piezo will sound a steady audible tone. (silent after Acknowledged)
• Any devices programmed as General Pending will activate.
• Any alarm relays or devices programmed as General Alarm or Alarm Pending type codes do
not activate.
• Any devices programmed as “Resound by Fire” will not activate.
• If the fire panel is programmed so that MN events have priority over fire events, and a fire
condition exists on the fire panel, any fire activation(s) will be suppressed locally as well as
for any network nodes that MN mapped to the panel via VeriFire Tools.
• The MN Alarm message will not be sent to the proprietary receiver via the network.
• If the ZF20 activation is received from the network and the fire panel is All Systems
Normal, “NETWORK MN ACTIVE” is displayed on the status bar of the fire panel.
ZF21 - MN Supervisory
When an MN Supervisory condition exists on the fire panel:
• ZF21 will activate and any CBE activations will be initiated.
• ZF21 activation is sent over the network.
• The SUPERVISORY LED will flash. (on steady after Acknowledged)
• The piezo will sound a warbling audible tone. (silent after Acknowledged)
• Any devices programmed as General Pending will activate.
• Any devices programmed as General Supervisory will not activate.
• Any devices programmed as “Resound by Supervisory” will not activate.
• The fire panel’s Supervisory relay will not activate.
• The MN Supervisory message is sent to the proprietary receiver via the network.
• If the fire panel is programmed so that MN events have priority over fire events, and a fire
condition exists on the fire panel, an MN Supervisory will not suppress any fire alarms
locally or for any network nodes that MN mapped to the panel via VeriFire Tools.
ZF22 - MN Trouble
When an MN trouble condition exists on the fire panel:
• ZF22 will activate and any CBE activations will be initiated.
• ZF22 activation is sent over the network.
• The TROUBLE LED will flash. (on steady after Acknowledged)
• The piezo will sound a pulsed audible tone. (silent after Acknowledged)
• Any devices programmed as General Pending, Trouble Pending and General Trouble will
activate.
• Any devices programmed as “Resound by Trouble” will not resound.
• The fire panel’s Trouble relay will activate.
• The MN Trouble message is sent to the proprietary receiver via the network.
• If the fire panel is programmed so that MN events have priority over fire events, and a fire
condition exists on the fire panel, an MN Trouble will not suppress any fire alarms locally or
for any network nodes that MN mapped to the panel via VeriFire Tools.
Topic Page
Detector Sensitivity Settings – Pre-Alarm and Alarm sensitivity settings for photo, ion, 142
laser, and multisensor detectors programmable on a per-detector basis.
Detector Maintenance Features – Instructions for viewing and printing detector 144
maintenance information.
A graphic representation of a detector analog reading using drift compensation and smoothing:
Alarm Level
without compensation
Awacs1a.cdr
Analog with compensation and
Reading smoothing
Time
MAINTENANCE REQ
Acceptable
Range
LOW THRESHOLD
Low
Value
Prealarm Threshold
Analog
Awacs4a.cdr
Reading
Time (days)
2.1%
OBSCURATION (% PER FOOT)
Figure D.4 Sample Sensitivity Levels for a FlashScan View Laser Detector
Combined
Alarm
SMOKE OBSCURATION
3 Sensors
Awacs5a.cdr
Time (minutes)
D.3 Pre-Alarm
D.3.1 Definition
The Pre-Alarm function is a programmable option which determines the system’s response to real-
time detector sensing values above the programmed setting. Use the Pre-Alarm function to get an
early warning of incipient or potential fire conditions. There are two levels of Pre-Alarm:
• Alert (Refer to “Alert Level” below)
• Action (Refer to Appendix D.3.3, “Action Level”, on page 142)
Alert and Action Pre-Alarm settings are set with point programming. Unique Pre-Alarm sensitivity
levels (PA) for individual detectors are listed in Appendix D.4, “Detector Sensitivity Settings”, on
page 142.
The LEDs on detectors polled in FlashScan mode will light steady green when in pre-alarm.
• The Pre-Alarm indication for this detector will restore automatically to normal if its
obscuration reading drops below pre-alarm level.
• A subsequent alarm for this detector also clears the Pre-Alarm indication.
* Detectors are suitable for open area protection within the listed air velocity range. Typically, this range is 0 - 4,000 ft/min for photoelectric
detectors and 0 - 1,200 ft/min for ionization detectors. Be sure to confirm this range before installing the detector by referring to the
manufacturer’s installation instructions.
† For ION detectors installed in Canada: Use only an alarm sensitivity setting of AL=1, AL=2 or AL=3.
‡ 1% max. on CLIP. Larger figures may display.
** The use of alarm sensitivities below 0.50% obscuration per foot requires a 90 day test to ensure that the environment for the detectors is suitable for the
higher sensitivity setting. (Refer to “To Test Detectors Set Below 0.50% Obscuration per Foot” on page 144.)
†† For Acclimate detectors installed in Canada: Use only the alarm settings of AL:1 or AL:2.
‡‡ Refer to the beam detector manual to determine the alarm settings: they are a function of the distance between the detector and its reflector.
There is no Prealarm for beam detectors in CLIP mode.
*** AL:6 and PA:6 are not available in CLIP mode.
****Within the 10 minute signature confirmation delay period, if there is a detection of another fire signature (Carbon Monoxide, Infrared
or Thermal) it overrides the 10 minute confirmation time.
Step Action
1 Initially set to the 0.50% obscuration per foot Alarm level.
2 Set the Pre-Alarm level to the desired final Alarm sensitivity.
3 Set the Pre-Alarm to Alert mode (non-latching).
2. Operate detectors continuously for 90 days with all environmental factors (such as,
temperature, humidity, air flow, occupancy, and so on) similar to the intended application for
the detectors. Record all events for each tested detector with an electronic History buffer or a
printout.
3. At the end of the 90-day test: An authorized Notifier representative, or an end user trained by
an authorized Notifier representative must inspect the results of the test. If the test results show
no alarms or pre-alarms for the tested detectors, reprogram the fire alarm system to set the
Alarm sensitivity to the more sensitive Pre-Alarm level of the test.
• Press ACCEPT
******DETECTOR MAINTENANCE******************************************************
NORMAL SMOKE(LASER) Detector L01D001 000330us 000340us Comp:000% Pk: 002%
Alarm: 000% PreAlarm: 000% A6P6 V000 L01D001
NORMAL SMOKE ACCLIM Detector L01D002 000030us 000000us Comp:000% Pk: 000%
Alarm: 000% PreAlarm: 000% A8P8 V000 L01D002
Field Identification
Long term average of
raw analog value in
microseconds
Current reading of raw analog
value in microseconds Compensation
percentage
Extended
Label Label Detector peak
State
DISABLED The point has been forced into a disabled state by an outside source.
The second field displays the point status. There are two designations that could appear in this field.
Point Status Description
Designation
The device is a detector (an input device) so by referring to the descriptions below, it can be
determined that the point is in a normal state.
Inputs: (detectors, monitor modules, zones)
If the point is not in trouble or disabled, and the point is automatically controlled by the panel, the
display will be one of the following:
AUTOMATIC INACTIVE
AUTOMATIC ACTIVE
AUTOMATIC PREALARM
If the point is disabled, the display will be one of the following. The Trouble Status field will
appear if the point is in trouble.
DISABLED INACTIVE <Trouble Status>*
DISABLED ACTIVE <Trouble Status>*
DISABLED PREALARM <Trouble Status>*
If the point is in trouble, the display will read:
TROUBLE INACTIVE <Trouble Status>*
TROUBLE ACTIVE <Trouble Status>*
Needs Cleaning 70 - 79 Clean the detector soon. The detector may cause a
false alarm because it has reached the drift
compensation tolerance value.
Needs Immediate Cleaning 80 - 100 Clean immediately! The detector is a false alarm risk.
The drift compensation tolerance value has been
exceeded.
Line 14
PEAKS: 56% - This value represents the highest percent per foot obscuration reading taken by
this detector. It can be a historical figure, and does not necessarily represent the highest reading
for this particular alarm. Re-initializing the detector would reset this value to zero.
VERIFY COUNT: 02 - This displays the number of times the detector has gone into alarm.
This count aids in differentiating false alarms from actual alarms by showing repeated alarm
events that have come into the device. In this example, the detector has gone into alarm two
times since the verification count was begun. The FACP will signal a trouble condition when
the verify count exceeds 20.
CO-OP: D100,158 - Indicates the address(es) of any detector(s) linked with the detector that’s in
alarm for Co-operative Multi-Alarm Sensing. This field will not display for Acclimate detectors.
Line 15 - The current time and date are displayed in this line.
E.1 Zones
There are four types of zones that may be listed to a point for CBE purposes.
General Zone A general zone is used to link input and output devices. When an input device activates, any general zone in its
zone map will be active, and any output device that has an active general zone in its map will be active. General
zones can be used as arguments in logic equations.
Zone Z000 is a general alarm zone: those points listing Z000 in their zone map participate in a general alarm.
The panel will support up to 1000 general zones, designated as Z0 through Z999. General zones can be used in
CCBE applications when a node number is entered before the zone number.
Logic Zone A logic zone consists of a logic equation. Whenever the logic equation becomes true, all output points mapped to
the logic zone will activate.
The panel will support up to 1000 logic zones, designated as ZL1 through ZL1000. Logic zones can be used in
CCBE applications when a node number is entered before the zone number.
Trouble Zone A trouble zone consists of a trouble equation. Whenever the trouble equation becomes true, all output points
mapped to the trouble zone will activate.
The panel will support up to one hundred trouble zones, designated as ZT001 through ZT100. Trouble zones can
be used in CCBE applications when a node number is entered before the zone number.
NOTE: Trouble zones can be used only in CCBE applications between NFS2-3030, NFS-3030 and NFS-640
FACPs. Trouble zones will not activate with other combinations.
Special Zone ZF0 An output participates in Presignal with this special zone in its zone map.
ZF1 (Trouble less AC) An output programmed to turn on/off if a system trouble - other than an AC power loss -
occurs.
ZF2 (AC Trouble) An output programmed to turn on/off if an AC power loss or a brownout condition occurs.
ZF3 (Security) An output programmed to turn on/off if a Security input activates.
ZF4 (Supervisory) An output programmed to turn on/off if a Supervisory input activates.
ZF5 Alternate An input programmed to switch from the active detector alarm sensitivities to the
Sensitivity Activation alternate alarm sensitivities when a non-fire point with ZF5 in its CBE activates.
ZF6 Plant Isolate special zone for Australian Mode. When the Plant Isolate button is pressed,
ZF6 will toggle between Normal and Active.
ZF7 Drill for Australian Mode. In the event of a drill activation, ZF7 will activate and will
remain active until a reset is performed on the fire panel.
ZF9 An output programmed to turn on/off if a PreAlarm is active (ALERT, ACTION).
ZF10 Any detector or module in alarm verification will activate this zone.
ZF11 When the drill key is pushed or drill is performed, ZF11 will go active. ZF11 will go to
normal after a 5 second delay.
ZF12 When the acknowledge key is pushed, or a block or event acknowledge is performed,
ZF12 will go active. After a five-second delay, ZF12 will go to normal.
ZF13 When the signal silence key is pushed or a signal silence is performed, ZF13 will go
active. After a five-second delay, ZF13 will go to normal.
ZF14 When the system reset key is pushed or a system reset is performed, ZF14 will go
active. After a ten-second delay, ZF14 will go to normal.
ZF15 When there are disabled events present in the system, ZF15 will be set to active. When
all disabled events have cleared, the state of ZF15 will go to normal.
ZF16 Drill Zone. This zone used when Drill Mode is set to Custom. When a drill is performed
on the fire panel, ZF16 will be set to active. ZF16 will return to normal following a system
reset.
ZF17 Signal Silence for Australian Mode operations. When a signal silence is performed, ZF17
will go active and will remain active until a System Reset is performed. The special zone
will only function when Australian Mode is enabled.
ZF18 CO Alarm. When a CO Alarm is present, ZF18 will activate.
ZF19 CO Pre-Alarm. When a CO Pre-Alarm is present, ZF19 will activate.
ZF20 When an mass notification alarm occurs on the fire panel, ZF20 will go active. If mass
notification events have priority over fire, network nodes MN mapped to the fire panel
(via VeriFire Tools) will suppress any active fire events. ZF20 will remain active until a
system reset is performed and the MN alarm is cleared.
ZF21 When a mass notification supervisory event occurs, ZF21 will activate. ZF21 will remain
active until the MN Supervisory condition is cleared. If the supervisory is latched, a
system reset will need to be performed to clear the condition.
ZF22 When a mass notification trouble occurs on the fire panel, ZF22 will activate. ZF22 will
remain active until the MN trouble is cleared
Time, date and holiday functions, which were formerly determined through special zones, are now defined in the panel programming
section of this manual.
E.2 Equations
Logic and Trouble Equations can define complex relationships between input and output devices.
The FACP supports up to 1000 Logic Equations, each designated with a Logic Zone number of
ZL1 through ZL1000. It also supports up to 100 Trouble Zones, each designated with a Trouble
Zone number of ZT001 through ZT100. Once created, these equations can be included in
input/output zone mapping.
1. Equations will always begin with a logic function. The function set is listed below.
2. Equations will be a maximum of 80 characters long, including parentheses and commas.
3. Logic and Trouble Equations can have a maximum of 10 logic functions unless a time delay
function is used: a time delay function must be the only function in its equation.
4. Equations are evaluated after all other devices have been evaluated.
5. One logic equation can be used as an argument in another logic equation, or one trouble
equation can be used in another trouble equation, only if the equation used has previously been
evaluated; that is, only zones with a lower number than the zone currently being edited can be
used as arguments.
6. A logic function can have a maximum of 20 arguments (inclusive start and stop address).
7. Maximum for the delay timer is 23 hours, 59 minutes, 59 seconds (23:59:59).
8. Mass Notification enabled systems: Logic zones must be written conditionally to ensure proper
event suppression. Refer to the Mass Notification manual for additional information.
9. CO Monitor devices: A device with the type ID of “CO Monitor” should not be used in logic
equations. To include a CO Monitor in a logic equation, use zones mapped to the CO Monitor
in the equation.
Equations are entered using Point Programming for logic or trouble zones. Refer to these sections
in this manual for instruction. The panel will check for errors after the user has entered the
complete equation. Possible errors are too many or too few parentheses, too many or too few
arguments inside the parentheses, unknown function and unknown device type.
Equations are made up of two basic components: functions (either logic or time delay) and
arguments.
E.2.1 Arguments
Arguments are discrete parts of a logic or time delay function used in a logic or trouble equation.
They can consist of another function, another equation, or any of the devices listed below.
Example: NOT(Z02)
The logic zone will remain activated until the argument activates.
If the argument activates the logic zone will deactivate.
• The “ONLY1” Operator
Requires that only one argument be active.
Example: ONLY1(Z02,Z05,Z09)
If only one of the arguments activates the logic zone will be activated.
• The “ANYX” Operator
Requires that the amount of arguments specified by the number preceding the arguments be
active.
Example: ANYX(2,Z02,Z05,Z09)
If any two or more of the arguments are in alarm the output point will be activated.
The X amount may be a value from 1 through 9.
• The “XZONE” Operator
Requires that any combination of two or more input devices programmed to a zone be active.
Example: XZONE(Z02)
If any combination of two or more initiating devices that have been mapped to this software
zone come into alarm, then outputs mapped to this zone will activate.
• The “RANGE” Operator
Each argument within the range must conform to the requirements of the governing function.
The range limit is 20 consecutive arguments.
Example: AND(RANGE(Z1,Z20))
Zone 1 through Zone 20 must all be active to activate the logic zone.
• The “DIS(point argument)” Operator
Requires that the point argument be disabled for the operator to go active.
• The “PRE(point argument)” Operator
Requires that the point argument be in prealarm for the operator to go active.
Example: AND(L1D1,PRE(L1D2))
The detector at address L1D1 must be active and the detector at L1D2 must be in prealarm for
this equation to go active.
• The “SUP(point argument)” Operator
Requires that the point argument be in an active supervisory state for the operator to go active.
Example: OR(L1D1,SUP(L1M1))
The detector at address L1D1 must be active, or the module at L1M1 must be in an active
supervisory state, for the equation to go active.
• The “FIRE(point argument)” Operator
Requires that the point argument be in an active fire alarm state for the operator to go active.
Example: AND(L1D1,FIRE(L1M1),FIRE(L1M2))
The detector at address L1D1 must be active, and the modules at L1M1 and L1M2 must be in
an active fire alarm state, for the equation to go active.
• The “NON(point argument)” Operator
Requires that the point argument be in an active non-alarm state for the operator to go active.
Example: AND(L1D1,NON(L1M1))
The detector at address L1D1 must be active, and the module at address L1M1 must be in an
active non-fire alarm state, for the equation to go active.
• The “SEC(point argument)” Operator
Requires that the point argument be in an active security alarm state for the operator to go
active.
Example: AND(L1M1,SEC(L1M2))
The module at address L1M1 must be active, and the module at address L1M2 must be in an
active security alarm state, for the equation to go active.
• The “AUTO(point argument)” Operator*
This operator will evaluate as “Active” if all of the SCS switches or specified switch group are
in the “Auto” position. When the SCS-8L/SCE-8L is disabled, the evaluation will be based on
the switch position prior to the disable.
Examples:
The switch associated with switch group 16 on Annunciator 1 must be set as “Auto” for the
equation to go active.
OR(AUTO(A1G16))
All the switches of Annunciator 1 must be set to “Auto” for the equation to go active.
OR(AUTO(A1))
• The “NORM(point argument)” Operator*
This operator will evaluate as “Active” if the entire SCS device or a specified switch group is
in a normal state.
Examples:
Switch group 16 on Annunciator 1 must be in the “normal” (no trouble) state for the equation
to go active.
OR(NORM(A1G16))
(All switches groups on) Annunciator 1 must be in the “normal” (no trouble) state for the
equation to go active.
OR(NORM(A1)
• The “SCSDIS(point argument)” Operator*
For use with the SCS-8L only. This operator will evaluate as “Active” if the keyswitch on the
specified SCS device is in the disabled position.
Example:
If the keyswitch on annunciator 25 is disabled, this equation will go active.
OR(SCSDIS(A25))
* For use with local SCS applications
Time-based Functions
The panel supports three time-based functions: DEL, SDEL, and TIM. Special rules apply to an
equation containing a time-based function:
• Only one time-based function may be used in an equation.
• The time-based function must appear only once, as the first entry of the equation.
• It may not be nested within parentheses in the equation.
• Logic functions may be used in an equation that begins with a DEL or SDEL time-based
function: however, they must appear within parentheses following the time-based function.
Delay and duration times are in 24-hour format (HHMMSS); the allowable range is 00:00:00 to
23:59:59.
The “DEL” Function
Used for delayed operation.
OR(AND(L1D1,L1D4),AND(L2D6,L2M3,NOT(L2M4)),ANYX(2,L1M13,L1M14,L1M15))
for this part to be TRUE for this part to be TRUE for this part to be TRUE
Then all outputs programmed with this equation will be turned ON.
F.1 Overview
The control panel automatically performs a detector initialization routine when a detector is added
or changed.
The detector initialization routine takes approximately 2.5 minutes. During this time, the detector
being initialized does not perform fire protection functions. The LEDs of detectors polled in
FlashScan mode will latch a steady green while initializing, and return to blinking green when
initialization is over.
While initializing a detector, follow these guidelines:
• Make sure the detector is free of residual smoke during detector initialization.
• Do not test a detector during detector initialization.
NOTE: The control panel only performs detector initialization if it senses that a detector was
removed for at least 15 seconds.
WARNING:
! IF ANY DETECTOR IS REPLACED WITH A DIFFERENT TYPE OF DETECTOR (FOR EXAMPLE,
A LASER DETECTOR IS REPLACED WITH A PHOTOELECTRIC DETECTOR), THE CONTROL
PANEL MUST BE PROGRAMMED IMMEDIATELY WITH THE NEW DETECTOR TYPE CODE.
FAILURE TO DO SO CAN CAUSE INCORRECT CONTROL PANEL OPERATION, INCLUDING
FALSE ALARMS.
Step Action
1 Delete the old detector point from FACP programming using the “Delete Point” screen on page
page 74.
3 Enter point programming for this point and change the Type and FlashScan Code Label to the values
appropriate for the new detector. (Refer to Section 3.4.1, “Detector Point”, on page 49 for
programming instructions).
Point Characteristics
Latching Activates Device/Point Function
Type Code Point Type (Y=yes CBE
N=no)
ASPIRATION* fire Y Y Aspiration laser or Intelligent Aspiration detector
ASPIR. (SUP)* supervisory Y Y Supervisory for an Intelligent Aspiration detector
ASPIR. (PRE)* prealarm N Y Pre-alarm for an Intelligent Aspiration detector
ASPIR. (NON)* non-fire N Y Non-fire for an Intelligent Aspiration detector
ASPIR. REF* non-fire N Y Reference for an Intelligent Aspiration detector
Note for Aspiration detector programming:
The FAAST Intelligent Aspiration detector requires five (5) SLC device addresses. Refer to the FAAST Installation document for additional programming
information.
SMOKE (ION) fire Y Y Ionization smoke detector
SUP L(ION)† supervisory Y Y Ionization smoke detector
SUP T(ION)†‡ supervisory N Y Ionization smoke detector
Point Characteristics
Latching Activates Device/Point Function
Type Code Point Type (Y=yes CBE
N=no)
SMOKE(DUCTI) fire Y Y Duct Ionization smoke detector
SUP L(DUCTI) supervisory Y Y Duct ionization smoke detector
SUP T(DUCTI)‡ supervisory N Y Ionization smoke detector used as a duct detector to report
supervisory condition rather than alarm.
SMOKE(PHOTO) fire Y Y Photoelectric smoke detector
SUP L(PHOTO)† supervisory Y Y Photoelectric smoke detector
SUP T(PHOTO)†‡ supervisory N Y Photoelectric smoke detector
SMOKE(DUCTP) fire Y Y Duct Photoelectric smoke detector
SUP L(DUCTP) supervisory Y Y Photoelectric smoke detector used as a duct detector to report
supervisory condition rather than alarm
SUP T(DUCTP)‡ supervisory N Y Photoelectric smoke detector used as a duct detector to report
supervisory condition rather than alarm.
RFSMOKE(PHOTO) fire Y Y Wireless Photoelectric smoke detector
SMOKE(HARSH) fire Y Y HARSH smoke detector
SMOKE(LASER) fire Y Y Laser smoke detector
SUP T (LASER)†‡ supervisory N Y Laser Smoke Detector
SUP L (LASER)† supervisory Y Y Laser Smoke Detector
SMOKE(DUCTL) fire Y Y Duct Laser smoke detector
SUP L(DUCTL) supervisory Y Y Laser smoke detector used as a duct detector to report supervisory
condition rather than alarm.
SUP T(DUCTL) supervisory N Y Laser smoke detector used as a duct detector to report supervisory
condition rather than alarm.
PHOTO/CO fire Y Y Combination Photoelectric/CO detector
P/CO (P SUP)* fire Y Y Combination Photoelectric/CO detector. Photo element activation
generates a supervisory condition.
P/CO (C SUP) fire Y Y Combination Photoelectric/CO detector. CO element activation
generates a supervisory condition.
Note: For Photo/CO detectors:
Detectors programmed as P/CO (P SUP), the Heat and CO elements will latch and require a system reset to clear. The Photo element will latch or track,
depending on the Photo/CO (P SUP) setting. Refer to “Panel Settings” on page 22.
Detectors programmed as P/CO (C SUP), the Heat and Photo elements will latch and require a system reset to cleat. The CO element will latch or track
depending on the Photo/CO (CO SUP) setting. Refer to “Panel Settings” on page 22.
AIR REF fire Y Y Assign to one or more FSL-751detectors used to monitor the quality of
air entering the protected area. The air quality measurement allows the
VIEW system to compensate for vehicle fumes, fog, or other particles
brought into the protected area through the ventilation system. Poor air
quality will lower the sensitivity of all FSL-751 detectors on the SLC.
The detector sensitivity, however, remains within approved limits
(always less than 1% obscuration per foot).
Note: A reference detector still functions as a smoke detector, but the detector sensitivity level should be set to the least sensitive level—AL:9 and PA:9
Alarm and Pre-Alarm sensitivity. Refer to “Detector Sensitivity Settings” on page 142 for a complete list of detector sensitivity settings.
HEAT fire Y Y 190oF heat detector
HEAT+ fire Y Y 190oF heat detector with low temperature warning
HEAT(FIXED) fire Y Y 135oF intelligent thermal sensor
HEAT (ROR) fire Y Y 15oF per minute rate-of-rise detector
SMOKE ACCLIM fire Y Y Combination Photoelectric/heat detector
SMOKE(ACCLI+) fire Y Y Combination Photoelectric/heat detector with low temperature
warning, or Intelliquad FSC-851 Photoelectric Multi-Criteria Smoke
Sensor.
SMOKE(MULTI)** fire Y Y Multisensor smoke detector
SMOKE(BEAM) fire Y Y Beam Smoke Detector
ACCL(P SUP) fire Yes (See Y Combination Photoelectric/Heat detector. Photo element activation
note below) generates a supervisory condition.
ACCL+(P SUP) fire Yes (See Y Combination Photoelectric/Heat detector with low temperature
note below) warning. Photo element activation generates a supervisory
condition.
Point Characteristics
Latching Activates Device/Point Function
Type Code Point Type (Y=yes CBE
N=no)
Note: For ACCL/ACCL+ detectors:
Detectors programmed as ACCL (P SUP) or ACCL+(P SUP). the Heat element will latch and require a system reset to clear. The Photo element will latch
or track, depending on the ACCL (P SUP) Latching setting. Refer to “Panel Settings” on page 22.
Point Characteristics
Point Characteristics
Switch
Silenceable Inhibit Walk Test Local Mode
Type Code (Y=yes (Y=yes, (Y=yes, SLC Output Point Group Point Device Function
N=no)* N=No)* Types
N=No)*
CONTROL† Y N Y NAC fire Supervised NAC
RELAY† Y N Y Relay n/a Relay output
BELL CIRCUIT Y N Y NAC fire Supervised NAC
STROBE CKT† Y N Y NAC fire Supervised NAC
HORN CIRCUIT† Y N Y NAC fire Supervised NAC
AUDIBLE CKT Y N Y NAC fire Supervised NAC
SPEAKER Y N Y NAC fire Supervised NAC for speaker circuits
blank† Y N Y NAC n/a Supervised NAC for undefined device
NONRESET N N N Relay or NAC n/a Supervised output, unaffected by “System Reset”
CTL† command
TELEPHONE N N N Telephone fire Supervised Telephone circuit
CONTROL NAC Y N Y NAC fire Supervised NAC
ISOLATED NAC Y N Y NAC fire Supervised NAC for notification appliance, used
with audio isolators. Activates even if there is a short
on its NAC circuit. For ULC installations only.
ISOLATED SPK Y N Y NAC fire Supervised NAC for speaker circuits, used with
audio isolators. Activates even if there is a short on
its audio circuit. For ULC installations only.
GEN ALARM† N Y Y NAC fire Control Module, XPC-8, or an XP5-C (in NAC mode)
configured as a Municipal Box Transmitter for NFPA
72 Auxiliary Fire Alarm Systems applications (MBT-
1 required). This Type ID can also be used for
general alarm activation.
GEN SUPERVIS† N Y Y NAC supervisory Control Module, XPC-8, or an XP5-C (in NAC mode)
activated under any Supervisory condition (includes
sprinkler type).
GEN TROUBLE† N Y Y NAC trouble Control Module, XPC-8, or an XP5-C (in NAC mode)
activated under any System Trouble condition.This
device will not turn ON when it is in trouble (short or
open).
GENERAL N Y Y NAC trouble Control Module XPC-8 circuit, or an XP5-C (in NAC
PEND† mode) that will activate upon receipt of an alarm
and/or trouble condition, and remain in the ON state
until all events have been ACKNOWLEDGED. This
device will not turn ON when it is in trouble (short or
open)
TROUBLE N Y Y NAC trouble Control Module or an XP5-C (in NAC mode) that will
PEND† activate upon receipt of a trouble condition, and
remain in the ON state until all troubles have been
ACKNOWLEDGED. This device will not turn ON
when it is in trouble (short or open).
ALARMS PEND† N Y Y NAC fire Control module or NAC for output that will activate
upon receipt of an alarm condition, and remain in
the alarm state until all alarms have been
acknowledged.
INST RELEASE‡ N Y N NAC (SLC only) fire Supervised for open circuits and ground faults.
Short = normal
REL. FORM C†,‡ N Y N Form-C relay n/a Directs relay outputs to perform a releasing function.
(SLC only)
RELEASE N Y N NAC (SLC only) n/a Directs outputs to perform a releasing
CKT†,‡ function.Supervised for open circuits and ground
faults. Short = normal
REL CKT ULC†,‡ N Y N NAC (SLC only) n/a Directs outputs to perform a release function as
required by ULC.
REL END BELL N Y N NAC n/a Activates NAC audio or visual device when
releasing circuits shut off.
REL AUDIBLE Y Y N NAC n/a Activates audio or visual devices steady when
releasing starts.
FORM C RESET† N Y N Form-C Relay n/a Relay module used to interrupt 24V power to four-
(SLC only) wire conventional detectors for 30 seconds upon
reset. Used in conjunction with a monitor module
with a conventional detector Type ID
MNS GENERAL N N N NAC n/a Activates NAC mass notification devices when an
MNS event occurs
MNS STROBE N N N NAC n/a Activates strobe mass notification devices when an
MNS event occurs
MNS SPEAKER N N N NAC n/a Activates speaker mass notification devices when
an MNS event occurs
MNS CONTROL N N N NAC n/a Activates control module mass notification devices
when an MNS event occurs
MNS RELAY N N N Relay n/a Activates relay mass notification devices when an
MNS event occurs
Label Device/Point
FlashScan Codes
4-20MA FMM-4-20
ACCLIMATE FAPT-751, FAPT-851
BEAM FSB-200,FSB-200S
IQUAD FSC-851,FCO-851
CONTROL FCM-1
HEAT FST-751/R, FST-851/R
HIGH HEAT FST-851H
ION FSI-751, FSI-851
LASER FSL-751
MANUAL STATION FSM-101 (NBG-12LX Series)
MINI/DUAL MONITOR FMM-101,FDM-1
RF PULL STATION FW-MM
RF MONITOR FW-MM
RF GATEWAY FWSG
RF HEAT FWH-200FIX135, FWH-200ROR135
RF PHOTO FWD-200P
RF ACCLIMATE FWD-200ACCLIMATE
RF RELAY FW-RM
MONITOR FMM-1
PHOTO FSP-751,FSD-751P/RP, FSP-851, FSD-751PL/RPL, FSH-751
PHOTO/HEAT FSP-751T, FSP-851T
PHOTO/CO FCO-851
PS MON PS MON
PS CONTROL ACPS CONTROL
PS RELAY ACPS RELAY
RELAY FRM-1
RELEASE FCM-1-REL
RFX MON RFX MON
RFX SMOKE SDRF-751
RFX SUP RFX SUP
TELEPHONE FTM-1
XPIQ BATTERY XPIQ BAT MON
XPIQ GND FLT XPIQ EF MON
XPIQ AC XPIQ AC MON
XPIQ TROUBLE XPIQ GEN MON
Label Device/Point
XPIQ STROBE XPIQ STROBE
XPIQ SPEAKER XPIQ SPEAKER
XPIQ TELEPHONE XPIQ TELEPHONE
XPIQ MUSIC XPIQ MUSIC
ZONE MONITOR FZM-1
FAAST FSA-8000/A
FAASTX FSA-20000/A, FSA-5000/A
SYSTEM TROUBLES
TROUBLE MESSAGE TYPE TROUBLE DESCRIPTION
DSBUS x AC FAIL The DSBUS at address x has lost AC power. Check wiring and source.
DSBUS x COMMFAIL The DSBUS at address x is not communicating with the fire panel. Check wiring and source.
DSBUS x HIGH BATT The battery voltage for the DSBUS at address x has exceeded 28 V. If the batteries are shared,
ensure that only one power supply is charging the batteries. Remove the batteries and measure
the charging voltage from the supply to ensure it is not exceeding 27.6 V. Call Technical
Services.
DSBUS x LOW BATT The battery voltage for the DSBUS at address x has fallen below 20.4 V. Charge or replace
batteries.
DSBUS x SELF TEST FAIL A device on the DSBUS at address X has failed self test. Reboot the device. If this does not
repair it, update the software of the device. If the self test fail trouble continues to be displayed,
call Technical Services.
EPROM ERROR The application and/or boot code is corrupt. Service required.
EXTERNAL RAM ERROR The external RAM test failed. Service required.
FLASH IMAGE ERROR The software is corrupt. Re-download the panel code software from VeriFire™ Tools. If the
trouble does not clear, call Technical Services.
FFT TROUBLE There is a short or open on an FFT riser on a Digital Audio Loop. Check that the DVC’s 4-wire
switch is set properly and that there is an end-of-line resistor in place for 2-wire operation.
GROUND FAULT A ground fault has occurred within the panel.
GROUND FAULT LOOP x There is a ground fault on loop x.
GROUND FAULT PORT x A ground fault has occurred on DAP x (A or B).
HARDWARE MISMATCH The device installed does not match what was previously installed. Install the correct device.
INTERNAL RAM ERROR The internal RAM test failed. Service required.
INVALID NODE TYPE MAPPED An invalid node type has been mapped to the NFS2-3030 for Network Display Mode. Check
network mapping and correct. Refer to “Limitations” on page 173 for valid network types.
INTERNAL RAM ERROR The internal RAM test failed. Service required.
LCD80 SUPERVISORY Communication has been lost with an LCD-80.
LOADING...NO SERVICE A program or database download is in progress. The panel is NOT providing fire protection
during the download. Proper authorities should be notified while a download is in progress so
that other means of fire protection can be supplied.
LOCAL MIC TROUBLE The DVCs local microphone is in trouble. There is no communication, or paging has been
enabled for over 28 seconds and no signal has been received. Investigate whether the mic is
plugged into the DVC, or whether there is a problem with the local mic.
LOCAL PHONE TROUBLE The DVC’s local FFT handset is in trouble. There is no communication, or paging has been
enabled for over 28 seconds and no signal has been received. Investigate whether the handset
is plugged into the DVC, or whether there is a problem with the handset.
LOOP x- x COMM FAILURE Loops x and x are not responding. The LCM and LEM for those loops must be serviced.
MAN EVAC INITIATED Local initiation of DRILL
MAN EVAC RECEIVED Network initiation of DRILL
MANUAL MODE ENTERED An annunciator has been placed in manual mode.
MODBUS COMMUNICATIONS The VESDA® Gateway can not communicate with the HLI, HLI may be damaged or not
FAULT powered, or the VESDA Gateway may be damaged.
NCM COMM LOSS Communication lost between CPU2-3030 or DVC and network communications module.
NCM CONNECTION LIMIT More than two panels have been connected to a high-speed network communications module.
EXCEEDED
NCM SNIFFER MODE ACTIVE The network is in a diagnostic state.
NETWORK FAIL PORT x Communication lost between NCM Port x and corresponding node.
NETWORK INCOMPATIBILITY The brand of this panel is incompatible with this network.
NETWORK MAPPING LIMIT More than 1 fire panel or more than 4 DVCs has been mapped to the NFS2-3030 for Network
EXCEEDED Display Mode. Check network mapping and correct.
NFN PAGING CHANNEL LIMIT Multiple paging sources are attempting to page over the NFN, exceeding the limit of one (1).
EXCEEDED reduce the number of paging sources to clear this trouble.
NFPA 24HR REMINDER This message occurs every day at 11 am if any troubles exist.
NVRAM BATT TROUBLE Battery backup and/or clock backup is low. Replace battery.
NO DEV. INST ON L1 No devices are installed on the system.
NO POWER SUPPLY INST The address of the main power supply has not been entered.
PANEL DOOR OPEN The panel door is open.
PHONE CHANNEL LIMIT The DVC has allocated all its phone channels, and there are still phones ringing in requesting
EXCEEDED more channels.
POWER SUPPLY TROUBLE There is a communication failure with the DAA onboard power supply. Call Technical Services.
SYSTEM TROUBLES
TROUBLE MESSAGE TYPE TROUBLE DESCRIPTION
PRIMARY AMP x FAIL The Primary Amp at address x has failed. Call Technical Services.
PRIMARY AMP x HARDWARE The Primary Amp at address x has had a hardware failure. Call Technical Services.
FAIL
PRIMARY AMP x LIMIT The Audio Circuit of the Primary Amplifier at address x has been overloaded or shorted so the
Audio Signal has been attenuated. Check wiring and source and ensure that there are no
shorts.
PRIMARY AMP x OVERCURRENT The Primary Amplifier at address x has overloaded and shut down. Check the total Load
calculations fir the DS-AMP and/or DS-BDA and ensure the total values do not exceed 120
watts.
PRIMARY AMP x TRIP The DS-BDA at DS-BUS address x (1-4) is drawing more current from the power supply than
expected and has been disabled. Refer to the DVC manual for additional troubleshooting.
PRINTER OFF LINE Communication loss with printer. Restore power and/or printer’s online status.
PRINTER PAPER OUT Add paper.
PROGRAM CORRUPTED The database that houses the panel’s programming is corrupt. It must be re-downloaded, or all
programming must be cleared and re-entered. Service required.
PROG MODE ACTIVATED A user is currently using the panel’s programming menus.
REMOTE DISPLAY x NO ANSWER The remote display at address x is not responding.
REMOTE DISPLAY x TROUBLE The remote display at address x is in trouble.
REMOTE MIC TROUBLE The DVC’s remote microphone is in trouble. It is installed and supervised, but no signal is
coming from it. Investigate and fix.
SELF TEST FAILED Diagnostic test failed. Service required. Call Technical Services.
SOFTWARE MISMATCH One or more LCM or DAA software revisions do not match other LCMs or DAAs, and/or the
network communications module is not network version 5.0, or LCD-160 software is
incompatible. Update the software as necessary.
STYLE 4 SHORT x LOOP x Service required. Call Technical Services.
STYLE 6 POS. LOOP x There is an open circuit on the positive side of loop x. Style 6 and Style 7 are supervised methods of
communicating with addressable devices. If the control panel detects a trouble (open only), it will
drive both ends of the loop, maintaining communication in an unsupervised method. The latching
trouble will display on the panel as a Style 6 trouble until you correct the condition and press reset.
Style 7 configuration of the SLC requires the use of ISO-X modules.
STYLE 6 NEG. LOOP x There is an open circuit on the negative side of loop x. Style 6 and Style 7 are supervised methods
of communicating with addressable devices. If the control panel detects a trouble (open only), it will
drive both ends of the loop, maintaining communication in an unsupervised method. The latching
trouble will display on the panel as a Style 6 trouble until you correct the condition and press reset.
Style 7 configuration of the SLC requires the use of ISO-X modules.
STYLE 6 SHORT LOOP x Style 6 and Style 7 are supervised methods of communicating with addressable devices. If the
control panel detects a trouble (open or short), it will drive both ends of the loop, maintaining
communication in an unsupervised method. The latching trouble will display on the panel as a
Style 6 trouble until you correct the condition and press reset. Style 7 configuration of the SLC
requires the use of ISO-X modules.
SYSTEM INITIALIZATION One or more devices (detectors or modules) can not report activation. This can occur following
system startup, when exiting Walk Test, or following a device trouble of No Response.
VESDA TROUBLE A trouble has occurred on a VESDA node. Possible troubles may include: Communication failure on
the VESDA detector loop, incompatible VESDA software versions, or VESDA configuration error.
REGIONAL SETTINGS
REGIONAL SETTINGS:SINGAPORE
TROUBLE
LOADING..NO SERVICE
LAKEVIEW GENERAL HOSPITAL
N083
BOOTLOADER
CONTINUE ABORT
User should select CONTINUE to initiate applications. User should select ABORT to abort applications.
I.2 Chicago
The REGIONAL SETTING choice of CHICAGO disallows local drill or signal silence.
• The DRILL and SIGNAL SILENCE keys at the panel will not function.
• Annunciator Control Modules and SLC modules given a drill or signal silence Mode or
Type Code will not allow local drill or signal silence initiation.
• Events must be acknowledged prior to system reset.
I.3 Australia
The REGIONAL SETTING choice of AUSTRALIA activates the following features:
• allows use of the Australian smoke control module SCS-8AU.
• “Brigade Act” LED is controlled by ZL1000.
• Test LED is lit during walktest.
• Ability to manually corrupt memory to test memory corruption detection. Special passwords
for testing memory corruption detection.
“corrupta” will temporarily corrupt a location in the application.
“corruptb” will temporarily corrupt a location in the boot.
“corruptd” will temporarily corrupt a location in the database.
“reset” will uncorrupt the panel and reboot.
• Plant Isolate button will disable/enable ZL999. Use special function zone ZF6 with ZL999.
• No softkeys on the panel will function while there is an unacknowledged alarm EXCEPT
scroll, silence, reset and disable.
• Silence Buzzer key acknowledges everything before silencing.
• Special Function Zone ZF17 may be used with Signal Silence. When a Signal Silence is
performed, ZF17 will go active and remain active until a System Reset is performed.
• Disable key disables the current event on the screen.
• Special Function Zone ZF7 may be used for Drill. When the drill key is pushed or a drill
performed, ZF7 will go to active. When the system reset key is pushed or a system reset is
performed, ZF7 will go normal.
• Fan control function per AS/NZS 1668:1:1998, section 4.13.2.
• First zone in alarm displayed at top of display. Additional zones in alarm also displayed,
until panel reset. Alarm zones not currently on display may be viewed using the scroll
button.
• Security events will light the supervisory LED. The supervisory scroll key will scroll
through security events.
• Display acknowledged and unacknowledged alarms at the same priority.
• Pre-alarm events will be displayed after alarms.
• The Main Menu includes an “Other events” menu key to scroll through other events.
• Password Bypass Timer enabled. After entering a valid password, the user does not need to
enter a password again until no key is pressed for ten minutes.
• Active Output events are displayed if Output Activations are enabled in the Event Logging
menu.
• Disable/Enable button will disable or enable the currently-displayed event.
• AMPS-24 supervision disabled.
• When the primary supply is not an AMPS-24, selecting AUX trouble supervisory setting
will generate a general power supply fault.
I.4 China
The REGIONAL SETTING choice of CHINA activates the following features:
• POM-8A support.
• Active output events displayed. A counter is displayed for active outputs.
• Municipal Communication panel settings.
• New special function zone for alarm verification.
• Prealarm automatically cleared after five minutes.
• Co-op detectors alarm functions
• Dual alarm window.
• Points in trouble will not activate.
• Ten minute limit for DEL and SDEL delay functions.
• Disable events do not light LED or trip the trouble relay.
• No system trouble generated upon entering program mode.
• Low AC operation of FACP.
• Power supply troubles.
• Ability to manually corrupt memory to test memory corruption detection.
J.1 Limitations
When in Network Display Mode:
1. Only the following network node types can be mapped to the NFS2-3030:
• NFS2-3030 • DVC
• NFS2-640 • NFS-640
• NFS-320 • NFS-3030
2. Read Status, Control On/Off, Disable/Enable, and Network Control-By-Event will only
function for the nodes that are mapped to the NFS2-3030.
3. The number of display type nodes for the entire network is limited to a total of 25. Display
nodes include NCA, NCA-2, a Gateway node, or an NFS2-3030 in Network Display Mode.
NOTE: Initiating an Acknowledge, System Reset, Signal Silence or Drill on a network node
mapped to the NFS2-3030 may affect nodes that are not participating in Network Display Mode
through Logic Zone Programming.
This section contains descriptions of terms essential to Drift Compensation An algorithm which permits the
know when programming the control panel. maintenance of a constant smoke detector sensitivity by
accounting for environmental contaminants and other
Alarm History See History buffer.
factors.
Alarm Verification Timer A user-defined global
Download A function for loading a system program
software timer function that can reduce the number of
from a file on a personal computer and storing the
nuisance alarms. When you select Alarm Verification
program in system memory of the control panel. Also
for a detector, the control panel delays an alarm signal
see Veri•Fire.
for a user-specified time period. (The control panel
ignores the Alarm Verification Timer if it detects FlashScan poll - a patented system (US Patent Number
another alarm during the verification period.) 5,539,389) that enhances the speed of communication
between analog intelligent devices. Communication is
Argument An argument is a discrete part of a logic
in a grouped fashion. When one of the devices within
function used in a CBE logic or trouble equation. It can
the group has new information, the panel CPU stops the
consist of panel/SLC addresses for detectors, modules,
group poll and concentrates on single points.
zones, special function zones, logic or trouble equations.
History buffer The control panel maintains a history
Auto Silence Timer A user-defined global software
buffer of the last 4000 events, each with a time and date
timer that functions like pressing the signal silence key.
stamp. History events include all alarms, troubles,
The control panel silences all active outputs
operator actions, and programming entries. The control
programmed as silenceable once the timer has reached
panel also maintains a 1000-event Alarm History buffer,
the selected time. For example, if 20 minutes is selected,
which consists of the 1000 most recent alarm events
when the timer reaches 20 minutes the control panel
from the 4000-event history buffer.
turns off all active outputs programmed as silenceable.
latching An attribute of a device that keeps it in an
Autoprogram A software routine that directs the
active state until the condition causing the activation is
control panel to identify and automatically load SLC-
corrected and the panel is reset.
connected devices into the program with default values
for all parameters. The Autoprogram Finds and displays Missing device A device that exists in a program, but is
all new or missing intelligent detectors and modules-- not found by the control panel during Autoprogram,
while ignoring devices already installed in memory--so typically because the device is disconnected.
you can edit default option selections. Typically, you
NAC (Notification Appliance Circuit) A circuit or path
Autoprogram the control panel as a first step in a new
directly connected to a notification appliance device (a
installation, or to add devices.
fire alarm system component--such as a bell, speaker,
Control module An addressable module that a) strobe, and so on--that produces an audible output, a
switches power to a Style Y or Style Z NAC; or b) visual output, or both). On this panel, NACs can be
functions as a Form-C control relay. transponder points or control modules.
CBE (Control-by-Event) A programming method that New device A device connected to the control panel,
lets you map inputs and outputs to provide a variety of but not in program memory.
output responses based on various initiating conditions
Non-latching An attribute of a device that follows the
(events).
state of the fire alarm system. That is, if a device is
CLIP poll - Classic Loop Interface Protocol - CLIP - is non-latching, it returns to its normal state automatically
standard polling of each intelligent device (as when the condition clears.
differentiated from FlashScan poll, a method of group
Notification Appliance Circuit see NAC.
polling described below).
Obscuration A reduction in the atmospheric
DCC (Display and Control Center) - Term for a
transparency caused by smoke, usually expressed in
display location, programmed to participate in DCC,
percent per foot.
when it has control of Acknowledge, Signal Silence,
System Reset and Drill functions. Output circuit A control module connected to the
SLC.
Point A system memory address occupied by an select a Type Code while programming a point). The
addressable SLC device, Software Zone, or annunciator. Type Code specifies what action the control panel takes
For example, the control panel considers “L01M102”, a when the point activates. For example, when a monitor
module on loop 1 at address 102, as a point. module with evacuate as a Type Code activates, the
control panel activates all outputs, as if someone pressed
Panel sounder The piezo sounder on control panel,
the drill key.
that pulses when troubles and alarms occur.
Upload A function for making a copy of a system
Primary zone The zone in the first position of a point’s
program and storing the program as a file on a personal
zone map. The FACP looks at this zone for certain
computer. Also see VeriFire™ Tools Programming
functions, such as some Cross Zone activations or Walk
Utility.
Test participation.
View (Very Intelligent Early Warning) System A smoke
Silence Inhibit Timer A user-defined timer that
detection system, consisting of the NFS2-3030 control
disables the signal silence key function for the
panel and intelligent laser detectors, that provides very
programmed time (0-300 seconds) when a fire alarm
early warning of smoldering fires.
occurs. All subsequent alarms can be silenced
immediately. VeriFire™ Tools Program Utility A software utility
for uploading and downloading a system program
SLC (Signaling Line Circuit) A physical wire loop
between a personal computer and the control panel
used to connect addressable detectors and modules to
through the EIA-232 port.
the control panel.
Walk Test A feature that lets a single (qualified)
General Zone A label, internal to the fire alarm
maintenance person test a fire alarm control panel and
system, assigned to a group of addressable devices.
initiating devices without causing the control panel to
Switch Inhibit A software function that allows the enter into an alarm state.
programming of control modules and NACs so an
Zone Map SLC inputs (detectors and monitor
operator cannot manually activate NACs. With Switch
modules) and outputs (control modules) provide for up
Inhibit enabled, an operator cannot manually activate
to ten zone selections for CBE.
the NACs from the control panel.
System Normal message A message that displays on
the second line of the LCD display during normal
operation of the control panel.
System Reset Pressing the System Reset fixed function
key will clear all latched alarms and other events if the
initiating condition is gone. LEDs associated with these
events will turn off. Unacknowledged events will not
prevent reset from functioning. If alarms or other off-
normal events exist after reset, they will resound the
system. The System Reset key will not function if the
programmable Silence Inhibit timer is running. If
multiple
The System Reset key will not immediately silence
active outputs. If the Control-by-event programming for
the output evaluates false after reset, the output will
deactivate. (Typically this is 30 seconds local, 60
seconds network.)
Terminal Interface EIA-232 bidirectional serial port
used for upload and download functions.
Tracking An attribute of a device that allows it to enter
an active state when a condition causes its activation,
then to return from an active to an inactive state when
the condition causing its activation is corrected.
Type Code A Type Code is a software function that
specifies the function of a detector, control module,
monitor module, transponder point, or NAC. (You can
ULC installation Alarm Verification timer Delete Program Menu, when programming panel
value 30, 70 the first time 18
Canada Event Order 23 Detector
CAUTION Address format 48
Do not mix general zones with other sourc- Alarm Sensitivity Levels 53, 83, 140
es... 39 Alarm Verification 52
Mapping of inputs not associated with Pri- Custom action message 52
mary Zones 120 Drift Compensation 138
On systems utilizing the DCC function… Extended label 50
24 FlashScan code label 49
CBE (Control-by-Event) 150, 175 Label 49
CCBE (Cooperative Control-By-Event) 150 Local Mode 52
Channel A,B thresholds 20 Maintenance Level messages 139
Clear Maintenance Warning 139
ACS programming 73 Multi-Detector (Coop) 52
All programming 73 Occupancy Schedule 54
History 85 Point programming 49
Loop programming 73 Poll 45
Panel programming 73 Pre-Alarm Sensitivity Level 140
Verify Counters 85 Print a Detector Maintenance Report 145
CLIP Mode 45 Sensitivity 52
Communication loss, panel & SLC 52 To replace 157
Control Module 175 To test detectors set below 0.50% obscura-
See Module, SLC tion per foot 144
Control On/Off 94 Type Codes 49
Cooperative Multi-Detector Sensing 52, 141 Weekly Occupancy Schedule 54
CPU2-3030 40 Zone map 50
Cross Zone 112 Disable/Enable Point Selection 81
Programming example 120 Displayless Mode
To activate a Releasing Zone 120 Service-level switches, ACK, SIG-SIL,
Types 120, 121 SYSRST, LAMP 12
CRT Supervision 40 Do not assign Releasing Type Codes to Panel Cir-
Custom Action message cuits 162
Detector 52, 53 Download 175
Module 59 Download screen 106
To create 46 Drift Compensation 138, 175
To view 46 Graphic representation 139
To view, point 53 Drill
Custom Drill Mode 135 AKS-1 41
Custom Tone Setup 27 Local control 22
Drill Mode 26, 135
D Drill Zone 135
DVC/DAA
DAA-5025/DAA-5070 72 Address format 49
Address format 49
DVC/DVC-EM 72
DCC Participation 24
Default settings soft key 24
Default Timers soft key 33 E
Delay Time 112 Equations
Delete point 73 Arguments 152
Delete Program 72 Editing 66
Clear Logic 151
ACS programming 73 Functions 152
All programming 73 Time-based functions 154
Loop programming 73 Trouble 156
Panel 73 Event Counts Display 16
Delete point 73 Event logging 47
Z
Z000 general alarm 141
Zone
Address format 48
Zone map
Control module 63
Detector 50
Monitor module 59
Zones
CBE 150
Fixed positions in map
Detectors, position one 51
Detectors, position ten 51
primary zone 49, 120
Sounder/relay bases, position nine 51
General Zone 64
Non-resettable control 64
Precedence Participation 64
Zone label 64
Logic 65
Add logic function 67
Add point 67
Add Time/Date 67
Delete equation 67
Edit Equation 66
Enter time 68
Logic function 68
Point select 67
Position layout 49, 50
Position one, initial programming 50, 59,
63
Releasing 65, 112–133
Abort Switch 65
Cross Zone 65
Delay Time 65
Soak Time 65
Special Zones 151
Trouble 69
Z000 general alarm 63, 142, 150
Warn-HL-08-2009.fm
www.notifier.com