SEL-2600A RTD Module Instruction Manual: Major Features & Benefits
SEL-2600A RTD Module Instruction Manual: Major Features & Benefits
Instruction Manual
Initial Checkout
Before installing the SEL-2600A, perform an initial checkout to assure successful
power up using the steps outlined below:
Step 1. Connect Terminal 26 to an appropriate ground.
Step 2. Apply line power to the SEL-2600A at one of the following
terminal combinations:
➢ 120 Vac—Terminal 23 is Hot and Terminal 24 is Neutral
➢ 240 Vac—Terminal 23 is Hot and Terminal 25 is Neutral
The SEL-2600A will power up and perform internal diagnostics.
The module is ready when the green ENABLED LED illuminates
(allow as much as 25 seconds maximum).
Step 3. Verify that the red TX LED pulses approximately every 0.6 second
(less than 0.75 second maximum).
Each pulse corresponds to the transmission of RTD data, device
status, and contact input status.
Step 4. Connect Terminal 20 to Terminal 21 to test the contact input.
The red INPUT LED illuminates when the contact input is
electrically shorted.
The unit is now ready for installation.
Installation
Physical Location
Proper placement of the SEL-2600A helps make certain that you receive years of
trouble-free operation.
The SEL-2600A is EN 61010-1 rated at Installation/Overvoltage Category II and
Pollution Degree 3. This rating specifies mounting the SEL-2600A indoors or in
an outdoor (extended) enclosure where it is protected against exposure to direct
sunlight, precipitation, and full wind pressure, but where neither temperature nor
humidity are controlled. For corrosive environment applications, be sure to mount
the RTD scanner to a vertical surface.
You can operate the SEL-2600A in a wide temperature and humidity range. See
Specifications on page 28. The altitude rating for the SEL-2600A is 2000 m
(6560 ft) above mean sea level.
Power Connections
The power terminals are isolated from the chassis ground. Use 1.5 mm2 (16 AWG)
size or heavier wire to connect to the power terminals. Connection to external
power must comply with IEC 60947-1 and IEC 60947-3.
Install an external switch, circuit breaker, or overcurrent device (fuse) in the power
leads for the SEL-2600A; this device must be able to isolate both hot and neutral
power leads. The maximum current rating for the device must be 20 A. Be sure to
locate this device within 3.0 m (9.8 ft) of the RTD module.
Provide appropriate protection to power supply terminals for protection against
electrical shock.
Operational power is internally fused with a power supply fuse. See Specifications
on page 28 for power supply and fuse ratings. Be sure to use fuses that comply
with IEC 60127-2.
Installation Steps
! CAUTION
Do not connect external voltages to the contact input. Permanent damage to the
product or external equipment can result from connecting external voltage to a
contact input because the contact input is internally wetted.
RTD1
RTD2
RTD3
RTD4
RTD5
RTD6
RTD7
RTD8
RTD9
RTD10
RTD11
RTD12
You can use one of the following methods to enter the settings
described above:
➢ Relay front-panel menus:
Set Relay > Relay Elements > RTD CONFIGURATION
➢ Personal computer connected to a relay serial port
running SEL-5807 (701PC) software.
➢ Personal computer connected to a relay serial port using a
terminal emulation software package.
Refer to the SEL-701 Motor Protection Relay Instruction Manual
for more details regarding calculating and entering settings.
Step 3. After accepting the relay settings, verify correct RTD temperature
measurement using one of these methods.
➢ Relay front-panel menus:
Meter Values > Thermal & RTD Data
➢ Personal computer connected to a relay serial port
running SEL-5807 (701PC) software.
➢ Personal computer connected to a relay serial port using a
terminal emulation software package and the METER T
command.
The relay indicates the temperatures of each connected, healthy
RTD. If the relay reports that an RTD is open or shorted, or if the
temperature reading is wrong, verify the wiring at the
SEL-2600A. Also verify that the RTD type connected to an input
matches the RTD type setting.
ST Fiber-Optic Ports
Up to 12 RTD inputs, plus (built into SEL-2600A & SEL-749M)
one contact (speed switch, etc.)
SEL-2600A SEL-749M
(ST option)
Relay
Simplex 62.5/125 µm
Motor Load multimode fiber-optic
cable ST/ST. SEL part number
C807Z010SSX0005 (5 meters)
(refer to the Model Option Table
for additional cable choices)
You can use any of the following methods to enter the settings:
➢ Relay front-panel menus:
Set/Show > RELAY > RTD Settings
➢ Personal computer connected to a relay serial port
running ACSELERATOR® SEL-5030 software.
➢ Personal computer connected to a relay serial port using a
terminal emulation software package and ASCII
commands.
Refer to the SEL-749M Motor Protection Relay Instruction
Manual for more details regarding calculating and entering
settings.
Step 3. After accepting the relay settings, verify the correct RTD
temperature measurement using one of the following methods.
➢ Relay front-panel menus:
Meter > Thermal
➢ Personal computer connected to a relay serial port
running ACSELERATOR.
➢ Personal computer connected to a relay serial port using a
terminal emulation software package and the METER T
command.
The relay indicates the temperatures of each connected, healthy
RTD. If the relay reports that an RTD is open or shorted, or if the
temperature reading is wrong, verify the wiring at the
SEL-2600A. Also verify that the RTD type connected to an input
matches the RTD type setting.
*>>SET P 4 <Enter>
DEVICE = S <Enter>
CONFIG = N <Enter>
PORTID = SEL-2600A RTD Module <Enter>
BAUD = 2400 <Enter>
DATABIT = 8 <Enter>
STOPBIT = 1 <Enter>
PARITY = N <Enter>
RTS_CTS = N <Enter>
XON_XOFF= N <Enter>
TIMEOUT = OFF <Enter>
*>>
SCADA PC/HMI
Motor Load
SCADA PC/HMI
Transformer
*>>SET A 4 <Enter>
AUTOBUF = N <Enter>
STARTUP ="" <Enter>
SEND_OPER= N <Enter>
REC_SER = N <Enter>
MSG_CNT = 0 <Enter>
ARCH_EN = N <Enter>
USER = 54 <Enter>
*>>
The USER setting reserves a data region with 54 registers. Each register is 2 bytes
for a total length of 108 bytes. This data region holds the received data packet and
mathematical equations for threshold comparisons.
An SEL communications processor automatically moves the data section of each
received data packet (see Table 4 on page 23) into the reserved USER data region
at the addresses shown in Table 3 on page 18.
The SEL-2600A data packet includes temperature information for each of the four
types of RTDs. To access the correct temperature, use the memory map location
associated with the correct RTD type.
Data from the USER region can be accessed using an absolute address or in the
form n:USER:offset where n is the port number and offset is the value shown in the
offset column of Table 3 on page 18. For example, access the RTD 2, 10-ohm
copper data using the absolute address F80Ah or the offset form 4:USER:0Ah.
The examples in the remainder of this section use the offset form.
*>>SET M 4 <Enter>
The text following the pound (#) symbols are comments and are not required to set
the SEL communications processor.
Line 1: Stores the temperature threshold in register 033h.
Line 2: Copies the threshold to register 034h in preparation for Line 3.
Line 3: Subtracts the measured RTD temperature from the threshold and
stores the result in register 034h. If the result is negative, the
measured RTD temperature is above the threshold and Bit 15 (the
sign bit) of 034h is set.
Line 4: Copies the sign bit (Bit 15) of 034h into Bit 0 of 035h.
Line 5: Clears Bit 0 of 35h if RTD is shorted.
Line 6: Clears Bit 0 of 35h if RTD is open.
This logic can be expanded to operate on additional RTDs. Use the SET A
command to reserve additional registers for mathematical equations.
Use the SET M command to add the equations. The following settings show how
to add RTD 12, 100-ohm platinum (4:USER:02Fh) at a threshold of 31°C.
*>>SET M 4 <Enter>
*>>SET L 10 <Enter>
Refer to the specific device instructional manual for more information on Fast
Operate commands, wiring, and configuration.
EIA-232
to SCADA or PC/HMI
Fiber-Optic Cablea
SEL-2800
Fiber-Optic
Transceiver Prime
Generator Mover
a Refer to the Model Option Table for cable choices.
EIA-232
to SCADA or PC/HMI
Fiber-Optic Cablea
SEL-2800
Fiber-Optic
Transceiver
Transformer
SEL-421 Protection,
Automation, and Control System Application
The SEL-421 Relay interfaces directly with SEL-2600A (V-pin option) to acquire
ambient temperature using an RTD. Use this temperature information to manage
thermal overload in the transmission line. Connect the SEL-2600A to the SEL-421
as shown in Figure 7. Set and test the SEL-421 as directed in Section 5: SEL
Communications Protocols in the SEL-421 Reference Manual.
SEL-2600A
Fiber-Optic Cablea
SEL-421 Relay
SEL-2800 Fiber-Optic
Transceiver
Wiring Diagram
01 + + 27
RTD7
RTD1
02 — — 28
03 RTN RTN 29
04 + + 30
RTD8
RTD2
05 — — 31
06 RTN RTN 32
07 + + 33
RTD3
RTD9
08 — — 34
09 RTN RTN 35
10 + + 36
RTD10
RTD4
11 — — 37
12 RTN RTN 38
13 + + 39
RTD5
RTD11
14 — — 40
15 RTN RTN 41
16 + + 42
RTD12
RTD6
17 — — 43
18 RTN RTN 44
19 N/C
CONTACT INPUT
20 IN+ LEDs
21 IN— ENABLED
Speed switch
or other contact 22 N/C
120 240
Vac Vac INPUT
+120 or 240 Vac (Hot)
AC POWER
23 +/H +/H
120 Vac (Neutral)
24 -/N N/C
240 Vac (Neutral) TX
25 N/C -/N
26
Note 1: RTN terminals for all 12 RTDs are internally connected to chassis ground.
Note 2: Fiber-Optic TX Port (not shown in figure) is available in
V-pin or ST connector options (refer to the SEL-2600A Model Option Table).
Figure 8 SEL-2600A Wiring Diagram
N=Neutral, N/C=No Connection, RTN=Return
Mechanical Diagram
I9020a
Figure 9 Mechanical Diagram
Specifications
General Communications
Binary data packet contains temperatures
12 RTD Inputs and self-test results.
Measuring Sent approximately every 0.6 second
Range: –50° to +250°C (maximum 0.75 seconds) at 2400 bps
Accuracy: ±2°C CRC-16 data security
RTD V-pin option:
Open-Circuit
Detection: >250°C As far as 500 m using 200 µm fiber-optic
cable with V-pin connectors
RTD C805Z010VVX0003, or equivalent
Short-Circuit (650 nm wavelength)
Detection: <–50°C
ST option:
RTD Types: PT100, NI100,
NI120, CU10 As far as 500 m using 62.5/125 µm
fiber-optic cable with ST connectors
RTD Lead C807Z01SSX0005, or equivalent
Resistance: 25 ohm max. per lead (820 nm wavelength)
Lead Length: <10 m to meet
IEC 60255-22-1 and
Operating Ratings
IEC 60255-22-5 Operating
Temperature –40° to +85°C
Update Rate: < 3 sec
(Surround Air): (–40° to +185°F)
Noise Immunity
Storage Temp: –40° to +85°C
on RTD Inputs: 1.4 Vacpeak ≥50 Hz
(–40° to +185°F)
Contact Input Relative
One dry contact input. Humidity: 0–95% noncondensing
Use for local speed switch or other monitoring. Rated Altitude: 2000 m
Notes
Notes
! WARNING ! AVERTISSEMENT
Equipment components are sensitive to electrostatic Les composants de cet équipement sont sensibles aux
discharge (ESD). Undetectable permanent damage can décharges électrostatiques (DES). Des dommages
result if you do not use proper ESD procedures. Ground permanents et indécelables peuvent résulter d’un
yourself, your work surface, and this equipment before manque de précautions contre le DES. Bien raccorder la
removing any cover from this equipment. surface de travail, l’appareil et le technicien à la terre
avant d’en retirer un panneau.
! WARNING ! AVERTISSEMENT
Disconnect or de-energize all external connections Débrancher ou neutraliser tous les raccordements
before opening this device. Contact with hazardous externes avant d’ouvrir cet appareil. Tout contact avec
voltages and currents inside this device can cause une tension ou un courant dangereux dans cet appareil
electrical shock resulting in injury or death. peut causer une décharge électrique dangereuse ou
même mortelle.
! WARNING ! AVERTISSEMENT
Have only qualified personnel service this equipment. Seules des personnes qualifiées peuvent travailler sur
If you are not qualified to service this equipment, you cet appareil. Ne pas être qualifié pour ce travail peut
can injure yourself or others, or cause equipment causer des blessures à vous ou à d’autres et peut
damage. endommager l’appareil.
! WARNING ! AVERTISSEMENT
To install an option card the relay must be Pour installer une option cardez le relais doit être
de-energized and then reenergized. When reenergized, déactivé et puis reenergized. Quand reenergized, le
the relay will reboot. Therefore, de-energize the relais rechargera. Déactivez par conséquent le moteur
protected motor before installing the option card to protégé avant d'installer la carte d'option pour
prevent damage to the motor. empêcher des dommages au moteur.
! WARNING ! AVERTISSEMENT
–Explosion Hazard– Substituting components might –Risque d'explosion– La substitution de composants
impair suitability for Class I, Division 2. peut compromettre la conformité avec la Classe I,
Division 2.
! DANGER ! DANGER
Disconnect power before removing top cover. Débrancher l’alimentation avant de retirer le couvercle
du dessus.