SEL-2600A RTD Module Instruction Manual: Major Features & Benefits

The SEL-2600A RTD Module transmits 12 RTD temperature measurements and one contact status over fiber-optic cable, offering improved noise immunity and compatibility with various SEL products. It supports multiple RTD types, operates in extreme temperatures, and includes features like LED indicators for status monitoring. Installation involves connecting to power, grounding, and ensuring proper placement for reliable operation.

Uploaded by

pablojgauto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
177 views32 pages

SEL-2600A RTD Module Instruction Manual: Major Features & Benefits

The SEL-2600A RTD Module transmits 12 RTD temperature measurements and one contact status over fiber-optic cable, offering improved noise immunity and compatibility with various SEL products. It supports multiple RTD types, operates in extreme temperatures, and includes features like LED indicators for status monitoring. Installation involves connecting to power, grounding, and ensuring proper placement for reliable operation.

Uploaded by

pablojgauto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 32

SEL-2600A RTD Module

Instruction Manual

Transmit 12 RTD-based temperature measurements and a single contact status as


far as 500 meters using inexpensive fiber-optic cable with the SEL-2600A RTD
Module.
The new, enhanced SEL-2600A provides superior RTD noise immunity (up to
1 Vac rms, 50 Hz or greater). Please note that the SEL-2600A with the V-pin
option is fully backward compatible with the SEL-2600 RTD Module.

Major Features & Benefits


➤ Selectable fiber-optic connection model options support V-pin or
ST connectors.
The fiber-optic link eliminates expensive cable pulls and provides
electrical noise immunity and ground isolation.
➤ New improved design provides superior RTD noise immunity.
➤ LEDs indicate device status, transmit status, and contact input status.
➤ Measures as many as 12 RTD temperatures plus one contact input with no
settings.

Date Code 20050303 SEL-2600A RTD Module


2 Major Features & Benefits

The device supports the following RTD types:


➢ 100-ohm platinum
➢ 100-ohm nickel
➢ 120-ohm nickel
➢ 10-ohm copper
➤ Powers from 120 Vac or 240 Vac
➤ Operates in extreme surrounding air temperatures from –40º to +85ºC
(–40º to +185ºF)
➤ Connects directly with the following SEL products:
➢ SEL-701 Motor Protection Relay (V-pin option)
➢ SEL-749M Motor Protection Relay (ST option)
➢ SEL-387A Current Differential Relay (V-pin option)
➢ SEL-300G Generator Protection Relay (V-pin option)
➢ SEL-421 Protection, Automation, and Control System (V-pin option)
➢ SEL-2032 or SEL-2030 Communications Processor (V-pin option)

SEL-2600A RTD Module Date Code 20050303


Initial Checkout 3

Initial Checkout
Before installing the SEL-2600A, perform an initial checkout to assure successful
power up using the steps outlined below:
Step 1. Connect Terminal 26 to an appropriate ground.
Step 2. Apply line power to the SEL-2600A at one of the following
terminal combinations:
➢ 120 Vac—Terminal 23 is Hot and Terminal 24 is Neutral
➢ 240 Vac—Terminal 23 is Hot and Terminal 25 is Neutral
The SEL-2600A will power up and perform internal diagnostics.
The module is ready when the green ENABLED LED illuminates
(allow as much as 25 seconds maximum).
Step 3. Verify that the red TX LED pulses approximately every 0.6 second
(less than 0.75 second maximum).
Each pulse corresponds to the transmission of RTD data, device
status, and contact input status.
Step 4. Connect Terminal 20 to Terminal 21 to test the contact input.
The red INPUT LED illuminates when the contact input is
electrically shorted.
The unit is now ready for installation.

Date Code 20050303 SEL-2600A RTD Module


4 Installation

Installation
Physical Location
Proper placement of the SEL-2600A helps make certain that you receive years of
trouble-free operation.
The SEL-2600A is EN 61010-1 rated at Installation/Overvoltage Category II and
Pollution Degree 3. This rating specifies mounting the SEL-2600A indoors or in
an outdoor (extended) enclosure where it is protected against exposure to direct
sunlight, precipitation, and full wind pressure, but where neither temperature nor
humidity are controlled. For corrosive environment applications, be sure to mount
the RTD scanner to a vertical surface.
You can operate the SEL-2600A in a wide temperature and humidity range. See
Specifications on page 28. The altitude rating for the SEL-2600A is 2000 m
(6560 ft) above mean sea level.

Power Connections
The power terminals are isolated from the chassis ground. Use 1.5 mm2 (16 AWG)
size or heavier wire to connect to the power terminals. Connection to external
power must comply with IEC 60947-1 and IEC 60947-3.
Install an external switch, circuit breaker, or overcurrent device (fuse) in the power
leads for the SEL-2600A; this device must be able to isolate both hot and neutral
power leads. The maximum current rating for the device must be 20 A. Be sure to
locate this device within 3.0 m (9.8 ft) of the RTD module.
Provide appropriate protection to power supply terminals for protection against
electrical shock.
Operational power is internally fused with a power supply fuse. See Specifications
on page 28 for power supply and fuse ratings. Be sure to use fuses that comply
with IEC 60127-2.

SEL-2600A RTD Module Date Code 20050303


Installation 5

Installation Steps
! CAUTION
Do not connect external voltages to the contact input. Permanent damage to the
product or external equipment can result from connecting external voltage to a
contact input because the contact input is internally wetted.

Step 1. Locate an appropriate mounting panel or enclosure near the


protected device.
Step 2. Drill four mounting holes (see Figure 9 on page 27).
Step 3. Secure the SEL-2600A using the four bolts and locknuts
provided.
Step 4. Ground the SEL-2600A by connecting Terminal 26 to an
appropriate electrical ground.
Step 5. Connect as many as 12 RTDs to the SEL-2600A terminal blocks
(see Figure 8 on page 26).
The SEL-2600A supports shielded three-lead RTDs, providing
terminals for +, –, and return (RTN) leads. The return lead provides
a means for lead-resistance compensation. For best
lead-resistance compensation, all three leads should be the same
length and wire gauge. Maximum lead resistance is 25 ohms. Use
0.082 mm2 (18 AWG) to 0.021 mm2 (24 AWG) wire gauge for
the leads. Belden 8771 or similar cable is recommended. Cable
shield should be connected to ground at the SEL-2600A (use the
RTN terminal for shield grounding).
➢ Performance to all specifications is guaranteed only when
using shielded RTD cables (twisted leads) no longer than
10 meters.
➢ While RTD cables longer than 10 meters can be used,
conformance to IEC 60255-22-1 and IEC 60255-22-5 is
no longer assured.
Step 6. Record the type and location of each RTD in Table 1 on page 8.
Step 7. Connect a dry contact to the SEL-2600A contact input
Terminals 20 and 21 as appropriate. The contact is internally
wetted at 8 Vdc.

Date Code 20050303 SEL-2600A RTD Module


6 Installation

Step 8. Connect the SEL-2600A to one of the following devices.


SEL-701 Motor Protection Relay Application
➢ Connect the SEL-2600A (V-pin option) to the SEL-701
using a single fiber-optic cable. (SEL part number
C805Z010VVX003 for 3-meter length cable. Other
lengths, heavy-duty jacketed, and waterproof heavy-duty
jacketed cables are available.)
➢ Follow the SEL-701 setting instructions in SEL-701
Motor Protection Relay Application on page 9 and in the
SEL-701 Motor Protection Instruction Manual.
SEL-749M Motor Relay
➢ Connect the SEL-2600A (ST option) to the SEL-749M
using ST connector-based fiber-optic cable. The ST
option RTD Module comes standard with a 5-meter cable,
C807Z010SSX0005; for other lengths, order
C807Z010SSX0001 (1 meter) or C807Z010SSX0015
(15 meter). Simplex, 62.5/125 µm, ST fiber-optic cables,
similar to Corning 001K38-31141-8 or General Cable
CT0011SNU are available in other lengths from many
industrial suppliers.
➢ Set and enable the RTD measurements according to the
SEL-749M setting instructions in SEL-749M Motor
Protection Relay Application on page 11 and in the
SEL-749M Motor Protection Instruction Manual.
SEL Communications Processor
➢ Connect the SEL-2600A (V-pin option) to an SEL
communications processor EIA-232 serial port using a
single SEL-2800 (V-pin) Fiber-Optic Transceiver and the
appropriate SEL fiber-optic cable (Figure 4 on page 15).
➢ Set the SEL communications processor as directed in SEL
Communications Processor Applications on page 14.
SEL-300G Multifunction Generator Relay
➢ Connect the SEL-2600A (V-pin option) to the SEL-300G
EIA-232 serial port using a single SEL-2800 (V-pin)
Fiber-Optic Transceiver and the appropriate SEL
fiber-optic cable (Figure 5 on page 20).
➢ Set the SEL-300G as directed in the SEL-300G
Multifunction Generator Relay Instruction Manual.

SEL-2600A RTD Module Date Code 20050303


Installation 7

SEL-387A Current Differential Relay


➢ Connect the SEL-2600A (V-pin option) to the SEL-387A
EIA-232 serial port using a single SEL-2800 (V-pin)
Fiber-Optic Transceiver and the appropriate SEL
fiber-optic cable (see Figure 6 on page 21).
➢ Set the SEL-387A as directed in the SEL-387A Current
Differential Relay Instruction Manual.
SEL-421 Protection, Automation, and Control System
➢ Connect the SEL-2600A (V-pin option) to the SEL-421
EIA-232 serial port using a single SEL-2800 (V-pin)
Fiber-Optic Transceiver and the appropriate SEL fiber-optic
cable (see Figure 7 on page 22).
➢ Set the SEL-421 as directed in Section 5: SEL
Communications Protocols in the SEL-421 Reference
Manual.
Step 9. Connect ac line power to the SEL-2600A via one of the following
terminal combinations:
➢ 120 Vac–Terminal 23 is Hot and Terminal 24 is Neutral
➢ 240 Vac–Terminal 23 is Hot and Terminal 25 is Neutral
The green ENABLED LED illuminates when ac power is applied
and the internal diagnostics are complete (allow up to 25 seconds
maximum).
Step 10. Verify that the SEL-2600A is operating properly by ensuring the
following:
➢ The green ENABLED LED is illuminated.
➢ The red TX LED pulses approximately once every
0.6 second (less than 0.75 seconds maximum).
➢ The SEL-701, SEL-749M, SEL communications
processor, SEL-300G, SEL-387A, or SEL-421 receives
valid RTD measurements.
➢ The red INPUT LED illuminates when the SEL-2600A
contact input is electrically shorted (connect Terminal 20
to Terminal 21).

Date Code 20050303 SEL-2600A RTD Module


8 Installation

Table 1 RTD Type and Location Worksheet

RTD Input RTD Location RTD Type

RTD1

RTD2

RTD3

RTD4

RTD5

RTD6

RTD7

RTD8

RTD9

RTD10

RTD11

RTD12

SEL-2600A RTD Module Date Code 20050303


SEL-701 Motor Protection Relay Application 9

SEL-701 Motor Protection Relay Application


The SEL-701 Motor Protection Relay provides comprehensive motor protection,
including short circuit, load loss, load jam, and frequent starting protection as well
as unbalance current and phase reversal protection. The patented motor thermal
protection element used by the SEL-701 accurately tracks the heating effects of
overloads and unbalance current.
Combining the SEL-2600A (V-pin option) and the SEL-701 enhances this list of
protection features by adding remote RTD-based thermal protection.

V-pin Fiber-Optic Ports


Up to 12 RTD inputs, plus (built into SEL-2600A & SEL-701)
one contact (speed switch, etc.)
SEL-2600A SEL-701
(V-pin option)
Relay
Up to 500 meters
Motor Load via single fiber-optic cable.
SEL part number C805Z010VVX0003 (3 meters)
(refer to the Model Option Table
for additional cable choices)
Figure 1 Motor Protection With the SEL-701
Step 1. Connect the SEL-2600A (V-pin option) to the SEL-701 using the
supplied fiber-optic cable C805Z010VVX0003, or equivalent.
Connect the cable between the SEL-2600A fiber-optic TX output
and the SEL-701 fiber-optic RX input.
Step 2. Set the SEL-701 to accept the RTD temperature data packets (see
Data Packet Definition on page 23) sent by the SEL-2600A.
a. Set the RTD Input Option setting (RTDOPT) equal to
EXT.
This enables use of the external module data.
b. Set the RTD Location and RTD Type settings based on
the information you recorded in Table 1 on page 8.
c. Set the RTD Alarm and Trip Temperature settings as
required for your application.
d. Repeat Step b and Step c for each RTD input used.

Date Code 20050303 SEL-2600A RTD Module


10 SEL-701 Motor Protection Relay Application

You can use one of the following methods to enter the settings
described above:
➢ Relay front-panel menus:
Set Relay > Relay Elements > RTD CONFIGURATION
➢ Personal computer connected to a relay serial port
running SEL-5807 (701PC) software.
➢ Personal computer connected to a relay serial port using a
terminal emulation software package.
Refer to the SEL-701 Motor Protection Relay Instruction Manual
for more details regarding calculating and entering settings.
Step 3. After accepting the relay settings, verify correct RTD temperature
measurement using one of these methods.
➢ Relay front-panel menus:
Meter Values > Thermal & RTD Data
➢ Personal computer connected to a relay serial port
running SEL-5807 (701PC) software.
➢ Personal computer connected to a relay serial port using a
terminal emulation software package and the METER T
command.
The relay indicates the temperatures of each connected, healthy
RTD. If the relay reports that an RTD is open or shorted, or if the
temperature reading is wrong, verify the wiring at the
SEL-2600A. Also verify that the RTD type connected to an input
matches the RTD type setting.

SEL-2600A RTD Module Date Code 20050303


SEL-749M Motor Protection Relay Application 11

SEL-749M Motor Protection Relay Application


The SEL-749M uses patented thermal overload protection to accurately track the
heating effects of overloads and unbalance current. The SEL-749M provides
comprehensive motor protection and includes short circuit, load loss, load jam,
and frequent starting protection, as well as unbalance current and phase reversal
protection.
Combining the SEL-2600A (ST option) and the SEL-749M enhances this list of
protection features by adding remote RTD-based thermal protection.

ST Fiber-Optic Ports
Up to 12 RTD inputs, plus (built into SEL-2600A & SEL-749M)
one contact (speed switch, etc.)
SEL-2600A SEL-749M
(ST option)
Relay
Simplex 62.5/125 µm
Motor Load multimode fiber-optic
cable ST/ST. SEL part number
C807Z010SSX0005 (5 meters)
(refer to the Model Option Table
for additional cable choices)

Figure 2 Motor Protection With the SEL-749M Relay


Step 1. Connect the SEL-2600A (ST option) to the SEL-749M using a
62.5/125 µm fiber-optic cable with ST connectors (the supplied
C807Z010SSX0005, or equivalent) between the SEL-2600A
fiber-optic TX output and the SEL-749M fiber-optic input labeled
RTD RX.
The SEL-749M and SEL-2600A (ST option) use 820 nm rated,
ST connector-based fiber-optic ports.
Step 2. Set the SEL-749M to accept the RTD temperature data packets
(Data Packet Definition on page 23) sent by the SEL-2600A:
a. Set RTD ENABLE (E49RTD) equal to Y.
This enables using the SEL-2600A data.
b. Set RTD Location and RTD Type settings based on the
information you recorded in Table 1 on page 8.
c. Set RTD Alarm and Trip Temperature settings as required
for your application.
d. Repeat Step b and Step c for each RTD input used.

Date Code 20050303 SEL-2600A RTD Module


12 SEL-749M Motor Protection Relay Application

You can use any of the following methods to enter the settings:
➢ Relay front-panel menus:
Set/Show > RELAY > RTD Settings
➢ Personal computer connected to a relay serial port
running ACSELERATOR® SEL-5030 software.
➢ Personal computer connected to a relay serial port using a
terminal emulation software package and ASCII
commands.
Refer to the SEL-749M Motor Protection Relay Instruction
Manual for more details regarding calculating and entering
settings.
Step 3. After accepting the relay settings, verify the correct RTD
temperature measurement using one of the following methods.
➢ Relay front-panel menus:
Meter > Thermal
➢ Personal computer connected to a relay serial port
running ACSELERATOR.
➢ Personal computer connected to a relay serial port using a
terminal emulation software package and the METER T
command.
The relay indicates the temperatures of each connected, healthy
RTD. If the relay reports that an RTD is open or shorted, or if the
temperature reading is wrong, verify the wiring at the
SEL-2600A. Also verify that the RTD type connected to an input
matches the RTD type setting.

Table 2 RTD Resistance Versus Temperature (Sheet 1 of 2)

Temp (°C) 100 Platinum 120 Nickel 100 Nickel 10 Copper

–50.00 80.31 86.17 74.30 7.10


–40.00 84.27 92.76 79.10 7.49
–30.00 88.22 99.41 84.20 7.88
–20.00 92.16 106.15 89.30 8.26
–10.00 96.09 113.00 94.60 8.65
0.00 100.00 120.00 100.00 9.04
10.00 103.90 127.17 105.60 9.42
20.00 107.79 134.52 111.20 9.81
30.00 111.67 142.06 117.10 10.19
40.00 115.54 149.79 123.00 10.58

SEL-2600A RTD Module Date Code 20050303


SEL-749M Motor Protection Relay Application 13

Table 2 RTD Resistance Versus Temperature (Sheet 2 of 2)

Temp (°C) 100 Platinum 120 Nickel 100 Nickel 10 Copper

50.00 119.39 157.74 129.10 10.97


60.00 123.34 165.90 135.30 11.35
70.00 127.07 174.25 141.70 11.74
80.00 130.89 182.84 148.30 12.12
90.00 134.70 191.64 154.90 12.51
100.00 138.50 200.64 161.80 12.90
110.00 142.29 209.85 168.80 13.28
120.00 146.06 219.29 176.00 13.67
130.00 149.82 228.96 183.30 14.06
140.00 153.58 238.85 190.90 14.44
150.00 157.32 248.95 198.70 14.83
160.00 161.04 259.30 206.60 15.22
170.00 164.76 269.91 214.80 15.61
180.00 168.47 280.77 223.20 16.00
190.00 172.46 291.96 231.80 16.39
200.00 175.84 303.46 240.70 16.78
210.00 179.15 315.31 249.80 17.17
220.00 183.17 327.54 259.20 17.56
230.00 186.82 340.14 268.90 17.95
240.00 190.45 353.14 278.90 18.34
250.00 194.08 366.53 289.10 18.73

Date Code 20050303 SEL-2600A RTD Module


14 SEL Communications Processor Applications

SEL Communications Processor Applications


Use the SEL-2600A (V-pin option) in combination with an SEL-2032 or
SEL-2030 Communications Processor to enhance many protection and monitoring
applications. The communications processor monitors temperature data from the
SEL-2600A, performs threshold comparisons, and sends control commands to a
protective relay.
The application shown in Figure 3 and Figure 4 on page 15 represent a few of the
possible configurations using the SEL-2600A and an SEL communications
processor. Contact SEL for help in applying these products in other
configurations.
Program an SEL communications processor to perform four automated steps:
Step 1. Receive temperature data from the SEL-2600A.
Step 2. Store the temperature data in memory.
Step 3. Perform temperature threshold comparisons.
Step 4. Issue control commands to a protective relay based on the
temperature comparisons.
The next few pages describe how to configure an SEL communications processor
to perform the four automated steps shown above. It is assumed that the
SEL-2600A is connected to Serial Port 4 of an SEL communications processor.
Refer to the instruction manual for your SEL communications processor for
further information on programming concepts.

Receive Temperature Data


Connect the SEL-2600A (V-pin option) to an SEL communications processor
using an SEL-2800 Fiber-Optic Transceiver and 200 µm fiber-optic cable
C805Z010VVX0003, or equivalent. Set the port settings of an SEL
communications processor as shown.

*>>SET P 4 <Enter>

DEVICE = S <Enter>
CONFIG = N <Enter>
PORTID = SEL-2600A RTD Module <Enter>
BAUD = 2400 <Enter>
DATABIT = 8 <Enter>
STOPBIT = 1 <Enter>
PARITY = N <Enter>
RTS_CTS = N <Enter>
XON_XOFF= N <Enter>
TIMEOUT = OFF <Enter>
*>>

SEL-2600A RTD Module Date Code 20050303


SEL Communications Processor Applications 15

SCADA PC/HMI

SEL Communications Processor


SEL-2800
EIA-232 Fiber-Optic Fiber-Optic Transceiver
Cablea
SEL-501 Relay SEL-2600A

Motor Load

a Refer to the Model Option Table for cable choices.


Figure 3 Motor Protection With the SEL-501 Relay

SCADA PC/HMI

SEL Communications Processor


SEL-2800
EIA-232 Fiber-Optic Fiber-Optic Transceiver
Cableb
SEL-587/SEL-387a Relay SEL-2600A

Transformer

a SEL-387-0, SEL-387-5, SEL-387-6, SEL-387-A.


b Refer to the Model Option Table for cable choices.

Figure 4 Transformer Protection With the


SEL-587 or SEL-387-0, SEL-387-5, SEL-387-6, or SEL-387A Relay

Date Code 20050303 SEL-2600A RTD Module


16 SEL Communications Processor Applications

Store Temperature Data


in SEL Communications Processor Memory
Use the SET A command to reserve memory.

*>>SET A 4 <Enter>

AUTOBUF = N <Enter>
STARTUP ="" <Enter>
SEND_OPER= N <Enter>
REC_SER = N <Enter>
MSG_CNT = 0 <Enter>
ARCH_EN = N <Enter>
USER = 54 <Enter>
*>>

The USER setting reserves a data region with 54 registers. Each register is 2 bytes
for a total length of 108 bytes. This data region holds the received data packet and
mathematical equations for threshold comparisons.
An SEL communications processor automatically moves the data section of each
received data packet (see Table 4 on page 23) into the reserved USER data region
at the addresses shown in Table 3 on page 18.
The SEL-2600A data packet includes temperature information for each of the four
types of RTDs. To access the correct temperature, use the memory map location
associated with the correct RTD type.
Data from the USER region can be accessed using an absolute address or in the
form n:USER:offset where n is the port number and offset is the value shown in the
offset column of Table 3 on page 18. For example, access the RTD 2, 10-ohm
copper data using the absolute address F80Ah or the offset form 4:USER:0Ah.
The examples in the remainder of this section use the offset form.

Perform Temperature Threshold Comparisons


The example communications processor settings shown below compare the
measured temperature of RTD 2 (10-ohm copper) against a threshold of 28°C. If
the measured temperature is valid (i.e., the RTD is not shorted or open) and is
above the threshold, Bit 0 of register 035H is set equal to 1. Serial Port 4 is again
assumed.

*>>SET M 4 <Enter>

1 033h = 28 #Store temp threshold <Enter>


2 034h = 4:USER:033h #Get the threshold <Enter>
3 034h -= 4:USER:0Ah #Subtract the RTD temp <Enter>
4 035h:0 = 4:USER:034h:15 #Get sign bit of result <Enter>
5 035h:0 *= !4:USER:0Ah:15 #Test bit 15 of temp <Enter>
6 035h:0 *= !4:USER:0Ah:14 #Test bit 14 of temp <Enter>
*>>

SEL-2600A RTD Module Date Code 20050303


SEL Communications Processor Applications 17

The text following the pound (#) symbols are comments and are not required to set
the SEL communications processor.
Line 1: Stores the temperature threshold in register 033h.
Line 2: Copies the threshold to register 034h in preparation for Line 3.
Line 3: Subtracts the measured RTD temperature from the threshold and
stores the result in register 034h. If the result is negative, the
measured RTD temperature is above the threshold and Bit 15 (the
sign bit) of 034h is set.
Line 4: Copies the sign bit (Bit 15) of 034h into Bit 0 of 035h.
Line 5: Clears Bit 0 of 35h if RTD is shorted.
Line 6: Clears Bit 0 of 35h if RTD is open.
This logic can be expanded to operate on additional RTDs. Use the SET A
command to reserve additional registers for mathematical equations.

*>>SET A USER 4 <Enter>


USER = 57

Use the SET M command to add the equations. The following settings show how
to add RTD 12, 100-ohm platinum (4:USER:02Fh) at a threshold of 31°C.

*>>SET M 4 <Enter>

7 036h = 31 #Store temp threshold <Enter>


8 037h = 4:USER:036h #Get the threshold <Enter>
9 037h -= 4:USER:02Fh #Subtract the RTD temp <Enter>
10 038h:0 = 4:USER:037h:15 #Get sign bit of result <Enter>
11 038h:0 *= !4:USER:02Fh:15 #Test bit 15 of temp <Enter>
12 038h:0 *= !4:USER:02Fh:14 #Test bit 14 of temp <Enter>
*>>

Date Code 20050303 SEL-2600A RTD Module


18 SEL Communications Processor Applications

Table 3 SEL-2032/SEL-2030 Communications Processor Memory Map

Address (hex) Offset Data Description

F800h–F801h 0–01h Milliseconds since device power-up


F802h 02h Device status
F803h 03h RTD 1, 100-ohm platinum
F804h 04h RTD 1, 100-ohm nickel
F805h 05h RTD 1, 120-ohm nickel
F806h 06h RTD 1, 10-ohm copper
F807h 07h RTD 2, 100-ohm platinum
F808h 08h RTD 2, 100-ohm nickel
F809h 09h RTD 2, 120-ohm nickel
F80Ah 0Ah RTD 2, 10-ohm copper


(this 4-register sequence is repeated for RTD 3 through RTD11)


F82Fh 2Fh RTD 12, 100-ohm platinum
F830h 30h RTD 12, 100-ohm nickel
F831h 31h RTD 12, 120-ohm nickel
F832h 32h RTD 12, 10-ohm copper
F833h–F835h 33h–35h Storage for mathematical functions

Issue Control Commands to Relay


Connect an SEL communications processor to the protective relay. Establish
communications as outlined in the SEL communications processor and the
protective relay instruction manuals.
Use the SET P command to set AUTO_CONFIG equal to Y. This enables
automatic control capabilities for the serial port connected to the relay. Use the
SET A command to set SEND_OPER equal to Y. This enables Fast Operate
commands based on logic bit transitions. Use the SET L command to control four
breakers using Fast Operate commands based on the result of a single temperature
comparison.

SEL-2600A RTD Module Date Code 20050303


SEL Communications Processor Applications 19

The following example settings assume the relay is connected to an SEL


Communications Processor Serial Port 10, and the SEL-2600A is connected to
Serial Port 4.

*>>SET L 10 <Enter>

SBR1 = 4:USER:35h:0 #If above threshold open breaker 1 <Enter>


CBR1 = 0 <Enter>
SBR2 = 4:USER:35h:0 #If above threshold open breaker 2 <Enter>
CBR2 = 0 <Enter>
SBR3 = 4:USER:35h:0 #If above threshold open breaker 3 <Enter>
CBR3 = 0 <Enter>
SBR4 = 4:USER:35h:0 #If above threshold open breaker 4 <Enter>
CBR4 = 0 <Enter>
*>>

The example can be modified to control each breaker based on separate


temperature thresholds. The section titled Perform Temperature Threshold
Comparisons on page 16 shows how to program an SEL communications
processor for multiple temperature comparisons. Use the comparisons along with
the following settings to control Breaker 1 and Breaker 2.

SBR1 = 4:USER:35h:0 #If RTD 2 > 28 degrees C open breaker 1 <Enter>


CBR1 = 0 <Enter>
SBR2 = 4:USER:38h:0 #If RTD 12 > 31 degrees C open breaker 2 <Enter>
CBR2 = 0 <Enter>

Refer to the specific device instructional manual for more information on Fast
Operate commands, wiring, and configuration.

Date Code 20050303 SEL-2600A RTD Module


20 SEL-300G Generator Protection Relay Application

SEL-300G Generator Protection Relay


Application
The SEL-300G has an optional RTD-based thermal protection feature using the
SEL-2600A (V-pin option) to acquire thermal data for alarm and trip functions.
Connect the SEL-2600A to the SEL-300G Generator Relay as shown in Figure 5.
Set and test the SEL-300G as directed in the SEL-300G Multifunction Generator
Relay Instruction Manual.

EIA-232
to SCADA or PC/HMI
Fiber-Optic Cablea

SEL-300G Relay SEL-2600A

SEL-2800
Fiber-Optic
Transceiver Prime
Generator Mover
a Refer to the Model Option Table for cable choices.

Figure 5 Generator Protection With the SEL-300G Relay

SEL-2600A RTD Module Date Code 20050303


SEL-387A Current Differential Relay Application 21

SEL-387A Current Differential Relay Application


The SEL-387A Relay interfaces directly with the SEL-2600A (V-pin option) to
provide temperature metering of transformers using RTDs.
Connect the SEL-2600A to the SEL-387A as shown in Figure 6. Set and test the
SEL-387A as directed in the SEL-387A Current Differential Relay Instruction
Manual.

EIA-232
to SCADA or PC/HMI
Fiber-Optic Cablea

SEL-387A Relay SEL-2600A

SEL-2800
Fiber-Optic
Transceiver
Transformer

a Refer to the Model Option Table for cable choices.

Figure 6 Transformer Protection With the SEL-387A Relay

Date Code 20050303 SEL-2600A RTD Module


22 SEL-421 Protection, Automation, and Control System Application

SEL-421 Protection,
Automation, and Control System Application
The SEL-421 Relay interfaces directly with SEL-2600A (V-pin option) to acquire
ambient temperature using an RTD. Use this temperature information to manage
thermal overload in the transmission line. Connect the SEL-2600A to the SEL-421
as shown in Figure 7. Set and test the SEL-421 as directed in Section 5: SEL
Communications Protocols in the SEL-421 Reference Manual.

RTD to Measure Ambient Temperature


BUS

SEL-2600A
Fiber-Optic Cablea

SEL-421 Relay
SEL-2800 Fiber-Optic
Transceiver

a Refer to the Model Option Table for cable choices.

Figure 7 Transmission Line Protection With the SEL-421

SEL-2600A RTD Module Date Code 20050303


Data Packet Definition 23

Data Packet Definition


The SEL-2600A sends a binary data packet approximately every 0.6 seconds
(0.75 second maximum). The packet contains data for all four supported RTD
types, so no settings are required in the SEL-2600A. With the SEL-2600A (V-pin
option) and the SEL-2800 Fiber-Optic Transceiver any EIA-232 device can be
configured to process the binary data packet contents shown in Table 4.

Table 4 SEL-2600A RTD Module Data Packet Definition (Sheet 1 of 2)

Data Value Data Size Description

A546h 2 bytes Beginning of Message Code


74h 1 byte Message Length (116 bytes)
0000000000h 5 bytes Routing Value (0)
00h 1 byte Status Byte
12h 1 byte Function Code
00h 1 byte Sequence Byte
00h 1 byte Pad Byte
xxxxxxx 4 bytes Milliseconds Since SEL-2600A Power-Up or Clock Roll-
over (86,400,000 ms/5265C00h)
xx 2 bytes Device Status (Bitmap)
Bit 0: Power Supply Status
(0 = okay; 1 = fail)
Bit 1: RTD Module Status
(0 = okay; 1 = fail)
Bit 2: Watchdog Timer Status
(0 = okay; 1 = fail)
Bit 3: 8 V Power Supply Status
(0 = okay; 1 = fail)
Bit 4: 5 V Power Supply Status
(0 = okay; 1 = fail)
Bit 5: –5 V Power Supply Status
(0 = okay; 1 = fail)
Bits 6–14: Unused, Zero
Bit 15: Contact Input State
(0=deasserted; 1=asserted)

Date Code 20050303 SEL-2600A RTD Module


24 Data Packet Definition

Table 4 SEL-2600A RTD Module Data Packet Definition (Sheet 2 of 2)

Data Value Data Size Description

xxxx 96 bytesa Temperature Data (°C)


Word One: PT100 temperature
Word Two: NI100 temperature
Word Three: NI120 temperature
Word Four: CU10 temperature

Use only the appropriate temperature for the type of RTD


connected to each input.
If an RTD circuit is open, the error code is 7FFFh; if the
circuit is shorted, the error code is 8000h. For approxi-
mately the first 20 seconds (less than 25 seconds maxi-
mum) after applying power the module sends the 7FF0h
error code.
yy 2 bytes CRC-16 Data Block Check Code
a 2 bytes per word • 4 words per RTD • 12 RTDs = 96 bytes.

SEL-2600A RTD Module Date Code 20050303


SEL-2600A Guideform Specification 25

SEL-2600A Guideform Specification


RTD (Resistance Temperature Detector) monitoring shall be provided by a
microprocessor-based module with the following characteristics:
➤ Module shall be capable of acquiring RTD data from as many as
12 RTDs.
➤ Module shall accept input from any of four different types of
three-wire RTDs (100-ohm platinum, 100-ohm nickel, 120-ohm
nickel, and 10-ohm copper) on every RTD input terminal.
➤ Module shall accept a single contact input.
➤ Module shall require no configuration settings.
➤ Module shall perform internal self-tests on the power supply and
RTD inputs.
➤ Module shall transmit over fiber optics all measured RTD values,
input contact status, and self-test status at less than 750 ms
intervals over a distance of as far as 500 meters.
➤ Module shall transmit valid RTD data within 25 seconds after
power up.
➤ Module shall secure data communications using CRC-16
(Cyclical Redundancy Check) error detection.
➤ Module shall be equipped with a fiber-optic port (V-pin option or
ST option).
➤ Module shall use LEDs (Light Emitting Diodes) to indicate
device self-test status, input contact status, and fiber port transmit
status.
➤ Module shall be capable of operating within specifications over a
temperature range of –40° to +85°C (–40° to +185°F).
➤ Module shall be line powered by 120 Vac or 240 Vac.
➤ Module shall mount to a flat surface and have package
dimensions not exceeding 241.3 mm x 117.8 mm x 63.5 mm
(9.5 in x 4.625 in x 2.5 in).

Date Code 20050303 SEL-2600A RTD Module


26 Wiring Diagram

Wiring Diagram

01 + + 27

RTD7
RTD1
02 — — 28
03 RTN RTN 29
04 + + 30

RTD8
RTD2
05 — — 31
06 RTN RTN 32
07 + + 33
RTD3

RTD9
08 — — 34
09 RTN RTN 35
10 + + 36

RTD10
RTD4

11 — — 37
12 RTN RTN 38
13 + + 39
RTD5

RTD11

14 — — 40
15 RTN RTN 41
16 + + 42
RTD12
RTD6

17 — — 43
18 RTN RTN 44
19 N/C
CONTACT INPUT

20 IN+ LEDs
21 IN— ENABLED
Speed switch
or other contact 22 N/C

120 240
Vac Vac INPUT
+120 or 240 Vac (Hot)
AC POWER

23 +/H +/H
120 Vac (Neutral)
24 -/N N/C
240 Vac (Neutral) TX
25 N/C -/N
26

Note 1: RTN terminals for all 12 RTDs are internally connected to chassis ground.
Note 2: Fiber-Optic TX Port (not shown in figure) is available in
V-pin or ST connector options (refer to the SEL-2600A Model Option Table).
Figure 8 SEL-2600A Wiring Diagram
N=Neutral, N/C=No Connection, RTN=Return

SEL-2600A RTD Module Date Code 20050303


Mechanical Diagram 27

Mechanical Diagram

I9020a
Figure 9 Mechanical Diagram

Date Code 20050303 SEL-2600A RTD Module


28 Specifications

Specifications
General Communications
Binary data packet contains temperatures
12 RTD Inputs and self-test results.
Measuring Sent approximately every 0.6 second
Range: –50° to +250°C (maximum 0.75 seconds) at 2400 bps
Accuracy: ±2°C CRC-16 data security
RTD V-pin option:
Open-Circuit
Detection: >250°C As far as 500 m using 200 µm fiber-optic
cable with V-pin connectors
RTD C805Z010VVX0003, or equivalent
Short-Circuit (650 nm wavelength)
Detection: <–50°C
ST option:
RTD Types: PT100, NI100,
NI120, CU10 As far as 500 m using 62.5/125 µm
fiber-optic cable with ST connectors
RTD Lead C807Z01SSX0005, or equivalent
Resistance: 25 ohm max. per lead (820 nm wavelength)
Lead Length: <10 m to meet
IEC 60255-22-1 and
Operating Ratings
IEC 60255-22-5 Operating
Temperature –40° to +85°C
Update Rate: < 3 sec
(Surround Air): (–40° to +185°F)
Noise Immunity
Storage Temp: –40° to +85°C
on RTD Inputs: 1.4 Vacpeak ≥50 Hz
(–40° to +185°F)
Contact Input Relative
One dry contact input. Humidity: 0–95% noncondensing
Use for local speed switch or other monitoring. Rated Altitude: 2000 m

Power Supply Pollution


Degree: PD3
120 Vac: ±20%
Overvoltage
240 Vac: ±20% Category: II
50/60 Hz: ±5% Type Tests
AC Burden: 5 VA Max
Environmental Tests
Voltage Dropout: <40 V within 1 minute of
power removal Corrosion: ASTM B117-03
Salt Spray (Fog)
Rated Insulation
Level: 300 Vac Enclosure
Protection
Rated Impulse Class: IEC 60529 IP20
Voltage: 4000 V
Cold: EN 60068-2-1
Inrush Current: <50 A Test Ad;
Internal Fuse Protection 16 hrs @ –40°C

Fuses: 2 Damp Heat, IEC 60068-2-30


Cyclic: Test Db; 25°–55°C,
Rated: 500 mA, 250 V 6 cycles, 95% relative
humidity

SEL-2600A RTD Module Date Code 20050303


Specifications 29

Dry Heat: EN 60068-2-2 IEEE C37.90.1-1989


Test Bd; 16 hrs @ 3000 V oscillatory
+85°C 5000 V transient
Radiated EN 55011/ 55022 Surge Immunity: IEC 60255-22-5
Emissions: Class B 500 V, 1000 V
line-to-line 500 V,
Conducted EN 55011/ 55022
1000 V, 2000 V
Emissions: Class B line-to-earth (applied
Dielectric Strength and Impulse Tests to power supply input
and contact input port)
Dielectric: IEEE C37.90
IEC 60255-5 Conducted RF IEC 60255-22-6
Immunity: 10 Vrms
2800 Vdc on power
supply Flicker: IEC 61000-3-3
510 Vdc on contact Part 3-3–equipment
input (not applicable with <16 A per phase
to RTD inputs)
Vibration and Shock Tests
Impulse: IEC 60255-5
0.5 J, 5000 V (not Shock and IEC 60255-21-2
applicable to RTD Bump: Class 1–Shock
inputs) withstand and bump
Class 2–Shock response
Electrostatic Discharge
Sinusoidal IEC 60255-21-1
ESD: IEC 60255-22-2 Vibration: Class 1–Endurance
15 kV air, 8 kV contact
Class 2–Response
Severity Level 4
Seismic: IEC 60255-21-3
RFI and Interference Tests Class 2–Quake
1 MHz Burst IEC 60255-22-1 response
Disturbance: 2500 V peak common
mode
Certifications
1000 Vdifferential ISO: Device is designed and manufactured
mode to an ISO-9001 certified quality program.
RF Immunity: IEC 60255-22-3 UL: UL listed to the requirements of
10 V/m UL 508 Industrial Control Equipment.
IEEE C37.90.2 UL50 Enclosure Type 1
10 V/m CSA: CSA C22.2 No. 14 for Industrial
Fast Transient IEC 60255-22-4 Control Equipment.
Disturbance: Severity Level 4 CE: Certified to EN 50263 (EMC) and
4 kV, 2.5 kHz at power EN61010-1 (LVD).
supply port
2 kV, 5 kHz at RTD, Hazardous Locations: Class I, Division 2,
contact input, and Groups A, B, C, and D; Temp. Code T4A;
functional earth port CSA C22.2 No. 213-M, 1987 (1999).

Date Code 20050303 SEL-2600A RTD Module


30 Notes

Notes

SEL-2600A RTD Module Date Code 20050303


Notes 31

Notes

Date Code 20050303 SEL-2600A RTD Module


32 Notes

The software (firmware), schematic drawings, module commands, and


module messages are copyright protected by the United States
Copyright Law and International Treaty provisions. All rights are
reserved. You may not copy, alter, disassemble, or reverse-engineer
the software. You may not provide the software to any third party.
ACSELERATOR, Connectorized, CONSELTANT, Job Done, MIRRORED BITS,
Schweitzer Engineering Laboratories, SEL, SELOGIC, and
SEL-PROFILE are registered trademarks of Schweitzer Engineering Lab-
oratories, Inc. All brand or product names appearing in this document
are the trademark or registered trademark of their respective holders.
This product is covered by U.S. Patent Number: 6,655,835 and U.S. and
Foreign Patents Pending. This product is covered by the standard SEL
10-year warranty. For warranty details, visit www.selinc.com or contact
your customer service representative.
© 2000–2005 Schweitzer Engineering Laboratories.
All rights reserved. PM2600A-01

! WARNING ! AVERTISSEMENT
Equipment components are sensitive to electrostatic Les composants de cet équipement sont sensibles aux
discharge (ESD). Undetectable permanent damage can décharges électrostatiques (DES). Des dommages
result if you do not use proper ESD procedures. Ground permanents et indécelables peuvent résulter d’un
yourself, your work surface, and this equipment before manque de précautions contre le DES. Bien raccorder la
removing any cover from this equipment. surface de travail, l’appareil et le technicien à la terre
avant d’en retirer un panneau.

! WARNING ! AVERTISSEMENT
Disconnect or de-energize all external connections Débrancher ou neutraliser tous les raccordements
before opening this device. Contact with hazardous externes avant d’ouvrir cet appareil. Tout contact avec
voltages and currents inside this device can cause une tension ou un courant dangereux dans cet appareil
electrical shock resulting in injury or death. peut causer une décharge électrique dangereuse ou
même mortelle.

! WARNING ! AVERTISSEMENT
Have only qualified personnel service this equipment. Seules des personnes qualifiées peuvent travailler sur
If you are not qualified to service this equipment, you cet appareil. Ne pas être qualifié pour ce travail peut
can injure yourself or others, or cause equipment causer des blessures à vous ou à d’autres et peut
damage. endommager l’appareil.

! WARNING ! AVERTISSEMENT
To install an option card the relay must be Pour installer une option cardez le relais doit être
de-energized and then reenergized. When reenergized, déactivé et puis reenergized. Quand reenergized, le
the relay will reboot. Therefore, de-energize the relais rechargera. Déactivez par conséquent le moteur
protected motor before installing the option card to protégé avant d'installer la carte d'option pour
prevent damage to the motor. empêcher des dommages au moteur.

! WARNING ! AVERTISSEMENT
–Explosion Hazard– Substituting components might –Risque d'explosion– La substitution de composants
impair suitability for Class I, Division 2. peut compromettre la conformité avec la Classe I,
Division 2.

! DANGER ! DANGER
Disconnect power before removing top cover. Débrancher l’alimentation avant de retirer le couvercle
du dessus.

SEL-2600A RTD Module Date Code 20050303

You might also like